Inverter FR-D700: Safety Stop Function Instruction Manual
Inverter FR-D700: Safety Stop Function Instruction Manual
FR-D700
CONTENTS
1. General description ............................................................................. 1
2. Installation and wiring ......................................................................... 2
3. Example of safety system configuration ........................................... 5
4. Test and checking failure .................................................................... 9
5. Safety parameters of FR-D700 .......................................................... 10
Compliance with the EU Machinery Directive – Functional Safety
WARNING
Any misuse of safety function could lead to personal injury or death, property damage, or economic loss.
To ensure that the system complies fully with requirement of safety, make a system-level risk assessment.
Mitsubishi Electric Co. cannot assume responsibility for any system to comply with safety directive.
CAUTION
The information of this manual is merely a guide for proper installation.
Mitsubishi Electric Co. cannot assume responsibility for the compliance or the noncompliance to any code,
national, local or otherwise for the proper installation of this equipment.
A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
WARNING
To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged before
performing any work on the drive. Measure the DC bus voltage at the P(+) and N(-) terminals or test points
(refer to your drive’s User Manual for locations and discharging time). The voltage must be zero.
WARNING
The safety stop function do not isolate electrically between drive and motor. To avoid an electric shock
hazard, disconnect/isolate power to the drive and verify to ensure that the voltage is zero before
performing any work on the motor (refer to your drive’s User Manual for discharging time).
CAUTION
If you are using a FR-D740-EC with serial number shown below, safety function does not work according
to safety standard. In such case please contact your sales person.
Check the SERIAL number indicated on the inverter rating plate or package.
Features
Mitsubishi FR-D700 safety stop function prevents a drive from supplying rotational energy to motors.
Dual safety channels ‘S1’ and ‘S2’ cut off the gate-drive power for IGBT to turn off.
Input power
+24V
FR-D700
S2
+24V
S1
Internal G G IGBTs
Safety
Circuit Gate Gate
Driver Driver
SC CPU
Safety relay module
WARNING
The safety stop function doesn’t isolate electrically between drive and motor. To avoid an electric shock
hazard, disconnect power to the drive and verify that the voltage is zero before performing any work on the
motor (refer to your drive’s User Manual for discharging time).
Directives
Mitsubishi FR-D700 safety stop function meets the following directives and categories.
ISO13849-1:2008 Category 3/PLd (applies to the FR-D700 manufactured in January 2012 or later)
IEC62061:2005 / IEC61800-5-2:2007 / IEC61508 SIL2
IEC60204-1:2006 / IEC61800-5-2:2007 Stop category 0
WARNING
The misuse of safety function leads to personal injury or death, property damage, or economic loss.
To ensure that the system complies fully with requirement of safety, make a system-level risk assessment.
Mitsubishi Electric Co. cannot assume responsibility for any system to comply with safety directive.
1
2. Installation and wiring
CAUTION
The following information is merely a guide for proper installation.
Mitsubishi Electric Co. cannot assume responsibility for the compliance or the noncompliance to any code,
national, local or otherwise for the proper installation of this equipment.
A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
CAUTION
Ensure the safety relay unit and the FR-D700 unit is mounted closely in enclosure meeting IP54 and all
interconnection wiring is short and protected against open and short circuit faults.
Refer EN/ISO13849-2.
Installation
Mitsubishi FR-D700 safety stop function should be used under following condition and environment.
Table.1 The condition and environment for using safety stop function
Item Condition
Temperature Operation -10°C to +50°C (non-freezing)
range Storage -20°C to +65°C
Ambient humidity 90%RH maximum (non-condensing)
Vibration 5.9m/s2 or less
Altitude maximum 1000m above sea level
Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Over voltage category II or less
Pollution degree II or less
Mounting wall mounting / vertical orientation
CAUTION
In order to meet safety stop, an approved safety relay unit to ISO13849-1/EN954-1 safety category 3 or better shall be
used in conjunction with FR-D700 as shown in example1,2.
In addition, all other components with in the safety stop loop shall be ‘safety approved’ types.
WARNING
To avoid an electric shock hazard, insert the magnetic contactor (MC) between power source and drive.
Open the contact of MC and keep away from drive for discharging time (refer to your drive’s User Manual
for information) before performing any work on the drive.
And verify that the voltage on the bus capacitors has discharged before Measure the DC bus voltage at the
P(+) and N(-) terminals or test points (refer to your drive’s User Manual for locations). The voltage must be
zero.
CAUTION
To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check
the correct function of the monitor signal. This test shall be carried out at system installation, any software changes,
parameterization changes, and/or at least once per year.
Refer to ‘4. Test and checking failure’.
2
Wiring
The safety related terminals are described in Table.2 and Table.3
Terminal
Description Rating
Symbol
For input of safety stop channel1. Input resistance:4.7kΩ
S1-SC is Current : 4 to 6 mA
S1
Open: In safety stop mode. (In case of shorted to SC)
Short: Non safety stop mode. Voltage : 21 to 26 V
For input of safety stop channel2. (In case of open from SC)
S2-SC is
S2
Open: In safety stop mode.
Short: Non safety stop mode.
As output for safety stop condition. Load: 24VDC/0.1A max.
SO terminal type is ‘Open collector output’. Voltage drop: 3.4V max.
SO-SC is (In case of ‘ON’ state)
SO OFF(Open): Drive enabled, or drive shutoff (with
(SAFE) internal circuit fault)
ON(Close): Drive shutoff (no internal circuit fault)
Important: SO terminal should be used for monitoring safety stop
condition only. SO terminal cannot be used for safety function.
Common terminal for S1, S2, SO terminals.
SC
*SC is connected terminal SD internally.
As output for failure detection and alarm. RUN terminal type is ‘Open Load: 24VDC/0.1A max.
collector output’. Voltage drop: 3.4V max.
RUN-SE is (In case of ‘ON’ state)
OFF(Open): Detect failure or Alarm.
ON(Close): No failure detected.
RUN
(SAFE2)
Attention: To use RUN terminal for monitor output of failure
detection, The parameter No.190 should be set 81
(Safety monitor 2).
Note: This terminal can be used for alarm or to prevent restart only,
no other safety function.
SE Common terminal for safety RUN terminal.
As output for failure detection. A,C terminal type is ‘Relay output’. Load: 30VDC/0.3A max.
A-C is
OFF(Open): Detect failure or Alarm.
ON(Close): No failure detected.
A,C
(SAFE2) Attention: To use A,C terminal for monitor output of failure
detection, The parameter No.192 should be set 81
(Safety monitor 2).
Note: This terminal can be used for alarm or to prevent restart only,
no other safety function.
SD Signal ground
3
Table.3 Truth table of Safety related signals
Jumper cable
The jumper cable between S1,S2 and SC terminal has been installed in the factory as shown in Fig.2.
AM
Before connecting safety input wire to S1,S2 and SC terminal, remove this jumper cable.
4
3. Example of safety system configuration
Example 1
R/L1 S/L2 T/L3
+24V
A(SAFE2)
B RY
C
STF STF
START
STOP
STOP
Emergency
stop button IGBTs
CPU
Gate Gate
Driver Driver
Fig.3 Safety system example 1 – STOP asynchronous with emergency stop button and fault
detection through A-C output.
The parameter No.192 (A,B,C terminal function selection) must be set to ‘81’. This setting makes the A-C
output to open in case of failure.
After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.
In the above configuration, after reset of emergency stop button, drive will be in safe-state until START
switch is pressed.
CAUTION
To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.
5
R/L1 S/L2 T/L3
+24V
A(SAFE2)
B RY
C
START
Emergency
stop button IGBTs
CPU
Gate Gate
Driver Driver
IM
A +24V
(SAFE2)
B RY
C
IGBTs
CPU
Gate Gate
Driver Driver
+24V
G G
S1
+24V
S2
SC
FR-D700 U V W
IM
6
• Example when using multiple FR-D700 inverters manufactured in December 2010 or before
R/L1 S/L2 T/L3
+24V
A(SAFE2)
B RY
C
START
K1
* S1
DC24V
Internal
Safety +24V
Circuit
K2
* S2
24G Z01 Z11 Z21
SC
MITSUBISHI MELSEC Safety relay module
QS90SR2SN-Q
FR-D700 U V W
IM
A +24V
(SAFE2)
B RY
C
IGBTs
CPU
Gate Gate
Driver Driver
+24V
G G
* S1
+24V
* S2
SC
FR-D700 U V W
* When connecting multiple inverters, use a diode on each safety input terminal to prevent a malfunction due to
undesirable current. Refer to the following for the specification of the diode. IM
Diode type : P-N junction type (Do not use a Schottky barrier diode.)
Electronic specification - Peak reverse voltage (Vrrm) : 50V or more, Peak forward voltage (Vf) : 1V or less (at 5mA),
Effective forward current (If) : 100mA or more
The number of inverters connected to a safety relay unit should be decided under considerations of output
terminal rating of a safety relay unit.
NOTE
• Do not connect the FR-E700-SC/NC/NF series together with the FR-D700 series. If connected
together, the safety stop function does not work properly.
7
Example 2
RUN (SAFE2)
SE
STF
START
STF
Emergency STOP
stop button IGBTs
CPU
STOP Gate Gate
Driver Driver
PC*
MITSUBISHI MELSEC Safety relay module
QS90SR2SN-Q
* If the control logic is SINK logic, the common FR-D700 U V W
terminal is terminal SD.
IM
Fig.6 Safety system example 2 – STOP synchronous with emergency stop button and fault
detection through RUN output.
XS0 should be connected to RUN terminal and XS1 should be connected to SE, because polarity of XS0 is
positive, XS1 is negative.
The parameter No.190 (RUN terminal function selection) must be set to ‘81’. This setting makes the RUN
output to turn off in case of failure.
After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.
In the above Fig.6, wired example 2, in the event of reset of ‘safe-condition’ the motor rotation will not
occur until STF is pressed.
(for normal ‘non-safety’ STF/STOP function, please refer to your drive’s User Manual)
CAUTION
To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.
8
4. Test and checking failure
CAUTION
To avoid systematic faults, a test even for faulty demands of the safety function has to be performed in order to check
the correct function of the monitor signal. This test shall be carried out at system installation, any software changes,
parameterization changes, and/or at least once per year.
In case of diagnostic or functionality test, check the I/O state whether it is same or not as Table.5.
Diagnostic
If the failure detected, FR-D700 output alarm signal and indicate ‘E.SAF’ at the display.
In case of FR-D700 output the alarm, please take following action.
(1) Check the S1-SC and S2-SC input signal logic is the same. If these are different logic, correct the input
signal and reset the FR-D700.
(2) Disconnect the wire from S1, S2, SC terminal, then reset or power-off and on, If the ‘SA’ letter is
flashed up at display, there is failure in system except FR-D700. But, still ‘E.SAF’ is displayed and
alarm output, there is malfunction on FR-D700.
9
5. Safety parameters of FR-D700
FR-D700 safety related I/O status obeys the following truth table.
10
REVISIONS
BCN-A211508-000-G 11
HEADQUARTERS EUROPEAN REPRESENTATIVES EUROPEAN REPRESENTATIVES EUROPEAN REPRESENTATIVES
MITSUBISHI ELECTRIC EUROPE GEVA AUSTRIA MITSUBISHI ELECTRIC IRELAND Beijer Electronics AB SWEDEN
EUROPE B.V. Wiener Straße 89 EUROPE B.V.-Irish Branch Box 426
German Branch A-2500 Baden Westgate Business Park S-20123 Malmö
Gothaer Straße 8 Phone: +43 (0) 2252 / 85 55 20 Ballymount Phone: +46 (0) 40 / 35 86 00
D-40880 Ratingen Fax: +43 (0) 2252 / 488 60 IRL-Dublin 24 Fax: +46 (0) 40 / 93 23 02
Phone: +49 (0) 21 02 / 486-0 e mail: [email protected] Phone: +353 (0) 1 / 419 88 00 e mall: ——
Hotline: +49 2102 1805 000-765 /-766 Fax: +353 (0) 1 / 419 88 90
Fax: +49 (0) 21 02 / 4 86-1 12 0 Getronics b.v. BELGIUM ECONOTEC AG SWITZERLAND
e mail: [email protected]
e mail: [email protected] Control Systems Postfach 282
www.mitsubishi-automation.com Pontbeeklaan 43 ALFATRADE LTD. MALTA CH-8309 Nürensdorf
B-1731 Asse-Zellik 99 Paola Hill Phone: +41 (0) 1 / 838 48 11
MITSUBISHI ELECTRIC FRANCE Phone: +32 (0) 2 / 4 67 17 51 Paola PLA 08 Fax: +41 (0) 1 / 838 48 12
FRANCE Fax: +32 (0) 2 / 4 67 17 45 Phone: +356 / 697816
25, Boulevard des Bouvets e mall: ——
e mail: [email protected] Fax: +356 / 697817
F-92741 Nanterre Cedex e mail: [email protected] GTS TURKEY
Phone: +33 1 55 68 55 68 TELECON CO. BULGARlA Darülaceze Cad. No. 43A KAT: 2
Fax: +33 1 49 01 07 25 4, A. Ljapchev Blvd. Getronics bv NETHERLANDS TR-80270 Okmeydani-Istanbul
e mail: [email protected] BG-1756 Sofia Control Systems Phone: +90 (0) 212 / 320 1640
Phone: +359 92 / 97 44 05 8 Donauweg 10 Fax: +90 (0) 212 / 320 1649
MITSUBISHI ELECTRIC ITALY Fax: +359 92 / 97 44 06 1 NL-1043 AJ-Amsterdam
EUROPE B.V. e mall: ——
e mail: —— Phone: +31 (0) 20 / 586 15 92
Italian Branch
Fax: +31 (0) 20 / 586 19 27
C.D. Colleoni-P. Perseo lng. 2 AutoCont CZECHIA
e mail: [email protected]
Via Paracelso 12 Control Systems s.r.o. EURASIAN REPRESENTATIVES
I-20041 Agrate Brianza (Ml) Nemocnicni 12 Beijer Electronics AS NORWAY
Phone: +39 (0) 39 / 60 53 1 CZ-70200 Ostrava 2 Teglverksveien 1 MITSUBISHI ELECTRIC RUSSIA
Fax: +39 (0) 39 / 60 53 312 Phone: +420 (0) 69 / 615 21 11 N-3002 Drammen EUROPE B.V.
e mail: [email protected] Fax: +420 (0) 69 / 615 21 12 Phone: +47 (0) 32 / 24 30 00 12/1 Goncharnaya St, suite 3C
e mail: —— Fax: +47 (0) 32 / 84 85 77 RUS-109240 Moskow
MITSUBISHI ELECTRIC SPAIN
e mall: —— Phone: +7 (0) 95 / 915-8624/02
EUROPE B.V. louis poulsen DENMARK
Pol. lnd. Can Magi-C. Fax: +7 (0) 95 / 915-8603
industri & automation MPL Technology SP.Z.o.o POLAND e mall: ——
Calle Joan Buscallá, 2-4 AC 420 Geminivej 32 ul.Wroclawska 53
E-08190 Sant Cugat del Vallés DK-2670 Greve PL-30-011 Kraków STC Drive Technique RUSSIA
Phone: +34 (9) 3 / 565 31 31 Phone: +45 (0) 43 / 95 95 95 Phone: +48 (0) 12 / 632 28 85 Poslannikov per., 9, str. 1
Fax: +34 (9) 3 / 589 29 48 Fax: +45 (0) 43 / 95 95 91 Fax: +48 (0) 12 / 632 47 82 RUS-107005 Moskow
MITSUBISHI ELECTRIC UK e mail: [email protected] e mail: [email protected] Phone: +7 (0) 95 / 786 21 00
EUROPE B.V. Fax: +7 (0) 95 / 786 21 01
UTU Elektrotehnika AS ESTONIA Sirius Trading&Services srl ROMANIA
UK Branch e mall: ——
Pärnu mnt. 160i Bd. Ghica nr. 112, BI. 41
Travellers Lane EE-10621 Tallinn RO-72335 Bucaresti 2 JV-CSC Automation UKRAINE
Hatfield, Hertfordshire, AL10 8 XB
Phone: +372 6 / 51 72 80 Phone: +40 (0) 1 / 210 55 11 15, M. Raskovoyi St., Floor 10,
Phone: +44 (0) 1707 / 27 61 00
Fax: +372 6 / 51 72 88 Fax: +40 (0) 1 / 210 55 11 Office 1010
Fax: +44 (0) 1707 / 27 86 95
e mail: [email protected] e mail: [email protected] U-02002 Kiev
MITSUBISHI ELECTRIC JAPAN Phone: +380 (4) 4 / 238 83 16
CORPORATION URHO TUOMINEN OY FINLAND ACP AUTOCOMP a.s. SLOVAKIA
Hevoshaankatu 3 Chalupkova 7 Fax: +380 (4) 4 / 238 83 17
Tokyo Bldg. e-Mail: [email protected]
2-7-3 Marunouchi Chiyoda-Ku FIN-28600 Pori SK-81109 Bratislava
Tokyo 100-8310 Phone: +358 (0) 2 / 55 08 00 Phone: +421 (0) 7 592 22 54
Phone: +81 (0) 3 / 32 18 31 76 Fax: +358 (0) 2 / 55 088 41 Fax: +421 (0) 7 592 22 48
Fax: +81 (0) 3 / 32 18 24 22 e mall: —— e mall: —— MIDDLE EAST REPRESENTATIVE
MITSUBISHI ELECTRIC USA UTECO A.B.E.E. GREECE lNEA d.o.o. SLOVENlA SHERF Motion Techn. LTD ISRAEL
AUTOMATION 5, Mavrogenous Str. Ljubljanska 80 Rehov Hamerkava 19
500 Corporate Woods Parkway GR-18542 Piraeus SI-1230 Dom z ale IL-58851 Holon
Vernon Hills, Illinois 60061 Phone: +30 (0) 1 / 42 10 050 Phone: +386 (0) 17 21 80 00 Phone: +972 (0) 3 / 559 54 62