Circular Fire Damper Cartridge Guide

This document provides information on circular fire damper cartridges. It discusses two types of cartridges: SC for closing ventilation ducts, and SCV with a finishing ventilation valve for installing at duct ends. The cartridges are tested to EN 1366-2 and provide a fire resistance of up to 120 minutes. Dimensions and installation details are provided for proper selection and installation of the dampers.

Uploaded by

Anjana2893
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views14 pages

Circular Fire Damper Cartridge Guide

This document provides information on circular fire damper cartridges. It discusses two types of cartridges: SC for closing ventilation ducts, and SCV with a finishing ventilation valve for installing at duct ends. The cartridges are tested to EN 1366-2 and provide a fire resistance of up to 120 minutes. Dimensions and installation details are provided for proper selection and installation of the dampers.

Uploaded by

Anjana2893
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

SC

S2-D 05/2012

Circular Fire Damper Cartridge


Rf-Technologies nv - Lange Ambachtstraat 40 - 9860 Oosterzele - Belgium - Tel +32 9 362 31 71 - Fax +32 9 362 33 07 - www.rft.be - [email protected]
SC Circular Fire Damper Cartridge
S2-D
05/2012

TABLE OF CONTENTS

CONTENTS • PRODUCT PRESENTATION • R ANGE ................................................................................................................... 2


FIRE CLASSIFICATION • APPROVALS AND TEST REPORTS • DIMENSIONS .................................................................................. 3
OPTIONS • STORING AND HANDLING • INSTALLATION ............................................................................................................. 4
OPERATION SC • MAINTENANCE • EVOLUTION - KITS .......................................................................................................... 7
TECHNICAL DATA ...................................................................................................................................................................... 8
WEIGHTS • SELECTION GRAPH ................................................................................................................................................. 9
PRESSURE LOSS COEFFICIENT • SELECTION DATA ....................................................................................................................10
CORRECTION FACTOR ∆L • S ELECTION G R APH SCV ........................................................................................................12
SAMPLE ORDER ........................................................................................................................................................................13
CE DECLARATION OF CONFORMITY .........................................................................................................................................14

PRODUCT PRESENTATION

Circular fire damper cartridges SC(V) are installed in circular ventilation ducts passing through a construction element in
order to stop the propagation of fire. The circular fire damper cartridge SC(V) has a fire resistance up to 120'. The circular
fire damper cartridges are equipped with a common fusible link mechanism.

There are two types of circular fire damper cartridges:


• SC : especially used to close ventilation ducts passing through a construction element.
• SCV : is equipped with a finishing ventilation valve and is especially used for installation at the end of ventilation ducts
passing through a construction element.

• Tested according to the European standard EN 1366-2 at a constant pressure of 300 Pa


• Minimal pressure drop
• Suitable for mounting in rigid wall, floor and flexible wall
• Easy to install
• Maintenance free
• For interior applications 4

1 3

1. Steel tunnel
2. Two semi circular blades 2
3. Intumescent strip around the tunnel 8
4. Rubber sealing rings 5
5. Fusible link 72°C
6. Two blocking hooks 7
7. End of range switch 9
8. Finishing ventilation valve
6
9. Product identification

fig. SC fig. SCV

RANGE

80
ØDn(mm) 100 125 160 200
only for SC90

Dn = nominal diameter

2
SC Circular Fire Damper Cartridge
S2-D
05/2012

FIRE CLASSIFICATION ACCORDING TO EN 13501-3 : 2005 - FIRE TESTS ACCORDING TO EN 1366-2

EI 120 S E 120 S EI 90 S EI 60 S

SC(V)60
Concrete wall
Rigid

SC(V)120 SC(V)0 SC(V)90 Ø 100 - 200


wall

110mm Ø 100 - 200 Ø 100 - 200 Ø 80 - 200 SC60 + BRF


(ve i o) Ø 200

Concrete floor SC(V)0 SC(V)60


Rigid floor

110mm Ø 100 - 200 Ø 100 - 200


(ho i o)

Concrete floor SC(V)120 SC(V)90


150mm Ø 100 - 200 Ø 80 - 200
(ho i o)
Flexible

Metal stud wall Pa= Pascal


SC(V)120 SC(V)90 SC(V)60
wall

120' 100mm Ø 100 - 200 Ø 80 - 200 Ø 100 - 200


E = integrity
(ve i o) I = thermal insulation
S = smoke leakage

ve = duct in which the circular fire damper is mounted directly in the wall
ho = directly mounted in a floor / ceiling o i = fire side = side intumescent layer

APPROVALS AND TEST REPORTS

All our circular fire damper cartridges are submitted to a number of tests by official test institutes. Reports of these tests
form the basis for the approvals of our dampers.

Europa : Classification according to EN 15650:2010 (certificate BC1-606-0464-15650.08-2517)

Seco : All our dampers are periodically audited by an external 'Third Party' according to the European
FPC regulations (Factory Production Control)

ISO : Certification: ISO 9001:2008

DIMENSIONS Øn-1,5
Øn-1,5

SC(V)0
ØD (mm) SC(V)90 SC(V)120 60 x fig. SC 110 x fig. SCV
SC(V)60
80 / 8 /
100 18 20 20 L
125 31 33 33
160 49 51 51
200 69 71 71

100 125 160 200 50


Ød

Ød1
ØD1

ØD [mm] 150 165 220 245


ØD

Ød [mm] 90 110 138 128


L 43 40 65 60 3
Ød1 [mm] 96.6 122.3 156 197
SC Circular Fire Damper Cartridge
S2-D
05/2012

OPTIONS

End of range switch FCU:

An end of range switch can be mounted on the metal body. The purpose is to determine the position of the circular fire
damper cartridge from a distance.

COM : black
NF : brown
NO : blue

Power supply : Max 250V

Power consumption : Max 6A


Degree of protection : IP65

Lenght of cable : 500mm

STORING AND HANDLING

As the circular fire damper cartridge is a safety element it needs to be stored and handled with caution.

Attention:
• Avoid any kind of damage
• Avoid contact with water
• Avoid deformation of the casing during the installation and sealing

It is recommended:
• to unload in a dry area
• to avoid heavy shocks

INSTALLATION

• The damper can be mounted with the axis vertically or horizontally


• The damper has to be installed in conformity with the test report
• Air movement may be from either direction
• The SC must be accessible for inspection and maintenance
Position axis
The circular fire damper cartridge SC(V) is always tested in standardized supporting constructions (rigid wall, floor as well
as flexible wall) according to NBN EN 1366-2: 1999 table 3/4/5 'standarized supporting constructions'. The achieved results
are valid for similar supporting constructions with a fire resistance and/or thickness and/or density equal to or bigger than
the supporting construction used during the test.

Examples of similar supporting constructions

reinforced concrete wall min. 110mm + density masonry in hollow or full bricks, reinforced concrete, aerated
2200 kg/m³ + fire resistance ≥120' concrete, light concrete, ...

reinforced concrete floor 150 mm + density concrete elements, pre-stressed concrete, ...
2200 kg/m³ + fire resistance ≥120' - 240'

flexible wall: metal stud + gypsum plasterboard: metal stud + Rf-boards, several layers of gypsum cardboard
100mm + fire resistance ≥60'
flexible wall: metal stud + gypsum plasterboard: metal stud + Rf-boards, several layers of gypsum cardboard
100mm + fire resistance ≥120'

4
SC Circular Fire Damper Cartridge
S2-D
05/2012

Installation in rigid wall, floor and ceiling

The circular fire damper cartridge was tested in a concrete wall of 110mm (fire resistance 120') as well as in reinforced
concrete floors of 110 and 150mm (fire resistance 120' up to 240').

1. Provide a minimal installation 2. Mount the metal duct in 3. The joint S between the duct
opening in the wall/floor/ceiling = the opening. and the wall/floor/ceiling must
Øn+50mm. be filled entirely with standard
mortar or sealed with fire
resistant flexible strips BRF for
SC60.

4. Mount the circular fire damper cartridge SC in the duct in such a way
that the front side of the SC is positioned at 40mm of the edge of the
wall.
An SCV has to be mounted with the valve positioned againt the wall.
The side of the SC(V) with the fusible link is positioned at the side
opposite of the fire.

BRF
Mortar Mortar
Mortar

40 40
∅n+50

∅n+50
∅n+50

min.100 min.100 min.100

fig. SC fig. SCV fig. SC60 + BRF


application massive wall application massive wall application massive wall
5
SC Circular Fire Damper Cartridge
S2-D
05/2012

Installation in flexible wall- Metal Stud Gypsum Plasterboard wall

The fire damper cartridge was tested in a metal stud plasterboard gypsum wall (fire resistance 60' and 120') with a minimal
thickness of 100mm. The fire resistance of the wall has to be equal to or bigger than the fire resistance of the damper cartridge.

Metal Stud gypsum plasterboard wall consists of:

• A metal framework made out of horizontal and vertical metal studs (min. width 50mm)
• Stonewool with a thickness of 40mm and a density of 40 kg/m³ between the boards
• Double boarding: two standard gypsum boards on both sides (fire resistance wall 60')

50
(∅n+50)
min

min. 600
1. Provide a minimal 2. Attach two standard 3. Isolate the entire wall with 4. Attach the lower
installation opening in the wall gypsum boards (with a stonewool (40mm-40kg/ coverplate with chipboard
= (Øn+50)mm x (Øn+50)mm thickness of 12,5 mm) to one m³) and finish off with two screws.
+ horizontal reinforcements. side of the metal stud wall. standard gypsum boards.
For metal stud walls with a
fire resistance 120´, use fire
resistant gypsum boards of
the same thickness.

5. Mount a metal duct in the 6. Attach the upper 7. The joint S between the 8. Finish off with
opening. coverplate. duct and the wall must be coverplates and attach them
filled with stonewool over with chipboard screws.
the entire width of the wall
(min. density 40 kg/m³)

Cover plate
Cover plate
Stonewool Stonewool

40
(∅n+50)

(∅n+50)

9. Mount the circular fire damper


cartridge SC in the duct in such
a way that the front side of the
SC is positioned at 40mm of the
edge of the wall.
An SCV has to be mounted with min.100 min.100
the valve positioned against the
wall.
The side of the SC(V) with the
fusible link is positioned at the fig. SC fig. SCV
side opposite of the fire. application flexible wall application flexible wall
6
SC Circular Fire Damper Cartridge
S2-D
05/2012

OPERATION SC

The fire damper cartridge is kept in the open position by a fusible link. When the temperature in the duct rises above 72°C,
the fusible link melts and releases the two semi circular blades. The damper is now closed. The two blocking hooks keep
these blades in their safety position which prevents any smoke or flames from passing through.

1. Press the two blocking 2. Manually move the blades 3. Click the fusible link 4. Unlock (close) the damper
hooks carefully to unlock towards each other. into the holder to lock the blades by pushing them
the blades. blades. towards each other. Carefully
unlock the fusible link by
pushing it sidewards.

MAINTENANCE
- No particular maintenance required
- Clean the whole unit before start-up
- Honour the maintenance regulations according to NF S 61-933
- Attention, butterfly dampers, in their closed position, can move in the duct when placed under too high pressure.

EVOLUTION KITS

KITS FCU SC KITS FT SC

Unipolar end of range


Fusible link (per set of 5)
switch

7
SC Circular Fire Damper Cartridge
S2-D
05/2012

TECHNICAL DATA

Operating mechanism SC SCV


Description Circular fire damper cartridge Circular fire damper cartridge with valve

Certifications

Classification Fire resistance according to EN 13501-3:


- SC(V)120 : EI120 (ve, ho o i)S : Ø100 - Ø200 : Mounting in massive wall 110mm
Mounting in massive floor 150mm
Mounting in flexible wall 120' 100mm

- SC(V)90 : EI90 (ve, ho o i)S : Ø80 - Ø200 : Mounting in massive wall 110mm
Mounting in massive floor 150mm
Mounting in flexible wall 120' 100mm

- SC(V)60 : EI60 (ve, ho o i)S : Ø100 - Ø200 : Mounting in massive wall 110mm
Mounting in massive floor 110mm
Mounting in flexible wall 120' 100mm

- SC(V)0: E120 (ve, ho i o)S : Ø100 - Ø200 : Mounting in massive wall 110mm
Mounting in massive floor 110mm

Pressure during test : 300 Pa

Durability test After 50 cycles the characteristics After 50 cycles the characteristics stay within the
stay within the declared limit values. declared limit values.

Safety position Closed Closed

Operation Automatically: by melting the fusible Automatically: by melting the fusible link 72°C
link 72°C

Unlocking Cold unlocking possible Cold unlocking possible

Functioning With internal energy With internal energy

Position indication Non Non

Installation direction Horizontally or vertically Horizontally or vertically

Fire side Side opposite of the fusible link Side opposite of the fusible link

Airmovement Random Random

Test pressure Max 300 Pa Max 300 Pa

Ambient temperature Max 50°C Max 50°C

Environment For interior use For interior use

Position switch Option: FCU Option: FCU


1mA...6A DC 5V....AC250V 1mA...6A DC 5V....AC250V

Degree of protection IP65 IP65

Maintenance Maintenance free Maintenance free

8
SC Circular Fire Damper Cartridge
S2-D
05/2012

WEIGHTS

Weight SC0/ SC60

Ø[mm] 100 125 160 200


m [kg] 0.220 0.250 0.340 0.470

Weight SC90/SC120

Ø[mm] 80 (for SC90) 100 125 160 200


m [kg] 0.130 0.230 0.280 0.390 0.510

Weight SCV0/ SCV60

Ø[mm] 100 125 160 200


m [kg] 0.420 0.470 0.640 0.980

Weight SCV90/ SCV120

Ø[mm] 100 125 160 200


m [kg] 0.430 0.500 0.690 1.020

SELECTION GRAPH

p[Pa] Dn[mm]
300
100
200
60 125

100 160
90
80
70 200
60
50
40
55
30

20 50

dB[A]
10 45
9
8
7 40
6
5
4 35
3

2 30

100
2 3 4 5 6 7 8 9 10 11 12 v[m/s]

9
SC Circular Fire Damper Cartridge
S2-D
05/2012

PRESSURE LOSS COEFFICIENT ζ [-]

Pressure loss coefficicient SC0/ SC60

100 125 160 200


ξ [-] 2.08 1.36 0.97 0.78

Pressure loss coefficicient SC90/ SC120

80 100 125 160 200


ξ [-] 4.35 2,19 1.44 1.00 0.80

q = Air flow in the duct [m³/h]


q ∆p = Static pressure drop [Pa]
∆p = v² x 0,6 x ζ v= ζ = Pressure loss coefficient zeta [-]
A A = Internal surface of the duct [m²]
v = Air speed in the duct [m/s]
LWA = A-weighted sound power level
Dn = Nominale diameter of the damper

Elaborated example of a pressure drop calculation ∆p with air speed v = 4m/s

SC0 / SC60 100 125 160 200 SC90 / SC120 80 100 125 160 200

∆p [Pa] 19.97 13.06 9.31 7.49 ∆p [Pa] 41.76 21.02 13.82 9.60 7.68

Elaborated example of a pressure drop calculation ∆p with air speed v = 7m/s

SC0 / SC60 100 125 160 200 SC90 / SC120 80 100 125 160 200

∆p [Pa] 61.15 39.98 28.52 22.93 ∆p [Pa] 127.89 64.39 42.34 29.40 23.52

SELECTION DATA

A-weighted sound power level LWA of 60dB(A) in the duct

SC0/ SC60 SC90/ SC120

∅ Dn [mm] 100 125 160 200 ∅ Dn [mm] 80 100 125 160 200
Sn [m²] 0.00366 0.00698 0.01328 0.02283 Sn [m²] 0.0013 0.00322 0.00641 0.01253 0.02187

Sn [%] 46.60 56.88 66.05 72.67 Sn [%] 27.39 41.00 52.23 62.32 69.61

Q [m³/h] 295 518 950 1617 Q [m³/h] 162 291 509 939 1597

∆p [Pa] 136 112 100 95 ∆p [Pa] 209 139 115 101 96

Sn = Free air passage


Q = Air flow
∆p = Pressure drop
Every air flow lower than the above mentioned maximum value, will meet the listed A-weighted sound power level 60dB(A), for the respective dimension.

10
SC Circular Fire Damper Cartridge 05/2012
S2-D

A-weighted sound power level LWA of 55dB(A) in the duct


Sn = Free air passage
SC0/ SC60 SC90/ SC120 Q = Air flow
∆p = Pressure drop

∅ Dn [mm] 100 125 160 200 ∅ Dn [mm] 80 100 125 160 200
Sn [m²] 0.00366 0.00698 0.01328 0.02283 Sn [m²] 0.0013 0.00322 0.00641 0.01253 0.02187

Sn [%] 46.60 56.88 66.05 72.67 Sn [%] 27.39 41.00 52.23 62.32 69.61

Q [m³/h] 209 367 673 1146 Q [m³/h] 115 206 361 666 1132

∆p [Pa] 68 56 50 48 ∆p [Pa] 105 70 68 51 48

Every air flow lower than the above mentioned maximum value, will meet the listed A-weighted sound power level 55dB(A), for the respective dimension.

A-weighted sound power level LWA of 50dB(A) in the duct


Sn = Free air passage
SC0/ SC60 SC90/ SC120 Q = Air flow
∆p = Pressure drop

∅ Dn [mm] 100 125 160 200 ∅ Dn [mm] 80 100 125 160 200
Sn [m²] 0.00366 0.00698 0.01328 0.02283 Sn [m²] 0.0013 0.00322 0.00641 0.01253 0.02187

Sn [%] 46.60 56.88 66.05 72.67 Sn [%] 27.39 41.00 52.23 62.32 69.61

Q [m³/h] 148 260 477 812 Q [m³/h] 81 146 256 172 802

∆p [Pa] 34 28 25 24 ∆p [Pa] 53 35 29 26 24

Every air flow lower than the above mentioned maximum value, will meet the listed A-weighted sound power level 50dB(A), for the respective dimension.

A-weighted sound power level LWA of 45dB(A) in the duct


Sn = Free air passage
SC0/ SC60 SC90/ SC120 Q = Air flow
∆p = Pressure drop

∅ Dn [mm] 100 125 160 200 ∅ Dn [mm] 80 100 125 160 200
Sn [m²] 0.00366 0.00698 0.01328 0.02283 Sn [m²] 0.0013 0.00322 0.00641 0.01253 0.02187

Sn [%] 46.60 56.88 66.05 72.67 Sn [%] 27.39 41.00 52.23 62.32 69.61

Q [m³/h] 105 184 338 576 Q [m³/h] 58 104 181 334 569

∆p [Pa] 17 14 13 12 ∆p [Pa] 26 18 15 13 12

Every air flow lower than the above mentioned maximum value, will meet the listed A-weighted sound power level 45dB(A), for the respective dimension.

A-weighted sound power level LWA of 40dB(A) in the duct


Sn = Free air passage
SC0/ SC60 SC90/ SC120 Q = Air flow
∆p = Pressure drop

∅ Dn [mm] 100 125 160 200 ∅ Dn [mm] 80 100 125 160 200
Sn [m²] 0.00366 0.00698 0.01328 0.02283 Sn [m²] 0.0013 0.00322 0.00641 0.01253 0.02187

Sn [%] 46.60 56.88 66.05 72.67 Sn [%] 27.39 41.00 52.23 62.32 69.61

Q [m³/h] 74 131 240 408 Q [m³/h] 41 73 128 237 403

∆p [Pa] 9 7 6 6 ∆p [Pa] 13 9 7 6 6

Every air flow lower than the above mentioned maximum value, will meet the listed A-weighted sound power level 40dB(A), for the respective dimension.

11
SC Circular Fire Damper Cartridge
S2-D
05/2012

CORRECTION FACTOR ∆L

To obtain the sound power level for the LW oct octave midband

LWA = A-weighted sound power level


∆L = Correction factor
LW oct = ∆L + LWA
LW oct = Sound power level for each octave midband

[Hz] 63 125 250 500 1000 2000 4000 8000


2-4 m/s 25 3 -7 -13 -22 -27 -28 -24

6-8 m/s 18 5 1 -3 -8 -11 -14 -20

10-12 m/s 13 2 0 -3 -7 -9 -10 -15

Deduct LWA from the selection graph on p. 9

SELECTION GRAPH SCV

a = amount of turns

Q[m3/h]
10 20 50 100 200
300

a=-16 -12 -8 -5 0 5 10 20

V 100
200

100
40

LWA[dB(A)]
35
50
30

25

20

p[Pa] 10
2 3 4 5 10 20 50 60
Q[l/s] Q[m3/h]
10 20 50 100 200
300

a=-3 0 4 9 15 20

V 125
200
25

100 40

35
50 LWA[dB(A)]
30

25

20

p[Pa] 10 12
2 3 4 5 10 20 50 80
Q[l/s]
SC Circular Fire Damper Cartridge
S2-D
05/2012

Q[m3/h]
10 20 50 100 200 300
300

a=-5 0 5 10 15 20 25

V 160
200

40
100
35
LWA[dB(A)]
30
50

25

20

p[Pa] 10
2 3 4 5 10 20 50 60
Q[l/s]

Q[m3/h]
10 20 50 100 200 300
300

a=-3 10 15 20 25
200

V 200
100 40

35
LWA[dB(A)]
50
30

25

20

p[Pa] 10
2 3 4 5 10 20 50 80
Q[l/s]

SAMPLE ORDER

Sample order = SC60 200 FCU

1 2 3

1 Type of damper cartridge

2 Diameter of the damper cartridge

3 Option: unipolar end of range switch

If the damper is manipulated in any other way than described in this manual, Rf-Technologies will decline any
responsibility and the guarantee will immediately expire 13
SC Circular Fire Damper Cartridge
S2-D
05/2012

RF-Technologies
Lange Ambachtstraat 40
9840 Oosterzele
BELGIUM

DECLARATION OF CONFORMITY
We, RF-Technologies NV,
Declare under our sole responsibility that the product
Circular fire damper cartridge SC & SCV
To which this declaration relates, is in compliance with all the applicable essential requirements according
to EN 15650:2010, and other provisions of the European Council Directive (89/106/EEC)

SC & SCV
Circular fire damper cartridge
Fire resistance according to EN 1366-2 and classification according to EN13501-3
-Maintenance of the cross ection (under E) -Smoke leakage S
- Integrity E - Mechanical stability (under E)
- Insulation I

SC0 & SCV0


Range Type Wall Sealing Classification
Ø100 Rigid Wall Reinforced concrete min.110 With mortar E120(vei→o)S - (300Pa)
up to
Ø200 Rigid Floor Reinforced concrete min.110 With mortar E120(hei→o)S - (300Pa)

SC60 & SCV60


Range Type Wall Sealing Classification
Rigid Wall Reinforced concrete min.110 With mortar EI60(vei→o)S - (300Pa)
Ø100
Rigid Floor Reinforced concrete min.110 With mortar EI60(hei→o)S - (300Pa)
up to
Ø200 Metal stud gypsum plasterboard GKA With stone wool
Flexible Wall EI60(vei→o)S - (300Pa)
(acc.EN520) min.100 +cover plates

SC90 & SCV90


Range Type Wall Sealing Classification
Rigid Wall Reinforced concrete min.110 With mortar EI90(vei→o)S - (300Pa)
Ø80
Rigid Floor Reinforced concrete min.150 With mortar EI90(hei→o)S - (300Pa)
up to
Ø200 Metal stud gypsum plasterboard GKF With stone wool
Flexible Wall EI90(vei→o)S - (300Pa)
(acc.EN520) min.100 +cover plates

SC120 & SCV120


Range Type Wall Sealing Classification
Rigid Wall Reinforced concrete min.110 With mortar EI120(vei→o)S - (300Pa)
Ø80
Rigid Floor Reinforced concrete min.150 With mortar EI120(hei→o)S - (300Pa)
up to
Ø200 Metal stud gypsum plasterboard GKF With stone wool
Flexible Wall EI120(vei→o)S - (300Pa)
(acc.EN520) min.100 +cover plates

Normal activation conditions/sensivity according to ISO 10294-4:


-Sensing element load bearing capacity Pass
-Sensing element response temperature
Response delay (response time) according to EN 1366-2:
-Closure time Pass

Operational reliability according to EN 1366-2:


-Cycling Pass

Durability of response delay according to EN 1366-2:


-Sensing element response temp. and load bearing capacity Pass

Durability of operational reliability according to EN 15650:


50 cycles
-open and closing cycle
Protection against corrosion according to EN 60068-2-52: NPD
Damper casing leakage according to EN 1751: NPD

Declaration based on certificate conformity BC-606-0464-15650.08-2517

Date & place of issue Signature


Oosterzele, 1 February 2012 Tom Van Leuven 14
Technical Director