Tutorial Power System Analysis - Power Flow Analysis-Solution

The document describes several power flow analysis examples using different methods: 1) It provides a single line diagram of a power system and asks to determine the bus admittance matrix. 2) It provides a two-bus system and uses the Gauss-Seidel method to determine the voltage at the load bus. 3) It provides a three-bus system and uses Gauss-Seidel to determine bus voltages, line flows, and losses.

Uploaded by

Adriana Shoppe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
3K views

Tutorial Power System Analysis - Power Flow Analysis-Solution

The document describes several power flow analysis examples using different methods: 1) It provides a single line diagram of a power system and asks to determine the bus admittance matrix. 2) It provides a two-bus system and uses the Gauss-Seidel method to determine the voltage at the load bus. 3) It provides a three-bus system and uses Gauss-Seidel to determine bus voltages, line flows, and losses.

Uploaded by

Adriana Shoppe
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

Tutorial Power Flow Analysis

1) A power system network is shown in Figure 1. The values marked are impedances in per unit on
a base of 100 MVA. Convert network impedances to admittances and determine the bus
admittance matrix.

Figure 1: Single line diagram with network impedances

Solution

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 1


Tutorial Power Flow Analysis

2) In the power system network shown in Figure 2 below, bus 1 is a slack bus with V1 = 1.00 per
unit and bus 2 is a load bus with S2 = 280 MW + j60 Mvar. The line impedance on a base of 100
MVA is Z = 0.02+j0.04 per unit.
a) Using Gauss-Seidel method, determine V2. Use an initial estimate of V2(0) = 1.0+j0.0 and
perform three iterations.
b) If after several iterations voltage at bus 2 converges to V2 = 0.90-j0.10, determine S1 and
the real and reactive power loss in the line.

Figure 2: Single line diagram of two-bus power system


Solution
a)

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 2


Tutorial Power Flow Analysis

3) Figure 3 shows the single-line diagram of a simple three-bus power system with generation at
buses 1 and 3. The voltage at bus 1 is V1 = 1.0250 per unit. Voltage magnitude at bus 3 is fixed
at 1.03 per unit with a real power generation of 300 MW. A load consisting of 400 MW and 200
Mvar is taken from bus 2. Line impedances are marked in per unit on a 100 MVA base. Line
resistances and line charging susceptances are neglected.
a) Using Gauss-Seidel method and initial estimates of V2(0) =1.0+j0 and V3(0) =1.03+j0 and
keeping V3 = 1.03 pu, determine the phasor values of V2 and V3. Perform two iterations.
b) If after several iterations the bus voltages converge to
V2  1.001243  2.1  1.000571 j 0.0366898pu
V3  1.031.36851  1.029706 j 0.0246pu
Determine the line flows and the line losses and the slack bus real and reactive power

c) Construct a power flow diagram and show the direction of the line flows

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 3


Tutorial Power Flow Analysis

Figure 3: Single line diagram of three-bus power system

Solution

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 4


Tutorial Power Flow Analysis

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 5


Tutorial Power Flow Analysis

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 6


Tutorial Power Flow Analysis

4) In the two-bus system shown in Figure 4, bus 1 is a slack bus with V1 =1.00 pu. A load of 150
MW and 50 Mvar is taken from bus 2. The line admittance is y12 = 10-73.74 pu on a base of
100 MVA. The expression for real and reactive power at bus 2 is given by

P2  10V2 V1 cos(106.26   2  1 )  10V2 cos(73.74)


2

Q2  10V2 V1 sin(106.26   2  1 )  10V2 sin(73.74)


2

Using Newton-Raphson method, obtain the voltage magnitude and phase angle of bus 2. Start
with an initial estimate of V2(0) = 1.0 pu and 2(0) = 0. Perform two iterations.

Figure 4: Single line diagram of two-bus system

Solution

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 7


Tutorial Power Flow Analysis

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 8


Tutorial Power Flow Analysis

5) Figure 5 shows the single-line diagram of a simple three-bus power system with generation at
buses 1 and 2. The voltage at bus 1 is V =1.00 per unit. Voltage magnitude at bus 2 is fixed at
1.05 pu with a real power generation of 400 MW. A load consisting of 500 MW and 400 Mvar is
taken from bus 3. Line admittances are marked in per unit on a 100 MVA base. Line resistances
and line charging susceptances are neglected.
a) Show that the expression for the real power at bus 2 and real and reactive power at bus 3
are:-
P2  40V2 V1 cos(90   2  1 )  20V2 V3 cos(90   2   3 )
P3  20V3 V1 cos(90   3  1 )  20V2 V3 cos(90   3   2 )
Q3  20V3 V1 sin(90   3   1 )  20V3 V2 sin(90   3   2 )  40V3
2

b) Using Newton-Raphson method, start with the initial estimates of V2(0) =1.0+j0 and V3(0)
=1.0+j0 and keeping V2 = 1.05 pu, determine the phasor values of V2 and V3. Perform
two iterations.

Figure 5: Single line diagram of three-bus power system


Solution

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 9


Tutorial Power Flow Analysis

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 10


Tutorial Power Flow Analysis

6) From Figure 5, obtain the power flow solution using the fast decoupled algorithm. Perform two
iterations.

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 11


Tutorial Power Flow Analysis

EET 308-Power System Analysis (Semester II – Session 2016/2017) Page 12