0% found this document useful (0 votes)
44 views7 pages

220Kv Transmission Line Mardan Tarbela 1 - Test Report - : Customer

- The document is a test report for a distance relay on a 220kV transmission line from Mardan to Tarbela 1. - It provides details of the test object (distance relay), test system used, installation location, scheme settings, line and source parameters, and results of the impedance monitoring (IMP) test points including fault type, zone, impedance, angle, tripping time reference, actual tripping time, and deviation from reference. - The IMP monitor test points show the distance relay operated correctly for faults within zones 1 and 2, with actual tripping times close to references times except for one point that deviated by 63.12%.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views7 pages

220Kv Transmission Line Mardan Tarbela 1 - Test Report - : Customer

- The document is a test report for a distance relay on a 220kV transmission line from Mardan to Tarbela 1. - It provides details of the test object (distance relay), test system used, installation location, scheme settings, line and source parameters, and results of the impedance monitoring (IMP) test points including fault type, zone, impedance, angle, tripping time reference, actual tripping time, and deviation from reference. - The IMP monitor test points show the distance relay operated correctly for faults within zones 1 and 2, with actual tripping times close to references times except for one point that deviated by 63.12%.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 7

- Test report -

- 220Kv Transmission Line Mardan Tarbela 1-

Customer
Name: Location:
Test job
Description:
Executed on: 11/18/2018 12:41:12 PM by: Administrator
Plant
Name:
Voltage level:
Bay:
Device under test
Designation: Distance RElay Order number: 421
Manufacturer: KoCoS Messtechnik AG Description:
Type series/Model:
Serial number:
Specification:
Test system
Name: ARTES 560 (ARTES 560) Serial number: 32901000255
Last adjustment: 10/26/2017 4:18:17 PM

created on: 11/18/2018 12:42:43 PM


ITTEHAD ELECTRIC CO. created by: Administrator
Signature:
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

Installation Location
Plant: Voltage level:
Bay:
Test object data
Designation: Distance RElay Serial number:
Manufacturer: KoCoS Messtechnik AG Build date: 14.11.2017
Type series/Model: HW-Version:
Specification: FW-Version:
Rated values: 5.000 A 63.509 V 50.000 Hz

IO-Interfaces
Analog inputs
Connection Signal Settings Ratio
Line voltage L1-N 63.509 (130.000) V 220.00/√3
kV/110.00/√3 V
Line voltage L2-N 63.509 (130.000) V 220.00/√3
kV/110.00/√3 V
Line voltage L3-N 63.509 (130.000) V 220.00/√3
kV/110.00/√3 V
Line current L1 4.000 In 1200.00 A/5.00 A
Line current L2 4.000 In 1200.00 A/5.00 A
Line current L3 4.000 In 1200.00 A/5.00 A
Binary outputs
Connection Signal Settings
Distance general trip command Normally open contact (NO)
Relay trip command Normally open contact (NO)
Voltage transformer - Energy system
Vendor/Type: Ratio: 220.00/√3 kV /
110.00/√3 V
Serial number: Power/Precision class: 0.000 VA /
Build date:
Current transformer - Energy system
Vendor/Type: Ratio: 1200.00 A / 5.00 A
Serial number: Power/Precision class: 0.000 VA / 0
Build date:

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 2/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

Scheme Settings
Instrument transformer Line current
Vendor/Type:
Serial number:
Build date:
Ratio: 1200.00 A / 5.00 A
Power/Precision class: 0.000 VA / 0
Instrument transformer Line voltage
Vendor/Type:
Serial number:
Build date:
Ratio: 220.00/√3 kV / 110.00/√3 V
Power/Precision class: 0.000 VA /

Line parameters
Line impedance Re/R1L;Xe/X1L
Z1L: 2.680 Ω 78.00 ° Fr=Re/R1L: 1.350
Z0L: 8.60 Ω 70.90 ° Fx=Xe/X1L: 0.700
Z01: 8.60 Ω 70.90 ° Fr1=Re1/R11: 1.350
Earth coefficient Fx1=Xe1/X11: 0.700
k0L: 0.740 -10.29 °
k01: 0.740 -10.29 °
Source parameters
Source impedance Earth coefficient
Z1s: 5.800 Ω 75.00 ° k0s: 1.000 0.00 °
Z0s: 23.200 Ω 75.00 °
Ze: 5.80 Ω 75.00 °

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 3/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

Settings IMP monitor


Non directional tripping time: 1s
Directional tripping time: 5s
Impedance correction: 1
Directional line: 172 °
-8 °
Shortest tripping time: 0.02 s

Distance protection test series


Duration: 10:32.582
Comments before testing:

Comments after testing:

IMP monitor test points

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 4/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

State Fault Zone Z |Z| Angle Tripping time


Loop (relative) Reference Actual Deviation
L1-E Z1 0.693 Z 1 1.616 Ω 78.00 ° 0.020 s 0.019 s -5.00 %
L1-E Z1 0.953 Z 1 2.221 Ω 78.00 ° 0.020 s 0.033 s 63.12 %
L1-E Z2 1.064 Z 1 2.481 Ω 78.00 ° 0.360 s 0.382 s 6.15 %
L1-E Z2 1.176 Z 1 2.740 Ω 78.00 ° 0.360 s 0.382 s 6.18 %
L1-E Z2 0.607 Z 3 3.260 Ω 78.00 ° 0.360 s 0.383 s 6.39 %
L1-E Z3 0.672 Z 3 3.606 Ω 78.00 ° 0.710 s 0.734 s 3.36 %
L1-E Z3 4.471 Ω 4.471 Ω 78.00 ° 0.710 s 0.732 s 3.08 %
L1-E Z3 5.249 Ω 5.249 Ω 78.00 ° 0.710 s n.t. 0.00 %
L1-E FIN 5.682 Ω 5.682 Ω 78.00 ° 1.000 s n.t. 0.00 %
L2-E Z1 0.693 Z 1 1.616 Ω 78.00 ° 0.020 s 0.019 s -6.25 %
L2-E Z1 0.953 Z 1 2.221 Ω 78.00 ° 0.020 s 0.034 s 67.50 %
L2-E Z2 1.064 Z 1 2.481 Ω 78.00 ° 0.360 s 0.388 s 7.74 %
L2-E Z2 1.176 Z 1 2.740 Ω 78.00 ° 0.360 s 0.382 s 6.15 %
L2-E Z2 0.607 Z 3 3.260 Ω 78.00 ° 0.360 s 0.382 s 6.11 %
L2-E Z3 0.672 Z 3 3.606 Ω 78.00 ° 0.710 s 0.732 s 3.15 %
L2-E Z3 4.471 Ω 4.471 Ω 78.00 ° 0.710 s 0.732 s 3.08 %
L2-E Z3 5.249 Ω 5.249 Ω 78.00 ° 0.710 s n.t. 0.00 %
L2-E FIN 5.682 Ω 5.682 Ω 78.00 ° 1.000 s n.t. 0.00 %
L3-E Z1 0.693 Z 1 1.616 Ω 78.00 ° 0.020 s 0.020 s -1.87 %
L3-E Z1 0.953 Z 1 2.221 Ω 78.00 ° 0.020 s 0.032 s 58.13 %
L3-E Z2 1.064 Z 1 2.481 Ω 78.00 ° 0.360 s 0.382 s 6.04 %
L3-E Z2 1.176 Z 1 2.740 Ω 78.00 ° 0.360 s 0.382 s 6.08 %

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 5/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

State Fault Zone Z |Z| Angle Tripping time


Loop (relative) Reference Actual Deviation
L3-E Z2 0.607 Z 3 3.260 Ω 78.00 ° 0.360 s 0.381 s 5.94 %
L3-E Z3 0.672 Z 3 3.606 Ω 78.00 ° 0.710 s 0.732 s 3.15 %
L3-E Z3 4.471 Ω 4.471 Ω 78.00 ° 0.710 s 0.733 s 3.26 %
L3-E Z3 5.249 Ω 5.249 Ω 78.00 ° 0.710 s n.t. 0.00 %
L3-E FIN 5.682 Ω 5.682 Ω 78.00 ° 1.000 s n.t. 0.00 %
L1-L2 Z1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.032 s 60.63 %
L1-L2 Z1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.032 s 61.88 %
L1-L2 Z2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.383 s 6.32 %
L1-L2 Z2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.381 s 5.94 %
L1-L2 Z2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.383 s 6.42 %
L1-L2 Z3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.731 s 1.56 %
L1-L2 Z3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.732 s 1.65 %
L1-L2 Z3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.732 s 1.61 %
L1-L2 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %
L3-L1 Z1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.033 s 63.12 %
L3-L1 Z1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.033 s 66.87 %
L3-L1 Z2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.382 s 6.04 %
L3-L1 Z2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.388 s 7.85 %
L3-L1 Z2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.382 s 6.11 %
L3-L1 Z3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.733 s 1.86 %
L3-L1 Z3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.732 s 1.67 %
L3-L1 Z3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.732 s 1.72 %
L3-L1 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %
L2-L3 Z1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.032 s 58.13 %
L2-L3 Z1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.033 s 62.50 %
L2-L3 Z2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.382 s 6.08 %
L2-L3 Z2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.382 s 6.15 %
L2-L3 Z2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.382 s 6.08 %
L2-L3 Z3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.733 s 1.74 %
L2-L3 Z3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.737 s 2.29 %
L2-L3 Z3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.733 s 1.84 %
L2-L3 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %
L1-L2-L3 Z 1 0.499 Z 2 1.702 Ω 78.00 ° 0.020 s 0.031 s 57.50 %
L1-L2-L3 Z 1 0.625 Z 2 2.135 Ω 78.00 ° 0.020 s 0.031 s 57.50 %
L1-L2-L3 Z 2 0.701 Z 2 2.394 Ω 78.00 ° 0.360 s 0.367 s 1.98 %
L1-L2-L3 Z 2 3.000 Ω 3.000 Ω 78.00 ° 0.360 s 0.368 s 2.15 %
L1-L2-L3 Z 2 3.346 Ω 3.346 Ω 78.00 ° 0.360 s 0.382 s 6.04 %

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 6/7
Plant: Bay:
Device under test: Distance RElay Specification:
Job: 2018-11-18 11:15

State Fault Zone Z |Z| Angle Tripping time


Loop (relative) Reference Actual Deviation
L1-L2-L3 Z 3 3.519 Ω 3.519 Ω 78.00 ° 0.720 s 0.732 s 1.63 %
L1-L2-L3 Z 3 4.125 Ω 4.125 Ω 78.00 ° 0.720 s 0.732 s 1.65 %
L1-L2-L3 Z 3 5.163 Ω 5.163 Ω 78.00 ° 0.720 s 0.732 s 1.63 %
L1-L2-L3 FIN 5.509 Ω 5.509 Ω 78.00 ° 1.000 s n.t. 0.00 %

Date: Name:
ITTEHAD ELECTRIC CO. Tested: 11/18/2018 12:41:12 Administrator
PM
Created: 11/18/2018 12:42:43 Administrator
PM
Page: 7/7