Miniature Circuit Breakers 02

The document discusses miniature circuit breakers (RI 60) and their technical specifications and accessories. The RI 60 is used for over-current protection and disconnection in case of electric shock. It comes in single-pole, two-pole, three-pole, and four-pole configurations. Accessories include auxiliary contacts, shunt trip releases, undervoltage releases, and busbars. Technical data includes standards, voltages, currents, frequencies, and more.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
58 views4 pages

Miniature Circuit Breakers 02

The document discusses miniature circuit breakers (RI 60) and their technical specifications and accessories. The RI 60 is used for over-current protection and disconnection in case of electric shock. It comes in single-pole, two-pole, three-pole, and four-pole configurations. Accessories include auxiliary contacts, shunt trip releases, undervoltage releases, and busbars. Technical data includes standards, voltages, currents, frequencies, and more.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Miniature

Circuit Breakers

RI 60

• RI 60 is used for over-current (overload and short-circuit) protection


of installations and devices, and as a disconnector in case of
electric shock
• RI 60 miniature circuit breakers are provided with two springs for
assembly to a 35 mm wide mounting rail (EN 60715). The springs
enable simple taking off irrespective of whether a busbar is
positioned below or above
• Special springs are available for fixing miniature circuit breakers with
two M5 screws
• A handle can be sealed in ON or OFF position
• Optional operation position
• Degree of protection IP20; degree of protection IP40 after
installation in a distribution box
• Additional colour indication of the position of main contacts
(red - contacts closed; green - contacts open)

Types
RI 61 single-pole
RI 61N single-pole + neutral pole
RI 61J single-pole (for DC circuits)
RI 62 two-pole
RI 62J two-pole (for DC circuits)
RI 63 three-pole
RI 63N three-pole + neutral pole
RI 64 four-pole

TECHNICAL DATA
AC DC
Standards IEC/EN 60898, IEC/EN 60947-2
Approvals VDE, GOST-R
No. of poles 1, 2, 3, 4, 1 + N, 3 + N 1. 2
Tripping characteristic (IEC/EN 60898) B, C, D, M C, M
Rated voltage Un V 230/400 -
Rated DC voltage max. 40 - 1 pole 440 - 2-pole
Un V
for t=15 ms 220 - 1-pole
Rated insulation voltage Ui V 500
Rated frequency f Hz 50/60 -
Rated current In A 0.2 to 63
Short-circuit capacity Icn kA 10 4.5
Selectivity class 3
Terminal capacity Cu 1.5 … 25
S mm2
Al 2.5 ... 25
Ambient temperature °C −25 … +55
Vibration resistance 3 g (8 - 50 Hz)

ORDERING DATA RI 61 - B - 16

Rated current In (A)


Tripping characteristic
Type
91
Miniature Circuit Breakers

RI 60

TRIPPING CHARACTERISTIC

B, C, D (EN 60898)


In ≥ 10 A
t (s)izklopni ~as
tripping time

nazna~eni tok
rated current x In

ACCESSORIES

AUXILIARY AND SIGNAL CONTACTS


• They are used with RI 60 miniature circuit breakers and RV 60 disconnection switches (0.5 module width).
• Delivered as a single unit or with RI 60 or RV 60, respectively; mounted on the left side by means of pins and screw.
• Serve for signalling of contact position of the breaker
• Degree of protectin IP20
• Types:
- PKJ, 2PKJ − one or two auxiliary changeover contacts; position of contacts corresponds to the position of
the main contacts of the breaker
- PKJ + SKJ − one auxiliary changeover contact and one signal change over contact (fault indicating contact)
- PKJ + SKJ + TEST − test button with two functions is added: signalling the position of signal contacts and
testing of control circuit (non-stable change of position of the contacts) by slight movement of push-button
upwards and downwards without change of contact position of the breaker

TECHNICAL DATA
Standards IEC/EN 60947-5-1
Rated insulation voltage Ui V 400
Rated operational voltage Ue V 230
Rated thermal current Ith A 16
Rated operational current
AC-15 Ie A 4 (Ue = 230 V)
DC-13 0.5 (Ue = 110 V)*
Terminal capacity S mm2 0.5 ... 2.5

*Connection of two auxiliary contacts in series at 220 V

92
Miniature Circuit Breakers

RI 60

SHUNT TRIP RELEASE VC


• Used with RI 60 miniature circuit breakers and RV 60 disconnection switches.
• Enables remote switch-off.
• Available as a single unit or together with RI 60 or RV 60; mounted on the the right side by means of pins and screw.

TECHNICAL DATA
Standards IEC/EN 60947-1
Control voltages AC 12, 24, 48, 60, 110, 230, 400
Uc V
DC 24, 48, 110
Range of control
Uc % 70 … 110
voltage
Max. tripping current AC 6 (12); 2.8 (24); 0.8 (48); 0.9 (60); 0.5 (110); 0.6 (230); 0.5 (400)
(at coil voltage) A (V)
DC 3 (24); 2 (48); 0.6 (110)
Rated frequency f Hz 50
Tripping time ms < 50
Terminal capacity S mm2 1.5 … 6

UNDERVOLTAGE RELEASE PC 60
• Used with RI 60, RI 120 miniature circuit breakers and RV 60, RV 120 disconnection switches;
• Protection of the load in the event of voltage drop (between 85% and 35% of its control voltage); uncontrolled restarting is
prevented;
• Indication of release position green/red;
• Mounted on the right side of the breaker;
• Test button for the correct function control;
• Degree of protection IP 20

TECHNICAL DATA
Standards IEC/EN 60947-1
Control voltage Uc V 24, 48, 120, 230, 400
Rated frequency f Hz 50
Coil power consumption W 3
Mechanical endurance op. c. 10,000
2
Terminal capacity S mm 0.75 … 2,5

OTHER ACCESSORIES
Busbar - universal
(for one-pole circuit breakers and one-pole circuit breakers with an auxiliary switch)
Designation Length (m) Cross-section (mm2)
G-1L-210 / 12 iso 0.21 12
G-1L-1000 / 12 iso 1 12
G-2L-1000 / 10 1 12

Busbar - fork-type, 3-phase


(for three-pole circuit breakers and one-pole circuit breakers in three-phase circuits)
Designation Length (m) Cross-section (mm2)
G-3L-1000 / 10 C 1 10
G-3L-1000 / 16 C 1 16
G-4L-1000 / 16 1 16

93
Miniature Circuit Breakers

RI 60

End caps (for three-phase busbars)

Designation Cross-section (mm2)


EK-C-3/10 10
EK-C-2+3/16 16

CONNECTION DIAGRAM
AC DC AUXILIARY CONTACTS
1-pole + N 2-pole 3-pole
PKJ 2PKJ, PKJ + SKJ

1-pole 2-pole
12 14 1 96 98 12 14 1

3-pole + N 4-pole

11 2 95 11 2

DIMENSIONS

RI 60, RV 60

PC 60
59
59
17.5
43
84

45

94