FRESH AIR CALCULATION

PACU-01

Design 475 lps


Average Velocity= 2.217 m/s
Free Area = 0.226 m2
Air flow (lps) = Velocity(m/s) x Free area (m2) x 1000
Air flow = 2.217 x 0.226x 1000= 501.04 lps

Therefore the actual fresh air exceeds the design value.

PACU-02

Design = 619 lps


Acutal Velocity= 4.91 m/s
Free Area = 0.13 m2
Air flow (lps) = Velocity(m/s) x Free area (m2) x 1000
Air flow = 4.91 x 0.13x 1000= 638 lps