B X L or D A: Calculation of Earth Grid Conductor Area As Per IEEE-80 258.40 3.744 475.39 SQMM

The document outlines the calculation of the cross-sectional area for an earth grid conductor according to IEEE-80. It provides the key parameters used in the calculation such as the thermal coefficient of resistivity at 0°C and a reference temperature, the specific heat and density of the conductor material, corrosion allowance percentage, and resistivity at the reference temperature. The calculation results in a required cross-sectional area of 475.39 square mm. A conductor with a cross-sectional area of 300 square mm is selected with dimensions of 50 mm x 6 mm.

Uploaded by

Vamsi Manoj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
130 views1 page

B X L or D A: Calculation of Earth Grid Conductor Area As Per IEEE-80 258.40 3.744 475.39 SQMM

The document outlines the calculation of the cross-sectional area for an earth grid conductor according to IEEE-80. It provides the key parameters used in the calculation such as the thermal coefficient of resistivity at 0°C and a reference temperature, the specific heat and density of the conductor material, corrosion allowance percentage, and resistivity at the reference temperature. The calculation results in a required cross-sectional area of 475.39 square mm. A conductor with a cross-sectional area of 300 square mm is selected with dimensions of 50 mm x 6 mm.

Uploaded by

Vamsi Manoj
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Calculation of Earth grid Conductor Area as per IEEE-80

Conductor size calculation :


K0 1/ α0 (or) 1/ αr-20 in °C = 258.40
TCAP Thermal Capacity Factor in J/cm /°C (= 4.184 × Specific Heat in
3
=
cal/ g/ °C × Specific Weight in gm/cc) 3.744

A Cross Sectional Area of the ground grid conductor = 475.39 Sqmm


1
 (1  cor )  I f 
TCAP 10 4
 K0  Tm 
x ln
 K T 

t f r  r  0 a 

d 2
A
Selected grid
conductor Area A  or   L X B = 300 Sqmm

4
Size of the ground grid conductor chosen L B
Flat 50 6

α0 Thermal Coefficient of resistivity of ground conductor at 0°C 0.00387


per °C

αr Thermal Coefficient of resistivity of ground conductor at a = 0.00423 per °C


reference temperature, Tr in per °C

s 0.114 cal/gm/°C
Specific heat of the material, cal/gm /°C =

δ 7.85 gm/cm3
Density of material (Specific Weight), gm/cm3 =
0.00
cor Corrosion allowance in percentage = %

15.0
ρr Resistivity of ground conductor (Material) at Tr in μ Ω-cm = μ Ω-cm
50.0 °C
Ta Ambient air temperature in °C =
500.0 °C
Tm Maximum allowable temperature in °C =
If Fault current 20 kA
t Duration of fault current 3 sec