18. DETAILED COATING SPECIFICATIONS
COATING SYSTEM DCS100
APPLICATION CONDITIONS:
Normal environment
Ferritic substrate below 70°C
(This specification applies to the painting of all items exposed to non-corrosive indoor and outdoor
conditions, namely, external surfaces of gearboxes, pumps, valves, air receivers, compressors and
piping (refer to detailed list for specifics)
PROCESS: ACTIVITY DFT
SURFACE PREPARATION: Abrasive blast-clean to Grade Sa 2,5 (ISO
8501-1).
PRIMER COAT Apply by brush, airless spray or dipping, one 15 to 25 micrometres
coat Single Pack Etch Primer.
UNDERCOAT: After allowing sufficient time for the primer 20 to 30 micrometres.
coat to dry, apply by brush or airless spray,
one coat of Alkyd Universal Undercoat.
FINAL COAT: After allowing sufficient time for the 25 to 30 micrometres
undercoat coat to dry, apply one coat of High
Gloss Alkyd Enamel.
Total dry film thickness of coating system: 60 to 85 micrometres
GENERAL: After installation, lining up, grouting etc., all
damage shall be repaired and coatings made
good to the Engineer’s approval.
ADDITIONAL NOTES:
With respect to aspects not mentioned in the Detailed Coating Specification (e.g. overcoating and
curing times, mixing ratios, pot life, thinning, safety precautions etc.), the manufacturer’s
recommendations shall be strictly adhered to (refer to specific Product and Material Safety Data
Sheets).
SAFETY NOTE:
The manufacturer’s recommendations regarding the safe handling and use of these materials shall be
adhered to.
Please consult the Material Safety Data Sheets for detail.
RECOMMENDED / APPROVED SUPPLIERS AND/OR PRODUCTS:
The following manufacturers and/or suppliers are recommended / approved based on results gained
through tests and experiences.
Any SABS approved supplier or products tested and accepted for use by a reputable testing facility.
ALTERNATIVE PRODUCTS WHICH MAY QUALIFY:
(Please contact the Engineer for latest test results)