Cable Size Calculation (24 VDC Power Supply) : Min Max Omin Omax

The document calculates the maximum cable length needed to power a solenoid valve from a 24 VDC power supply. It determines the solenoid's power consumption, operating voltages and current draw. Based on the minimum operating voltage, it calculates the maximum cable resistance and then determines the maximum cable length for various cable sizes to ensure the solenoid receives sufficient power along the run. The analysis finds that a 1.5 mm^2 cable can power the solenoid over 4.5 km from the 24 VDC source.

Uploaded by

Khairul Ashraf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
107 views3 pages

Cable Size Calculation (24 VDC Power Supply) : Min Max Omin Omax

The document calculates the maximum cable length needed to power a solenoid valve from a 24 VDC power supply. It determines the solenoid's power consumption, operating voltages and current draw. Based on the minimum operating voltage, it calculates the maximum cable resistance and then determines the maximum cable length for various cable sizes to ensure the solenoid receives sufficient power along the run. The analysis finds that a 1.5 mm^2 cable can power the solenoid over 4.5 km from the 24 VDC source.

Uploaded by

Khairul Ashraf
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 3

CABLE SIZE CALCULATION (24 VDC POWER SUPPLY)

LOAD REQUIREMENT : Solenoid Valve POWER SUPPLY REQUIREMENT :

Power Consumption (P) 0.43 Watts Minimum (Vmin) 13 VDC Based on IS Barrier Output (V>=13)
Nominal Oper. Voltage (Vo) 11.22 VDC Maximum (Vmax) VDC
Min. Oper. Voltage (Vomin) 9.376 VDC Minimum operated voltage based on 32mA minimum current pull in voltage as per solenoid datasheet (32mA
Max. Oper. Voltage (Vomax) VDC

Current ( Io ) 0.038324 Amps (P/Vo) Current at Nominal output (0.43W and at coil rating 293ohm)
Resistance ( Ro ) 292.7637 Ohms (Vo/Io) Coil rating based on solenoid datasheet (293ohm)

Oper. Current at Minimum Voltage (Imov) 0.032026 Amps (Vomin/Ro) Operating current pull in voltage Based on solenoid datasheet (>=32mA)

Maximum Resistance of Cable (Rmax) 113.1587 Ohms (Vmin-Vomin)/(Imov)

Type of Cable (Nominal Area of Conductor) Maximum Resistance of Cable (ohm/km) (Rc) - Based on Kerpen Instrument Cables

1 pair 0.5 mm² 36.7 (Note : May vary from one ca


1 pair 0.75 mm² 25.0 manufacturer to anoth
1 pair 1.0 mm² 18.4 Hi essence
1 pair 1.3 mm² 14.2
1 pair 1.5 mm² 12.3 Hi essence

Maximum Cable Length for 0.5 mm² 1541.67 metres (1000 x Rmax)/(Rcx2)
Maximum Cable Length for 0.75 mm² 2263.17 metres (1000 x Rmax)/(Rcx2)
Maximum Cable Length for 1.0 mm² 3074.96 metres (1000 x Rmax)/(Rcx2)
Maximum Cable Length for 1.3 mm² 3984.46 metres (1000 x Rmax)/(Rcx2)

420004182.xls
Written By Azizi
05/10/2019
Maximum Cable Length for 1.5 mm² 4599.95 metres (1000 x Rmax)/(Rcx2)

420004182.xls
Written By Azizi
05/10/2019
Based on IS Barrier Output (V>=13)

erated voltage based on 32mA minimum current pull in voltage as per solenoid datasheet (32mA*293ohm)

Operating current pull in voltage Based on solenoid datasheet (>=32mA)

(Note : May vary from one cable


manufacturer to another)