IEEE 43 (Testing Insulation Rotating Machine)
IEEE 43 (Testing Insulation Rotating Machine)
Abstract: Radio Influence Voltage (RIV) testing was safely measure the high frequency PD signals and
developed and is still heavily used in North America, a voltage divider to measure the test voltage.
while most other countries prefer Partial Discharge 4. A PD measuring instrument to measure the
(PD) testing. Transformer manufacturing becomes apparent charge according to IEC 60270 [3].
increasingly an international business, requiring For transformer testing, a wide-band PD detector
knowledge of both testing methods. with a lower bandwidth of less than 70 kHz and
An overview of the similarities and differences an upper bandwidth of less than 300 kHz is
between Radio Influence Voltage and Partial recommended [4]
Discharge testing will be given. 5. A PD calibrator for calibrating the test circuit.
A computer controlled test system that automatically This calibrator simulates a PD with a known
measures both, Partial Discharge and Radio Influence apparent charge. The response of the test circuit
Voltage, will be explained. to this known impulse is measured and used to
calibrate the measuring instrument to this test
1. Introduction setup. When applying high voltage, the calibrator
usually has to be removed.
Description of PD Testing
Partial Discharge measurement and testing aims at
detecting and characterizing the electric sparks inside
an insulation, which could be harmful for the
insulation over time.
Since it is believed that the strongest sparks are
causing the most damage to the insulation, the main
emphasis is the correct measurement of the energy of
these strongest partial discharges.
-20dB
RIV
-40dB
150
Weigthing Factor [%]
100
50
0
1 10 100 1000
Pulse Repetition Rate [Hz]
PD RIV 160ms RIV 600ms Figure 5 RIV Processing Unit Hardware Module
Figure 4 Pulse Weighting Factor vs. Repetition Rate The RIV unit is a user-swappable module. Additional
outputs can be used to monitor the signals at an
Summary oscilloscope (1), record the level with an X-Y-plotter
(2), observe the inter-frequency (IF) (3), and listen to
PD and RIV testing have a lot in common, but also the signal using a headphone or external loudspeaker
many differences. While the market in the USA (4).
prefers RIV testing, most international customers From the very beginning, this detector was designed
demand PD testing. A tendency to move towards PD as a modular system with easy expandability. The
testing in the USA can be seen [3], but it is a very basic system can take up to four processing units that
slow progress. Until everybody uses PD testing a run in parallel.
measuring system that measures both quantities Most often used is the standard wide-band processing
simultaneously without additional work for the test unit together with a noise-gating module.
technician would be useful. The RIV processing unit is the latest addition to the
This idea is not new. An experimental device was product line. It fulfills the requirements of ANSI
built by IREQ more than 20 years ago [1]. Although C63.2 [5] and CISPR C57.12.90 [6] with regards to
so far commercial products don’t seem to be very transformer testing [7], [8]. As a special feature it
successful, probably due to the increased cost of the permits to measure according to the two definitions of
test equipment and difficulty in operating it. ANSI C63.2, namely with the standard 9kHz
This is going to change. To survive in today’s bandwidth with 160ms/160ms time constants and the
competitive markets, more and more test fields need special 4.5kHz bandwidth with 600ms/1s time
to measure both, RIV and PD. New computer constants for high voltage tests. As a third, the quasi-
controlled measuring systems simplify the operation peak time constants can be switched to 440ms as
and automatically create a test report or aid in failure described in IEC 60270 for a narrow-band PD
recognition without additional work from the detector. The input frequency can be tuned between
technician’s side. Thus, the time is ripe for a 800kHz and 1.2MHz.
combined PD and RIV measuring instrument.
[1] G. Vaillancourt, A.Dechamplain, R.Malewski “Simultaneous [6] C.I.S.P.R. Publication 16, Part 1: “Specification for Radio
Measurement of Partial Discharge and Radio-Interference Disturbance and Immunity Measuring Equipment”
Voltage”, IEEE Transactions on Instrumentation and
Measurement, Vol. IM-1, No. 1, March 1982 [7] IEEE C57.12.90 – 1999, “IEEE Standard Test Code for
Liquid-Immersed Distribution, Power, and Regulating
[2] IEC 60270 – 1997-06, “High-Voltage Testing – Partial Transformers”
Discharge Measurements”
[8] NEMA Standard No. 107 – 1987 “Methods of Measurement
[3] IEEE C57.113-1991 “IEEE Recommended Practice for Partial of Radio Influence Voltage (RIV) of High-Voltage Apparatus”
Discharge Measurements in Liquid-Filled Power Transformers
and Shunt Reactors” [9] User Manual “Digital Partial Discharge Detector LDS-6”,
Lemke Diagnostics GmbH, Germany, 2002
[4] IEC Standard 76-3 (1980), “Power Transformers Part 3:
Insulation level and dielectric tests”