DeltaV Distributed Control System Product Data Sheet

July 2017

M-series Intrinsically Safe I/O


„„ Features full system modularity

„„ Reduces system footprint

„„ Decreases installation time and expense

„„ Plug-and-play installation saves money

„„ Phased installation saves time

„„ Easy to use

„„ This fail-safe design enables you to DeltaV™ M-series Intrinsically Safe I/O makes your I.S. installations
initially install I.S. easy and compact.

„„ Real-time, online equipment additions

Introduction Decreases installation time and expense. DeltaV Intrinsically


Safe I/O are native DeltaV I/O cards that are part of the
DeltaV™ M-series Intrinsically Safe Input/Output (I.S. I/O)
controller’s I/O subsystem. This eliminates the need for third
provides the perfect solution to the precarious situation of
party barriers or interface mapping. Save even further on wiring
running I/O in hazardous areas. DeltaV I.S. I/O is a distributed
expenses by installing I.S. I/O in the field, close to the actual
I/O system capable of withstanding Class I Division 2 and
field devices. Mounting the controller with the I/O further
IEC Zone II environmental conditions. The I.S. I/O subsystem
reduces your wiring expenditures by eliminating the need for
connects field circuits and field devices to the DeltaV system.
long runs of multi-cores.
Intrinsically safe field circuits and field devices can enter Class
I Division 1, Zone 1, and Zone 0. The DeltaV I.S. I/O supports Plug-and-play installation saves money. We talked to
industry-standard AI, AO, DI, and DO, applications. customers like you to find out what you wanted in an I/O
system. We designed and produced exactly what you wanted.
Benefits The I.S. I/O subsystem is easy to use. All I.S. I/O components
Features full system modularity. The I.S. I/O subsystem plug into the I/O interface carrier. You can install the I/O
was designed to optimize your automation investment. All interface carriers to manage anticipated growth, without
components are fully modular and installable under power. purchasing the I/O interfaces until you’re ready to install your
You add I/O interface carriers and I/O interfaces in groups of 8 additional field devices.
channels, as you need them. The modular design enables you to Phased installation saves time. Mount the I/O interface
buy the exact amount of I/O cards and power/controllers that carrier and you are ready to begin installing the field devices.
you need. Add more DeltaV I/O as your system grows. I/O terminal blocks plug directly onto the I/O interface carrier—
Reduces system footprint. The state-of-the-art form factor there’s no need to have the I/O cards installed.
design of the DeltaV I/O components enables you to mount Easy to use. I.S. I/O interfaces and terminal blocks have I/O
the I/O interface carrier in a junction box in the field. You function keys. These keys ensure that the correct I/O card is
significantly reduce the footprint of your equipment and free up always plugged into the corresponding terminal block—easy!
valuable control room space for other uses.
M-series Intrinsically Safe I/O July 2017

This fail-safe design enables you to initially install I.S. I/O Product Description
quickly and efficiently. When you need to replace an I/O card
A variety of analog and discrete I/O cards are available to meet
the function key design ensures that you will always install it
your specific requirements. All I/O cards are enclosed in a
correctly. DeltaV I.S. I/O—easy to install and maintain.
common form factor that plugs into the I/O interface carrier.
Real-time, online equipment additions. Online addition The housing is clearly labeled with the I/O card type. Clearly
of new I/O interfaces means your process does not get visible LEDs on the top of the I/O card display the power,
interrupted. As new equipment is added, DeltaV Explorer error, and status to the channels included in the I/O card. (It is
acknowledges it and assigns it basic configuration. important to note that, when connecting standard I/O carriers
to I.S.I/O carriers, more standard I.O. carriers may not be added
after I.S. carriers—the I.S.I/O carriers must always be mounted
last in line.)

Hardware Specifications
Common Environmental Specifications for all I/O Interfaces
Category Specifications
Operating temperature -40 to 60 °C
(-40 to 140 °F)
Storage temperature -40 to 85 °C
(-40 to 185 °F)
Relative humidity 5 to 95% , non-condensing
Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Protection rating IP 20
Hazardous area/location* CENELEC Zone 2 IIC T4 hazardous area
I/O Interfaces Class I, Div 2, Groups A. B, C, D T4 hazardous locations.
Field circuits CENELEC Zone 0, IIC hazardous area or Class 1, Div 1, Groups
A,B,C,D hazardous locations
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from
5 to 16 Hz;
0.5 g from
16 to 150 Hz
Dimensions H 10.7 cm (4.2 in.)
W 4.1 cm (1.6 in.)
Depth 10.5 cm (4.1 in.)

www.emerson.com/deltav 2
M-series Intrinsically Safe I/O July 2017

*Refer to Zone 0 installation instructions (12P1990) for information on installing in hazardous areas.

Intrinsically Safe Analog I/O Cards


Specifications for DeltaV I.S. I/O AI, 4 to 20 mA with HART
Number of channels 8
Isolation
LocalBus to any channel 60 VAC
Between channels None
I. S. Channel to non-I. S. LocalBus 250 VAC
Nominal signal range (span) 4 to 20 mA
Full signal range 2 to 22 mA,
LocalBus current (12 VDC nominal) per card 600 mA
Line fault detection
short circuit current >21.5 mA
open circuit current < 0.5 mA
Resolution 16 bits
Calibration None required
Optional loop disconnect Yes
Voltage to transmitter @ 20 mA 15 V (min)
Temperature stability ±0.006% of span per °C

Specifications for DeltaV I.S. I/O AO, 4 to 20 mA with HART


Number of channels 8
Isolation
LocalBus to any channel 60 VAC
Between channels None
I. S. channel to non-I. S. LocalBus 250 VAC
Nominal signal range (span) 4 to 20 mA
Full signal range 1 to 22 mA,
LocalBus current (12 VDC nominal) per card 630 mA (typical)
Open circuit detection threshold 0.7 mA ±0.2 mA
Resolution 12 bits
Calibration None required
Optional loop disconnect Yes
Voltage to load 13 V (min) @ 20 mA
Load resistance 650 Ω max.
Temperature stability ±0.006% of span per °C

www.emerson.com/deltav 3
M-series Intrinsically Safe I/O July 2017

Intrinsically Safe Discrete I/O Cards


Specifications for DeltaV I.S. I/O DI
Number of channels 16
Isolation
LocalBus to any channel 60 VAC
Between channels None
I. S. Channel to non-I. S. LocalBus 250 VAC
Detection level for On >2.1 mA
Detection level for Off <1.2 mA
Output Impedance 100 Ω @ >6 mA (wetting current)
LocalBus current (12 VDC nominal) per card 350 mA
Switching hysteresis 200 µA nominal
Applicable specifications NAMUR, DIN 19234
Voltage applied to sensor 7.0 to 9.0 V from 1 k Ω ±10%
Line fault detection
short circuit < 100 Ω
open circuit > 50 k Ω
Maximum input frequency in pulse counting mode 20 Hz
Minimum pulse width detected 45 ms
Optional loop disconnect No

www.emerson.com/deltav 4
M-series Intrinsically Safe I/O July 2017

Specifications for DeltaV I.S. I/O DO


Number of channels 4
Isolation
LocalBus to any channel 60 VAC
Between channels None
I. S. Channel to non-I. S. LocalBus 250 VAC
Output range 22 V
11 V @ 45 mA load
25 V maximum
Off state leakage N/A
LocalBus current (12 VDC nominal) per card 560 mA
Field circuit power per card None
Configurable channel types: Output
Discrete Output Output stays in last state submitted by the controller.
Momentary Output Output is active for a pre-configured time period
(100 ms to 100 s).
Continuous Pulse Output Output is active as a percentage of a pre-configured base time
period (100 ms to 100 s). Resolution = 5 ms
Minimum output voltage 22 V (open circuit) 11 V at 45 mA
Maximum output voltage 25 V
Current limit per channel 45 mA (min)
Output supply ripple <0.5% of output (peak to peak)
Optional loop disconnect Yes

www.emerson.com/deltav 5
M-series Intrinsically Safe I/O July 2017

Intrinsically Safe Power Supply


The intrinsically safe power supply accepts 24 VDC power and converts it to 12 VDC to power the DeltaV I.S. I/O cards. The number
of I/O cards that can be powered by a single Intrinsically Safe Power Supply depends on the I. S. I/O card type. Optional power supply
redundancy is supported by adding power supplies at a rate of n + 1. The following table gives the specifications for the DeltaV I.S.
I/O Power Supply.

I.S. I/O Power Supply Specifications


Input voltage 18.5 36 VDC
Output current 5A
Output voltage 12 VDC ±5%
Input protection Internally fused, non-replaceable
Input/output isolation 250 V ac rms (tested at 1,500 V ac rms)
Input connection 2 part screw terminal, each duplicated
Cable size 2.5 mm2
Overvoltage protection Output protected at 110% to 120%
Operating temperature
optimum orientation (full load) 0 to 55 °C (32 to 131 °F)
worst case orientation 0 to 50 °C (32 to 122 °F)
Storage temperature -40 to +85 °C (-40 to 185 °F)
Relative humidity 5 to 95%, non-condensing
Airborne contaminants ISA-S71.04-1985 airborne contaminants class G3
Shock 10 g, 11 ms pulse width, to BS EN 60 068-2-27
Vibration 2 g @ 10-100 Hz to BS IN60 068-2-6 and BS 2011 part 2.1
Mounting On either slot of 2-wide power/controller carrier
LED Indicators:
Green – DC Power Input DC power is applied and internal fuse/diode is sound.
External connectors:
Primary power DC input, 3-wire

www.emerson.com/deltav 6
M-series Intrinsically Safe I/O July 2017

LocalBus Isolator
„„ The DeltaV LocalBus Isolator protects the I.S. I/O from fault voltages from AC main power supplies. The LocalBus Isolator also links
intrinsically safe I/O with non-intrinsically-safe I/O. The following table gives the specifications for the DeltaV LocalBus Isolator.

LocalBus Isolator Specifications


Dimensions Centimeters Inches
Height 11.0 4.3
Width 4.2 1.7
Depth 16.0 6.2
Weight 250 grams 8.7 oz

Carriers
All DeltaV I.S. I/O cards are contained in modular 8-wide carriers. Connect the carriers in the most efficient configuration for
your plant. The carriers have multi-pin connectors to ensure that I.S. I/O is never connected to non-I.S. I/O.

Power supplies for I.S. I/O modules using field wiring have their own modular carriers. These carriers connect between
the I/O carriers.

Use a LocalBus isolator to connect I.S. I/O with non-I.S. field wiring. The LocalBus isolator resides on its own carrier.

Carrier Specifications
Common Environmental Specifications for all Carriers
Category Specifications
Relative humidity 5 to 95% RH, non-condensing
Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Protection rating IP 20, NEMA 12
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from 5 to 16 Hz;
0.5 g from 16 to 150 Hz
Hazardous area/location* CENELEC Zone 2 IIC T4 hazardous areas
Class I, Div 2, Groups A, B, C, D T4 hazardous locations.
Applicable standards Factory Mutual Research Co., Class I Div 2, Groups A-D
hazardous locations.
EN 50 014: 1992 electrical apparatus for potentially explosive
atmospheres, general requirements.
EN 50 020: 1995 Electrical apparatus for potentially explosive
atmospheres, intrinsically safe “i”.
EC directive 94/9/EC (ATEX 100A)

www.emerson.com/deltav 7
M-series Intrinsically Safe I/O July 2017

*Refer to Zone 0 installation instructions (12P1990) for information on installing in hazardous areas.

8-Wide I.S. I/O Carrier Specifications


Capacity Eight I/O cards and eight terminal blocks
Dimensions Centimeters Inches
Height 16.5 6.5
Width 33.6 13.2
Depth 3.1 1.2

I.S. I/O Power Supply Carrier Specifications


Capacity One I.S. power supply
Dimensions Centimeters Inches
Height 16.5 6.5
Width 8.4 3.3
Depth 3.1 1.2

LocalBus Isolator Carrier Specifications


Capacity One LocalBus Isolator
Dimensions Centimeters Inches
Height 16.5 6.5
Width 8.4 3.3
Depth 3.1 1.2

I.S. 1-wide Carrier Extender (Left and Right) Specifications


Capacity Single cable
Dimensions Centimeters Inches
Height 16.5 6.5
Width 4.2 1.7
Depth 3.1 1.2

www.emerson.com/deltav 8
M-series Intrinsically Safe I/O July 2017

System Compatibility
„„ M-series I/O cards are not compatible with S-series Controllers and Carriers.

Ordering Information
Description Model Number
8-channel AI, 4-20 mA with HART
with I/O term block VE4012S2B1
with loop disconnect term block VE4012S2B2
8-channel AO, 4-20 mA with HART
with I/O term block VE4013S2B1
with loop disconnect term block VE4013S2B2
16-channel DI, switch/proximity detector VE4010B1
4-channel, DO, solenoid driver, IIC Gas Groups
with I/O term block VE4011B1
with loop disconnect term block VE4011B2
8-wide carrier without carrier extension cable VE4060C0
with carrier extension cable VE4060C1
24 VDC input I/O module supply and carrier VE5010
LocalBus isolator and carrier VE4070

Emerson
North America, Latin America: ©2017, Emerson. All rights reserved.
+1 800 833 8314 or
The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
+1 512 832 3774
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
Asia Pacific:
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
Europe, Middle East: guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.