Easy to use
This fail-safe design enables you to DeltaV™ M-series Intrinsically Safe I/O makes your I.S. installations
initially install I.S. easy and compact.
This fail-safe design enables you to initially install I.S. I/O Product Description
quickly and efficiently. When you need to replace an I/O card
A variety of analog and discrete I/O cards are available to meet
the function key design ensures that you will always install it
your specific requirements. All I/O cards are enclosed in a
correctly. DeltaV I.S. I/O—easy to install and maintain.
common form factor that plugs into the I/O interface carrier.
Real-time, online equipment additions. Online addition The housing is clearly labeled with the I/O card type. Clearly
of new I/O interfaces means your process does not get visible LEDs on the top of the I/O card display the power,
interrupted. As new equipment is added, DeltaV Explorer error, and status to the channels included in the I/O card. (It is
acknowledges it and assigns it basic configuration. important to note that, when connecting standard I/O carriers
to I.S.I/O carriers, more standard I.O. carriers may not be added
after I.S. carriers—the I.S.I/O carriers must always be mounted
last in line.)
Hardware Specifications
Common Environmental Specifications for all I/O Interfaces
Category Specifications
Operating temperature -40 to 60 °C
(-40 to 140 °F)
Storage temperature -40 to 85 °C
(-40 to 185 °F)
Relative humidity 5 to 95% , non-condensing
Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Protection rating IP 20
Hazardous area/location* CENELEC Zone 2 IIC T4 hazardous area
I/O Interfaces Class I, Div 2, Groups A. B, C, D T4 hazardous locations.
Field circuits CENELEC Zone 0, IIC hazardous area or Class 1, Div 1, Groups
A,B,C,D hazardous locations
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from
5 to 16 Hz;
0.5 g from
16 to 150 Hz
Dimensions H 10.7 cm (4.2 in.)
W 4.1 cm (1.6 in.)
Depth 10.5 cm (4.1 in.)
www.emerson.com/deltav 2
M-series Intrinsically Safe I/O July 2017
*Refer to Zone 0 installation instructions (12P1990) for information on installing in hazardous areas.
www.emerson.com/deltav 3
M-series Intrinsically Safe I/O July 2017
www.emerson.com/deltav 4
M-series Intrinsically Safe I/O July 2017
www.emerson.com/deltav 5
M-series Intrinsically Safe I/O July 2017
www.emerson.com/deltav 6
M-series Intrinsically Safe I/O July 2017
LocalBus Isolator
The DeltaV LocalBus Isolator protects the I.S. I/O from fault voltages from AC main power supplies. The LocalBus Isolator also links
intrinsically safe I/O with non-intrinsically-safe I/O. The following table gives the specifications for the DeltaV LocalBus Isolator.
Carriers
All DeltaV I.S. I/O cards are contained in modular 8-wide carriers. Connect the carriers in the most efficient configuration for
your plant. The carriers have multi-pin connectors to ensure that I.S. I/O is never connected to non-I.S. I/O.
Power supplies for I.S. I/O modules using field wiring have their own modular carriers. These carriers connect between
the I/O carriers.
Use a LocalBus isolator to connect I.S. I/O with non-I.S. field wiring. The LocalBus isolator resides on its own carrier.
Carrier Specifications
Common Environmental Specifications for all Carriers
Category Specifications
Relative humidity 5 to 95% RH, non-condensing
Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Protection rating IP 20, NEMA 12
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from 5 to 16 Hz;
0.5 g from 16 to 150 Hz
Hazardous area/location* CENELEC Zone 2 IIC T4 hazardous areas
Class I, Div 2, Groups A, B, C, D T4 hazardous locations.
Applicable standards Factory Mutual Research Co., Class I Div 2, Groups A-D
hazardous locations.
EN 50 014: 1992 electrical apparatus for potentially explosive
atmospheres, general requirements.
EN 50 020: 1995 Electrical apparatus for potentially explosive
atmospheres, intrinsically safe “i”.
EC directive 94/9/EC (ATEX 100A)
www.emerson.com/deltav 7
M-series Intrinsically Safe I/O July 2017
*Refer to Zone 0 installation instructions (12P1990) for information on installing in hazardous areas.
www.emerson.com/deltav 8
M-series Intrinsically Safe I/O July 2017
System Compatibility
M-series I/O cards are not compatible with S-series Controllers and Carriers.
Ordering Information
Description Model Number
8-channel AI, 4-20 mA with HART
with I/O term block VE4012S2B1
with loop disconnect term block VE4012S2B2
8-channel AO, 4-20 mA with HART
with I/O term block VE4013S2B1
with loop disconnect term block VE4013S2B2
16-channel DI, switch/proximity detector VE4010B1
4-channel, DO, solenoid driver, IIC Gas Groups
with I/O term block VE4011B1
with loop disconnect term block VE4011B2
8-wide carrier without carrier extension cable VE4060C0
with carrier extension cable VE4060C1
24 VDC input I/O module supply and carrier VE5010
LocalBus isolator and carrier VE4070
Emerson
North America, Latin America: ©2017, Emerson. All rights reserved.
+1 800 833 8314 or
The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
+1 512 832 3774
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
Asia Pacific:
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while every
effort has been made to ensure their accuracy, they are not to be construed as warranties or
Europe, Middle East: guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.