Planing

The summary identifies issues found across multiple substations including missing fire extinguishers, covered smoke detectors, non-working lighting fixtures, incorrect lighting connections, locked panels/drawers, non-working air conditioners, damaged equipment, and alarm/warning issues.

Uploaded by

Atiq Ur Rehman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views16 pages

Planing

The summary identifies issues found across multiple substations including missing fire extinguishers, covered smoke detectors, non-working lighting fixtures, incorrect lighting connections, locked panels/drawers, non-working air conditioners, damaged equipment, and alarm/warning issues.

Uploaded by

Atiq Ur Rehman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 16

Classifications/ Substation

Fire fighting system Lighting & sockets Air conditions Panels


No
Substation inspection
Roof & around
191/Limestone crusher

Missing fire
one lighting fixture not
extinguishers & all
Cables room smoke detectors are
working & no power
socket
covered

The drawer 111.FN312


is locked / CB No
3 lighting fixtures not
F01/02/04/05 are tripped
Substation working / wrong
in 110VDC charger / The
connection for EMG light
internal light not working
in 101CS110A01)

Roof & around


194/Storage Area

all smoke detectors are


Cables room covered
no power socket

drawer 113.FN092 is
3 lighting fixtures not locked/ door locks in
Substation working
one A.C not working
panels 101LV200 +
NA02/N03 are damage
291/Gypsum crusher

Roof & around

Missing fire
extinguishers & all
Cables room smoke detectors are
no power socket
covered
drawer 242.FN552 is
Substation one A.C not working
locked

Roof & around


391/Raw mill
Classifications/ Substation
Fire fighting system Lighting & sockets Air conditions Panels
No
391/Raw mill
Missing fire
Cables room extinguishers
no power socket

drawer 321.FN292 is
3 lighting fixtures not locked/ internal lights in
Substation working / wrong panels
connection for EMG light 301CS100A01&A02 are
damage

Roof & around

Cables room & Missing fire wrong connection for


extinguishers & all
diesel generator smoke detectors are exit lights & no power
room socket
covered
491/Kiln

one capacitor circuit is


damage/ door lock is
damage in panel
7 lighting fixtures not 331EP300A01/ There
Substation working
5 A.C not working
are an alarm in panels
331EP302A01&303/
There is a warning in
UPS

Roof & around


492/Cooler

Missing fire
wrong connection for
extinguishers & all
Cables room smoke detectors are
exit lights & no power
socket
covered

Substation 2 A.C not working The UPS is bypass

Roof & around


497/Clinker transport

Missing fire
extinguishers & all
Cables room smoke detectors are
no power socket
covered
497/Clinker transport
Classifications/ Substation
Fire fighting system Lighting & sockets Air conditions Panels
No

one lighting fixture not


Substation working
one A.C not working The UPS is bypass

Roof & around


591&592/Cement mill

Missing fire one lighting fixture not


extinguishers & all working & no power
Cables room smoke detectors are socket / wrong
covered connection for EMG light

door lock is damage in


some bulbs not working/ panel 501CS100A03/
Substation wrong connection for one A.C not working Battery test is fault in
EMG lights UPS 110VDC
502UP100A01

Roof & around

Missing fire
no power socket /
691/Packing plant

extinguishers & all


Cables room smoke detectors are
wrong connection for
EMG light
covered
in panels
601CS100A01&A02
some earthing wire
wrong connection for
Substation EMG lights
2 A.C not working disconnect & some
cables disconnect w/o
isolation/ The capacitor
banks disenergize

Roof & around


791/Compressor
room1

Cables room
791/Compressor
Classifications/ Substation
room1
Fire fighting system Lighting & sockets Air conditions Panels
No
The capacitor bank
all smoke detectors are
Substation covered
one A.C not working 701.LV100-NA04
disenergize
792/Compressor room2

Roof & around

Cables room

The capacitor bank


all smoke detectors are some lighting fixtures not 702.LV100-NA03
Substation covered working
one A.C not working
disenergize / The UPS
disenergize

Roof & around


891/Main substation

Missing fire
extinguishers & all
Cables room smoke detectors are
no power socket
covered

1 lighting fixture not door locks are damage


Substation working/ wrong 3 A.C not working in panels
connection for exit light 701CS100A01&A02
Classifications/ Substation
Fire fighting system Lighting & sockets Air conditions Panels
No
Sub controller room inspection
Sub controller
reclaim reclai

Missing fire
mer
Additive Mix

room extinguishers

Sub controller Missing fire


er

room extinguishers
stacker stacker

Sub controller Missing fire The A.C not working & 131.ST200A01 not
Weigh feeder of Additive Mix

room extinguishers cabin very hot working & short circuit

the internal light in the


Sub controller Missing fire The A.C not working &
panel 133.ST200A01
room extinguishers cabin very hot
not working

in panel
raw mill

311.WF150/250/350/450
Sub controller fire fighting sys not lighting switch not filter of air condition
the drawing not available
room working working need to clean
, internal light not
working & need to clean
/ HYD CF silo treatme

lighting switch not the drawing for panels


Water

Sub controller
smoke detector covered working / one lighting 762.WP212 not
nt

room fixture not working available

Sub controller fire extinguisher not whole lights not working filter of air condition
room available & room is dark need to clean
Rawmill

the drawing for panel


Sub controller
room

one lighting fixture not


321.HY110A01 not
room working
available
whole lights not working
Conditioni
ng tower

Sub controller fire extinguisher not & room is dark / the


The A.C not working
room available emergency light not
charging
whole lights not working the drawing for panel
Raw mill

Sub controller & room is dark / the 321.HG700A01 not


smoke detector covered
room emergency light not available & the display
charging not available
Classifications/ Substation
Fire fighting system Lighting & sockets Air conditions Panels
No
calciner
Blaster

Sub controller filter of air condition


smoke detector covered
of

room need to clean


analyzer
Kiln gas

Sub controller
room
Boiler Kiln burner lubricati

fire extinguisher not lock door for panels


Sub controller wrong connection for no air conditions for that
Kiln

on

available & no fire 431.HT120A01&431.GS


room fighting system
emergency lights room
160A01 are damage
lights not working /
Sub controller fire extinguisher not wrong connection for
room available emergency lights & not
charging
Sub controller fire extinguisher not lighting switch not
one A.C not working
room available working
smoke detector
Cement

wrong connection for


Sub controller
mill 1

covered / fire
emergency lights & not
room extinguisher not
charging
available
Weigh feeder of

/ in panel
cement mill 1

511.WF150/250/350
fire extinguisher not
Sub controller filter of air condition door is damage ,
available / smoke
room detector covered
need to clean drawings not available &
arm of main circuit
breaker is damage
Sub controller
mill 2

Missing fire whole lights not working


Cem
ent

room extinguishers & room is dark


Cement Weigh feeder of
cement mill 2

/ in panel
fire extinguisher not 512.WF150/250/350
Sub controller
available / smoke internal light not working
room detector covered & arm of main circuit
breaker is damage

drawing for panel


Sub controller
silo 1

wrong connection for


smoke detector covered 611.SI100A01 not
room emergency lights
available
Classifications/ Substation
Fire fighting system Lighting & sockets Air conditions Panels
No
Cement

drawing for panel


Sub controller
silo 2
one lighting fixture not filter of air condition
smoke detector covered 612.SI100A01 not
room working need to clean
available

in panels of packer
Packing plant

machine 1&2 lock door


are damage / in panel of
Sub controller one lighting fixture not some air conditions not
packer machine 4 one
room working working
internal light not working
& still missing the Amp
meter for elevator

Transformer inspection
Limestone

wrong connection for


crusher

missing install fire


101LV100T01 extinguisher outdoor
emergency lighting / one
lighting fixture is damage
Storage

missing install fire


area

101LV200T01 extinguisher outdoor


Raw Gypsum
mill crusher

missing install fire


201LV100T01 extinguisher outdoor

missing install fire


331EP300T01 extinguisher outdoor

The smoke detector one lighting bulb not


401LV100T01 covered missing install working & outdoor push
fire extinguisher outdoor button is not working

331EP300T01
Kiln

431MD140T01
Kiln
Classifications/ Substation
Fire fighting system Lighting & sockets Air conditions Panels
No

one lighting fixture is not


331FN400T01 working

one lighting fixture is not


331FN110T01 working

missing install fire


441LV335T01 extinguisher outdoor
Cooler

one lighting fixture is not


401LV200T01 working
one lighting fixture is not
801LV200T01 working
transpo
Clinker

rtation

missing install fire one lighting fixture is not


401LV400T01 extinguisher outdoor working

push button lighting not


501LV100T01
Cement mill

working

wrong connection for


missing install fire
502LV100T01 extinguisher outdoor
emergency lighting / one
lighting bulb not working

wrong connection for


Packing

missing install fire emergency lighting &


plant

601LV100T01 extinguisher outdoor one lighting fixture not


working
Compr Compre

one indoor fixture


room2 room1

missing install fire


essor ssor

701LV100T01 extinguisher outdoor


lighting not working &
outdoor lighting broken
missing install fire
702LV100T01 extinguisher outdoor
substation

The smoke detector


one lighting fixture is not
Main

801LV100T01 covered missing install


working
fire extinguisher outdoor
Miscellaneous

Visitor book / LV panel


drawing

Visitor book / LV panel


drawing

Visitor book / LV panel


drawing
Miscellaneous

Visitor book / LV panel


drawing

one enclosure of
earthing pit is damage

Visitor book / LV panel


drawing / Telephone not
available

Visitor book / LV panel


drawing
Miscellaneous

Visitor book / LV panel


drawing / The main door
is damage & The MV
circuit breaker table not
available

Visitor book / LV panel


drawing

Visitor book / LV panel


drawing
Miscellaneous

Visitor book / LV panel


drawing / need cleaning

Visitor book / LV panel


drawing / need cleaning

Visitor book / LV&MV


panel drawing / The door
is damage / The
telephone is not working
Miscellaneous

The drawing not


available

The drawing not


available

room need to clean

Lock door is damage

Room door is damaged

Room door is damaged


Miscellaneous

the drawing for panel


421.BQ185A01 not
available

Drawing not available

Room door is damaged

Lock door is damage

Lock door is damage

Lock door is damage


Miscellaneous

The transformer
temperature gauge is
damage

The lock need repair /


still unlocked / The
transformer room need
cleaning

The lock need to


lubricate

The lock need to


lubricate
The lock need to
lubricate & The
transformer room need
cleaning
The lock need to
lubricate

The lock need to


lubricate / The
transformer temperature
gauge is damage
Miscellaneous

The lock need to


lubricate & oil leakage in
the transformer
The lock need to
lubricate & Silica gel
color is black
The transformer room
need cleaning / Silica gel
color is black
The transformer room
need cleaning
The transformer room
need cleaning

The lock need to


lubricate

The transformer room


need cleaning

open door could not

The transformer room


need cleaning & The
transformer temperature
gauge is damage