MANUAL fcps24fs6 PDF
MANUAL fcps24fs6 PDF
H1
Document 51883
4/14/2011 Rev:
P/N 51883:H1 ECN 11-237
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the National Fire Protection Association IMPORTANT! Smoke detectors must be installed in the
Standard 72 (NFPA 72), manufacturer's recommendations, same room as the control panel and in rooms used by the sys-
State and local codes, and the recommendations contained in tem for the connection of alarm transmission wiring, communi-
the Guides for Proper Use of System Smoke Detectors, which cations, signaling, and/or power. If detectors are not so
are made available at no charge to all installing dealers. located, a developing fire may damage the alarm system, crip-
These documents can be found at http://www.systemsen- pling its ability to report a fire.
sor.com/html/applicat.html. A study by the Federal Emer- Audible warning devices such as bells may not alert people
gency Management Agency (an agency of the United States if these devices are located on the other side of closed or
government) indicated that smoke detectors may not go off in partly open doors or are located on another floor of a building.
as many as 35% of all fires. While fire alarm systems are Any warning device may fail to alert people with a disability or
designed to provide early warning against fire, they do not those who have recently consumed drugs, alcohol or medica-
guarantee warning or protection against fire. A fire alarm sys- tion. Please note that:
tem may not provide timely or adequate warning, or simply
may not function, for a variety of reasons: • Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on • Studies have shown that certain people, even when they
roofs, or on the other side of closed doors. Smoke detectors hear a fire alarm signal, do not respond or comprehend the
also may not sense a fire on another level or floor of a building. meaning of the signal. It is the property owner's responsi-
A second-floor detector, for example, may not sense a first- bility to conduct fire drills and other training exercise to
floor or basement fire. make people aware of fire alarm signals and instruct them
on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire
may not reach the sensing chambers of smoke detectors • In rare instances, the sounding of a warning device can
because: cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or A fire alarm system will not operate without any electrical
chimneys may inhibit particle or smoke flow. power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
• Smoke particles may become “cold,” stratify, and not reach been properly maintained and replaced regularly.
the ceiling or upper walls where detectors are located.
Equipment used in the system may not be technically com-
• Smoke particles may be blown away from detectors by air patible with the control panel. It is essential to use only equip-
outlets. ment listed for service with your control panel.
• Smoke particles may be drawn into air returns before Telephone lines needed to transmit alarm signals from a
reaching the detector. premise to a central monitoring station may be out of service
The amount of “smoke” present may be insufficient to alarm or temporarily disabled. For added protection against tele-
smoke detectors. Smoke detectors are designed to alarm at phone line failure, backup radio transmission systems are rec-
various levels of smoke density. If such density levels are not ommended.
created by a developing fire at the location of detectors, the The most common cause of fire alarm malfunction is inade-
detectors will not go into alarm. quate maintenance. To keep the entire fire alarm system in
Smoke detectors, even when working properly, have sensing excellent working order, ongoing maintenance is required per
limitations. Detectors that have photoelectronic sensing the manufacturer's recommendations, and UL and NFPA stan-
chambers tend to detect smoldering fires better than flaming dards. At a minimum, the requirements of NFPA 72 shall be
fires, which have little visible smoke. Detectors that have ion- followed. Environments with large amounts of dust, dirt or
izing-type sensing chambers tend to detect fast-flaming fires high air velocity require more frequent maintenance. A main-
better than smoldering fires. Because fires develop in different tenance agreement should be arranged through the local man-
ways and are often unpredictable in their growth, neither type ufacturer's representative. Maintenance should be scheduled
of detector is necessarily best and a given type of detector monthly or as required by National and/or local fire codes and
may not provide adequate warning of a fire. should be performed by authorized professional fire alarm
Smoke detectors cannot be expected to provide adequate installers only. Adequate written records of all inspections
warning of fires caused by arson, children playing with should be kept.
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of Limit-C1-2-2007
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity 93% ± 2% RH (non- Always ground yourself with a proper wrist strap before han-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful dling any circuits so that static charges are removed from the
life of the system's standby batteries and the electronic com- body. Use static suppressive packaging to protect electronic
ponents may be adversely affected by extreme temperature assemblies removed from the unit.
ranges and humidity. Therefore, it is recommended that this Follow the instructions in the installation, operating, and pro-
system and its peripherals be installed in an environment with gramming manuals. These instructions must be followed to
a normal room temperature of 15-27º C/60-80º F. avoid damage to the control panel and associated equipment.
Verify that wire sizes are adequate for all initiating and indi- FACP operation and reliability depend upon proper installation.
cating device loops. Most devices cannot tolerate more than a Precau-D1-9-2005
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits
protection against such interference when devices are radioelectriques depassant les limites applicables aux
operated in a commercial environment. Operation of this appareils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
LiteSpeed™ is a trademark; and FireLite® Alarms is a registered trademark of Honeywell International Inc. Microsoft® and Windows® are registered
trademarks of the Microsoft Corporation.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about
our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact
Technical Services.
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Canadian Electrical Code, Part 1
This product has been certified to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with prod-
ucts not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the
approval of the local Authority Having Jurisdiction (AHJ).
1.1 General
The FCPS-24FS power supplies can be used as remotely mounted power supplies and battery char-
gers to power four noncoded or coded NACs. The Main FACP (Fire Alarm Control Panel) NAC(s)
is connected to the remote power supply input circuit(s). When the control input circuit activates
due to reverse polarity of the NAC from the FACP, the power supply will activate its Notification
Appliance Circuits.
During the inactive or nonalarm state, the power supply supervises its NAC field wiring for short
and open conditions. AC fail, battery, charger and ground fault troubles will also be monitored by
the power supply. If an NAC or power supply fault is detected, the power supply Normally-Closed
Trouble contact will open.
If an alarm condition occurs and the NAC is activated, the supervision is disabled and the Notifica-
tion Appliance Circuit is no longer supervised (except for shorts). Supervision of other power sup-
ply faults such as low battery, AC loss, ground fault and battery charger trouble will continue and
may be monitored via the Trouble relay contacts.
1.2 Features
• Self-contained in a lockable cabinet
• 24 VDC remote power supply
• Outputs are completely power-limited
• Two optically-isolated input/control circuits, compatible with 12 VDC and 24 VDC control
panel NACs
• Four output circuits:
– Fully filtered power
– Four 24 VDC Style Y (Class B) NACs (special application)
– Optional ZNAC-4 Class A converter module for conversion to Style Z NACs
– Alternatively, all four circuits may be configured as 24 VDC special application power
outputs
– Output circuits may be configured as resettable or nonresettable
• NAC Trouble LED - blinks to indicate the number of the circuit in trouble
• Maximum current available for any one output circuit: 3.0 amps
1.4 Jumpers
CAUTION: DISCONNECT POWER
! REMOVE ALL POWER (AC & DC) BEFORE CUTTING OR MOVING ANY JUMPERS.
24s8jp3b.wmf
• If the source voltage to the input circuit is a noncoded (steady
voltage) input signal, the jumper for the corresponding input
circuit should be in the default position which jumpers the
jumpers
bottom two pins (as illustrated in drawing at left).
Jumper positions shown
• If the source voltage to the input circuit is coded (variable for noncoded (steady)
voltage), the jumper for the corresponding input circuit should source voltage
be moved to jumper the top two pins.
1.6 Specifications
Refer to Figure 1.1 on page 12 for terminal locations.
Primary AC Power - TB1
• FCPS-24FS6(C) & FCPS-24FS8(C): 120 VAC, 60 Hz, 3.2 amps maximum
• FCPS-24FS6E & FCPS-24FS8E: 240 VAC, 50 Hz, 1.6 amps maximum
• Wire size: minimum #14 AWG with 600V insulation
Control Input Circuits - TB4, Terminals 3 (+) & 4 (-) and 7 (+) & 8 (-)
• Trigger Input Voltage: 9 to 32 VDC
• Input Current Draw in Alarm Polarity:
– 16 to 32 volts, 2.0 mA maximum per input
– 9 to 16 volts, 1.0 mA maximum per input
NAC/Output Circuits - TB2, Terminals 1 (+) & 2 (-), 3 (+) & 4 (-), 5 (+) & 6 (-) and
7 (+) & 8 (-) alarm polarity
• Supervised, Special Application and power-limited
• Voltage Rating: 24 VDC filtered
• Current:
– Maximum for any one circuit - 3.0 amps
– Maximum total continuous current for all output:
FCPS-24FS6 - 4.0 amps
FCPS-24FS8 - 6.0 amps
– Maximum total short term current (one hour maximum) for all outputs:
FCPS-24FS6 - 6.0 amps
FCPS-24FS8 - 8.0 amps
• Output Circuit Types:
– Four Style Y NACs (require 4.7 KEnd-of-Line Resistors) or
Style Z NACs using the optional ZNAC-4 Class A converter module
OR
– Four resettable or nonresettable 24 VDC power outputs
• Refer to the Fire•Lite Device Compatibility Document #15384 for listed compatible devices.
• For wiring requirements, refer to “Wire Requirements” on page 43.
Trouble Relay Contact Rating - TB5
• Fail-safe Form-C relay (normally energized, transfers with loss of power)
• 5.0 amps @ 24 VDC or 5.0 amps @ 30 VAC
Secondary Power (battery) Charging Circuit - JP4
• Supervised, nonpower-limited
• Supports lead acid type batteries only
• Float Charge Voltage: 27.6 VDC
• Maximum Charge Current: 1.5 A
• Battery fuse (F1) 15A, 32V (Canadian version is nonreplaceable 12A, 32V)
• Maximum Battery Capacity: 18.0 AH
• Minimum Battery Capacity: 7.0 AH
• Power supply draws maximum standby current of 65 mA from batteries
Auxiliary Special Application Power Output - TB4 Terminals 9 (+) & 10 (-)
• Special application power
• Power-limited, nonsupervised
• Voltage Rating: 24 VDC
• Current:
– 170 mA maximum with internal 7.0 Amp Hour batteries
Power-limited, Supervised,
Special Application
in NAC Mode
Nonpower-limited
To Transformer #1 NAC/Out 1 +
To Transformer #2 NAC/Out 1 -
Trouble Relay
NAC/Out 2 + Form-C Fail-safe
Supervised, NAC/Out 2 - Nonsupervised
Nonpower-limited NAC/Out 3 + (shown energized)
Earth NAC/Out 3 - Normally Open
AC Neutral NAC/Out 4 + Normally Closed
AC Hot Common
NAC/Out 4 -
OUT4 OUT3 OUT2 OUT1
- NAC4 + - NAC3 + - NAC2 + - NAC1 + TB2
AUX TBL
EARTH NEUT HOT NO NC COM
TB5
8 7 6 5 4 3 2 1
TB1
3 2 1
JP1 Ground Fault
Detection
(cut to disable)
see Note at
bottom of the
J2
JP1
page.
TRANSFORMER 2
J3
J3
JP2
ZNAC-4 Connector
JP2 & JP3
JP3
J1
Coded/Noncoded
Input Selection
TRANSFORMER 1
24fs8brd.wmf
SYNC IN -
- Sync Input
SYNC IN + 1
- + AC
GND NAC AC/
FLT BATT TRBL CHGR
SW1
ON + Sync Input
JP4 1 2 3 4 5 6 7 8 TB4
BATTERY
JP4 Supervised
+ Battery SW1 *Note: Auxiliary Power
- Battery LEDs Programming Output is power-limited
18 AH, 24 VDC but not supervised
Nonpower-
Charger Trouble/AC Loss (yellow) DIP Switches
F1 (change switch
limited NAC Trouble (yellow)
Battery Fuse settings only
Battery Trouble (yellow) when all power
15A, 32V
(Canadian version Ground Fault (yellow) (AC & DC) is
is nonreplaceable removed)
AC Power (green)
12 A, 32V)
Figure 1.1 FCPS-24FS Board Layout
NOTE: Cutting Ground Fault jumper JP1 voids UL/NFPA Style/Class identifications for circuits
unless Ground Faults are being monitored by an FACP connected to the power supply. Cut
jumper JP1 only if a panel connected to the power supply is monitoring for Ground Faults or with
the approval of AHJ (Authority Having Jurisdiction).
1.7 General
The FCPS may be used in a number of different applications. It may be used as a remotely-
mounted power supply and battery charger where it can provide up to four coded or noncoded, syn-
chronized or nonsynchronized NACs (Notification Appliance Circuits). Alternatively, output #4
can be used as a door holder circuit which will provide a steady 24 VDC output until an alarm con-
dition or AC fail condition causes it to drop to 0 VDC following a 10 second delay. All four out-
puts can also provide power.
Style Y NAC
Note: All NAC or Door
outputs can be Holder Power
converted to Style Z Style Y NAC Style Y NAC Style Y NAC FCPS Trouble
Output #4 Output #3 Output #2 Output #1 Contact Output
with a ZNAC-4
option module
24 VDC Specific
AC Power Application Power
NAC Control
Input #1
(from FACP)
Sync. Input
24fsblok.wmf
Battery Charger
One possible application for the FCPS remote power supply utilizes the NAC repeater feature. In
this application, one or two NACs are connected from the main FACP to the remote power supply
control input circuits. When the control input circuits are activated by the reverse polarity of the
NACs, the power supply will activate its corresponding output circuits as programmed by SW1
DIP switch configuration (refer to Table 3.1 on page 20).
During the inactive state, the remote power supply supervises its NAC field wiring for short and
open conditions. If a fault is detected, the power supply will enter a trouble condition and illumi-
nate the NAC Trouble LED. When the NACs are activated, the supervision is disabled and the cir-
cuits are no longer supervised (except for short circuit conditions). Supervision of other power
supply faults such as low battery, battery charger trouble, ground fault and AC loss will continue
and may be monitored via the power supply trouble relay.
If an application requires that all four outputs activate at the same time, only one NAC is required
from the FACP. For this application, the NAC is connected to control input circuit #1 and SW1
DIP switch is set for this operation.
1. Remove the PC board and transformers from the backbox before installing backbox. Set the
board and transformers aside in a safe, clean place. Avoid static discharge which may damage
static sensitive components on the board.
2. Mark and predrill holes for the top two keyhole mounting bolts.
3. Install two upper fasteners in the wall with the screw heads protruding approximately ¼”.
4. Using the upper keyholes, mount the backbox over the two screws.
5. Mark the lower two holes, remove the backbox from the wall and drill the mounting holes.
6. Mount the backbox, install the remaining fasteners and tighten all screws.
7. When the location is dry and free of construction dust, reinstall the PC board and transformers
and continue with the installation.
8. IMPORTANT! Make certain to connect the supplied grounding strap between the Earth
terminal on TB1 (AC Terminal Block) of the main circuit board and the chassis ground stud as
illustrated in Figure 2.1:
Mounting Plate
Grounding Strap
Ground Stud
24fsgrnd.wmf
Backbox
Top
2.875” (7.3 cm)
Depth = 3.050”
Backbox = 14.5” (7.75 cm)
(36.8 cm)
0.75”
(1.9 cm) 2.7”
9.1” (23.1 cm) (6.86cm)
Ground Stud
10.625”
(26.99 cm)
Height=15.00” Mounting Plate Pem Studs
(38.10 cm)
fcpscabb.wmf
Backbox Mounting Holes
4.7K ELR
Horn Strobe
Horn Strobe
24fsclsb.wmf
FCPS-24FS Circuit Board
Horn Strobes
Alarm Polarity
Shown
ZNAC-4
J3
24fsclsa.wmf
NOTE: The optional module mounting kit (P/N 90286) is required to install an addressable
module on the power supply main circuit board. The kit includes four female/female and four
male/female standoffs as well as four mounting screws.
*If the SLC device does not match the one in this figure,
refer to the SLC manual wiring conversion charts for leg-
acy and newer versions of the modules.
standoff standoff
standoff standoff
24fsmodltpH.wmf
Module Installation female/female standoffs
1. Remove FCPS-24FS main circuit board from
mounting plate by removing four corner screws.
2. Install four male/female standoffs through bottom of
board in holes indicated in illustration above.
female/female standoffs
3. Screw four female/female standoffs to male ends of
standoffs installed in Step 2 to secure in place.
4. Place addressable module over standoffs installed in mounting screw
Step 3 and secure with supplied screws.
24fsmodinstl.wmf
Input Circuits
Power-limited Circuit
Specific Application
Power & SLC are
Power-limited Circuits
24fsswitc.wmf
Switch 8 shown in
ON (Closed) position
sync input terminals to the FACP sync output connector instead of the FACP NAC.
Note that the Synchronization Type configured by DIP switches 1 and 2 must be set to the same type
as the signal being fed to the Sync Input circuit in the event that Selective Silence is employed.
Important! In Slave Mode, if the Input is active, but no signal is present on the Sync Input circuit,
the power supply will turn the NACs on steady until a sync signal appears. The NACs will turn off
when the Input becomes inactive.
Also in Slave Mode, if the Input is active and the Sync Input is suddenly lost (FCPS or wiring fail-
ure), there will be a three second period when NAC outputs are indeterminate. After this three sec-
ond period, the power supply will turn the NACs on steady until the Input becomes inactive.
NOTE: Control Input #2 (terminals 7 & 8) cannot be used to supervise the power supply for
internal troubles, but an ELR is still required for FACP wiring supervision.
• With SW1 switch 4 set to the ON position, AC Fail/brownout reporting will be delayed 2 hours
and the following trouble conditions will cause the normally energized Aux. Trouble Relay to
change states regardless of whether the panel is in alarm or standby:
– An AC fail condition at the power supply
– A battery fail condition at the power supply
– A battery charger fail on the power supply
– A ground fault condition on the power supply (zero impedance between the power supply
and ground
– A field wiring fault on the NAC output of the power supply. (If the panel is in alarm, only a
short circuit on the NAC will be detected as a trouble)
NOTE: The NAC Trouble LED will indicate which NAC circuit is in trouble by blinking once for
Circuit 1, twice for Circuit 2, three times for Circuit 3 and four times for Circuit 4. If more than one
circuit is in trouble, the LED will blink the highest circuit number in trouble.
• With SW1 switch 4 set to the OFF position, AC Fail/brownout reporting will occur
immediately and the Aux. Trouble Relay will change state only for AC Fail/brownout
conditions. A monitor module can be used to monitor the relay for AC fail.
SLC
NO
NC
T7
T6
FCPS-24FS6/8
Aux. Trouble Relay Monitor Module*
In this application, the power supply has been set as a master with synchronized outputs and selec-
tive silence (see SW1 switch settings in following illustration). All four FCPS-24FS output cir-
cuits, which are shown as NACs (Notification Appliance Circuits), can be controlled from one
input such as an addressable control module as illustrated in Figure 5.1. The control module can be
powered from the FCPS-24FS auxiliary 24 VDC power output (TB4, Terminals 9 & 10) and super-
vised by an EOL relay. An addressable relay module, programmed as an alarm output and a
silenceable point, can be used as a selective silence input.
The control module is shown to demonstrate the use of a remotely mounted device associated with
an addressable fire alarm control panel. The module could be replaced with any circuit capable of
polarity reversal, such as an FACP NAC.
Horn/Strobes Horn/Strobes
Alarm Polarity Shown Alarm Polarity Shown
Style Y (Class B)
Style Z (Class A)
Output/NAC 4
24fsapp7tpH.wmf
Internal Trouble Contact
ZNAC-4
Output/NAC 3
Option Module
Output/NAC 2
Output/NAC 1
FCPS-24FS
5. Supervise the power wiring between the FCPS-24FS auxiliary 24 VDC output on TB4,
Terminals 9 & 10 with an EOL relay (P/N: EOLR-1).
6. For a list of compatible devices, refer to the Fire•Lite Device Compatibility Document #15384.
7. IMPORTANT! When the power supply is programmed for both Selective Silence and Slave
Mode, TB4 Terminal 7 (IN+) must be jumpered to Terminal 9 (AUX+) and Terminal 8 (IN-)
must be jumpered to Terminal 10 (AUX-). The FACP will control the Selective Silence feature
with this configuration.
If the terminals are not jumpered as indicated, the horn portion of the horn/strobes will be
silenced at all times.
SYNC SYNC IN+ IN- OUT+ OUT- IN2+ IN2- AUX+ AUX-
1 2 3 4 5 6 7 8 9 10
TB4
5.2 Controlling Three NACs and One Door Holder With One
Input
In this application, the power supply has been set as a master with synchronized outputs. All four
FCPS-24FS output circuits, three NACs and one door holder, can be controlled from one input such
as an addressable control module as illustrated in Figure 5.2. The control module can be powered
from the FCPS-24FS auxiliary 24 VDC power output (TB4, Terminals 9 & 10).
The control module is shown to demonstrate the use of a remotely mounted device associated with
an addressable fire alarm control panel. The module could be replaced with any circuit capable of
polarity reversal, such as an FACP Notification Appliance Circuit.
Note: All NACs are supervised and power-limited
Style Z (Class A)
Style Y (Class B)
24fsapp6tpH.wmf
Control Module*
*If the SLC device does not match the one in this
figure, refer to the SLC manual wiring conversion
charts for legacy and newer versions of the modules.
Figure 5.2 Controlling Three NACs and One Door Holder With One Input
4. An End-of-Line Resistor must be installed between terminals 5 & 6 for control module wiring
supervision (the ELR value is dependent on the module employed).
5. For a list of compatible devices, refer to the Fire•Lite Device Compatibility Document #15384.
power supply output circuits 1 & 2 to turn on. Control Input #2 (TB4, Terminals 7 & 8) is con-
nected to an FACP Notification Appliance Circuit which is used to activate the power supply’s tem-
poral output circuits 3 & 4.
-NAC4+
+
OUT4
7
+
8
-NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL Temporal Bell Circuit 4
Internal Trouble Contact 7 OUT4
6
Temporal Bell Circuit 3
OUT3 OUT2
5
ZNAC-4
4
Option Module Horn/Strobe Circuit 2
SYNC IN -
SYNC IN +
3
OUT1+
OUT1-
FCPS-24FS 2
AUX +
AUX -
IN1-
OUT1
IN2+
Horn/Strobe Circuit 1
IN1+
IN2-
J3
1
TB4
3
NO NC COM
1 2 3 4 5 6 7 8 9 10 2
End-of-Line 1
JP3
JP1
TB5
Resistor supplied
JP2
Control Module*
*If the SLC device does not match the one in this
figure, refer to the SLC manual wiring conversion
charts for legacy and newer versions of the modules.
NOTE: All four outputs can be configured as resettable or all four can be configured as
nonresettable by setting the power supply for General Alarm and then connecting a resettable
power source to Control Input 1 or a nonresettable power source, such as the Aux. Power output
of the FCPS-24FS, to Control Input 1.
For addressable panel applications, an addressable monitor module can be used to monitor the trou-
ble contact of the FCPS-24FS and the resettable power connection from the FACP using an End-of-
Line power supervision relay. If the FCPS-24FS enters a trouble condition, the Normally Closed
trouble contact will open and if the resettable power from the FACP is lost, the Normally Closed
power supervision relay contact will open.
SLC
Power Output 4
Nonresettable
FCPS-24FS
Power Output 3
Nonresettable
Power Output 2
Resettable
Power Output 1
Resettable
T11
T10 T1
T9 T2
T8 T3
T7 T4
T6 T5
24fsapp4tpH.wmf
versions of the modules.
SW1 Switch Settings Relay
24 VDC EOLR-1
Resettable 1 = OFF
Power 2 = OFF No Sync (energized)
3 = OFF (master)
FACP 4 = ON (Aux Trouble Relay responds
to all troubles)
5 = OFF
Split Alarm
6 = ON
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
OUT3 OUT2
5
FACP 4 4 = OFF (no AC Fail
SYNC IN -
SYNC IN +
3
reporting delay)
OUT1+
OUT1-
AUX +
AUX -
2
IN2-
IN1+
IN2+
IN1-
OUT1
5 = OFF general alarm
J3
1
FCPS-24FS
6 = OFF
TB4
3
NO NC COM
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
1 7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
JP3
JP1
TB5
ELR
JP2
See Note 3
NAC1 -
(programmed
for sync)
+
24fsapp1c.wmf
Figure 5.5a: Supervised Master/Slave Connections (Filtered, Synchronized NAC Source)
5
4
4 = OFF (no AC Fail
SYNC IN -
SYNC IN +
3
FACP
OUT1+
OUT1-
AUX +
reporting delay)
AUX -
2
IN2-
IN1+
IN2+
IN1-
OUT1
J3
1
5 = OFF
TB4
3
NO NC COM
6 = OFF
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
1
7 = OFF (charger enabled)
JP3
JP1
TB5
ELR
JP2
Remote Sync
-
Output
+ 24fsapp1b.wmf
OUT3 OUT2
Standby Polarity Shown 5
4
SYNC IN -
SYNC IN +
3
OUT1+
OUT1-
FACP
AUX +
AUX -
2
IN2-
IN1+
IN2+
IN1-
24fsapp11b.wmf
OUT1
J3
FCPS-24FS 1
TB4
3
NO NC COM
AUX TBL
1 2 3 4 5 6 7 8 9 10 2
1
NAC with no
JP3
JP1
TB5
syncronization
JP2
ELR for
- FACP
SW1 Switch Settings
1 & 2 = sync (any setting
NAC1 NAC
but OFF/OFF)
+ 3 = OFF (master)
4 = OFF (No AC Fail
Reporting Delay)
5 = OFF general alarm
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
• The negative (-) battery terminal of the FCPS-24FS power supply must be connected to the
negative (-) battery terminal of the host FACP.
Cut JP1
24fsCanadiantpH.wmf
Battery - Battery -
*If the SLC device does not match the one in this figure, refer to the SLC man-
ual wiring conversion charts for legacy and newer versions of the modules.
6.1 Overview
This section contains instructions and tables for calculating power supply currents in alarm and
standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
FCPS-24FS6/8(C) 3.2
or 1 x or =
FCPS-24FS6/8E 1.6
[ ] [ ] x [ ] =
[ ] [ ] x [ ] =
Table 6.3 contains three columns for calculating current draws. For each column, calculate the cur-
rent and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calcu-
lation Column 2 and Calculation Column 3 to Table 6.4 on page 41.
Calculation Column 3
Calculate Column 1 Calculate Column 2
Secondary, Non-Fire Alarm
Device Type Primary, Non-Fire Alarm Current Primary, Fire Alarm Current
Current
(amps) (amps)
(amps)
Qty X (current draw) = Total Qty X (current draw) = Total Qty X (current draw) = Total
NAC/Output #1 [ ] X[ ]=
NAC/Output #2 [ ] X[ ]=
NAC/Output #3 [ ] X[ ]=
NAC/Output #4 [ ] X[ ]=
Current Draw [ ]= [ ]= [ ]=
from TB4
Terminals 9 & 10
NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
current 11 O
voltage 11
output
input circuit 8
circuit types 11
activation 8
maximum current 3.0 amps 11
compatibility 8
output circuit
see also control 11 current 11
installation 14
maximum current 8
see also NAC output 11
J Style 11
JP1 Jumper voltage rating 11
ground fault detection 10 output power 8
JP2 Jumper
Coded/Noncoded Input 10 P
JP3 Jumper
Power
Coded/Noncoded Input 10
nonresettable 8
Jumper
resettable 8
JP1 ground fault detection 9, 10
power supply
JP2 Coded/NonCoded Input 10 board layout drawing 12
JP3 Coded/Noncoded Input 10
connectors and jumpers 12
power supply requirements 38
L powering supply 38
LED power-limited 8
AC power 10 power-limited wiring 18
battery/charger trouble 10
Charger Trouble 10 R
Ground Fault 10
relay
NAC Trouble 10
trouble 8, 9, 11, 25
LED indicators 10
reporting delay
AC loss 26
M resettable power 23
mounting
see also installation 14 S
secondary power
N see also battery 11
NAC Special Application Power
activation 8 see also Auxiliary Power 11
coding 8 specifications 10
see also Notification Appliance Circuit 8 Startup Procedure 9
supervision 25 strobe synchronization 9
NAC Circuit Wiring 16 Style
NAC output see also NFPA Style 8
see also output circuit 11 Style Y
NAC style see also Class B 8
see alsoNFPA Style 8 supervision 8
NAC Trouble LED 10 NAC 25
NACs 9 trouble 25
NEC power-limited wiring requirements 18 synchronization
NFPA Style ADA compatible 8
see also Style 8 selectable 9
nonalarm state 8
Noncoded Input 10 T
nonresettable power 23
trouble
Notification Appliance Circuit supervision 25
see also NAC 8
trouble relay 8, 9, 11, 25
contact rating 11
trouble supervision 8
troubles 25
power supply 8
W
wiring 9
AC power 10
power-limited 18
Z
ZNAC-4 16
see also Class A Converter Module 8
Warn-HL-08-2009.fm
www.firelite.com