Rev. 2/DACT-UD: Intelligent Address-Able FACP With Optional 2nd Loop
Rev. 2/DACT-UD: Intelligent Address-Able FACP With Optional 2nd Loop
MS-9600
Rev. 2/DACT-UD: Intelligent Address-
able FACP with Optional 2nd Loop
Addressable
General
The Fire•Lite MS-9600 is a compact, cost-effective, intelligent
addressable fire alarm control panel with a capacity of 318
addressable Fire•Lite devices on one Signaling Line Circuit
(SLC) or a total of 636 addressable points with an optional
second loop (SLC-2). An optional modem (DACT-UD) is avail-
able for remote site upload/download and/or remote monitor-
ing.
Each Signaling Line Circuit (SLC) loop supports up to 159
addressable detectors including photoelectric, photoelectric
with heat, ionization, photoelectric duct, fixed heat, fixed heat
with rate-of-rise, and fixed high-heat detectors. It also supports
up to 159 addressable modules including monitor (two-wire
detector, normally open devices), dual-monitor functions (two
monitor circuits from one module, two addresses used), con-
trol (for Notification Appliance Circuits), and relay (two Form-
C) modules. The panel uses surface-mount technology and is
designed for ease of installation, programming, and mainte-
nance. It features the latest in advanced fire protection tech-
nology, including maintenance alert and automatic detector
test functions.
52103ph1.jpg
SPECIAL FEATURES:
• Optional modem.
• Remote site upload/download capability (with DACT-UD).
• Selectable strobe synchronization per NAC.
• Two-level user-programmable passwords.
• Remote site upload/download.
• Custom English labels (per point) may be manually entered
• Four Class B or two Class A NAC circuits. or selected from an internal library file.
• Two programmable Form-C relay outputs.
FEATURES • 99 software zones.
SLC Loop: User Interface:
• SLC can be configured for NFPA Style 4, 6, or 7 operation. • Optional modem (DACT-UD).
• SLC supports up to 318 addressable devices per loop (159 • Remote Acknowledge, Silence, Reset and Drill via address-
detectors and 159 monitor, control, or relay modules), able monitor modules, ACS Series annunciators or LCD-
including the new addressable dual-monitor module, heat 80F remote annunciator.
detectors, and duct detector.
• EIA-232 printer/PC interface (variable baud rate) on main
• SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG circuit board.
(3.31 mm²). Requires twisted, shielded wire (3,000 ft./914.4
• Integral 80-character LCD display with backlighting.
m untwisted, unshielded wire).
• Real-time clock/calendar with automatic daylight savings
adjustments.
Notification Appliance Circuits (NACs): • History file with 1,000-event capacity.
• Four onboard NACs with additional NAC capability using • EIA-485 supporting up to 32 ACS Series annunciators.
output control modules (CMF-300 or CMF-300-6). • EIA-485 supporting up to 32 LCD-80F annunciators.
• Silence Inhibit and Auto Silence timer options. • Maintenance alert warns when smoke detector dust accu-
• Continuous, March Time, Temporal or California code for mulation is excessive.
main circuit board NACs with two-stage capability. • Automatic device type-code verification.
• Selectable strobe synchronization per NAC. • One person audible or silent walk test with walk-test log and
printout.
Advanced Fire Technology: • Point trouble identification.
• Sensitivity testing with printable results, onsite or offsite. • Local piezo sounder.
• Automatic drift compensation. • Waterflow (nonsilenceable) selection per monitor point.
Programming and Software: • System alarm verification selection per detector point.
• Autoprogram (learn mode) reduces installation time. • PAS (Positive Alarm Sequence) and presignal delay per
point (NFPA 72 compliant).
• Fully programmable from local keypad, local PS-2 keyboard
or PC via PK-Plus Windows® utility.
Distance in
Wire Requirements Typical Wire Size
Feet (m)
10,000 feet 12 AWG (3.31 mm²): Belden 9583, Genesis
Twisted-pair, shielded
(3,048 m) 4410, Signal 98230, WPW D999.
8,000 feet 14 AWG (2.08 mm²): Belden 9581, Genesis
Twisted-pair, shielded
(2,438 m) 4408, Signal 98430, WPW D995.
4,875 feet 16 AWG (1.31 mm²): Belden 9575, Genesis
Twisted-pair, shielded
(1,486 m) 4406 and 4606, Signal 98630, WPW D991.
3,225 feet 18 AWG (0.821 mm²): Belden 9574, Genesis 52395d1.wmf
Twisted-pair, shielded
(983 m) 4402 and 4602, Signal 98300, WPW D975.
3,000 feet
Untwisted, unshielded 12 – 18 AWG (3.31 – 0.821 mm²).
(915 m)
BB-55F: Battery box, required to house two 25 AH batteries MMF-300-10: Ten-input monitor module. Mount one or two
and one CHG-120F battery charger. For batteries greater modules in a BB-2F cabinet (optional). Mount up to six mod-
than 25 AH, consult factory for housing/mounting arrange- ules on a CHS-6 chassis in a BB-6F.
ments. MMF-302-6: Six-zone interface module. Mount one or two
BB-26: Battery backbox, holds up to two 25 AH batteries. modules in a BB-2F cabinet (optional). Mount up to six mod-
ules on a CHS-6 chassis in a BB-6F.
CHG-120F: Remote battery charging system for lead-acid bat-
teries with a rating of 25 to 120 AH. CHG-120F or CHG-75 CMF-300-6: Six-circuit supervised control module. Mount one
required for charging greater than 25 AH batteries. or two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
CHG-75: Battery charger for lead-acid batteries with a rating
of 25 to 75 AH. CHG-120F or CHG-75 required for charging CRF-300-6: Six Form-C relay control module. Mount one or
greater than 25 AH batteries. two modules in a BB-2F cabinet (optional). Mount up to six
modules on a CHS-6 chassis in a BB-6F.
BAT Series: Batteries, see data sheet DF-52397.
NOTES: 1) Compatible with legacy Fire•Lite 300 Series
PRT/PK-CABLE: Cable printer/personal computer interface devices. Please consult factory for further information on previ-
cable. ous 300 Series devices: CP300/CP350, SD300(T)/SD350(T),
D350(R)P, M300, M301, M302, C304, and BG-10LX. 2) “A”
suffix should be included only when ordering ULC listed units
(e.g., SD355A, MMF-300A). 3) For more information on Com-
Compatible Addressable Devices patible Addressable Devices for use with the MS-9600, see
All feature a polling LED and rotary switches for addressing. the following data sheets (document numbers): AD355
CP355: Addressable low-profile ionization smoke detector. (DF-52386), BG-12LX (DF-52013), CMF-300-6 (DF-52365),
CRF-300-6 (DF-52374), CMF/CRF Series (DF-52130),
SD355: Addressable low-profile photoelectric smoke detector. CP355 (DF-52383), D350PL/D350RPL (DF-52398), H355
SD355T: Addressable low-profile photoelectric smoke detector Series (DF-52385), I300 (DF-52389), MMF-300 Series/MDF-
with thermal sensor. 300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-
52356), SD355/SD355T (DF-52384).
H355: Fast-response, low-profile heat detector.
H355R: Fast-response, low-profile heat detector with rate-of-
rise option.
Compatible Annunciators
AD355: Low-profile, intelligent, “Adapt” multi-sensor detector
(B350LP base included). EIA-485 interface: Built into the motherboard.
D350PL: Photoelectric low-flow duct smoke detector. ACS/ACM Annunciator Series: Allows annunciation of loop
modules and detectors. For more information, refer to data
D350RPL: Photoelectric low-flow duct smoke detector with sheet DF-52378.
relay option.
LDM Graphic Series: Lamp Driver Module series for use with
MMF-300: Addressable Monitor Module for one zone of nor- custom graphic annunciators. For more information, refer to
mally-open dry-contact initiating devices. Mounts in standard data sheet DF-51384.
4.0" (10.16 cm) box. Includes plastic cover plate and end-of-
line resistor. Module may be configured for either a Style B LCD-80F (Liquid Crystal Display) point annunciator: 80-
(Class B) or Style D (Class A) IDC. character, backlit LCD-type fire annunciators capable of dis-
playing English-language text. Up to 32 LCD-80F annunciators
MDF-300: Dual Monitor Module. Same as MMF-300 except it may be connected to the EIA-485 terminal mode serial inter-
provides two Style B (Class B) only IDCs. face on the MS-9600 motherboard. For more information,
MMF-301: Miniature version of MMF-300. Excludes LED and refer to data sheet DF-52185.
Style D option. Connects with wire pigtails. May mount in
device backbox.
MMF-302: Similar to MMF-300, but may monitor up to 20 con- Temperature and Humidity Ranges
ventional two-wire detectors. Requires resettable 24 VDC
power. Consult Device Compatibility Document for compatible This system meets NFPA requirements for operation at 0 –
smoke detectors. 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH(non-
condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
CMF-300: Addressable Control Module for one Style Y/Z life of the system's standby batteries and the electronic com-
(Class B/A) zone of supervised polarized Notification Appli- ponents may be adversely affected by extreme temperature
ances. Mounts directly to a 4.0" (10.16 cm) electrical box. ranges and humidity. Therefore, it is recommended that this
Notification Appliance Circuit option requires external 24 VDC system and its peripherals be installed in an environment with
to power notification appliances. a normal room temperature of 15 – 27°C/60 – 80°F.
CRF-300: Addressable relay module containing two isolated
sets of Form-C contacts, which operate as a DPDT switch.
Mounts directly to a 4.0" (10.16 cm) box, surface mount using
the SMB500.
BG-12LX: Addressable manual pull station with interface mod-
ule mounted inside.