Eaton 9PX UPS technical specifications (8 and 11 kVA models*)
Model overview
Catalog Power rating Dimensions Weight
number (VA/watts) Input Output (HxWxD, in.)** (lb.)
208V output, 50/60 Hz bundles
9PX8KHW 8000/7200 Hardwired Hardwired 10.2 (6U) x 17.3 x 27.6 190
9PX8K 8000/7200 Hardwired Hardwired, (3) L6-30R 10.2 (6U) x 17.3 x 30.0 205
9PX11KHW 11000/10000 Hardwired Hardwired 10.2 (6U) x 17.3 x 27.6 190
9PX11K 11000/10000 Hardwired Hardwired, (3) L6-30R 10.2 (6U) x 17.3 x 30.0 205
120/208V output, 50/60 Hz bundles
Hardwired, (2) L6-30R,
9PX8KTF5 8000/7200 Hardwired (18) 5-20R 15.3 (9U) x 17.3 x 30.0 300
Hardwired, (2) L6-30R,
9PX11KTF5 11000/10000 Hardwired (18) 5-20R 15.3 (9U) x 17.3 x 30.0 300
Hardwired, (2) L14-30R,
9PX11KTF11 11000/10000 Hardwired (8) 5-20R 15.3 (9U) x 17.3 x 27.6 377
**Each module of every 9PX bundle ships with a 4-post rail kit. ***Terminal block with L6-30P cord.
Battery backup times (in minutes)****
Load
(watts) Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs +5 EBMs
10000 3.0 10 18 25 34 42
7500 5.5 15 25 37 48 61
5000 10.0 25 42 61 80 98
2500 25.0 60 97 136 163 184
1000 74.0 159 237 341 461 541
****Runtimes are shown at full load with maximum power factor, are approximate and may vary with equipment, configuration,
battery age, temperature, etc. View interactive runtime graphs at www.eaton.com/9PX.
Additional specifications
General
Topology Double-conversion online
Configuration Rack/tower
Color Black and silver
Diagnostics Full system self test at power up
Warranty 2 years
Rail kit 4-post rail kit and tower pedestals included
Remote emergency power off ROO and RPO: Rear deck emergency stop connectors (for remote on/off and power
(REPO) off)
Contents (Ships with the UPS
following items) Network-MS Web/SNMP card
4-post rail kit
User manual
Quick start guide
Tower pedestals
Intelligent Power Software Suite CD
RS-232 serial cable
USB cable
Cable gland for hardwire connection
Phillips head screw driver
Electrical input
Input voltage range Full load: 176-276V, Derating: 100-276V
Nominal voltage 200/208/220/230/240V
Eaton.com/9PX TD153002EN November 2012
Page 2 of 2
Default voltage NEMA: 208V. IEC: 230V
Frequency 50/60 Hz
Frequency range 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
Input power factor >.99
Input current distortion <5%
Electrical output
Power ratings 8 kVA 200/208/220/230/240/250V: 8000 VA / 7200 watts
Power ratings 11 kVA 230/240V: 11000 VA / 10000 watts
220V: 11000 VA / 9900 watts
208V: 10000 VA / 9000 watts
200V: 10000 VA / 9000 watts
250V: 10000 VA / 9000 watts
Nominal voltage 208V default (200/208/220/230/240/250V)
Output voltage regulation ±1% steady-state
Voltage THD <2% for linear loads
Power factor 0.9+
Efficiency 94% with resistive load
Transfer time 0 ms
Battery
Optional extended battery 9PXEBM240RT
module (EBM)
Maximum number of EBMs Add up to 5 EBMs with the UPS ; add up to 12 EBMs with SC240RT 240V super
charger module
Battery description Sealed, lead-acid; maintenance free
Battery management ABM technology; 3-stage charging extends battery service life by 50% and provides
advance warning for battery replacement
Battery replacement Hot-swappable internal batteries and extended battery modules (EBMs)
Start on battery Cold-start enabled; first cold start is always forbidden
Communications
User interface Graphical display. UPS status in a single view.
LEDs 4 status-indicating LEDs
Communication ports RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables
included
Communications card slot Network Card-MS included
Power management software Eaton Intelligent Power Software Suite CD (included)
Environmental & standards
RoHS compliance Yes
Surge protection IEEE ANSI C62.41 Cat B2
Heat dissipation (BTU/hr; 9PX8K: Online: 1570. Battery: 2140
battery full charged, resistive 9PX11K: Online: 1920. Battery: 2900
load)
Audible noise <45 dB at 1 meter
Operating temperature 0 to 40°C (32°F to 104°F)
Safety conformance CE / cULus / NOM
EMC markings IEC 62040-2:2006 Cat C2 / CISPR22 Class A / FCC part 15 Class A
Storage temperature 0 to 35°C (32°F to 95°F); without batteries: -15 to 60°C (5°F to 140°F)
Relative humidity 0 to 95% non-condensing
Altitude <1,000 meters for nominal power; 10% power derating every 1000 meters (up to
3000 meters) at 40°C
*Due to continuing product improvement programs, specifications are subject to change without notice.
Eaton.com/9PX TD153002EN November 2012