0% found this document useful (0 votes)
516 views2 pages

PSR327 Compact Battery Charging Rectifier

This document summarizes a single-phase rectifier module that converts 230V AC to 220V DC with a power output of 2.7kW. It has a compact 1/4 x 19" 3U design with sinusoidal input current and integrated overvoltage protection. The modular design allows additional modules to be added for higher power requirements. The modules communicate via CAN-Bus interface and include features like temperature controlled fan cooling and compatibility with lead-acid and NiCd batteries.

Uploaded by

fan liu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
516 views2 pages

PSR327 Compact Battery Charging Rectifier

This document summarizes a single-phase rectifier module that converts 230V AC to 220V DC with a power output of 2.7kW. It has a compact 1/4 x 19" 3U design with sinusoidal input current and integrated overvoltage protection. The modular design allows additional modules to be added for higher power requirements. The modules communicate via CAN-Bus interface and include features like temperature controlled fan cooling and compatibility with lead-acid and NiCd batteries.

Uploaded by

fan liu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

RECTIFIER

PSR327
In: 230VAC
Out: 220VDC (2.7kW)

· Single-phase module 1/4 x 19’’, 3U Power supply modules of series PSR327 are com-
pact battery charging rectifiers with an optimized
with sinusoidal input current (PFC) switching principle and therefore with a very high
power density. The rectifier can be used in all DC
· Input overvoltage protection applications with or without battery.
· “Hot plug-in“ design with backplane Due to the modular concept and a high scalability
the user is able to equip the power supply with
connection
additional modules according to his actual power
· High power density profile. The chargers are very user friendly and can
be swapped and upgraded during operation.
· CAN-Bus interface
The devices get their operation parameters via
· Integrated decoupling from the DC bus the system wide CAN communication bus. After a
successful login a central monitoring unit controls
· Front-to-rear airflow with temperature- and monitors the devices. In case of CAN-Bus in-
terruption the modules operate continuously with
controlled fan cooling internal default values. The current sharing bet-
· Suitable for Pb and NiCd batteries ween the rectifier modules operates independent
of the CAN communication bus. Up to 4 modules
can be integrated in a 19” sub rack with 3U
(216V/50A).

DC power supply facilities with or without battery in


all areas of industry, power generation and power
distribution.
Type PSR327/220-12.5
Article code 101-027-188.00
Nominal input voltage 230VAC ±20%
Nominal input current 12.9AAC
Input frequency range 47-63Hz
Power factor >0.99 at Pnom >50%
Total harmonic distortion <5%
Efficiency ≥91%
Internal input fusing 16A (6.3x32mm)
Nominal output voltage 216VDC
Nominal output current @ 216V 12.5ADC
Nominal output power 2.7kW
Charge characteristic IV characteristic according to DIN41772/DIN41773; power limited
Adjustable output voltage range 170 - 295VDC
Default value of the charging voltage (factory set) 245.2VDC (2.27V/cell; lead acid battery); over CAN dongle settable for NiCd batteries
Output over voltage Vo> (factory set) 270VDC (2.5V/cell; lead acid battery); over CAN dongle settable for NiCd batteries
Voltage ripple ≤200mVpp
Dynamic accuracy of the charging voltage <3% Vnom at load changes between 10%-90%-10% Inom; transient time ≤1.5ms
Short circuit protection Continuously short circuit proof; 1x Inom
Parallel operation Yes; current sharing ≤10% Inom
Internal decoupling at the output Yes, in the positive output line
Internal output fuse 20A
LED signalling Operation (green), Vo OK (green), Vo> (red), Alarm (red)
Main processor 16Bit Fujitsu
Isolated signalling contacts “General fault”; relay COM/NO/NC, maximum contact load: 60VDC/500mA
Communications interface CAN-Bus, proprietary protocol
Ambient temperature Operation: -20°C to +55°C, storage: -40°C to +85°C
Cooling Fan cooling (temperature-controlled, r.p.m.-monitored)
Climatic conditions according to IEC 721-3-3 class 3K3/3Z1/3B1/3C2/3S2/3M2
Max. installation altitude ≤ 1500m
Audible noise <45dB (A)
Type of construction 1/4 x 19’’, 3U
Dimensions (W/H/D) 106.3/133/326.5mm
Weight approx. 3.9kg
Type of enclosure / Protection class IP20 (front panel) / 1
Colour Front panel: RAL 7035, neutral, black print RAL 9005
CE conformity yes
Compliance to safety standards EN60950-1; VDE0100 T410; VDE0110; EN50178; EN60146
Compliance to EMC standards EN55022/24 (ITE), class “A“; EN61000-4 T2-5
Electrical connector AC input, DC output and signalization: DIN41612-M-connector

Article code View Designation

102-327-318.HV01 Assembly set 19” sub rack 3U incl.


backplane for 3 pcs. rectifiers
PSR327/220 V and 1pcs. DC control-
ler UPC3-220 V; connection board
DCC-CB1 included in delivery.

102-327-408.HV01 Assembly set 19“ sub rack 3U incl.


backplane for 4 pcs. rectifiers
PSR327/220 V

301-003-898.02 Monitoring, controlling and signal-


ling unit (DC controller) UPC3-220 V

302-DCC-CB1.00 Connection board, necessary to


connect all measuring, control and
signalling wires over the sub rack to
the UPC3 (MSTB screw terminals)
(Spare part)

881-MEC-BPL.03.21.B Cover plate (with handle) to cover


not used PSR slots, 1/4 x 19’’, 3U;
RAL 7035

880-CAN-DNG.00 CAN dongle, supplied over CAN-Bus,


12V, incl. software

DS_PSR327_220V_2009_E_R01 - Subject to change without notice - Eltek Valere Industrial GmbH