SIPROTEC 7SL86

Combined line differential and distance protection

www.siemens.com/siprotec

Description
The combined SIPROTEC 7SL86 line differential and dis-
tance protection has specifically been designed for the
protection of lines. With its modular structure, flexibility
and the powerful DIGSI 5 engineering tool, the SIPROTEC
7SL86 device offers future-oriented system solutions with
high investment security and low operating costs.

Main function Differential and Distance Protection

Tripping 3-pole, minimum tripping time: 9 ms

Inputs and 12 predefined standard variants with 4/4


outputs or 8/8 current/voltage transformers, 5 to
SIPROTEC 5 Device with Expansion Module
31 binary inputs, 8 to 46 binary outputs

Hardware Flexibly adjustable I/O quantity structure


• Protection data communication over different dis-
flexibility within the scope of the SIPROTEC 5
modular system
tances and physical media, such as optical fiber, two-
wire connections, and communication networks
Housing width 1/3 × 19 inch to 2/1 × 19 inch
• Phasor Measurement Unit (PMU)
Applications Functions
DIGSI 5 permits all functions to be configured and com-
• Line protection for all voltage levels with 3-pole trip-
bined as required.
ping
• Minimum tripping time: 9 ms
• Phase-selective protection of overhead lines and ca-
bles with single-ended and multi-ended infeed of all • Main protection function is differential protection
lengths with up to 6 line ends with adaptive algorithm for maximum sensitivity and
stability even with the most different transformer er-
• Also used in switchgear with breaker-and-a-half layout
rors, current-transformer saturation and capacitive
• Transformers and compensating coils in the protec- charging currents
tion zone
• Several distance-protection functions selectable as
• Detection of ground faults in isolated or arc- backup protection or secondary main protection: Clas-
suppression-coilground power systems in star, ring, or sic, reactance method (RMD), impedance protection
meshed arrangement for transformers
• Directional backup protection and various additional
functions
Efficient and modular

• Adaptive power-swing blocking, out-of-step protec- • Serial protection data communication via optical fi-
tion bers, twowire connections and communication net-
works (SDH networks, MPLS electrical power systems,
• Detection of ground faults of any type in compen-
for example using IEEE C37.94, and others), including
sated or isolated electrical power systems using the automatic switchover between ring and chain topolo-
following functions: 3I0>, V0>, fleeting contact, gy.
cos φ, sin φ, harmonic, dir.
• Reliable data transmission via PRP and HSR redundan-
• Detection of intermittent ground faults and admit- cy protocols
tance
• Extensive cyber security functionality, such as role-
• Ground fault detection using the pulse detection based access control (RBAC), protocolling security-
method related events or signed firmware
• Detection of current-transformer saturation for fast • Simple, quick and secure access to device data via a
tripping with high accuracy standard Web browser – without additional software
• Arc protection
• Phasor measurement unit (PMU) for synchrophasor
• Automatic frequency relief for underfrequency load measured values and IEEE C37.118 protocol
shedding, taking changed infeed conditions due to
• Time synchronization using IEEE 1588
decentralized power generation into consideration
• Powerful fault recording (buffer for a max. record
• Directional reactive power undervoltage protection
time of 80 sec. at 8 kHz or 320 sec. at 2 kHz)
(QU protection)
• Auxiliary functions for simple tests and commission-
• Detection of current and voltage signals up to the
ing
50th harmonic with high accuracy for selected protec-
tion functions (such as thermal overload protection) • Flexibly adjustable I/O quantity structure within the
and operational measured values scope of the SIPROTEC 5 modular system
• 3-pole automatic reclosing function Benefits
• Control, synchrocheck and switchgear interlocking • Safety due to powerful protection functions
protection
• Highest availability even under extreme environmen-
• Graphical logic editor to create powerful automation tal conditions by “conformal coating“ of electronic
functions in the device boards
• Single-line representation in small or large display • Powerful communication components warrant safe
• Integrated electrical Ethernet RJ45 for DIGSI 5 and and effective solutions
IEC 61850 (reporting and GOOSE) • High investment security and low operating costs due
• Up to 4 optional pluggable communication modules, to future-oriented system solutions
usable for different and redundant protocols
(IEC 61850, IEC 60870-5-103, IEC 60870-5-104, Mod-
bus TCP, DNP3 serial and TCP, PROFINET IO)

For all products using


security features of
OpenSSL, the
Siemens AG following shall apply:
Energy Management Division This product includes
Freyeslebenstraße 1 software developed
91058 Erlangen, Germany by the OpenSSL
Project for use in the
SIPROTEC 7SL86 Profile E7.8.docx OpenSSL Toolkit
(www.openssl.org),
Printed in Germany | © 09.18 Siemens AG cryptographic soft-
ware written by Eric
E-Mail: [email protected] Young
Tel: +49 180 524 70 00 ([email protected])
and software devel-
oped by Bodo
Moeller.