0% found this document useful (0 votes)
552 views1 page

Schedule of Electrical Loads: Total Load Computations

The document provides a schedule of electrical loads including calculations for sizing transformers, feeder wires, and circuit breakers. It determines: - A 25kVA, 1-phase transformer is needed, along with wiring consisting of 2-22mm2 and 1-8.0mm2 THHN cables in 25mm PVC conduit. - A 90AT/90AF, 2-pole main circuit breaker is required. - For a 3-phase system, 3-167kVA transformers rated for 13.2kV/440V/230V along with 3 sets of 3- 300mm2 THHN cables and 1- 200mm2 THHN ground cable in a 3"

Uploaded by

whendel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
552 views1 page

Schedule of Electrical Loads: Total Load Computations

The document provides a schedule of electrical loads including calculations for sizing transformers, feeder wires, and circuit breakers. It determines: - A 25kVA, 1-phase transformer is needed, along with wiring consisting of 2-22mm2 and 1-8.0mm2 THHN cables in 25mm PVC conduit. - A 90AT/90AF, 2-pole main circuit breaker is required. - For a 3-phase system, 3-167kVA transformers rated for 13.2kV/440V/230V along with 3 sets of 3- 300mm2 THHN cables and 1- 200mm2 THHN ground cable in a 3"

Uploaded by

whendel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SCHEDULE OF ELECTRICAL LOADS

TOTAL LOAD COMPUTATIONS


I = 90.351 AMP + 0.25(8.0) X 0.8 DF= 73.88 AMPS SIZE OF TRANSFORMER:
USE: 25KVA,1-PHASE, 440V/230V, DRY TYPE TRANSFORMER
USE : 2-22mm² THHN + 1-8.0mm² THHN (G)
in 25mmØ PVC
AMPACITY: 95 AMPS.

MAIN CB:
USE: 90AT / 90AF, 2POLE, 60HZ, 230V,
BOLT-ON TYPE, MCCB NEMA 1 ENCLOSURE

SCHEDULE OF LOADS (MCC PANEL)

TOTAL CURRENT @ 440 V = I 3PH x 0.8 DEMAND FACTOR SIZE OF TRANSFORMER:


= 575.94A x 0.8 D.F. USE: 3 - 167KVA, 13.2KV/440V/230V, 3PH, 60HZ
= 460.75 AMP.
SIZE OF GENSET:
FEEDER WIRE: 3 SETS x 3 - 300mm² THHN + 1 - 200mm² THHN (G) USE: 375KVA, 440V, 3PH, 60HZ
IN 3" DIAMETER CONDUIT

MAIN CB:
USE: 500AT/600AF, 3P, 440V, 60HZ, MAIN CIRCUIT BREAKER