Extension module 4AI + 4AO
AK-XM 103A
Technical brochure
Introduction
Application
The extension module should be used with a controller in the
same serial connection if there is not enough connections on the
controller itself.
Function
The module contains:
• 4 analog inputs for temperature sensors, pressure transmitters,
voltage signals and contact signals.
• Four analogue outputs (0-10V) for speed control of e.g. frequen-
cy converters
Installation
• The module is connected to the plug from the previous module
in the sequence.
Supply voltage
The supply voltage to the module comes from the previous mod-
ule in the row.
Supply voltage to a pressure transmitter can be taken from either
the 5 V output or the 12 V output depending on transmitter type.
Light-emitting diodes
Only the two top LED’s are used. They indicate the following:
• Voltage supply to the module
• Communication with the controller is active (red = error)
Connections
Galvanic isolation Max. 10 V
There are three groups, and the signals should not be mixed up:
• Inputs and 5V and 12V supplies for the signals connected to the
inputs.
• Output 1 and 2
• Output 3 and 4
Max. 2.5 mA
2 Technical brochure RD8BS102 © Danfoss 10-2009 AK-XM 103A
Data
Supply voltage Received from the AK controller, which the extension module is connected to
Power consumption 2 VA
Analog inputs Pt 1000 ohm /0°C Resolution: 0,1°C
Accuracy: +/- 0,5°C
Pressure transmitter type AKS 32R / Resolution 1 mV
AKS 32 (1-5 V) Accuracy +/- 20 mV
Voltage signal 0-10 V
Contact function (On/Off ) On at R < 20 ohm
Off at R > 2K ohm
(Gold -plated contacts not necessary)
Analog outputs Voltage signal 0-10 V
Max. load I < 2.5 mA
R > 4 Kohm
Supply for pressure transmitters 5V Max. 25 mA
12 V Max. 100 mA
Galvanic isolation 3 groups AI 1-4
AO 1-2
AO 3-4
Environment During transport -40 to 70°C
During operation -20 to 55°C ,
0 to 95% RH (non condensing)
No shock influences / vibrations
Enclosure Material PC / ABS
Density IP10 , VBG 4
Mounting For mounting on panel wall or DIN rail
Weight with screw terminals Ca. 200 g
Approvals EU low voltage directive and EMC require- LVD tested according to EN 60730
ments are complied with EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
UL 873, UL file number: E166834
Dimensions
Ordering
Type Application Function Code no.
AK-XM 103A Extension module for control- 4 Analog inputs. 4 Analog outputs 080Z0032
ler in the AK-series For sensors, pressure transmitters 0 -10 V d.c.
etc.
AK-XM 103A Technical brochure RD8BS102 © Danfoss 10-2009 3
Point Terminal 9: 12 V
Terminal 10: 5V
Terminal 11, 12:
Terminal 2, 4, 6, 8: GND-AI 1-4
Terminal 17, 19: GND-AO 1+2
Terminal 21, 23: GND-AO 3+4
Galvanic isolation:
AI 1-4 ≠ AO 1-2 ≠ AO 3-4
Signal Signal
type
AI
S (sensor) S1
S2
Pt 1000 ohm/0°C Saux1 Pt 1000
Saux2 Address
SSA
SdA
(Communication module)
P (pressure)
AKS 32R
AKS 32R
P0A -1 - xx bar
P0B
PcA AKS 32 (Controller)
AKS 32 PcB -1 - zz bar
Signal Signal type / Module Point Terminals
Active at
U (voltage)
1 (AI 1) 1-2
0-5V 2 (AI 2) 3-4
... 0 - 10 V
3 (AI 3) 5-6
4 (AI 4) 7-8
5 (AO 1) 17 - 18
On/Off Ext. Active
Main at: 6 (AO 2) 19 - 20
switch
Closed 7 (AO 3) 21 - 22
Day/ /
Night Open 8 (AO 4) 23 - 24
Door
AO
0-10 V
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
DE-BD
All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
4 Technical brochure RD8BS102 © Danfoss 10-2009 AK-XM 103A