Perbandingan Logic CCS
Rembang - Pacitan
Perbandingan Blok FUEL CONTROLLER
3 sec
FLOWRATE T f(t) FLOWRATE
FEEDER A FEEDER A
FLOWRATE 3 sec
T f(t) FLOWRATE
FEEDER B FEEDER B
FLOWRATE 3 sec RI01
FEEDER C T f(t)
+ 2
FLOWRATE
FEEDER C + f(x)
FLOWRATE 3 sec X (T/H) Y (%)
T f(t) FLOWRATE
FEEDER D FEEDER D 0 0
3 sec 200 100
FLOWRATE T f(t) FLOWRATE
FEEDER E FEEDER E
0
T Jumlah T
BPC 1 f(x) BPC 1
PI Feeder PI
X Y
Auto MA
MA 0 80
PI PI
300 LR 1 80 LR
PBAND 2 110 PBAND BPC 2
BPC 2
LOGIC HOLIM HOLIM 3 150 HOLIM
LOLIM 4 200 LOLIM
LOGIC LOLIM TRACK PI 5 250 TRACK PI
HOLD HOLD
RUNBACK
LOGIC HOLIM
LOGIC LOLIM
0
FEEDER FEEDER
BIAS BIAS
1. Feedback Blok Fuel Controller dari fungsi konversi linear 0-200
1. Feedback Blok Fuel Controller dari total jumlah flowrate feeder
t/h menjadi 0-100%
dibagi 2. Pembacaan flowrate didelay 3 detik
2. Nilai PBAND (Respon Proportional) berubah-rubah sesuai
2. Nilai PBAND (Respon Proportional) diberi nilai tetap sebesar
jumlah feeder yang auto
300
3. Logic pembatasan nilai maximum (HOLIM) dan nilai minimum
3. Logic pembatasan nilai maximum (HOLIM) dan nilai minimum
(LOLIM) diterangkan di slide lain
(LOLIM) diterangkan di slide lain
4. Output Fuel Controller tidak ditahan (hold) jika terjadi runback
4. Output Fuel Controller akan ditahan (hold) jika terjadi runback
NAME = 2E_FUELM:PIDA1 NAME = 2E_FUELM:PBAND
NAME = 1FUELMASTER:PIDA1 TYPE = PIDA TYPE = CHARC
TYPE = PIDA DESCRP = TOTAL FUEL CONTROL MEAS = 2E_FUELM:PBANDLOG.RO01
DESCRP = TOTAL FUEL CONTROL MEAS = 2E_FUELM:CHARC5.OUT HSCI1 = 100
MEAS = :MATH1.RO02 HSCI1 = 100 LSCI1 = 0
HSCI1 = 100 LSCI1 = 0 HSCO1 = 300.0
LSCI1 = 0 SPT = 0 LSCO1 = 0
SPT = 74.643127441 RSP = 2E_FUELM:MATH1.RO01 STARTP = 1
RSP = 1CCSDMD:AOUT1.OUT LR = 2E_FUELM:PIDA1.MA ENDP = 6
LR = 1 MODOPT = 4 X_1 = 0
MODOPT = 4 PBAND = 2E_FUELM:PBAND.OUT
PBAND = 300.0 Y_1 = 80
INT = 0.600000024 X_2 = 1.0
INT = 0.200000003 BIAS = 0
BIAS = 0.0 Y_2 = 80
HSCO1 = 100
HSCO1 = 100 X_3 = 2.0
LSCO1 = 0
LSCO1 = 0 Y_3 = 110
HOLIM = 2E_FUELM:SWCH2.OUT
HOLIM = :SWCH2.OUT X_4 = 3.0
LOLIM = 2E_FUELM:SWCH3.OUT
LOLIM = :SWCH3.OUT Y_4 = 150
TRACK = 0
TRACK = 0.0 X_5 = 4.0
TRKENL = 0
TRKENL = 0 HOLD = 0 Y_5 = 200
HOLD = 1RB:RB004.BO01 BCALCI = 0 X_6 = 5.0
BCALCI = 37.0 FBK = 2E_FUELM:CALCA2.RO01 Y_6 = 250
FBK = 37.171989441 MANSW = 2E_FUELLG:LOGIC1.BO01
MANSW = :CALCA3.BO01 NAME = 2E_FUELM:PBANDLOG
TYPE = CALCA
BI01 = 2E_FUELF:BIAS1.MA
NAME = 2E_FUELM:CALCA1 BI02 = 2E_FUELF:BIAS2.MA
TYPE = CALCA BI03 = 2E_FUELF:BIAS3.MA
RI01 = 2E_FUELC:CALCA1.RO01 BI04 = 2E_FUELF:BIAS4.MA
RI02 = 2E_FUELM:SWCH8.OUT BI05 = 2E_FUELF:BIAS5.MA
RI03 = 2E_FUELM:LLAG1.OUT STEP01 = CST
M01 = 1.665205 STEP02 = IN BI01
STEP01 = CST STEP03 = IN BI02
STEP02 = IN RI02 STEP04 = IN BI03
STEP03 = IN RI01 STEP05 = IN BI04
STEP04 = MUL STEP06 = IN BI05
STEP05 = OUT RO02 ; CORRECTED STEP07 = ADD 5
COAL FLOW STEP08 = OUT RO01
STEP07 = IN RI03
STEP08 = IN M01
STEP09 = MUL
STEP10 = OUT RO03 ; CORRECTED
OIL FLOW
STEP12 = IN RO02
STEP13 = IN RO03
STEP14 = ADD
STEP15 = OUT RO01 ; CORRECTED
FUEL FLOW
Perbandingan PROTEKSI LIMIT FUEL CONTROLLER (HOLIM)
FUEL CONTROLLER FUEL CONTROLLER
RATA-RATA SPEED RATA-RATA SPEED
FEEDER RUNNING 2 FEEDER RUNNING
2
PI PI
T
MA T MA
A FEEDER MAN 1 LR LR
B FEEDER MAN PBAND A FEEDER MAN 1
PBAND
C FEEDER MAN HOLIM B FEEDER MAN HOLIM
D FEEDER MAN LOLIM C FEEDER MAN
E FEEDER MAN LOLIM
100 % TRACK D FEEDER MAN
E FEEDER MAN
TRACK
HOLD HOLD
HA FLOWRATE 100 %
FEEDER A 1 2
T 1 2
M/A FEEDER A T
HA FLOWRATE
FEEDER A FEEDER SPEED
CONTROLLER
M/A FEEDER A
I
HA FLOWRATE
FEEDER A MA
LR
M/A FEEDER A
HOAIND
HOLIM
LOLIM
HA FLOWRATE
TRACK
FEEDER A
83 HOLD
M/A FEEDER A
HA FLOWRATE 1. Jika semua feeder manual maka HOLIM dari rata2 speed
FEEDER A
M/A FEEDER A
feeder (CO) yang running
2. Jika permintaan coal flow dari blok fuel controller lebih besar
dari rata2 speed feeder (setpoint) maka blok feeder speed
1. Jika semua feeder manual maka HOLIM dari rata2 speed controller akan mengeluarkan output yang terus naik (secara
feeder (CO) yang running integral) mulai dari 0 hingga 100%, jika output tersebut
2. Jika ada minimal 1 feeder running auto maka jika feeder yang mencapai nilai HOLIM feeder speed controller (83) maka
running auto semua mencapai batas alarm (HABLIM = 44.5) muncul HOAIND yang membuat output Fuel controller ditahan
maka output Fuel controller akan ditahan nilainya nilainya
NAME = 1FUELFEEDER:CALCA21 NAME = 2E_FUELM:PIDA2
TYPE = CALCA NAME = 1FUELFEEDER:REALM2 TYPE = PIDA
BI01 = :REALM2.HAIND
TYPE = REALM DESCRP = FEEDER SPEED DMD
BI02 = :BIAS1.MA
MEAS = 2E_FUELM:PIDA1.OUT
BI03 = :REALM4.HAIND MEAS = :BIAS1.OUT
BI04 = :BIAS2.MA RSP = 2E_FUELM:CALCA2.RO01
BI05 = :REALM6.HAIND HSCI1 = 100 MODOPT = 2
BI06 = :BIAS3.MA LSCI1 = 0 INT = 0.100000001
BI07 = :REALM8.HAIND TRACK = 2E_FUELM:CALCA2.RO01
BI08 = :BIAS4.MA HLAOPT = 2 TRKENL = 2E_FUELLG:LOGIC1A.BO01
BI09 = :REALM10.HAIND HABLIM = 44.5 HOLD = 0
BI10 = :BIAS5.MA
STEP01 = CST LABLIM = 0.0 FBK = 2E_FUELM:PIDA2.OUT
STEP02 = AND BI01 BI02 HOALIM = 80.0
ABSDB = 0.0 HOATXT =
STEP03 = OR ~BI02
STEP04 = ABSPRI = 5 LOALIM = 0
STEP05 = AND BI03 BI04 LOATXT =
STEP06 = OR ~BI04
ABSGRP = 1
END
STEP07 = ABSRAL = 0
STEP08 = AND BI05 BI06
STEP09 = OR ~BI06
ABSINC = 5
STEP10 = END
STEP11 = AND BI07 BI08
STEP12 = OR ~BI08
STEP13 =
STEP14 = AND BI09 BI10
STEP15 = OR ~BI10
STEP16 =
STEP17 = AND 5
STEP18 = OUT BO01
STEP19 =
STEP20 =
STEP21 = END
Perbandingan Blok BIAS FEEDER
+
INITI
BCALCI
HOLIM
LOLIM
AOUT
NAME = 1FUELFEEDER:BIAS1
TYPE = BIAS
DESCRP = ECF A FEEDER RATE DMD
LOOPID = 1OHFB10GC001
MEAS = 1FUELMASTER:PIDA1.OUT
HSCI1 = 100
LSCI1 = 0
HOLIM = :CALCA6.RO01
LOLIM = :SWCH1.OUT
MANSW = :CALCA1.BO01
HOLD = 1FUELFEEDER1:LOGIC1.BO01
INITI = 1LDAS:AO150402.INITO
BCALCI = 1LDAS:AO150402.BCALCO
END
NAME = 1LDAS:AO150402
TYPE = AOUT
DESCRP = ECF A FEEDER RATE
COMMOND
LOOPID = 1OHFB10GC001A001
IOMOPT = 1
IOM_ID = 1L1504
PNT_NO = 2
SCO = 3
MEAS = 1FUELFEEDER:BIAS1.OUT
HSCI1 = 60.0
LSCI1 = 0.0
HSCO1 = 60.00
LSCO1 = 0.0
HOLIM = 60.00
LOLIM = 0.0
END
Perbandingan Blok BOILER PRESSURE CONTROL
PI
Perbandingan Blok MW CONTROLLER
PI
Perbandingan Blok BOILER PRESSURE CONTROL
PI