General TC10-L
Specification Temperature Controller
(Limit Control Type)
GS 05C01E81-11EN
■ General
The TC10-L is an FM approved limit controller that can
be configured either as a high limit or as a low limit
controller by a user. The TC10-L features universal
input, 3 Dynamic Colors Led Display two alarm outputs,
retransmission output, a timer to count the total time the
setpoint is exceeded, and a register to retain the
maximum temperature reached. The RS-485
communication interface is available optionally.
■ Limit Control Function
(High limit control) (Low limit control)
When a measured value (PV) exceeds a setpoint When a measured value (PV) exceeds a setpoint
(SP), “EXCEEDED” lamp lights, and “OUT” lamp (SP), “EXCEEDED” lamp lights, and “OUT” lamp
turns ON (A). The limit output relay is deenergized turns ON (A).
then. “EXCEEDED” lamp turns off when PV goes The limit output relay is deenergized then.
into normal condition, while the output (OUT) display “EXCEEDED” lamp turns off when PV goes into
lamp stays on as it is (B). The output (OUT) display normal condition, while the output (OUT) display
lamp turns off when a confirming operation is done lamp stays on as it is (B). The output (OUT) display
by an operator (C). The way to confirm is pressing lamp turns off when a confirming operation is done
the RST ( ) key (or by DI1, according to the by an operator (C). The way to confirm is pressing
setting of setup parameter DIS). The confirming the RST ( ) key (or by DI1, according to the
operation is not accepted during PV exceeds SP (D) setting of setup parameter DIS). The confirming
(during EXCEEDED lamp lights*). State of output operation is not accepted during PV exceeds SP (D)
relay is de-energized whenever “OUT” lamp is on. (during EXCEEDED lamp lights*). State of output
* Check the “HYS” value if the EXCEEDED lamp is not relay is de-energized whenever “OUT” lamp is on.
turn off when PV is lower than SP. * Check the “HYS” value if the EXCEEDED lamp is not
turn off when PV is higher than SP.
(A) (B) (C) (A) (D) (B)
(A) (B) (C) (A) (D) (B)
SP
PV
PV
SP
off lit off lit off
off lit off lit off off off
lit lit
on off on off
off lit off lit
on off on off
Operation
(RST key or Confirmation Confirmation
external contact input) (accepted) (not accepted)
Operation
(RST key or Confirmation Confirmation
external contact input) (accepted) (not accepted)
GS 05C01E81-11EN
2nd Edition Nov. 2019
■ Hardware Specifications Regulatory Compliance
CE marking, UL(USA/CANADA)
Display Specifications EMC Directive:
Main display: 4 digits height 15.5 mm, 3 color red, EN 61326-1 Class A, Table 2 (For use in industrial
green and amber locations)
Secondary display: 4 digits height 7 mm, green color EN 55011 Class A, Group 1
Display updating time: 500 ms (During the test, the instrument continues to
Universal Input Specifications operate at the measurement accuracy within
TC J -50 to +1000°C -58 to +1832°F
specification.)
LV Directive:
TC K -50 to +1370°C -58 to +2498°F
EN 61010-1, EN 61010-2-030
TC S (*) -50 to +1760°C -58 to +3200°F UL 61010-1 CSA 61010-1
TC R -50 to +1760°C -58 to +3200°F Certified for FM-3810 and FM-3545.
TC T -70 to +400°C -94 to +752°F Installation category: II
TC N -50 to +1300°C -58 to +2372°F Pollution category: 2
Pt100 -200 to +850°C -328 to +1562°F
RoHS Directive:
EN 50581
Pt1000 -200 to +850°C -328 to +1562°F
Linear 0 to 60 mV
Power Supply Specification and Isolation Voltage
Linear 12 to 60 mV 100 to 240 VAC (-15 to +10% of the nominal value)
Linear 0 to 20 mA (this selection forces Out 4 = TX) Power consumption: 6.0 VA max. (100 to 240 VAC)
Linear 4 to 20 mA (this selection forces Out 4 = TX) Isolation Voltage
Linear 0 to 5 V 3000 V AC for 1 minute between primary and
secondary terminals
Linear 1 to 5 V
(Primary terminals = Power and relay output
Linear 0 to 10 V
terminals, Secondary terminals = Analog I/O signal
Linear 2 to 10 V terminals, contact input terminals, and
Sampling time: 130 ms communication terminals.)
Resolution: 30000 counts
Total Accuracy: ±0.5% of F.S. ±1 digit
*: ±1.0% of F.S. ±1 digit
Resistance-temperature detector (RTD) measured
current; Pt100: 150 μA, Pt1000: 15.5 μA
Response time: 2 second or less, 63% (10 - 90%)
(The time required for transmission output to reach
63% of the maximum excursion when PV abruptly
changes from 10% to 90%)
Environmental Conditions
Output Specifications Normal Operating Conditions
OUT 1: Analog output: 0/4 to 20 mA, galvanically Operating temperature: 0 to 50°C (32 to 122°F)
isolated, RL max. 600Ω ±0.2% of F.S. or 0/2 Humidity: 20 to 90% RH, not condensing
to 10 V, galvanically isolated, RL min.: 500Ω Temperature Effects
±0.3% F.S. Analog input: It is part of the global accuracy
OUT 2: Relay SPST -NO 2A/250 Vac or voltage to Reference junction compensation: ±0.1°C/°C or less
drive SSR 13V max. @1mA, 10.5 min Analog output: ±0.05% of F.S./°C or less
@15mA ±10% Storage temperature
OUT 3: Relay SPST -NO 2A/250 Vac or voltage to Storage temperature: -20 to +70°C (-4 to +158°F)
drive SSR 13V max. @1mA, 10.5 min Humidity: 20 to 95% RH, not condensing
@15mA ±10%
OUT 4: programmable: voltage output to drive SSR
13V max. @1mA, 10.5 min. @15mA ±10%,
12 VDC (20 mA) transmitter power supply or
2nd digital input
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation GS 05C01E81-11EN 2nd Edition Nov. 2019
■ External Dimensions and Panel ■ Terminal Arrangement
Cutout Dimensions
■ Construction, Mounting, and Wiring
Case: Plastic, self-extinguishing degree: V-0 according
to UL 94
Front protection: IP 65 (when the optional panel gasket
is mounted) for indoor locations according to EN
60070-1
Terminals protection: IP 20 according to EN 60070-1
Installation: Panel mounting
Terminal block: 16 screw terminals for cables of 0.25 to
2.5 mm2 (AWG22 to AWG14) with connection
diagram, tightening torque 0.5 Nm;
Dimensions: 48 x 48, depth 62 mm
(depth from the panel surface)
(1.89 x 1.89 x 2.87 in.)
Panel cutout: 45[-0, +0.6] x 45[-0, +0.6] mm
(1.78[- 0.000, +0.023] x 1.78[- 0.000, +0.023] in.)
Weight: 180 g max.
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation GS 05C01E81-11EN 2nd Edition Nov. 2019
■ Model and Suffix Code
Model Code Suffix codes Description
Temperature Controller
TC10 -L □ C □ □ □ D □ F with an universal input, one logic input, and one
voltage output for SSR.
Type -L Always “-L”
Power supply H 100 to 240 VAC
Fixed code C Always "C"
Relay outputs for limit control and alarm with PV
A R R
analog transmission
Relay output for limit control with PV analog
OUT1-3 A R N
transmission
N R R Relay outputs for limit control and alarm
N R N Relay output for limit control
Selectable I/O (logic input / 12V SSR drive output
IN/OUT4(Fixed code) D
/ 12VDC 20mA transmitter power supply)
S RS-485 communication Modbus/RTU
Serial communication
N None
Fixed code F Always "F"
Fixed code /GK Panel gasket for IP65 (mandatory for FM)
■ Items to be specified when ordering
Model and suffix code.
■ Standard accessories
Brackets (mounting hardware), Quick Guide
■ Optional accessory
Panel gasket for IP65: A00336
■ User’s Manual
Product user’s manuals can be downloaded or viewed at the following URL.
URL: http://www.yokogawa.com/ns/tc10/im
All Rights Reserved. Copyright © 2018, Yokogawa Electric Corporation GS 05C01E81-11EN 2nd Edition Nov. 2019