Sa Lien T Features: Seriescs 310 0
Sa Lien T Features: Seriescs 310 0
SA LIENT FEATURE S
6P rogram m able M icrocontroller B ased U nit
6E ight / S ix digit counter w ith non-volatile m em ory
6Independent display for flow rate indication
6P rogram m able A larm (on flow rate) and B atching Facility
6S erial C om m unication P ort w ith M O D B U S RTU P rotocol
6Isolated 4 to 20 m A retransm ission output
6B uilt-in tw o-w ire transm itter supply
6Various C utouts and sizes
6S ingle C hip design for ruggedness and low cost
6B uilt-in TE M P E R ATU R E P R E S S U R E C O M P E N S ATIO N (optional)
Th e µC S 300 0 serie s F low Integra tor Tota lizers a re pre cision instru me nts used along w ith flow m ete rs,
flow tran sm itters to indicate th e instan tan eous flo w rate and carry out the tota lization of flow.
Tw o set-points a re pro vided w hich can be configured on flow rate or on batches a nd hence can be u sed
as batch controllers.
Fo r Flow Com puting Unit havin g bu ilt-in Tem perature Pressure Com pensation , the re w ill be tw o
add itional in puts, one from pressure transm itter and other from tem pe ra ture sensor in addition to th e input
fro m Flow Tra nsm itter. A ll oth er specificatio ns w ill be as ab ove.
Series µCS
Flow Integrators Totalizers Series CS 3000
3000
Flow C om puting U nit is used for m easu ring co rre cted flow of ste am / ga ses. It is w ell kn ow n tha t th e flow of a ny ga s
varies substa ntially w ith the chang e in tem perature or p re ssu re . A s a result no rm al flow m easuring techniq ues d o n ot
give the proper flow m easu re m e nt. To obtain the proper / correcte d flow, o ne h as to take into conside ra tio n the change s
in tem perature a nd pressu re. It is spe cifically for this ap plication that ou r Flow C om puting U nit h as be en designe d.
1) F ro m D ifferential P ressure Transm itter (or a ny flow m eter) correspo nding to uncorrected flow
2) F ro m G au ge Pre ssure Transm itter corresponding to actual pressure
3) F ro m Tem perature S en sor or Tem perature Tran sm itter
Th e F low C om puting U nit utilizes the follow ing form ula fo r correction :
Q = Q ` X S q.rt.(D P * P /T )
W h ere,
Q = C o rre cted Flow
Q` = U n co rre cted Flow
D P = Input from D P Transm itter (4 to 20 m A D C )
P = Input from P ressure Tra nsm itter (4 to 2 0 m A D C )
T = Input from RTD , Th/C se nsor or Transm iiter (4 to 20 m A D C )