0% found this document useful (0 votes)
54 views

Instrument Air Consumtion For Naidupeta Project Area Control Valve Nos NM3/HR SCFM

The document provides calculations of instrument air consumption for different areas of the Naidupeta project in NM3/hr and SCFM. It lists the control valve numbers and associated air consumption for three fluidized bed areas and air used in heat transfer fluid drying. It also includes consumption estimates for demineralized water, mechanical seal support equipment, purge losses, loading station valves, leakage, and totals the overall estimated air consumption in NM3/hr and SCFM. It provides conversion factors between NM3/hr and SCFM.

Uploaded by

Kishore Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
54 views

Instrument Air Consumtion For Naidupeta Project Area Control Valve Nos NM3/HR SCFM

The document provides calculations of instrument air consumption for different areas of the Naidupeta project in NM3/hr and SCFM. It lists the control valve numbers and associated air consumption for three fluidized bed areas and air used in heat transfer fluid drying. It also includes consumption estimates for demineralized water, mechanical seal support equipment, purge losses, loading station valves, leakage, and totals the overall estimated air consumption in NM3/hr and SCFM. It provides conversion factors between NM3/hr and SCFM.

Uploaded by

Kishore Kumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

1 CV =

INSTRUMENT AIR CONSUMTION FOR NAIDUPETA PROJECT

AREA CONTROL VALVE NOS NM3/HR SCFM


FD 1 20 30 17.67
FD 2 20 30 17.67
FD 3 20 30 17.67
AIR IN HTF FD ALL 3 PLANTS
KG/HR 15X3 45 26.505
DM WATER 20 NM/HR 20 11.78
MSES 8 12 7.068

PURGE LOSS IN DRYER 15%


CONSIDER 200CFM 30
LOADING STATION CONTROL VALVE 6 9 5.301
AIR LEAKAGE 10% 20
TOTAL AIR CONSUMPTION 153.664
1.5 NM3/HR AIR CONSUMTION
CT

1M3/HR = 0.589 SCFM


1SCFM= 1.699 1NM3/HR