2. Type designation
N VF 300 M - □/ T □□
2:200V~240V
4:380V~460V
D: Single phase input
S: Three-phase input
General type
Motor adaption power
Mini type
Design SN
Inverter
Enterprise characteristic code
NVF300M Series Inverter 3. Operating conditions
3.1 Temperature
1. General Operating ambient temperature ranges from -10℃ to 40℃ .
NVF300M Series Mini inverter is a kind of high-performance When the temperature is above 40℃, the inverter will be
vector control inverter, which is independently developed by used through derating at 1% of the rated power for every
our company. It adopts advanced control strategy to achieve increase of 1℃.
a high-precision magnetic flux vector torque control, and it 3.2 Humidity
is characterized by high control precision, wide speed range, 5%~95%RH, without condensed water.
large starting torque, high reliability, strong overload capacity 3.3 Altitude
and flexible and convenient operation. Rich and practical Inverter which is installed below the altitude of 1000 meters
speed control, torque control, process close loop control, can output the rated power. When the altitude exceeds 1000
simple PLC, swing frequency control, multi-section speed meters, the inverter needs to be used through derating and is
control and other functions can meet the needs of a variety used through derating at 10% of the rated power for every
of complex high precision drive. increase of 1000 meters.
3.4 Shock and vibration
NVF300M Series Mini inverter is divided into single-phase and Do not allow the inverter to fall to the ground or suffer from
three-phase general inverters, which has strong load adaptability, sudden impact. Do not install the inverter in places where there
stable and reliable operation, automatic energy-saving operation may be often vibration.
and other functions. It can be widely applied in medical care, 3.5 Electromagnetic radiation
food, water treatment, papermaking, textile, machine tool, Install the inverter in places far away from the source
conveyor belt, carpentry, traffic and transportation, of electromagnetic radiation.
communication, machinery and equipment and other electric 3.6 Water and moisture protection
drive and automation control fields. Do not install the inverter in places where there may be water
spray or dew.
Products are designed and tested in accordance with the 3.7 Air pollution
international standard; user environment test is strictly simulated. Do not install the inverter in an air polluted place, such as dust,
corrosive gas and other environment etc.
Accordant standards: GB/T 12668.2-2002, IEC 61800-2. 3.8 Storage environment
Do not install the inverter in environment with direct sunlight,
oil, steam and vibration.
1000m
Altitude Ambient temperature Well Ventilated
Empower the World >> 12
Inverter & Soft-Starter
Inverter
4. Technical data
4.1 Inverter specifications
Input voltage level Single phase 200V~240V
Inverter power (kW) 0.4/TD2 0.75/TD2 1.5/TD2
Applicable motor power (kW) 0.4 0.75 1.5
Rated output current (A) 2.5 4.0 7.5
Input voltage level Three-phase 200V~240V
Inverter power (kW) 0.4/TS2 0.75/TS2 1.5/TS2
Applicable motor power (kW) 0.4 0.75 1.5
Rated output current (A) 2.5 4.0 7.5
Input voltage level Three-phase 200V~240V
Inverter power (kW) 0.4/TS4 0.75/TS4 1.5/TS4
Applicable motor power (kW) 0.4 0.75 1.5
Rated output current (A) 1.2 2.1 3.8
4.2. Standard technical features
Input voltage range: 200V~240V(-15%~+10%)/380V~460V(-15%~+10%)
Input and output Input frequency range:(47~63)Hz
characteristics Output voltage range:0 ~ Input voltage
Output frequency range:(0 ~ 300)Hz
Programmable digital input: 5-way input (including 1-way high-speed pulse input)
Programmable analog input: AI1:(0 ~ 10)V or (0/4 ~ 20)mA input; AI2:(0 ~ 10)V or (0/4 ~ 20)mA input;
Peripheral
interface
High speed pulse output: 1-way output
Relay output: 1-way output
Analog output: 1-way output, optional (0 ~ 10)V or (0/4 ~ 20)mA
Torque boost: Automatic torque boost; manual torque boost 0.1%~30.0%
Dynamic braking: Built-in brake unit, external braking resistance
DC braking: optional start and stop; operating frequency: (0~60)Hz; brake current: (0~100)% rated current; action time (0.0~30.0)s
Jog control: Jog frequency range:(0 ~ 50.0)Hz; jog acceleration and deceleration time (0.1 ~ 6000.0)s
Operation
function
Multi-speed operation: To achieve multi-speed operation through installing the simple PLC internally or controlling
features the m u l t i-function terminal control
Automatic voltage regulation (AVR): Can automatically keep the output voltage constant when the grid voltage changes
Automatic current limiting: Automatically limit the current during operation to prevent frequent over-current fault tripping
Built-in PID controller: Can easily constitute a close-loop control system
Protection function: Provide as many as 20 kinds of fault protection functions: overcurrent, overvoltage, undervoltage,
overheating, open phase, overload, PID disconnection and other protection functions.
Control mode: Without PG vector control, V/F control
Overload capacity: 150% of rated current 60s
Technical Starting torque: Without PG vector control, 0.5Hz/150 %( rated torque)
characteristics Speed ratio: 1:100(without PG control); 1:50 (V/F control)
Speed control precision:±0.5% of maximum speed
Carrier frequency:(0.5 ~ 15)kHz
Protection grade: IP20
Structure Brake unit: Three-phase general inverter comes standard with the built-in brake unit, and the single phase general inverter is
equipped with the optional brake unit.
Cooling mode: Cooling by high-speed DC fans
13 >> Empower the World
Inverter & Soft-Starter
Inverter
5. Wiring diagram
5.1 Standard wiring diagram
Brake resistance
+ B
QF
U
R(L)
Input AC V
S(N) M
power supply
W
T
Main circuit
Inverter grounding
Control
circuit terminal
X1
V I
X2 1 2 3 AO Analog output
Multifunction X3 V:(0-10)V
J3/AO GND
programmable I:{0(4)-20}mA
input terminal X4
HDI (High-speed pulse input)
COM
RC Relay output
Analog input
power supply RA 250VAC/3A
Analog input +10V RB 28VDC/1A
V I
1 2 3
V:(0-10)V AI1
I:{0(4)-20}mA J1/AI1
AI2 V I
1 2 3 +24V
Analog input public places
GND J2/AI2
HDO
Open collector output
485+
RS485 communication COM (High-speed pulse output)
485-
RA RB HDI X1 X2 X3 X4 AI1 AI2
Correspond to control terminals arrangement RC HDO +24V COM 485+ 485- GND +10V AO
J1 J2 J3 jumper selection:
J1 and J2 positions (AI1 and AI2 analog input interfaces):
When 1 is connected to 2: 0V~10V analog voltage input; when 2 is connected to 3, 0/4mA~20mA analog current input
J3 position(AO analog output interface):
When 1 is connected to 2: 0V~10V analog voltage output; when 2 is connected to 3, 0/4mA~20mA analog current output
Empower the World >> 14
Inverter & Soft-Starter
Inverter
5.2 Notes to main circuit terminal
Terminal mark Terminal name and description
R, S, T AC power input terminal, connecting the three-phase fundamental frequency power supply (200V~240V)/(380V~460V)
L, N AC power input terminal, connecting the single-phase fundamental frequency power supply (200V~240V)
+,B Connecting the brake resistor terminal
U, V, W AC output terminal, connecting the motor
Ground terminal, for inverter grounding
5.3. Control circuit terminal description
Category Terminal Name Terminal function description Specifications
screen
Power +10V +10V Power supply Provide +10V reference power supply externally Maximum allowable output current 5mA
supply GND +10V Power ground Analog signal and+10V power supply reference ground Internal isolation of GND and COM
Analog single Accepting analog voltage or current single end input; Input voltage range: -10V~10V
AI1 end input AI1 voltage / current input are selected by the control board (input impedance: 45kΩ);
Analog jumper J1 (reference ground: GND) resolution: 1/4000
input Accepting analog voltage or current single end input; Input current range: 0mA~20 mA;
AI2 Analog single
end input AI2 voltage / current input are selected by the control board resolution: 1/2000
jumper J2 (reference ground: GND) (jumper is needed)
Providing analog voltage / current output; the output
Analog voltage and current are selected by the control board Output voltage range:(0~10)V
A0 Analog output 1
output jumper J3; see Function code F6.11 description for the Current output range:(0/4~20)mA
factory default output voltage (reference ground: GND)
Commu-
458+ RS485 communication Positive terminal of 485 differential signal Standard RS485 communication interface
nication 485- interface Negative terminal of 485 differential signal Please use the twisted pair or shielded wire
X1 Multi -function input terminal 1
Programmable is defined as a multi-function switch Photoelectric coupling isolation input
Multi - X2 Multi -function input terminal 2
impedance: R=3.3kΩ;
input terminal; introduction to functions of F5.00~
function X3 Multi -function input terminal 3 X1~X4 maximum input frequency:
F5.04 andF5.07 input terminals in switch input terminals
input X4 Multi -function input terminal 4 200Hz;X7 maximum input frequency:
(group F5)
terminal 100kHzInput voltage range:20~30V
Multi-function or pulse
HDI input terminal HDI
Multi - Programmable is defined as a multi-function pulse signal
Open collector pulse
function HDO output terminal; introduction to functions of F6.00 and Output frequency range: Determined
output terminal
output F6.02 output terminals in switch input terminals (group F6) by F6.18, maximum 100kHz
terminal ( Public terminal: COM)
Power +24V +24V Power supply Providing +24V power supply externally to use with X1-X4, Maximum output current: 200mA
supply HDI, HDO and other terminals Internal isolation of COM and GND
COM +24VPublic power end
RA RA-RB: Normally closed, RB-RC: Normally
Relay Programmable is defined as a multi-function relay output open Contact capacity: NO/NC:5A/3A
output RB Relay output terminal; introduction to functions of F6.03 output terminal 250V~ See F6 for Methods of use.
in switch output terminals (group F6) Overvoltage level of the input voltage
terminal 1
of the relay output terminal is overvoltage
RC
level II.
6. Overall and mounting dimensions (mm)
Outside drawing for display box
25
73.5(W1)
63
15.6
111.5(H1)
RUN/PRGF/R LOC/REM FAULT Hz A V
93
PRG - + SET
MF SHIFT
< <
RUN STOP
15 >> Empower the World
Inverter & Soft-Starter
Inverter
NVF300M-0.4/TD2~1.5/TD2, 0.4/TS2~1.5/TS2, 0.4/TS4~1.5/TS4
MF SHIFT
H1
PRG SET
H
RUN STOP
W1 D1
W
D
Installation size Weight
Model
W H D W1 H1 D1 d kg
Display box 73.5 111.5
NVF300M-0.4/TD2
NVF300M-0.75/TD2
NVF300M-1.5/TD2
NVF300M-0.4/TS2
85 154 123 76 143 61 5 0.9
NVF300M-0.75/TS2
NVF300M-1.5/TS2
NVF300M-0.4/TS4
NVF300M-0.75/TS4
NVF300M-1.5/TS4
7. Ordering information
7.1 Select the model and specifications desired in accordance with the description of model and meaning when ordering:
For example:
Single phase 200V~240V series: NVF300M-0.75/TD2
Three-phase200V~240V series:NVF300M-0.75/TS2
Three-phase 380V~460V series:NVF300M-0.75/TS4
7.2. Selection guide
7.2.1 To ensure the reliable operation of inverter, its power must be equal to or greater than the motor power.
7.2.2 General inverter is suitable for fan, water pump, rolling mill, mixer, ball mill, centrifuge and other loads.
8. Peripheral equipment options
Inverter Brake attachment options AC input reactor AC output reactor
Configuration of Brake resistance Config- Rated Ind uctan ce Config- Rated Inductance
brake unit (10%
NVF30 0M -□/□□□ of the braking ratio) Resista nce (Ω) Power (W) uration current(A) (mH) uration current (A) (mH)
0.4/TD2 220 80 2.4 4.6 2.4 4.5
0.75/TD2 220 80 4.5 2.4 4.5 2.3
External selection
External selection
Brake unit
1.5/TD2 100 260 7 1.6 7 1.5
built-in
0.4/TS2 selection 220 80 2.4 4.6 2.4 4.5
0.75/TS2 220 80 4.5 2.4 4.5 2.3
1.5/TS2 100 260 7 1.6 7 1.5
0.4/TS4 Brake unit 750 80 2.5 2.83 3 2.1
0.75/TS4 built-in 750 80 3.7 2.239 3 2.1
selection 400 260 3.7 2.239 6.3 1.5
1.5/TS4
Display extension Display
Display
line and display box extension
box pallet
pallet physical map line
Note: if it is necessary to pull the inverter panel for control, it shall be specially noted when ordering and length of the display extension line indicated.