SPM33 Multifunction Power Meter
Feature
Economical multifunction power meter
Suit for voltage distribution system up to 650kV
Dual Source kWh phasetrac record seperately grid &
generator supply
31st Harmonic analysis, THD
One RS485, support MODBUS-RTU protocol
Phase sequence adjustment
2 status input (standard) Generator
Alarm setpoint (optional)
Grid
Basic Function
SPM33 measure and display real-time parameters:
Voltage—Ua, Ub, Uc, Uab, Ubc, Uca, Frequency--F
Voltage unbalance rate – UL-L unbal, UL-N unbal Active energy—kWh
Reactive energy– kvarh
Current—Ia, Ib, Ic, In
Apparent energy - kVAh
Current unbalance rate –I unbal
Dual source kWh record seperately grid & generator supply
Active power – Pa, Pb, Pc, ∑P (Import & export kWh)
Reactive power –Qa, Qb, Qc, ∑Q Demand and Max. record for I, P, Q, S
Apparent power—Sa, Sb,Sc, ∑S 31st harmonic, THD
Power factor—PFa, PFb, PFc, ∑PF 2 DI, One RS485,
Optional Function
2 Relay output
Technical Specification
Connection Mode 3 phase 3 wires, 3 phase 4 wires Power Supply AC 85~265V or DC 100~300V
Metering True RMS, 1 sec refresh time Power loss <5VA
Input Rated current: 5A or 1A Communication RS485 serial, support Modbus-RTU
Rated voltage: 220/380V, 35Hz~65Hz Baudrate: 4800, 9600, 19200bps
Address: 1~247
Current:
120% of rated, continuously Dimension Panel: 96 x 96 x 18 mm
Instantaneous current: 10 times/ (L x W x H) Cut-out: 89.5 x 89.5 x 69.8 mm (+0.5mm)
Overload
Low voltage system: IP index IP54 (front panel) and IP20 (case)
Up to 400V(L-N) / 650V (L-L)
Weight Approx. 500gr.
High voltage system:
Up to 650kV Normal operating temperature: -10℃ +55℃~
~
Operating temperature: -25℃ +55℃
Status input
voltage
2 channel active status input,less than 60V
is open,more than 140V is closed,the
Environment ~
Storage temperature: -40℃ +70℃
maximum input is 300V Humidity: 5%~95% non-condensing
Relay output 2 channels, Electrostatic discharge immunity test
(optional) IEC 61000-4-2,Level 4
Node capacity: 250Vac/5A
Radiated immunity test
Power frequency withstand voltage AC 2KV/minute IEC 61000-4-3,Level 4
Standard (EMC) Electrical fast transient/burst immunity test
Insulation resistance ≥ 100MΩ IEC 61000-4-4,Level 4
Impulse withstand voltage 5kV (peak), 1.2/50uS
~
Surge immunity test (1, 2/50µs 8/20µs)
IEC 61000-4-5,Level 4
Parameter Accuracy Measuring Range
:
Line - line 0 ~ 650V
:
Line - Neutral 0 ~ 400V
Voltage 0.5%
PT primary side: up to 650KV
PT secondary side: 100 - 400V (L-N) (Settable)
:
Each phase 0 ~ 65,000A
Current 0.5%
:
Zero sequence 0 ~ 65,000A
Power factor 0.5% -1~1
Active power 0.5% 0~ 99,999,999.9 W
Reactive power 1.0% 0~ 99,999,999.9W
Active energy 1.0% 0~ 99,999,999.9 kWh
Reactive energy 2.0% 0~ 99,999,999.9 kVarh
Three-phase voltage unbalance class B 0%~100%
Three-phase current unbalance class B 0%~100%
THD class B 0%~100%
Dimension & Installation
Unit: mm
Order Information
SPM33--①---②
R Two relay alarm output
V1 ×
3 230/398V, 5A (support Hight voltage system up to 650KV, PT secondary settable )
V2 ×
3 230/ 398V,1A
Example: Model No. SPM33-R-V1 indicates the device provide basic function, two relay alarm output, rated input 220/ 380V, 5A
E-Power Technology Ltd. Representative:
Add: 32-7488 Salisbury Ave. Burnaby, BC, Canada VITECT Electric Automation Solution Co.,Ltd.
Tel: 1-604-3396315 Add: No 8/3/1, Bui Huy Bich, Hoang Liet, Hoang Mai,
Email:
[email protected] Ha Noi.
http://www.e-powertech.ca Tel: +84.978.158.141 / +84.902.105.226
Email:
[email protected] http://www.vitect.com.vn