This inspection checklist summarizes the findings of a fire pump system inspection conducted at Cotton Clothing Ltd. on November 4, 2019. The inspector found that as-built drawings and most required documentation were available, but individual fire pump acceptance test reports and manufacturer curves were missing. Visual inspection found that the isolation valve, flow meter, and pressure gauges met requirements, but the diesel pump controller had an abnormal condition. The factory was asked to provide missing documentation and address deficiencies including supervision of closed valves and a missing reservoir level gauge.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100%(2)100% found this document useful (2 votes)
487 views1 page
Fire Pump Check List
This inspection checklist summarizes the findings of a fire pump system inspection conducted at Cotton Clothing Ltd. on November 4, 2019. The inspector found that as-built drawings and most required documentation were available, but individual fire pump acceptance test reports and manufacturer curves were missing. Visual inspection found that the isolation valve, flow meter, and pressure gauges met requirements, but the diesel pump controller had an abnormal condition. The factory was asked to provide missing documentation and address deficiencies including supervision of closed valves and a missing reservoir level gauge.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Inspection Checklist
Factory: Cotton Clothing Ltd. Date of Inspection: 4-Nov-2019
Accord ID: 12051 Inspector(s): Safawan Abyaz
Fire Pump System
Pre-T&CVI Documentation and Equipment Review Document Review Yes x No Approved as-built drawings are available and on-site, including: Pump Room Detail Fire Water Storage Tank Detail Yes x No Required documentation is available and on-site, including: Pump Acceptance Testing x Product Information Sheets and Listing Information x Third Party Listing Certificates Manufacturer's Fire Pump Test Curve Pump and Driver Information Model Number: NF-S-150-100 Suction/Discharge Diameter: 6X4 Rated Flow/Pressure: 750/116 psi Diesel Pump Impeller Diameter: 248 mm Rated Speed (RPM): 2900 Maximum Operating Pressure: 127 psi Churn Pressure: _____________ Head at 150% Capacity: 88 psi Diesel Motor Model Number: FD140H Rated Power (HP): 127 Rated Speed (RPM): 2900 Model Number: NF-S-150-100 Suction/Discharge Diameter: 6X4 Rated Flow/Pressure: 750/116 psi Electric Pump Impeller Diameter: 248 mm Rated Speed (RPM): 2900 Maximum Operating Pressure: 125 psi Churn Pressure: _____________ Head at 150% Capacity: 87 psi Electric Motor Model Number: NMCM501002PO Rated Power (kW): 75 Rated Speed (RPM): 2940 Visual Pre-Inspection X Yes No Isolation valve provided for pump room test header line X Yes No Fire pump room test header line flow meter listed and calibrated X Yes No Pressure gauge provided on suction and discharge sides of fire pump(s) Yes X No Fire pump controllers free of abnormal system conditions Pre T&C Inspection notes * Disel pump controller was not free of abnormal condition. * Normally closed valves shall be supervised. (Flow Testlines) * Reservoir level gauge is missing. * factory has to provide invidual fire pump acceptance test report. * factory has to provide invidual fire pump manufacturer curve. * PS lines, Fuel Lines, Flow test line, anti-vortex plates details required. * Provide reservoir details with section drawing.