Assignment 4
Assignment 4
Assignment No.4
From Figure 1,
Determine the time-delay lever setting to achieve an operating time of 1.0 s for a relay set at
10.0A pickup and an operating current of 50 A.
Figure 1
Draw the one-line diagram of a 138/12 kV, 10 000 kVA, 15%, grounded-wye/delta transformer,
12 kV circuit breaker, 138 kV motor-operated switch, and 138 kV 1200/5 MR CTs connected
600/5. Add the following relays and meters: three instantaneous overcurrent relays, two phase
time-delay overcurrent relays, three ammeters, and onetime-delay overcurrent ground relay.
Show the appropriate ANSI device function numbers. (b) Draw the associated three-phase AC
CT secondary, relay, and meter connections. (c) Draw the DC tripping circuit showing the relay
contacts and the circuit breaker trip coil and auxiliary switch.
horo witz manual1 4.2
Problem 3: Marks[20]
Figure 2
Figure 3a
Figure 3b
Problem 5: problem 2 in Assignment 5_2008_Solution Marks[10]
A three-phase line is connected to sources A, B and C (figure 4). A three phase fault occurs at
the half way point between T and C. Calculate the impedance seen by the relays at circuit
breaker 1 and 2 before any circuit breaker open. Assume that the voltages of all the three
sources are 1.0 p.u.
Figure 4
Determine the three zone settings for the relay Rab in the system shown in Figure 5. The
system nominal voltage is 138 kV and the positive sequence impedances for the various
elements are given in the figure3. Assume that the maximum load at the relay site is 120MVA,
and select a CT ratio accordingly. The available distance relay has zone 1 and zone 2 6 Of 11
settings from 0.2 to 10 ohms and zone 3 settings from 0.5 to 40 ohms in increments of 0.1
ohm. The angle of maximum torque can be adjusted to 75° or 90°.
Figure 5
problem 1 in Assignment 5_2008_Solution & mnual 5.1
Problem 7: Marks[15]
Figure 6