Po Atex 2017-En
Po Atex 2017-En
Ex db eb IIC T6 Gb
0081 II 2 G/D
Ex tb IIIC T80°C Db IP66
MARKING FOR ASSOCIATED EQUIPMENT
(e.g. intrinsic safety interfaces)
[Ex ia Ga ] IIC
0081 II (1) G/D
[Ex ia Da ] IIIC
Number of Notified Body (0081=LCIE) for evaluation of the quality system
[ 1 mm wires
Dust-protected (minor ingress) 5 5 Water-jets from any direction
METHOD OF PROTECTION FOR ELECTRICAL EQUIPMENT - GAS AREAS METHOD OF PROTECTION FOR ELECTRICAL EQUIPMENT - DUST AREAS
General rules for Electrical Equipment in Gas Areas EN/IEC 60079-0 General rules - Electrical Equipment in Dust Areas EN/IEC 60079-0
Method of Method of
Installation Category Principe Standard EN/IEC Examples Installation Category Principe Standard EN/IEC Examples
protection protection
ia Intrinsic safety 60079-11
Zone 0
ma Encapsulation 60079-18
ia Intrinsic safety 60079-11
Zone 20
II 1 G
op is / op sh Optical radiation 60079-28
II 1 D ma Encapsulation 60079-18
da Explosion-proof enclosure 60079-1
ta Protective enclosure 60079-31
ib Intrinsic safety 60079-11 Intrinsic safety
Protective
m / mb Encapsulation 60079-18 enclosure
op is /op sh /op pr Optical radiation 60079-28
Zone 1
II 2 G m / mb Encapsulation 60079-18
px / pxb / py / pyb Pressurised enclosure 60079-2 II 2 D
q / qb Powder-filled 60079-5 pb Pressurised enclosure 60079-2
o / ob Oil immersion 60079-6 Explosion-proof tb Protective enclosure 60079-31 Encapsulation
enclosure
e / eb Increased safety 60079-7
ic Intrinsic safety 60079-11
m / mc Encapsulation 60079-18 ic Intrinsic safety 60079-11
Zone 22
The T(X) marking can be applied on an equipment : it indicates that the temperature classification is dependent
on particular conditions of use - Refer to the associated manual.
po-atex6-en-20-04-2017