PCV1131

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or VRV indoor units combine with
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion. residential indoor units, all in one system
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Single outdoor unit series


—suitable for homes, offices, shops, and middle-sized buildings

Catalogue No: VRV3-0315-A


Cooling Only 50 Hz
Contents

Main Features................................page 3 Option List....................................page 35

Outdoor Unit Lineup......................page 4 Indoor units.............................page 35


• VRV.....................................page 35
Meet the new single outdoor Indoor Unit Lineup.........................page 9
• VRV.....................................page 9
• Residential..........................page 37
BP units...................................page 38

unit series, connectable to both • Residential........................page 19

Specifications...............................page 24
Outdoor units...........................page 38
Control Systems...........................page 39

VRV and residential indoor units Indoor units.............................page 24


• VRV.....................................page 24
• Residential..........................page 31

BP units...................................page 33
Outdoor units...........................page 34

First launched in Japan in 1982, the Daikin VRV system


OFFICES
has been embraced by world markets for nearly 30 years.
Now, Daikin proudly introduces the new VRVIII single
outdoor unit series which enables a mixed combination of
VRV indoor units and residential indoor units all in one
system, opening the door to stylish and quiet indoor units.

SHOPS

1
HOMES 2
Contents

Main Features................................page 3 Option List....................................page 35

Outdoor Unit Lineup......................page 4 Indoor units.............................page 35


• VRV.....................................page 35
Meet the new single outdoor Indoor Unit Lineup.........................page 9
• VRV.....................................page 9
• Residential..........................page 37
BP units...................................page 38

unit series, connectable to both • Residential........................page 19

Specifications...............................page 24
Outdoor units...........................page 38
Control Systems...........................page 39

VRV and residential indoor units Indoor units.............................page 24


• VRV.....................................page 24
• Residential..........................page 31

BP units...................................page 33
Outdoor units...........................page 34

First launched in Japan in 1982, the Daikin VRV system


OFFICES
has been embraced by world markets for nearly 30 years.
Now, Daikin proudly introduces the new VRVIII single
outdoor unit series which enables a mixed combination of
VRV indoor units and residential indoor units all in one
system, opening the door to stylish and quiet indoor units.

SHOPS

1
HOMES 2
Main Features

Wide range of choices


Indoor units
Indoor units can be selected from 2 lineups, both VRV and
residential indoor units, to match rooms and preferences.

BP unit BP unit
Connection unit

VRV indoor units Residential indoor units

VRV indoor units 15 types 73 models Residential indoor units with connection to BP units 7 types 21 models
20 25 32 40 50 63 80 100 125 140 200 250 25 35 50 60 71
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP Type Model Name Rated Capacity 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW
Capacity Index 20 25 31.25 40 50 62.5 80 100 125 140 200 250 Capacity Index 29 40 55 68 79
Ceiling Mounted
Ceiling Mounted
Cassette FXFQ-PVE FCQ-BVE
Cassette
(Round Flow)
Ceiling Mounted Ceiling Mounted
Cassette FXZQ-MVE Cassette FFQ-BV1B
(Compact Multi Flow) (Compact Multi Flow)
Ceiling Mounted
Ceiling Mounted
Cassette FXCQ-MVE FBQ-BV1
Built-in
(Double Flow)

Ceiling Mounted
FXKQ-MAVE FDKS-EAVMB
Cassette Corner (700 mm width type)
Slim Ceiling
Mounted Duct
FXDQ-PBVE FDKS-C(A)VMB
(with drain pump)
(900/1,100 mm width type)

FXDQ-PBVET (700 mm width type)


(without drain pump) FTKS-DVM
Slim Ceiling
Mounted Duct Wall Mounted
FXDQ-NBVE
(with drain pump) FTKS-FVM

Note: BP units are necessary for residential indoor units. Refer to page 33 for BP unit details.
FXDQ-NBVET (900/1,100 mm width type)
(without drain pump)

FXMQ-PVE
Ceiling Mounted
Duct Outdoor units
FXMQ-MAVE The new VRVIII single outdoor unit series single outdoor unit series
offers 6 models to select from, providing
Ceiling Suspended FXHQ-MAVE the power that suits your needs.

Wall Mounted FXAQ-MAVE

Floor Standing FXLQ-MAVE

Concealed
Floor Standing FXNQ-MAVE
8, 10 HP 12, 14, 16, 18 HP
Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system. Outdoor unit lineup
VRV indoor units connection unit series
Model Name RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1
71 100 125
Capacity Range 3 HP 4 HP 5 HP
Type Model Name HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
Capacity Index 71 100 125 Capacity
Connection Unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE Range
kW 22.4 kW 28.0 kW 33.5 kW 40.0 kW 45.0 kW 49.0 kW
Ceiling Suspended
Note:
Cassette FXUQ-MAV1 Capacity Index 200 250 300 350 400 450
Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.
3 4
Main Features

Wide range of choices


Indoor units
Indoor units can be selected from 2 lineups, both VRV and
residential indoor units, to match rooms and preferences.

BP unit BP unit
Connection unit

VRV indoor units Residential indoor units

VRV indoor units 15 types 73 models Residential indoor units with connection to BP units 7 types 21 models
20 25 32 40 50 63 80 100 125 140 200 250 25 35 50 60 71
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP Type Model Name Rated Capacity 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW
Capacity Index 20 25 31.25 40 50 62.5 80 100 125 140 200 250 Capacity Index 29 40 55 68 79
Ceiling Mounted
Ceiling Mounted
Cassette FXFQ-PVE FCQ-BVE
Cassette
(Round Flow)
Ceiling Mounted Ceiling Mounted
Cassette FXZQ-MVE Cassette FFQ-BV1B
(Compact Multi Flow) (Compact Multi Flow)
Ceiling Mounted
Ceiling Mounted
Cassette FXCQ-MVE FBQ-BV1
Built-in
(Double Flow)

Ceiling Mounted
FXKQ-MAVE FDKS-EAVMB
Cassette Corner (700 mm width type)
Slim Ceiling
Mounted Duct
FXDQ-PBVE FDKS-C(A)VMB
(with drain pump)
(900/1,100 mm width type)

FXDQ-PBVET (700 mm width type)


(without drain pump) FTKS-DVM
Slim Ceiling
Mounted Duct Wall Mounted
FXDQ-NBVE
(with drain pump) FTKS-FVM

Note: BP units are necessary for residential indoor units. Refer to page 33 for BP unit details.
FXDQ-NBVET (900/1,100 mm width type)
(without drain pump)

FXMQ-PVE
Ceiling Mounted
Duct Outdoor units
FXMQ-MAVE The new VRVIII single outdoor unit series single outdoor unit series
offers 6 models to select from, providing
Ceiling Suspended FXHQ-MAVE the power that suits your needs.

Wall Mounted FXAQ-MAVE

Floor Standing FXLQ-MAVE

Concealed
Floor Standing FXNQ-MAVE
8, 10 HP 12, 14, 16, 18 HP
Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system. Outdoor unit lineup
VRV indoor units connection unit series
Model Name RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1
71 100 125
Capacity Range 3 HP 4 HP 5 HP
Type Model Name HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
Capacity Index 71 100 125 Capacity
Connection Unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE Range
kW 22.4 kW 28.0 kW 33.5 kW 40.0 kW 45.0 kW 49.0 kW
Ceiling Suspended
Note:
Cassette FXUQ-MAV1 Capacity Index 200 250 300 350 400 450
Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.
3 4
Main Features

Energy efficiency and quiet operation


A collection of cutting-edge technologies
Outdoor units use Daikin’s unique scroll compressor to realise energy saving performance realises efficient and quiet operation
and quiet operation.
5
1 High efficiency compressor 3

Reluctance DC scroll compressor


High COPs Daikin’s unique scroll compressor reduces heat loss, and is driven
2 4
by a high efficiency motor to achieve significant energy savings.
It has become essential for air conditioning manufacturers to develop systems that provide high
energy savings. We at Daikin have made great efforts in this field, and the VRVIII delivers highly
efficient performance, contributing to high energy savings. High torque and efficiency is attained with the adoption of
neodymium magnets.
1
Achieving a high COP 4.27
We have reached a high level of 3.75 Powerful magnets
4 3.54 Use of neodymium magnets in the motor enables efficient
efficiency, thanks to advanced generation of high torque.
features such as the heat 3
exchanger, the grille and the Neodymium magnets are well known for
2 their powerfulness compared to commonly
dual DC fans. used ferrite magnets.
1 High-performance, low-noise scroll compressor
operates at a fast rate. The speed increase has been
Reluctance achieved through advanced stress analysis for
8 HP 10 HP 12 HP DC motor increased strength and utilisation of the advantages
• Cooling operating conditions: Indoor temp. of 27°CDB, 19.0 °CWB, and outdoor temp. of 35°CDB. (oil film control) of the high thrust mechanism.*

*High thrust mechanism


By introducing high pressure oil, the reactive force from the fixed
Nighttime quiet operation function scroll is added to the internal force, thereby reducing thrust losses.
This results in improved efficiency and suppressed sound levels.

Operation sound level selectable from 3 steps for the night mode
Mode 1. Automatic mode
2 Heat exchanger 3 Compact aero box
Set on the outdoor PCB. Time of maximum
temperature is memorised. The low Mode 1. Automatic mode
Thanks to an optimised e-Pass heat exchanger, heat Realises a compact casing by stacking the Inverter and
operating mode will initiate 8 hours*1 after the change effectiveness has been increased, thus control PCBs plus optimising the internal design to suit
peak temperature in the daytime, and normal contributing to a high COP. airflow speed. This achieves low noise and reduces the
operation will resume 10 hours*2 after that. power required by the large-diameter fanned outdoor unit.
Operation sound dB(A) Load % Capacity %

The operation sound level for the night mode Peak in outdoor temperature (For 10 HP outdoor unit)
100
can be selected from 55 dB(A) (Step 1),
50 dB(A) (Step 2) and 45 dB(A) (Step 3). 4 Smooth sine wave DC Inverter 5 DC fan motor
8 hrs 10 hrs
(Initial setting) (Initial setting)
50 • Efficiency improvement by approximately 40% especially at
By adoption of the Sine Wave, which smoothes the
rotation of the motor, operation efficiency is improved low speed.
Mode 2. Manual mode
sharply. DC fan motor DC motor efficiency
Starting time and ending time can be input. 0 Night Mode structure (comparison with AC motor)
(An external control adaptor for outdoor unit, 58 100
Step 1 max. - 3dB(A) Step 1: 55 dB(A) DC motor
DTA104A53/61/62, and a locally obtained 55 80

Efficiency (%)
timer are necessary.) Step 2 max. - 8dB(A) Step 2: 50 dB(A)
50 60 Approx.
40%
increase
Mode 3. Combined mode Step 3 max. - 13dB(A) Step 3: 45 dB(A) 40
45 AC motor
Combinations of modes 1 and 2 can be used Night mode starts Night mode ends 20

depending on your needs. 8:00 12:00 16:00 20:00 0:00 4:00 8:00
0
200 300 400 500 600 700 800 900 1000
*1. Initial setting. Can be selected from 6, 8 and 10 hours. Notes: • This function is available in setting at site. Motor speed (rpm)
*2. Initial setting. Can be selected from 8, 9 and 10 hours. • The relationship of outdoor temperature (load) and time shown in the Note: Data are based on studies conducted under controlled conditions
graph is just an example. at a Daikin laboratory.
The capacity reduction rate differs depending on the operation sound level step selected.

5 6
Main Features

Energy efficiency and quiet operation


A collection of cutting-edge technologies
Outdoor units use Daikin’s unique scroll compressor to realise energy saving performance realises efficient and quiet operation
and quiet operation.
5
1 High efficiency compressor 3

Reluctance DC scroll compressor


High COPs Daikin’s unique scroll compressor reduces heat loss, and is driven
2 4
by a high efficiency motor to achieve significant energy savings.
It has become essential for air conditioning manufacturers to develop systems that provide high
energy savings. We at Daikin have made great efforts in this field, and the VRVIII delivers highly
efficient performance, contributing to high energy savings. High torque and efficiency is attained with the adoption of
neodymium magnets.
1
Achieving a high COP 4.27
We have reached a high level of 3.75 Powerful magnets
4 3.54 Use of neodymium magnets in the motor enables efficient
efficiency, thanks to advanced generation of high torque.
features such as the heat 3
exchanger, the grille and the Neodymium magnets are well known for
2 their powerfulness compared to commonly
dual DC fans. used ferrite magnets.
1 High-performance, low-noise scroll compressor
operates at a fast rate. The speed increase has been
Reluctance achieved through advanced stress analysis for
8 HP 10 HP 12 HP DC motor increased strength and utilisation of the advantages
• Cooling operating conditions: Indoor temp. of 27°CDB, 19.0 °CWB, and outdoor temp. of 35°CDB. (oil film control) of the high thrust mechanism.*

*High thrust mechanism


By introducing high pressure oil, the reactive force from the fixed
Nighttime quiet operation function scroll is added to the internal force, thereby reducing thrust losses.
This results in improved efficiency and suppressed sound levels.

Operation sound level selectable from 3 steps for the night mode
Mode 1. Automatic mode
2 Heat exchanger 3 Compact aero box
Set on the outdoor PCB. Time of maximum
temperature is memorised. The low Mode 1. Automatic mode
Thanks to an optimised e-Pass heat exchanger, heat Realises a compact casing by stacking the Inverter and
operating mode will initiate 8 hours*1 after the change effectiveness has been increased, thus control PCBs plus optimising the internal design to suit
peak temperature in the daytime, and normal contributing to a high COP. airflow speed. This achieves low noise and reduces the
operation will resume 10 hours*2 after that. power required by the large-diameter fanned outdoor unit.
Operation sound dB(A) Load % Capacity %

The operation sound level for the night mode Peak in outdoor temperature (For 10 HP outdoor unit)
100
can be selected from 55 dB(A) (Step 1),
50 dB(A) (Step 2) and 45 dB(A) (Step 3). 4 Smooth sine wave DC Inverter 5 DC fan motor
8 hrs 10 hrs
(Initial setting) (Initial setting)
50 • Efficiency improvement by approximately 40% especially at
By adoption of the Sine Wave, which smoothes the
rotation of the motor, operation efficiency is improved low speed.
Mode 2. Manual mode
sharply. DC fan motor DC motor efficiency
Starting time and ending time can be input. 0 Night Mode structure (comparison with AC motor)
(An external control adaptor for outdoor unit, 58 100
Step 1 max. - 3dB(A) Step 1: 55 dB(A) DC motor
DTA104A53/61/62, and a locally obtained 55 80

Efficiency (%)
timer are necessary.) Step 2 max. - 8dB(A) Step 2: 50 dB(A)
50 60 Approx.
40%
increase
Mode 3. Combined mode Step 3 max. - 13dB(A) Step 3: 45 dB(A) 40
45 AC motor
Combinations of modes 1 and 2 can be used Night mode starts Night mode ends 20

depending on your needs. 8:00 12:00 16:00 20:00 0:00 4:00 8:00
0
200 300 400 500 600 700 800 900 1000
*1. Initial setting. Can be selected from 6, 8 and 10 hours. Notes: • This function is available in setting at site. Motor speed (rpm)
*2. Initial setting. Can be selected from 8, 9 and 10 hours. • The relationship of outdoor temperature (load) and time shown in the Note: Data are based on studies conducted under controlled conditions
graph is just an example. at a Daikin laboratory.
The capacity reduction rate differs depending on the operation sound level step selected.

5 6
Main Features

Design flexibility As many as 29 indoor units can be connected


VRVIII single outdoor unit series enables a mixed combination of VRV and residential indoor units by
connecting BP units. As many as 29 indoor units can be connected, making this series a highly versatile
Long piping length Actual piping length Total piping length
system.
Long piping length offers flexibility during installation. Max. 100 m Max. 250 m
BP unit BP unit

Colours in the diagram below are merely for identifying


Max.
When only VRV indoor units are connected
pipes referenced with symbols such as a .
29 Indoor
units Residential indoor units

a
b c d
e f g h i
First indoor branch
VRV indoor units
Max.
50 m k Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
Max. Refer to page 34 for the maximum number of connectable indoor units.
j 15 m

When only VRV indoor units are connected Actual Equivalent


piping length Example piping length
Refrigerant piping length 100 m a+b+c+d+i 125 m High external static pressure of 78.4 Pa
Maximum allowable
Total piping length 250 m a+b+c+d+e+f+g+h+i —
piping length High external static pressure has been achieved thanks to the fan grilles
Between the first indoor branch and the farthest indoor unit 40 m b+c+d+i — 78.4 Pa
and the dual DC fans that reduce internal pressure loss. Daikin offers 78.4
Level Difference Example
Pa (8 mm H2O) external static pressure by field setting to meet the
Between the indoor units 15 m j
Maximum allowable requirements for installation on each floor.
level difference Between the outdoor unit If the outdoor unit is above. 50 m k
and the indoor unit If the outdoor unit is below. 40 m k

When a mixed combination of VRV and Colours in the diagram below are merely for identifying
pipes referenced with symbols such as a .
residential indoor units is connected

VRV: VRV indoor unit


a b c d Easy Installation High reliability
RA: Residential indoor unit e f g Max.
BP: BP unit First indoor branch
o
BP 40 m Small and light, significantly reducing
Max. Max.
m
Backup operation
h i 15 m
50 m n
j
BP constraints during carry-in If one of the multiple compressors malfunctions, the
Carry-in possible using other compressors take over for emergency operation.*1
RA RA VRV
k ordinary elevators Easy belt
Max. suspension
l
RA VRV If one compressor
15 m malfunctions...
RA

When a mixed combination of VRV and residential indoor units is connected


Actual
or when only residential indoor units are connected piping length Example
Refrigerant piping length 100 m a+b+c+g+k, a+b+c+d
Total piping length 250 m a+b+c+d+e+f+g+h+i+j+k

Maximum allowable If indoor unit capacity index < 68. 2 m–15 m


piping length Between BP unit
If indoor unit capacity index is 68. 2 m–12 m h, i, j, k
and indoor unit
If indoor unit capacity index is 79. 2 m–8 m Emergency operation occurs.*1
Between the first indoor branch and the farthest BP unit or
50 m*1 b+c+g, b+c+d
between the first indoor branch and the farthest VRV indoor unit *1. Possible only with single outdoor unit systems that are
Can be carried on a
Minimum allowable piping length Between outdoor unit and the first indoor branch 5m a equipped with two or more compressors. Local setting of
fork-lift without a pallet
the outdoor unit is necessary.

Level Difference Example


Between the indoor units 15 m l
Automatic test operation Less chances of refrigerant leakage
Between BP units 15 m m
Maximum allowable
If the outdoor unit is above. 50 m n
Simply press the test operation button and the unit The shutoff valve connections for outdoor unit
level difference Between the outdoor unit
and the indoor unit If the outdoor unit is below. 40 m n performs an automatic system check, including are brazed, meaning less chance of refrigerant
Between the outdoor unit and the BP unit 40 m o wiring, shutoff valves, and sensors. The results are leakage compared with flanged or flared
*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased. Please refer to Engineering returned automatically after the check finishes. connections.
Data Book for details.

7 8
Main Features

Design flexibility As many as 29 indoor units can be connected


VRVIII single outdoor unit series enables a mixed combination of VRV and residential indoor units by
connecting BP units. As many as 29 indoor units can be connected, making this series a highly versatile
Long piping length Actual piping length Total piping length
system.
Long piping length offers flexibility during installation. Max. 100 m Max. 250 m
BP unit BP unit

Colours in the diagram below are merely for identifying


Max.
When only VRV indoor units are connected
pipes referenced with symbols such as a .
29 Indoor
units Residential indoor units

a
b c d
e f g h i
First indoor branch
VRV indoor units
Max.
50 m k Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
Max. Refer to page 34 for the maximum number of connectable indoor units.
j 15 m

When only VRV indoor units are connected Actual Equivalent


piping length Example piping length
Refrigerant piping length 100 m a+b+c+d+i 125 m High external static pressure of 78.4 Pa
Maximum allowable
Total piping length 250 m a+b+c+d+e+f+g+h+i —
piping length High external static pressure has been achieved thanks to the fan grilles
Between the first indoor branch and the farthest indoor unit 40 m b+c+d+i — 78.4 Pa
and the dual DC fans that reduce internal pressure loss. Daikin offers 78.4
Level Difference Example
Pa (8 mm H2O) external static pressure by field setting to meet the
Between the indoor units 15 m j
Maximum allowable requirements for installation on each floor.
level difference Between the outdoor unit If the outdoor unit is above. 50 m k
and the indoor unit If the outdoor unit is below. 40 m k

When a mixed combination of VRV and Colours in the diagram below are merely for identifying
pipes referenced with symbols such as a .
residential indoor units is connected

VRV: VRV indoor unit


a b c d Easy Installation High reliability
RA: Residential indoor unit e f g Max.
BP: BP unit First indoor branch
o
BP 40 m Small and light, significantly reducing
Max. Max.
m
Backup operation
h i 15 m
50 m n
j
BP constraints during carry-in If one of the multiple compressors malfunctions, the
Carry-in possible using other compressors take over for emergency operation.*1
RA RA VRV
k ordinary elevators Easy belt
Max. suspension
l
RA VRV If one compressor
15 m malfunctions...
RA

When a mixed combination of VRV and residential indoor units is connected


Actual
or when only residential indoor units are connected piping length Example
Refrigerant piping length 100 m a+b+c+g+k, a+b+c+d
Total piping length 250 m a+b+c+d+e+f+g+h+i+j+k

Maximum allowable If indoor unit capacity index < 68. 2 m–15 m


piping length Between BP unit
If indoor unit capacity index is 68. 2 m–12 m h, i, j, k
and indoor unit
If indoor unit capacity index is 79. 2 m–8 m Emergency operation occurs.*1
Between the first indoor branch and the farthest BP unit or
50 m*1 b+c+g, b+c+d
between the first indoor branch and the farthest VRV indoor unit *1. Possible only with single outdoor unit systems that are
Can be carried on a
Minimum allowable piping length Between outdoor unit and the first indoor branch 5m a equipped with two or more compressors. Local setting of
fork-lift without a pallet
the outdoor unit is necessary.

Level Difference Example


Between the indoor units 15 m l
Automatic test operation Less chances of refrigerant leakage
Between BP units 15 m m
Maximum allowable
If the outdoor unit is above. 50 m n
Simply press the test operation button and the unit The shutoff valve connections for outdoor unit
level difference Between the outdoor unit
and the indoor unit If the outdoor unit is below. 40 m n performs an automatic system check, including are brazed, meaning less chance of refrigerant
Between the outdoor unit and the BP unit 40 m o wiring, shutoff valves, and sensors. The results are leakage compared with flanged or flared
*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased. Please refer to Engineering returned automatically after the check finishes. connections.
Data Book for details.

7 8
Indoor Unit Lineup
VRV Indoor Units

Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type

FXFQ25P/ FXFQ32P/ FXFQ40P


FXZQ20M / FXZQ25M / FXZQ32M
FXFQ50P/ FXFQ63P/ FXFQ80P
FXZQ40M / FXZQ50M
FXFQ100P/ FXFQ125P

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details.

360° airflow improves temperature distribution


Quiet, compact, and designed for user comfort
and offers a comfortable living environment.
The industry’s first* Round Flow Ceiling Mounted Dimensions correspond with 600 mm X 600 mm
Cassette type offers 360° airflow with improved architectural module ceiling design
temperature distribution. specifications.
4-way flow Round Flow

Low operation sound level (dB(A))

FXZQ-M 20/25 32 40 50

Sound level 230 V 30/25 32/26 36/28 41/33

There are areas of There are much fewer (H/L) 240 V 32/26 34/28 37/29 42/35
uneven temperature. areas of uneven temperature.
* As of April 2004, the release date for Japan.
All models are lighter than the conventional ones. Comfortable airflow
Ex: Models FXFQ25P-50P are 4.5 kg lighter
1 Wide discharge angle: 0° to 60°
(reduced from 24 kg to 19.5 kg).
Auto swing Fixed angles: 5 levels
Drain pump is equipped as
standard accessory, and the
850 mm
lift height has been improved 0° 0° 0° 0°

from 750 mm to 850 mm. 60°


60° 60° 60°
A modern sophisticated decoration panel has An antibacterial treatment that uses silver ions
Angles can be also set on site to prevent drafts (0°-35°)
been applied, with a panel surface that has been has been applied to the drain pan, preventing or soiling of the ceiling (25°-60°), other than standard setting (0°-60°).
treated with a dirt-repellant coating. the growth of slime, mould and bacteria that
Treated surface Untreated surface
cause blockages and odours. 2
Dirt and
2-, 3-, and 4-way airflow patterns are available,
Resists grime • Condition after
exposure to the The horizontal louvres prevent dew enabling installation in the corner of a room.
soiling
smoke of 600
cigarettes in 1 m
3 condensation. Their non-flocking surfaces, which
enclosed space.
repel dirt, are easy to clean. Drain pump is equipped as standard
Control of the airflow rate has been improved
accessory with 750 mm lift.
from 2-step to 3-step control.
The air filter has an anti-mould and antibacterial
Low operation sound level (dB(A)) treatment that prevents the growth of mould
FXFQ-P 25/32 40 50 63 80 100 125
generated from dust or moisture that may
Sound L-shaped 750 mm
level 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34 adhere to the filter. 4-way flow 3-way flow 2-way flow
(HH/H/L)
For 3-way or 2-way flow installation, the sealing member for air discharge
All-round flow 4-way flow 3-way flow L-shaped 2-way flow outlet (option) must be used to close each unused outlet.
Example of airflow patterns:
360° airflow is available, as well as 2- to
4-way flows, so you can choose the most
suitable airflow pattern depending on
location or room layout.

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.
9 10
Indoor Unit Lineup
VRV Indoor Units

Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type

FXFQ25P/ FXFQ32P/ FXFQ40P


FXZQ20M / FXZQ25M / FXZQ32M
FXFQ50P/ FXFQ63P/ FXFQ80P
FXZQ40M / FXZQ50M
FXFQ100P/ FXFQ125P

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details.

360° airflow improves temperature distribution


Quiet, compact, and designed for user comfort
and offers a comfortable living environment.
The industry’s first* Round Flow Ceiling Mounted Dimensions correspond with 600 mm X 600 mm
Cassette type offers 360° airflow with improved architectural module ceiling design
temperature distribution. specifications.
4-way flow Round Flow

Low operation sound level (dB(A))

FXZQ-M 20/25 32 40 50

Sound level 230 V 30/25 32/26 36/28 41/33

There are areas of There are much fewer (H/L) 240 V 32/26 34/28 37/29 42/35
uneven temperature. areas of uneven temperature.
* As of April 2004, the release date for Japan.
All models are lighter than the conventional ones. Comfortable airflow
Ex: Models FXFQ25P-50P are 4.5 kg lighter
1 Wide discharge angle: 0° to 60°
(reduced from 24 kg to 19.5 kg).
Auto swing Fixed angles: 5 levels
Drain pump is equipped as
standard accessory, and the
850 mm
lift height has been improved 0° 0° 0° 0°

from 750 mm to 850 mm. 60°


60° 60° 60°
A modern sophisticated decoration panel has An antibacterial treatment that uses silver ions
Angles can be also set on site to prevent drafts (0°-35°)
been applied, with a panel surface that has been has been applied to the drain pan, preventing or soiling of the ceiling (25°-60°), other than standard setting (0°-60°).
treated with a dirt-repellant coating. the growth of slime, mould and bacteria that
Treated surface Untreated surface
cause blockages and odours. 2
Dirt and
2-, 3-, and 4-way airflow patterns are available,
Resists grime • Condition after
exposure to the The horizontal louvres prevent dew enabling installation in the corner of a room.
soiling
smoke of 600
cigarettes in 1 m
3 condensation. Their non-flocking surfaces, which
enclosed space.
repel dirt, are easy to clean. Drain pump is equipped as standard
Control of the airflow rate has been improved
accessory with 750 mm lift.
from 2-step to 3-step control.
The air filter has an anti-mould and antibacterial
Low operation sound level (dB(A)) treatment that prevents the growth of mould
FXFQ-P 25/32 40 50 63 80 100 125
generated from dust or moisture that may
Sound L-shaped 750 mm
level 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34 adhere to the filter. 4-way flow 3-way flow 2-way flow
(HH/H/L)
For 3-way or 2-way flow installation, the sealing member for air discharge
All-round flow 4-way flow 3-way flow L-shaped 2-way flow outlet (option) must be used to close each unused outlet.
Example of airflow patterns:
360° airflow is available, as well as 2- to
4-way flows, so you can choose the most
suitable airflow pattern depending on
location or room layout.

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.
9 10
Indoor Unit Lineup
VRV Indoor Units

Ceiling Mounted Cassette (Double Flow) Type Ceiling Mounted Cassette Corner Type

FXCQ20M / FXCQ25M / FXCQ32M


FXKQ25MA /FXKQ32MA
FXCQ40M / FXCQ50M / FXCQ63M
FXKQ40MA /FXKQ63MA
FXCQ80M / FXCQ125M

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details.

Thin, lightweight, and easy to install in


narrow ceiling spaces Slim design for flexible installation
The thin unit (only 305 mm high) can be Slim body needs only 220 mm space above the Providing 3 different settings of standard, draft
installed in a ceiling space as narrow as ceiling. If you use a panel spacer (option), the prevention and ceiling soiling prevention, the
350 mm. All models feature a compact unit can be installed in the minimum space of auto swing mechanism realises even
design with a depth of only 600 mm. 195 mm. distribution of airflow and room temperature.
(m)
3
Min.195 mm 28˚C 26˚C
24˚C
305 mm
Panel spacer
2 32˚C 30˚C
22˚C
20 mm 1 20˚C
(When a high-efficiency filter is attached, the
0 1 2 3 4 5 6 (m)
unit's height is 400 mm.)
Single-flow type allows effective air discharge
from corner or from drop-ceiling. Front discharge is possible with an air
Low operation sound level (dB(A))
discharge unit (option), which allows the
FXCQ-M 20 25/32 40/50 63 80 125
Drain pump is equipped as standard installation in the drop-ceiling or sagging wall.
Sound level 220 V 32/27 34/28 34/29 37/32 39/34 44/38 accessory with 500 mm lift.
(H/L) Main body
240 V 34/29 36/30 37/32 39/34 41/36 46/40

Downward discharge
500 mm
Designed with higher airflow suitable for
high ceiling application up to 3 metres. Air discharge grille (Option)

Providing 2 different settings of standard


and ceiling soiling prevention, the auto Set for front discharge using a suspended ceiling.

swing mechanism realises even distribution Two types of optional high-efficiency filter are Main body
of airflow and room temperature. available (65% and 95%, colourimetric method).

Drain pump is equipped as standard A long-life filter (maintenance free up to one


Air discharge grille
accessory with 600 mm lift. year*) is equipped as standard accessory. (Option)
3
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m

Major maintenance work can be performed by


600 mm Downward discharge is shut off and air is blown straight out
removing the panel. A flat-type suction grille (front discharge).
and a detachable blade make cleaning easy.
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

11 12
Indoor Unit Lineup
VRV Indoor Units

Ceiling Mounted Cassette (Double Flow) Type Ceiling Mounted Cassette Corner Type

FXCQ20M / FXCQ25M / FXCQ32M


FXKQ25MA /FXKQ32MA
FXCQ40M / FXCQ50M / FXCQ63M
FXKQ40MA /FXKQ63MA
FXCQ80M / FXCQ125M

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details.

Thin, lightweight, and easy to install in


narrow ceiling spaces Slim design for flexible installation
The thin unit (only 305 mm high) can be Slim body needs only 220 mm space above the Providing 3 different settings of standard, draft
installed in a ceiling space as narrow as ceiling. If you use a panel spacer (option), the prevention and ceiling soiling prevention, the
350 mm. All models feature a compact unit can be installed in the minimum space of auto swing mechanism realises even
design with a depth of only 600 mm. 195 mm. distribution of airflow and room temperature.
(m)
3
Min.195 mm 28˚C 26˚C
24˚C
305 mm
Panel spacer
2 32˚C 30˚C
22˚C
20 mm 1 20˚C
(When a high-efficiency filter is attached, the
0 1 2 3 4 5 6 (m)
unit's height is 400 mm.)
Single-flow type allows effective air discharge
from corner or from drop-ceiling. Front discharge is possible with an air
Low operation sound level (dB(A))
discharge unit (option), which allows the
FXCQ-M 20 25/32 40/50 63 80 125
Drain pump is equipped as standard installation in the drop-ceiling or sagging wall.
Sound level 220 V 32/27 34/28 34/29 37/32 39/34 44/38 accessory with 500 mm lift.
(H/L) Main body
240 V 34/29 36/30 37/32 39/34 41/36 46/40

Downward discharge
500 mm
Designed with higher airflow suitable for
high ceiling application up to 3 metres. Air discharge grille (Option)

Providing 2 different settings of standard


and ceiling soiling prevention, the auto Set for front discharge using a suspended ceiling.

swing mechanism realises even distribution Two types of optional high-efficiency filter are Main body
of airflow and room temperature. available (65% and 95%, colourimetric method).

Drain pump is equipped as standard A long-life filter (maintenance free up to one


Air discharge grille
accessory with 600 mm lift. year*) is equipped as standard accessory. (Option)
3
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m

Major maintenance work can be performed by


600 mm Downward discharge is shut off and air is blown straight out
removing the panel. A flat-type suction grille (front discharge).
and a detachable blade make cleaning easy.
A long-life filter (maintenance free up to one
year*) is equipped as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

11 12
Indoor Unit Lineup
VRV Indoor Units

Slim Ceiling Mounted Duct Type Ceiling Mounted Duct Type

Slim design, quietness and FXMQ20P/ FXMQ25P/FXMQ32P


static pressure switching FXMQ40P/ FXMQ50P/FXMQ63P
FXMQ80P/FXMQ100P/ FXMQ125P
FXMQ140P
* Remote controllers are an optional accessory. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details. Refer to page 39 for remote controller details.

Suited to use in drop-ceilings!


FXDQ40NB/ FXDQ50NB/ FXDQ63NB Middle and high static pressure
FXDQ20PB/ FXDQ25PB/ FXDQ32PB allows for flexible duct design
Only 200 mm in height, this model can be
Only 700 mm in width and 23 kg in weight, this A DC fan motor increases the external static
installed in rooms with as little as 240 mm depth pressure capacity range to include middle to high
model is suitable to install in limited spaces like between the drop-ceiling and ceiling slab. static pressures, increasing design flexibility.
drop-ceilings in hotels.
30 Pa–100 Pa for FXMQ20P-32P
30 Pa–160 Pa for FXMQ40P
Great for 50 Pa–200 Pa for FXMQ50P-125P
hotel use! 50 Pa–140 Pa for FXMQ140P
All models are only 300 mm in height, an
200 mm improvement over the 390 mm height of
900 mm conventional models. The weight of the
200 mm FXMQ40P has been reduced from 44 kg to 28 kg.
1,100 mm in width for the FXDQ63NB model.
Only 700 mm Drain pump is equipped as
standard accessory with 700 mm
700 mm lift.
Suspension bolt* Air filter
Ceiling

Improved ease of installation


Control of the airflow rate has been improved
AIR 240 mm from 2-step to 3-step control.
The airflow rate can be controlled using a remote
controller during test operation. With the conventional
Discharge grille* Low operation sound level (dB(A)) model, the airflow rate was controlled from the PC
Suction grille*
AIR FXMQ-P 20/25 32 40 50 63 80/100 125 140 board. It is automatically adjusted to the range
* To be obtained locally Sound between approximately ±10% of the rated HH tap
level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
(HH/H/L) airflow for FXMQ20P–125P.
External static pressure selectable by remote
controller switching make this indoor unit a very Energy-efficient Improved ease of maintenance
comfortable and flexible model. The drain pan can be detached for easy cleaning. An
The adopted DC fan motor is much more efficient than
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models. antibacterial treatment that uses silver ions has been
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models. the conventional AC motor, yielding an approximate applied to the drain pan, preventing the growth of slime,
20% decrease in energy consumption (FXMQ125P). mould and bacteria that cause blockages and odours.
FXDQ-PB and FXDQ-NB models are available in
two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXMQ200MA/FXMQ250MA Built-in Drain Pump (Option)
FXDQ-PB/NBVET: without a drain pump Housing the drain pump inside the unit reduces the
Control of the airflow rate has been improved space required for installation.
from 2-step to 3-step control.
Without drain pump With drain pump
Low operation sound level (dB(A))
750 mm 0–250
FXDQ-PB/NB 20/25/32 40 50 63 mm

Sound level 470 mm 470 mm


33/31/29 34/32/30 35/33/31 36/34/32 Simplified Static Pressure Control 222 mm
(HH/H/L)
Ceiling 25 mm
The values of operation sound level represent those for rear-suction operation. External static pressure can be easily adjusted using
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
Values are based on the following conditions:
a change-over switch inside the electrical box to meet Indoor unit Indoor unit
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa. the resistance in the duct system.
13 14
Indoor Unit Lineup
VRV Indoor Units

Slim Ceiling Mounted Duct Type Ceiling Mounted Duct Type

Slim design, quietness and FXMQ20P/ FXMQ25P/FXMQ32P


static pressure switching FXMQ40P/ FXMQ50P/FXMQ63P
FXMQ80P/FXMQ100P/ FXMQ125P
FXMQ140P
* Remote controllers are an optional accessory. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details. Refer to page 39 for remote controller details.

Suited to use in drop-ceilings!


FXDQ40NB/ FXDQ50NB/ FXDQ63NB Middle and high static pressure
FXDQ20PB/ FXDQ25PB/ FXDQ32PB allows for flexible duct design
Only 200 mm in height, this model can be
Only 700 mm in width and 23 kg in weight, this A DC fan motor increases the external static
installed in rooms with as little as 240 mm depth pressure capacity range to include middle to high
model is suitable to install in limited spaces like between the drop-ceiling and ceiling slab. static pressures, increasing design flexibility.
drop-ceilings in hotels.
30 Pa–100 Pa for FXMQ20P-32P
30 Pa–160 Pa for FXMQ40P
Great for 50 Pa–200 Pa for FXMQ50P-125P
hotel use! 50 Pa–140 Pa for FXMQ140P
All models are only 300 mm in height, an
200 mm improvement over the 390 mm height of
900 mm conventional models. The weight of the
200 mm FXMQ40P has been reduced from 44 kg to 28 kg.
1,100 mm in width for the FXDQ63NB model.
Only 700 mm Drain pump is equipped as
standard accessory with 700 mm
700 mm lift.
Suspension bolt* Air filter
Ceiling

Improved ease of installation


Control of the airflow rate has been improved
AIR 240 mm from 2-step to 3-step control.
The airflow rate can be controlled using a remote
controller during test operation. With the conventional
Discharge grille* Low operation sound level (dB(A)) model, the airflow rate was controlled from the PC
Suction grille*
AIR FXMQ-P 20/25 32 40 50 63 80/100 125 140 board. It is automatically adjusted to the range
* To be obtained locally Sound between approximately ±10% of the rated HH tap
level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
(HH/H/L) airflow for FXMQ20P–125P.
External static pressure selectable by remote
controller switching make this indoor unit a very Energy-efficient Improved ease of maintenance
comfortable and flexible model. The drain pan can be detached for easy cleaning. An
The adopted DC fan motor is much more efficient than
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models. antibacterial treatment that uses silver ions has been
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models. the conventional AC motor, yielding an approximate applied to the drain pan, preventing the growth of slime,
20% decrease in energy consumption (FXMQ125P). mould and bacteria that cause blockages and odours.
FXDQ-PB and FXDQ-NB models are available in
two types to suit different installation conditions.
FXDQ-PB/NBVE: with a drain pump (750 mm lift)
as a standard accessory
FXMQ200MA/FXMQ250MA Built-in Drain Pump (Option)
FXDQ-PB/NBVET: without a drain pump Housing the drain pump inside the unit reduces the
Control of the airflow rate has been improved space required for installation.
from 2-step to 3-step control.
Without drain pump With drain pump
Low operation sound level (dB(A))
750 mm 0–250
FXDQ-PB/NB 20/25/32 40 50 63 mm

Sound level 470 mm 470 mm


33/31/29 34/32/30 35/33/31 36/34/32 Simplified Static Pressure Control 222 mm
(HH/H/L)
Ceiling 25 mm
The values of operation sound level represent those for rear-suction operation. External static pressure can be easily adjusted using
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
Values are based on the following conditions:
a change-over switch inside the electrical box to meet Indoor unit Indoor unit
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa. the resistance in the duct system.
13 14
Indoor Unit Lineup
VRV Indoor Units

Ceiling Suspended Type Wall Mounted Type

FXAQ20MA/FXAQ25MA
FXHQ32MA / FXHQ63MA
FXAQ32MA/FXAQ40MA
FXHQ100MA
FXAQ50MA/FXAQ63MA
* Remote controllers are an optional accessory. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details. Refer to page 39 for remote controller details.

Sophisticated design and compact casing


Slim body with quiet and wide airflow
harmonised with your interior décor
Adoption of QUIET STREAM FAN Compact and stylish design that does not
Uses the quiet stream fan and many detract from the décor of the room.
more advanced technologies.
Sound absorption
member Low operation sound level (dB(A))
FXAQ-MA 20 25 32 40 50 63
Sound level
(H/L) 35/29 36/29 37/29 39/34 42/36 46/39

Turbulent flow Quiet stream fan Drain pan and air filter can be kept clean by
is produced
Straightening vane
mildew-proof polystyrene.

Low operation sound level (dB(A)) Washable grille, the front grille can be easily
FXHQ-MA 32 63 100 removed for washing.
Sound level
36/31 39/34 45/37
(H/L)
Auto-swing realises efficiency of air
distribution. The louvre closes automatically
Installation is easy
when the unit stops.
Drain pump kit (option) can be easily
incorporated.
5 steps of discharge angle can be set by
600 mm
remote controller.
Maintenance is easy
Discharge angle is automatically set at the Drain pump kit is available as optional
Drain pump kit Non-dew Flap with no implanted bristles
(built inside main unit) Bristle-free Flap minimises
same angle as the previous operation when accessory, which lifts the drain 1,000 mm from
contamination and makes restarting. (Initial setting: 10˚ for cooling) the bottom of the unit.
cleaning simpler.
Wide air discharge openings produce a Non-dew Flap
Height of drain-up
Easy-to-clean flat design Flexible installation
spreading 100° airflow.
Maintenance is easier because everything can Drain pipe can be fitted to from either left or
be performed from below the unit. right sides.
1,000 mm

A long-life filter (maintenance free up to one


year*) is equipped as standard accessory.
Indoor unit
100° * 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Drain pump kit

15 16
Indoor Unit Lineup
VRV Indoor Units

Ceiling Suspended Type Wall Mounted Type

FXAQ20MA/FXAQ25MA
FXHQ32MA / FXHQ63MA
FXAQ32MA/FXAQ40MA
FXHQ100MA
FXAQ50MA/FXAQ63MA
* Remote controllers are an optional accessory. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details. Refer to page 39 for remote controller details.

Sophisticated design and compact casing


Slim body with quiet and wide airflow
harmonised with your interior décor
Adoption of QUIET STREAM FAN Compact and stylish design that does not
Uses the quiet stream fan and many detract from the décor of the room.
more advanced technologies.
Sound absorption
member Low operation sound level (dB(A))
FXAQ-MA 20 25 32 40 50 63
Sound level
(H/L) 35/29 36/29 37/29 39/34 42/36 46/39

Turbulent flow Quiet stream fan Drain pan and air filter can be kept clean by
is produced
Straightening vane
mildew-proof polystyrene.

Low operation sound level (dB(A)) Washable grille, the front grille can be easily
FXHQ-MA 32 63 100 removed for washing.
Sound level
36/31 39/34 45/37
(H/L)
Auto-swing realises efficiency of air
distribution. The louvre closes automatically
Installation is easy
when the unit stops.
Drain pump kit (option) can be easily
incorporated.
5 steps of discharge angle can be set by
600 mm
remote controller.
Maintenance is easy
Discharge angle is automatically set at the Drain pump kit is available as optional
Drain pump kit Non-dew Flap with no implanted bristles
(built inside main unit) Bristle-free Flap minimises
same angle as the previous operation when accessory, which lifts the drain 1,000 mm from
contamination and makes restarting. (Initial setting: 10˚ for cooling) the bottom of the unit.
cleaning simpler.
Wide air discharge openings produce a Non-dew Flap
Height of drain-up
Easy-to-clean flat design Flexible installation
spreading 100° airflow.
Maintenance is easier because everything can Drain pipe can be fitted to from either left or
be performed from below the unit. right sides.
1,000 mm

A long-life filter (maintenance free up to one


year*) is equipped as standard accessory.
Indoor unit
100° * 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Drain pump kit

15 16
Indoor Unit Lineup
VRV Indoor Units
Connection unit series indoor units
Floor Standing Type Ceiling Suspended Cassette Type

FXLQ20MA / FXLQ25MA FXUQ71MA/FXUQ100MA


FXLQ32MA/FXLQ40MA FXUQ125MA
FXLQ50MA / FXLQ63MA

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details.

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details.
This thin indoor unit achieves
Suitable for perimeter zone air conditioning optimum air distribution, and can be installed
Floor Standing types can be hung on the wall for easier without the need for ceiling cavity.
cleaning. Running the piping from the back allows the unit to be
hung on walls. Cleaning under the unit, where dust tends to
Depending on installation site requirements or room
accumulate, is considerably easier.
conditions, 2-way, 3-way and 4-way discharge
The adoption of a fibre-less discharge grille featuring an original patterns are available.
design to prevent condensation also helps prevent staining and
makes cleaning easier.
4-way airflow The 3-way airflow can distribute
A long-life filter (maintenance free up to one year*) is equipped from the centre of the store. comfortable air throughout the room.

as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Wall hanging Floor installation

Concealed Floor Standing Type

Only one unit is needed to distribute comfortable air


throughout an L-shaped store.

FXNQ20MA / FXNQ25MA
FXNQ32MA/FXNQ40MA
FXNQ50MA / FXNQ63MA

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details.

Designed to be concealed in the perimeter skirting-wall Connection unit Connection unit is the device for connecting above indoor unit to VRV III.
BEVQ71MA/BEVQ100MA/BEVQ125MA
The unit is concealed in skirting-wall of perimeter, that enables
Refrigerant piping layout External wiring layout *1 Maximum piping length
to create high class interior design. Connection unit for indoor unit Model between the BEV unit
and the indoor unit.
The connecting port faces VRV series FXUQ-MA 5m
outdoor unit
Notes:
downward, greatly facilitating BEVQ-MA Super wiring ( DIII-NET ) • When connecting centralised-control device, it is
Liquid Gas pipe necessary to install an interface adaptor for an
on-site piping work. Connecting pipe Single-phase 220-240 V
power supply indoor unit (DTA102A52).
port • Connection unit BEVQ-MA is necessary for each
Indoor unit indoor unit.
A long-life filter (maintenance Refrigerant
• The refrigerant piping height difference between
the indoor units and the BEV unit must be within
free up to one year*) is equipped piping 4 m.
• The BEV unit must be installed within a
as standard accessory. Piping length*1 Indoor unit maximum height difference between indoor units
of 15 m.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Applies also to Floor Standing type (FXLQ-MA).
Remote controller • Branching of the refrigerant piping is not
possible downstream of the BEV unit.

17 18
Indoor Unit Lineup
VRV Indoor Units
Connection unit series indoor units
Floor Standing Type Ceiling Suspended Cassette Type

FXLQ20MA / FXLQ25MA FXUQ71MA/FXUQ100MA


FXLQ32MA/FXLQ40MA FXUQ125MA
FXLQ50MA / FXLQ63MA

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details.

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details.
This thin indoor unit achieves
Suitable for perimeter zone air conditioning optimum air distribution, and can be installed
Floor Standing types can be hung on the wall for easier without the need for ceiling cavity.
cleaning. Running the piping from the back allows the unit to be
hung on walls. Cleaning under the unit, where dust tends to
Depending on installation site requirements or room
accumulate, is considerably easier.
conditions, 2-way, 3-way and 4-way discharge
The adoption of a fibre-less discharge grille featuring an original patterns are available.
design to prevent condensation also helps prevent staining and
makes cleaning easier.
4-way airflow The 3-way airflow can distribute
A long-life filter (maintenance free up to one year*) is equipped from the centre of the store. comfortable air throughout the room.

as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Wall hanging Floor installation

Concealed Floor Standing Type

Only one unit is needed to distribute comfortable air


throughout an L-shaped store.

FXNQ20MA / FXNQ25MA
FXNQ32MA/FXNQ40MA
FXNQ50MA / FXNQ63MA

* Remote controllers are an optional accessory.


Refer to page 39 for remote controller details.

Designed to be concealed in the perimeter skirting-wall Connection unit Connection unit is the device for connecting above indoor unit to VRV III.
BEVQ71MA/BEVQ100MA/BEVQ125MA
The unit is concealed in skirting-wall of perimeter, that enables
Refrigerant piping layout External wiring layout *1 Maximum piping length
to create high class interior design. Connection unit for indoor unit Model between the BEV unit
and the indoor unit.
The connecting port faces VRV series FXUQ-MA 5m
outdoor unit
Notes:
downward, greatly facilitating BEVQ-MA Super wiring ( DIII-NET ) • When connecting centralised-control device, it is
Liquid Gas pipe necessary to install an interface adaptor for an
on-site piping work. Connecting pipe Single-phase 220-240 V
power supply indoor unit (DTA102A52).
port • Connection unit BEVQ-MA is necessary for each
Indoor unit indoor unit.
A long-life filter (maintenance Refrigerant
• The refrigerant piping height difference between
the indoor units and the BEV unit must be within
free up to one year*) is equipped piping 4 m.
• The BEV unit must be installed within a
as standard accessory. Piping length*1 Indoor unit maximum height difference between indoor units
of 15 m.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Applies also to Floor Standing type (FXLQ-MA).
Remote controller • Branching of the refrigerant piping is not
possible downstream of the BEV unit.

17 18
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units

Ceiling Mounted Cassette Type Ceiling Mounted Cassette (Compact Multi Flow) Type

FCQ35B/FCQ50B/FCQ60B/FCQ71B FFQ25B/FFQ35B/FFQ50B/FFQ60B

Option Signal receiver unit


Option Signal receiver unit
Note: Remote controller Note: Wireless remote
cables not included. Note: Remote controller Option Note: Wireless remote
Option controllers and signal
Cables should be cables not included. controllers and signal
receiver units are sold
obtained locally. Cables should be receiver units are sold
as a set.
obtained locally. as a set.

Specially designed for false ceilings


Quiet, compact, and designed for user comfort
—for a smooth, modern interior finish
All models feature a decoration panel with the Three convenient patterns for auto-swing operation Designed to fit 600 mm wide ceiling grids Low draft performance is
same size and simple design in consideration of Standard 575 mm
designed for your comfort. 0° Horizontal Flow 0°

harmonised interior décor.


575 mm
Less draught
286
mm
950 mm

Draft prevention act


Same for Comp e panel
rativ
all models deco
Comfortable across all areas
700 mm Conditioned air is distributed Adjustable airflow angle to
evenly by Auto-swing operation. suit all room conditions.
Decoration panel is optional
700 mm AUTO-SWING 5 direction
950 mm Soiling prevention
Standard 0° 0°
setting Auto-swing Settable to 5 different levels
T-bar grid does not need to be cut. between 0° and 60° between 0° and 60°
60° 60°
The indoor units weigh only 24 kg and require an
Ceiling panel Draft
installation space with a height of just 245 mm. prevention 0°

T-bar setting Auto-swing Settable to 5 different levels

Min. 245 mm
Drain pump is equipped as (Set on site) 35° between 0° and 35° 35° between 0° and 35°

standard with 750 mm. 750 mm Setting to


prevent
600 mm soiling of 25° Auto-swing 25° Settable to 5 different levels
600 mm ceiling
between 25° and 60° between 25° and 60°
(Set on site) 60° 60°

Low operation sound level (H/L)


Note: Angles shown above are provided as a guide. They may differ depending on the installation site.

These models have the Low operation sound level


FCQ35B FCQ50B FCQ60B FCQ71B (H/L) Drain pump is equipped as standard
power to provide a
33/29 dB (A) 33/29 dB (A) 35/30 dB (A) 35/30 dB (A) comfortable airflow Max. 3.8 m FFQ25B FFQ35B FFQ50B FFQ60B accessory with 750 mm lift.
even with a ceiling 29.5/24.5 dB (A) 32/25 dB (A) 36/27 dB (A) 41/32 dB (A)
height of up to 3.8 m.
750 mm

19 20
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units

Ceiling Mounted Cassette Type Ceiling Mounted Cassette (Compact Multi Flow) Type

FCQ35B/FCQ50B/FCQ60B/FCQ71B FFQ25B/FFQ35B/FFQ50B/FFQ60B

Option Signal receiver unit


Option Signal receiver unit
Note: Remote controller Note: Wireless remote
cables not included. Note: Remote controller Option Note: Wireless remote
Option controllers and signal
Cables should be cables not included. controllers and signal
receiver units are sold
obtained locally. Cables should be receiver units are sold
as a set.
obtained locally. as a set.

Specially designed for false ceilings


Quiet, compact, and designed for user comfort
—for a smooth, modern interior finish
All models feature a decoration panel with the Three convenient patterns for auto-swing operation Designed to fit 600 mm wide ceiling grids Low draft performance is
same size and simple design in consideration of Standard 575 mm
designed for your comfort. 0° Horizontal Flow 0°

harmonised interior décor.


575 mm
Less draught
286
mm
950 mm

Draft prevention act


Same for Comp e panel
rativ
all models deco
Comfortable across all areas
700 mm Conditioned air is distributed Adjustable airflow angle to
evenly by Auto-swing operation. suit all room conditions.
Decoration panel is optional
700 mm AUTO-SWING 5 direction
950 mm Soiling prevention
Standard 0° 0°
setting Auto-swing Settable to 5 different levels
T-bar grid does not need to be cut. between 0° and 60° between 0° and 60°
60° 60°
The indoor units weigh only 24 kg and require an
Ceiling panel Draft
installation space with a height of just 245 mm. prevention 0°

T-bar setting Auto-swing Settable to 5 different levels

Min. 245 mm
Drain pump is equipped as (Set on site) 35° between 0° and 35° 35° between 0° and 35°

standard with 750 mm. 750 mm Setting to


prevent
600 mm soiling of 25° Auto-swing 25° Settable to 5 different levels
600 mm ceiling
between 25° and 60° between 25° and 60°
(Set on site) 60° 60°

Low operation sound level (H/L)


Note: Angles shown above are provided as a guide. They may differ depending on the installation site.

These models have the Low operation sound level


FCQ35B FCQ50B FCQ60B FCQ71B (H/L) Drain pump is equipped as standard
power to provide a
33/29 dB (A) 33/29 dB (A) 35/30 dB (A) 35/30 dB (A) comfortable airflow Max. 3.8 m FFQ25B FFQ35B FFQ50B FFQ60B accessory with 750 mm lift.
even with a ceiling 29.5/24.5 dB (A) 32/25 dB (A) 36/27 dB (A) 41/32 dB (A)
height of up to 3.8 m.
750 mm

19 20
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units

Ceiling Mounted Built-in Type Slim Ceiling Mounted Duct Type

700 mm width type

FBQ60B/FBQ71B
FDKS25EA/FDKS35EA

900/1,100 mm width type

FDKS25CA/FDKS35CA/FDKS50C/FDKS60C

Option
Note: Remote controller
cables not included. Standard accessory
Cables should be Note: Remote controllers
obtained locally. other than the standard
accessory wireless remote
controller cannot be used.

Flexible air discharge unit to fit various forms of space Slim and smooth design suits your shallow ceiling
The indoor unit can be installed in rooms with as Options 7 High-performance filter Models in the FDKS-EA series are only 700 mm Low operation sound level (H/L/SL)
little as 350 mm between the drop ceiling and 1 Decorative panel 8 Inspection panel
in width and 21 kg in weight, so are easily
ceiling slab. It also works with both flexible and
2 Air discharge opening adaptor 9 Rear intake blocking pad FDKS25 FDKS35 FDKS50 FDKS60
3 Canvas bellows and air intake panel 10 Air discharge opening flange installed in limited spaces. Just 200 mm in height,
Flexible duct Rear intake filter chamber
ordinary ducts. 4
Air discharge grille
11
all models can be installed in rooms with as little 35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
5 12 Branch duct
6 Air discharge chamber 13 Low-draft filter chamber
as 240 mm depth between the drop ceiling and
ceiling slab, making them ideal for even shallow
Home Leave Operation prevents large rises or
Standard installation examples With high-efficiency filter ceilings.
In crawl space With canvas bellows and air intake panel (sold separately) falls in the indoor temperature by continuing
2 Air conditioner

6 2 Air conditioner 2 Air conditioner 4 540 mm or more FDKS-EA operation* while you are sleeping or out of your
4 350 mm or more
4 6
13 7
Great for
6
Long-life filter 3
425 mm or more 3
home. This means that an air-conditioned
5 1
5 1 hotel use!
Air blow
Air intake Long-life filter 5
Air blow Air intake
1 Air blow Air intake welcome awaits when you wake or return. It also
45 mm
means that the indoor temperature can quickly
Ceiling return Ceiling return with high-efficiency filter With ordinary ducts
return to your favourite comfort setting.
Ordinary duct Ordinary duct
2 Air conditioner 2 Air conditioner 540 mm or more Air conditioner
(procured locally) (procured locally) * Home Leave Operation can be selected for any temperature from 18 to
6
4
Long-life filter Air intake
450 mm or more
6 4 11
Air intake
10
460 mm or more
200 mm 32˚C for cooling operation and 10 to 30˚C for heating operation.
9 7 9
* Home Leave Operation function must be set using the remote controller
5 8
5 8
8
Air intake
Only 700 mm when going to sleep or leaving the house, and after waking up or returning
Air blow Air blow
Air blow home.

FDKS25EA FDKS35EA FDKS25CA FDKS35CA


Dimensions (H x W x D) 200 x 700 x 620 mm 200 x 900 x 620 mm
To cope with the challenges of L-shaped or Drain pump is equipped as standard accessory with Weight 21 kg 25 kg Suspension bolt* Suction duct*
Air discharge duct*
Air filter
U-shaped spaces, it is possible to install the air 250 mm lift. Airflow rate (H)
3
8.7 m /min 3 3
9.5 m /min 10 m /min Air discharge grille*
discharge unit away from the main unit. This External static pressure 30 Pa 40 Pa
extends the possibilities for coping with human AIR
gathering patterns or sun lighting. At the same 250 mm
time, different types of architectural space can be 240 mm Chamber
Air suction
kept comfortable. Signal receiver wire
Length = 1,900 mm Signal
grille*
receiver AIR * Locally obtained parts

Notes:
Option 1. To prevent an increase in operation noise, avoid
installing the air suction grille directly below the
suction chamber.
Low operation sound level (H/L)
2. Grilles, piping connections, ducts, and installation
parts should be obtained locally. Slim Ceiling
Mounted Duct type FDKS models do not have
FBQ60B FBQ71B Suction grille (KDGF19A45) drain-up pumps.
3. The signal receiver unit must be located near the
Signals from the wireless remote controller are air suction inlet, because the unit includes a
L-shaped room U-shaped room Long room 41/35 dB (A) 41/35 dB (A) transmitted to the signal receiver.
sensor that detects room temperature.

21 22
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units

Ceiling Mounted Built-in Type Slim Ceiling Mounted Duct Type

700 mm width type

FBQ60B/FBQ71B
FDKS25EA/FDKS35EA

900/1,100 mm width type

FDKS25CA/FDKS35CA/FDKS50C/FDKS60C

Option
Note: Remote controller
cables not included. Standard accessory
Cables should be Note: Remote controllers
obtained locally. other than the standard
accessory wireless remote
controller cannot be used.

Flexible air discharge unit to fit various forms of space Slim and smooth design suits your shallow ceiling
The indoor unit can be installed in rooms with as Options 7 High-performance filter Models in the FDKS-EA series are only 700 mm Low operation sound level (H/L/SL)
little as 350 mm between the drop ceiling and 1 Decorative panel 8 Inspection panel
in width and 21 kg in weight, so are easily
ceiling slab. It also works with both flexible and
2 Air discharge opening adaptor 9 Rear intake blocking pad FDKS25 FDKS35 FDKS50 FDKS60
3 Canvas bellows and air intake panel 10 Air discharge opening flange installed in limited spaces. Just 200 mm in height,
Flexible duct Rear intake filter chamber
ordinary ducts. 4
Air discharge grille
11
all models can be installed in rooms with as little 35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
5 12 Branch duct
6 Air discharge chamber 13 Low-draft filter chamber
as 240 mm depth between the drop ceiling and
ceiling slab, making them ideal for even shallow
Home Leave Operation prevents large rises or
Standard installation examples With high-efficiency filter ceilings.
In crawl space With canvas bellows and air intake panel (sold separately) falls in the indoor temperature by continuing
2 Air conditioner

6 2 Air conditioner 2 Air conditioner 4 540 mm or more FDKS-EA operation* while you are sleeping or out of your
4 350 mm or more
4 6
13 7
Great for
6
Long-life filter 3
425 mm or more 3
home. This means that an air-conditioned
5 1
5 1 hotel use!
Air blow
Air intake Long-life filter 5
Air blow Air intake
1 Air blow Air intake welcome awaits when you wake or return. It also
45 mm
means that the indoor temperature can quickly
Ceiling return Ceiling return with high-efficiency filter With ordinary ducts
return to your favourite comfort setting.
Ordinary duct Ordinary duct
2 Air conditioner 2 Air conditioner 540 mm or more Air conditioner
(procured locally) (procured locally) * Home Leave Operation can be selected for any temperature from 18 to
6
4
Long-life filter Air intake
450 mm or more
6 4 11
Air intake
10
460 mm or more
200 mm 32˚C for cooling operation and 10 to 30˚C for heating operation.
9 7 9
* Home Leave Operation function must be set using the remote controller
5 8
5 8
8
Air intake
Only 700 mm when going to sleep or leaving the house, and after waking up or returning
Air blow Air blow
Air blow home.

FDKS25EA FDKS35EA FDKS25CA FDKS35CA


Dimensions (H x W x D) 200 x 700 x 620 mm 200 x 900 x 620 mm
To cope with the challenges of L-shaped or Drain pump is equipped as standard accessory with Weight 21 kg 25 kg Suspension bolt* Suction duct*
Air discharge duct*
Air filter
U-shaped spaces, it is possible to install the air 250 mm lift. Airflow rate (H)
3
8.7 m /min 3 3
9.5 m /min 10 m /min Air discharge grille*
discharge unit away from the main unit. This External static pressure 30 Pa 40 Pa
extends the possibilities for coping with human AIR
gathering patterns or sun lighting. At the same 250 mm
time, different types of architectural space can be 240 mm Chamber
Air suction
kept comfortable. Signal receiver wire
Length = 1,900 mm Signal
grille*
receiver AIR * Locally obtained parts

Notes:
Option 1. To prevent an increase in operation noise, avoid
installing the air suction grille directly below the
suction chamber.
Low operation sound level (H/L)
2. Grilles, piping connections, ducts, and installation
parts should be obtained locally. Slim Ceiling
Mounted Duct type FDKS models do not have
FBQ60B FBQ71B Suction grille (KDGF19A45) drain-up pumps.
3. The signal receiver unit must be located near the
Signals from the wireless remote controller are air suction inlet, because the unit includes a
L-shaped room U-shaped room Long room 41/35 dB (A) 41/35 dB (A) transmitted to the signal receiver.
sensor that detects room temperature.

21 22
Indoor Unit Lineup Specifications
Residential Indoor Units with connection
to BP units VRV Indoor Units

Wall Mounted Type


Ceiling Mounted Cassette (Round Flow) Type
MODEL FXFQ25PVE FXFQ32PVE FXFQ40PVE FXFQ50PVE FXFQ63PVE FXFQ80PVE FXFQ100PVE FXFQ125PVE
FTKS25D/FTKS35D Power supply 1-phase, 220- 240 V/220 V, 50/60 Hz
kcal/h(*1) 2,500 3,200 4,000 5,000 6,300 8,000 10,000 12,500
Btu/h (*1) 9,900 12,600 16,000 19,800 24,900 31,700 39,600 49,500
Cooling capacity
(*1) 2.9 3.7 4.7 5.8 7.3 9.3 11.6 14.5
kW
(*2) 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Power consumption kW 0.033 0.033 0.047 0.052 0.066 0.093 0.187 0.209
Casing Galvanised steel plate
m3/min 13/11.5/10 13/11.5/10 15/13/11 16/13.5/11 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5
Standard accessory* Airflow rate (HH/H/L)
cfm 459/406/353 459/406/353 530/459/388 565/477/388 671/583/477 742/636/530 1,130/918/706 1,165/989/794
Sound level (HH/H/L) dB(A) 30/28.5/27 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
FTKS50F/FTKS60F/FTKS71F
Dimensions (HXWXD) mm 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 288X840X840 288X840X840
Machine weight kg 19.5 19.5 19.5 19.5 22 22 25 25
Liquid (Flare) 6.4 6.4 6.4 6.4 9.5 9.5 9.5 9.5
Piping
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 15.9 15.9 15.9 15.9
Drain VP25 (External Dia, 32/Internal Dia, 25)
Model BYCP125K-W1
Panel Colour Fresh white
Standard
(Option)
accessory* * Remote controllers other than the standard accessory wireless remote controller cannot be used. Dimensions (HXWXD) mm 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950
Weight kg 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Stylish flat panel harmonises with your interior décor


Wall Mounted indoor units achieve quiet sound Titanium apatite is a photocatalytic material with
levels of 22 dB (A). high adsorption power. Titanium apatite also Ceiling Mounted Cassette (Compact Multi Flow) Type
(H/L/SL)
effectively adsorbs and decomposes bacteria MODEL FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE
FTKS25D FTKS35D FTKS50F FTKS60F FTKS71F across its entire surface. The photocatalyst is
Power supply 1-phase, 220- 240 V/220 V, 50/60 Hz
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A) activated simply by exposure to light.
kcal/h(*1) 2,000 2,500 3,200 4,000 5,000
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8
Intelligent Eye with its infrared sensor kW
(*2) 2.2 2.8 3.6 4.5 5.6
automatically controls air conditioner operation Power consumption kW 0.073 0.073 0.076 0.089 0.115
according to human movement in a room. When Air filter Casing Galvanised steel plate
catches dust
there is no movement, it adjusts the temperature m3/min 9/7 9/7 9.5/7.5 11/8 14/10
by 2˚C for energy savings. Airflow rate (H/L)
cfm 318/247 318/247 335/265 388/282 493/353
Sound level
230 V-240 V dB(A) 30/25-32/26 30/25-32/26 32/26-34/28 36/28-37/29 41/33-42/35
Titanium Apatite (H/L)
Photocatalytic Dimensions (HXWXD) mm 286X575X575
Air-purifying Filter
Machine weight kg 18
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4
Piping
mm
These filters are not medical devices. Benefits such as the connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7
adsorption and decomposition of bacteria are only effective for Drain VP20 (External Dia, 26/Internal Dia, 20)
When you are in the room When you go out substances that are collected on and in direct contact with the
Model BYFQ60B8W1
Titanium Apatite Photocatalytic Air-Purifying Filter.
3-D Airflow Bacteria Removal Test Panel Colour White (6.5Y9.5/0.5)
(Option) Dimensions (HXWXD)
combines Vertical Testing method: dropping method mm 55X700X700 55X700X700 55X700X700 55X700X700 55X700X700

and Horizontal Result certificate: No. 012553-1 and 012553-2 Weight kg 2.7 2.7 2.7 2.7 2.7
Testing organisation: Japan Spinners Inspecting Foundation
Auto-Swing to Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
circulate air to every • Equivalent piping length: 7.5 m
• Level difference: 0 m
part of a room for •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
uniform cooling of even During actual operation, these values are normally somewhat higher as a result of ambient conditions.

large spaces.
* This function is available for A uniform temperature
FTKS50/60/71F. is achieved throughout
the entire room.

23 24
Indoor Unit Lineup Specifications
Residential Indoor Units with connection
to BP units VRV Indoor Units

Wall Mounted Type


Ceiling Mounted Cassette (Round Flow) Type
MODEL FXFQ25PVE FXFQ32PVE FXFQ40PVE FXFQ50PVE FXFQ63PVE FXFQ80PVE FXFQ100PVE FXFQ125PVE
FTKS25D/FTKS35D Power supply 1-phase, 220- 240 V/220 V, 50/60 Hz
kcal/h(*1) 2,500 3,200 4,000 5,000 6,300 8,000 10,000 12,500
Btu/h (*1) 9,900 12,600 16,000 19,800 24,900 31,700 39,600 49,500
Cooling capacity
(*1) 2.9 3.7 4.7 5.8 7.3 9.3 11.6 14.5
kW
(*2) 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0
Power consumption kW 0.033 0.033 0.047 0.052 0.066 0.093 0.187 0.209
Casing Galvanised steel plate
m3/min 13/11.5/10 13/11.5/10 15/13/11 16/13.5/11 19/16.5/13.5 21/18/15 32/26/20 33/28/22.5
Standard accessory* Airflow rate (HH/H/L)
cfm 459/406/353 459/406/353 530/459/388 565/477/388 671/583/477 742/636/530 1,130/918/706 1,165/989/794
Sound level (HH/H/L) dB(A) 30/28.5/27 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
FTKS50F/FTKS60F/FTKS71F
Dimensions (HXWXD) mm 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 288X840X840 288X840X840
Machine weight kg 19.5 19.5 19.5 19.5 22 22 25 25
Liquid (Flare) 6.4 6.4 6.4 6.4 9.5 9.5 9.5 9.5
Piping
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 15.9 15.9 15.9 15.9
Drain VP25 (External Dia, 32/Internal Dia, 25)
Model BYCP125K-W1
Panel Colour Fresh white
Standard
(Option)
accessory* * Remote controllers other than the standard accessory wireless remote controller cannot be used. Dimensions (HXWXD) mm 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950
Weight kg 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5

Stylish flat panel harmonises with your interior décor


Wall Mounted indoor units achieve quiet sound Titanium apatite is a photocatalytic material with
levels of 22 dB (A). high adsorption power. Titanium apatite also Ceiling Mounted Cassette (Compact Multi Flow) Type
(H/L/SL)
effectively adsorbs and decomposes bacteria MODEL FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE
FTKS25D FTKS35D FTKS50F FTKS60F FTKS71F across its entire surface. The photocatalyst is
Power supply 1-phase, 220- 240 V/220 V, 50/60 Hz
37/25/22 dB (A) 39/26/23 dB (A) 43/34/31 dB (A) 45/36/33 dB (A) 46/37/34 dB (A) activated simply by exposure to light.
kcal/h(*1) 2,000 2,500 3,200 4,000 5,000
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8
Intelligent Eye with its infrared sensor kW
(*2) 2.2 2.8 3.6 4.5 5.6
automatically controls air conditioner operation Power consumption kW 0.073 0.073 0.076 0.089 0.115
according to human movement in a room. When Air filter Casing Galvanised steel plate
catches dust
there is no movement, it adjusts the temperature m3/min 9/7 9/7 9.5/7.5 11/8 14/10
by 2˚C for energy savings. Airflow rate (H/L)
cfm 318/247 318/247 335/265 388/282 493/353
Sound level
230 V-240 V dB(A) 30/25-32/26 30/25-32/26 32/26-34/28 36/28-37/29 41/33-42/35
Titanium Apatite (H/L)
Photocatalytic Dimensions (HXWXD) mm 286X575X575
Air-purifying Filter
Machine weight kg 18
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4
Piping
mm
These filters are not medical devices. Benefits such as the connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7
adsorption and decomposition of bacteria are only effective for Drain VP20 (External Dia, 26/Internal Dia, 20)
When you are in the room When you go out substances that are collected on and in direct contact with the
Model BYFQ60B8W1
Titanium Apatite Photocatalytic Air-Purifying Filter.
3-D Airflow Bacteria Removal Test Panel Colour White (6.5Y9.5/0.5)
(Option) Dimensions (HXWXD)
combines Vertical Testing method: dropping method mm 55X700X700 55X700X700 55X700X700 55X700X700 55X700X700

and Horizontal Result certificate: No. 012553-1 and 012553-2 Weight kg 2.7 2.7 2.7 2.7 2.7
Testing organisation: Japan Spinners Inspecting Foundation
Auto-Swing to Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
circulate air to every • Equivalent piping length: 7.5 m
• Level difference: 0 m
part of a room for •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
uniform cooling of even During actual operation, these values are normally somewhat higher as a result of ambient conditions.

large spaces.
* This function is available for A uniform temperature
FTKS50/60/71F. is achieved throughout
the entire room.

23 24
Specifications
VRV Indoor Units

Ceiling Mounted Cassette (Double Flow) Type Slim Ceiling Mounted Duct Type (700 mm width type)
with
MODEL FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE drain pump FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
MODEL without
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET
drain pump
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 8,000 12,500 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 31,700 49,500 kcal/h(*1) 2,000 2,500 3,200
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 9.3 14.5
kW Btu/h(*1) 7,800 9,900 12,600
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0 Cooling capacity
(*1) 2.3 2.9 3.7
Power consumption kW 0.077 0.092 0.092 0.130 0.130 0.161 0.209 0.256 kW
(*2) 2.2 2.8 3.6
Casing Galvanised steel plate
Power consumption
m3/min 7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25 kW 0.086 0.086 0.089
(FXDQ-PBVE)
Airflow rate (H/L)
cfm 247/177 318/230 318/230 424/318 424/318 582/459 918/741 1,165/883 Power consumption
kW 0.067 0.067 0.070
(FXDQ-PBVET)
220 V 32/27 34/28 34/28 34/29 34/29 37/32 39/34 44/38
Sound level (H/L) dB(A) Casing Galvanised steel plate
240 V 34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40
m3/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Dimensions (HXWXD) mm 305X775X600 305X775X600 305X775X600 305X990X600 305X990X600 305X1,175X600 305X1,665X600 305X1,665X600 Airflow rate (HH/H/L)
cfm 282/254/226 282/254/226 282/254/226
Machine weight kg 26.0 26.0 26.0 31.0 32.0 35.0 47.0 48.0
External static pressure Pa 30-10 1
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 9.5 9.5
Piping Sound level (HH/H/L) 2 3 dB(A) 33/31/29 33/31/29 33/31/29
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9
Dimensions (HXWXD) mm 200X700X620 200X700X620 200X700X620
Drain VP25 (External Dia, 32/Internal Dia, 25)
Machine weight kg 23.0 23.0 23.0
Model BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
Liquid (Flare) 6.4 6.4 6.4
Panel Colour White (10Y9/0.5) Piping
mm
(Option) Dimensions (HXWXD) mm 53X1,030X680 53X1,030X680 53X1,030X680 53X1,245X680 53X1,245X680 53X1,430X680 53X1,920X680 53X1,920X680 connections Gas (Flare) 12.7 12.7 12.7
Drain VP20 (External Dia, 26/Internal Dia, 20)
Weight kg 8.0 8.0 8.0 8.5 8.5 9.5 12.0 12.0

Ceiling Mounted Cassette Corner Type Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
MODEL FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE with
drain pump FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz MODEL without
kcal/h (*1) 2,500 3,200 4,000 6,300 drain pump FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
Btu/h (*1) 9,900 12,600 16,000 24,900 Power supply 1-phase, 220 -240 V/220 V, 50/60 Hz
Cooling capacity
(*1) 2.9 3.7 4.7 7.3 kcal/h (*1) 4,000 5,000 6,300
kW
(*2) 2.8 3.6 4.5 7.1 Btu/h(*1) 16,000 19,800 24,900
Cooling capacity
Power consumption kW 0.066 0.066 0.076 0.105 (*1) 4.7 5.8 7.3
kW
Casing Galvanised steel plate (*2) 4.5 5.6 7.1
m3/min 11/9 11/9 13/10 18/15 Power consumption
Airflow rate (H/L) kW 0.160 0.165 0.181
cfm 388/318 388/318 459/353 635/530 (FXDQ-NBVE)
220 V 38/33 38/33 40/34 42/37 Power consumption
Sound level (H/L) kW 0.147 0.152 0.168
dB(A) (FXDQ-NBVET)
240 V 40/35 40/35 42/36 44/39
Casing Galvanised steel plate
Dimensions (HXWXD) mm 215X1,110X710 215X1,110X710 215X1,110X710 215X1,310X710
Machine weight kg 31.0 31.0 31.0 34.0 m3/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Airflow rate (HH/H/L)
Liquid (Flare) 6.4 6.4 6.4 9.5 cfm 371/335/300 441/388/353 583/512/459
Piping External static pressure Pa 44-15 1
Gas (Flare) mm 12.7 12.7 12.7 15.9
connections
Drain VP25 (External Dia, 32/Internal Dia, 25) Sound level (HH/H/L) 2 3 dB(A) 34/32/30 35/33/31 36/34/32
Model BYK45FJW1 BYK71FJW1 Dimensions (HXWXD) mm 200X900X620 200X900X620 200X1,100X620
Panel Colour White (10Y9/0.5) Machine weight kg 27.0 28.0 31.0
(Option) Dimensions (HXWXD) mm 70X1,240X800 70X1,240X800 70X1,240X800 70X1,440X800
Liquid (Flare) 6.4 6.4 9.5
Weight kg 8.5 8.5 8.5 9.5 Piping
mm
Note: Specifications are based on the following conditions; connections Gas (Flare) 12.7 12.7 15.9
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Drain VP20 (External Dia, 26/Internal Dia, 20)
•Equivalent piping length: 7.5 m • Level difference: 0 m
Note: Specifications are based on the following conditions;
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
3: Values are based on the following conditions: external static pressure of 10 Pa.
• Equivalent piping length: 7.5 m • Level difference: 0 m
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

25 26
Specifications
VRV Indoor Units

Ceiling Mounted Cassette (Double Flow) Type Slim Ceiling Mounted Duct Type (700 mm width type)
with
MODEL FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE drain pump FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
MODEL without
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET
drain pump
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 8,000 12,500 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 31,700 49,500 kcal/h(*1) 2,000 2,500 3,200
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 9.3 14.5
kW Btu/h(*1) 7,800 9,900 12,600
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0 Cooling capacity
(*1) 2.3 2.9 3.7
Power consumption kW 0.077 0.092 0.092 0.130 0.130 0.161 0.209 0.256 kW
(*2) 2.2 2.8 3.6
Casing Galvanised steel plate
Power consumption
m3/min 7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25 kW 0.086 0.086 0.089
(FXDQ-PBVE)
Airflow rate (H/L)
cfm 247/177 318/230 318/230 424/318 424/318 582/459 918/741 1,165/883 Power consumption
kW 0.067 0.067 0.070
(FXDQ-PBVET)
220 V 32/27 34/28 34/28 34/29 34/29 37/32 39/34 44/38
Sound level (H/L) dB(A) Casing Galvanised steel plate
240 V 34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40
m3/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Dimensions (HXWXD) mm 305X775X600 305X775X600 305X775X600 305X990X600 305X990X600 305X1,175X600 305X1,665X600 305X1,665X600 Airflow rate (HH/H/L)
cfm 282/254/226 282/254/226 282/254/226
Machine weight kg 26.0 26.0 26.0 31.0 32.0 35.0 47.0 48.0
External static pressure Pa 30-10 1
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 9.5 9.5
Piping Sound level (HH/H/L) 2 3 dB(A) 33/31/29 33/31/29 33/31/29
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9
Dimensions (HXWXD) mm 200X700X620 200X700X620 200X700X620
Drain VP25 (External Dia, 32/Internal Dia, 25)
Machine weight kg 23.0 23.0 23.0
Model BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
Liquid (Flare) 6.4 6.4 6.4
Panel Colour White (10Y9/0.5) Piping
mm
(Option) Dimensions (HXWXD) mm 53X1,030X680 53X1,030X680 53X1,030X680 53X1,245X680 53X1,245X680 53X1,430X680 53X1,920X680 53X1,920X680 connections Gas (Flare) 12.7 12.7 12.7
Drain VP20 (External Dia, 26/Internal Dia, 20)
Weight kg 8.0 8.0 8.0 8.5 8.5 9.5 12.0 12.0

Ceiling Mounted Cassette Corner Type Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
MODEL FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE with
drain pump FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz MODEL without
kcal/h (*1) 2,500 3,200 4,000 6,300 drain pump FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
Btu/h (*1) 9,900 12,600 16,000 24,900 Power supply 1-phase, 220 -240 V/220 V, 50/60 Hz
Cooling capacity
(*1) 2.9 3.7 4.7 7.3 kcal/h (*1) 4,000 5,000 6,300
kW
(*2) 2.8 3.6 4.5 7.1 Btu/h(*1) 16,000 19,800 24,900
Cooling capacity
Power consumption kW 0.066 0.066 0.076 0.105 (*1) 4.7 5.8 7.3
kW
Casing Galvanised steel plate (*2) 4.5 5.6 7.1
m3/min 11/9 11/9 13/10 18/15 Power consumption
Airflow rate (H/L) kW 0.160 0.165 0.181
cfm 388/318 388/318 459/353 635/530 (FXDQ-NBVE)
220 V 38/33 38/33 40/34 42/37 Power consumption
Sound level (H/L) kW 0.147 0.152 0.168
dB(A) (FXDQ-NBVET)
240 V 40/35 40/35 42/36 44/39
Casing Galvanised steel plate
Dimensions (HXWXD) mm 215X1,110X710 215X1,110X710 215X1,110X710 215X1,310X710
Machine weight kg 31.0 31.0 31.0 34.0 m3/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Airflow rate (HH/H/L)
Liquid (Flare) 6.4 6.4 6.4 9.5 cfm 371/335/300 441/388/353 583/512/459
Piping External static pressure Pa 44-15 1
Gas (Flare) mm 12.7 12.7 12.7 15.9
connections
Drain VP25 (External Dia, 32/Internal Dia, 25) Sound level (HH/H/L) 2 3 dB(A) 34/32/30 35/33/31 36/34/32
Model BYK45FJW1 BYK71FJW1 Dimensions (HXWXD) mm 200X900X620 200X900X620 200X1,100X620
Panel Colour White (10Y9/0.5) Machine weight kg 27.0 28.0 31.0
(Option) Dimensions (HXWXD) mm 70X1,240X800 70X1,240X800 70X1,240X800 70X1,440X800
Liquid (Flare) 6.4 6.4 9.5
Weight kg 8.5 8.5 8.5 9.5 Piping
mm
Note: Specifications are based on the following conditions; connections Gas (Flare) 12.7 12.7 15.9
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Drain VP20 (External Dia, 26/Internal Dia, 20)
•Equivalent piping length: 7.5 m • Level difference: 0 m
Note: Specifications are based on the following conditions;
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
3: Values are based on the following conditions: external static pressure of 10 Pa.
• Equivalent piping length: 7.5 m • Level difference: 0 m
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

25 26
Specifications
VRV Indoor Units

Ceiling Mounted Duct Type Ceiling Mounted Duct Type


MODEL FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE MODEL FXMQ200MAVE FXMQ250MAVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Power supply 1-phase, 220- 240 V/220 V, 50/60 Hz
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 kcal/h(*1) 19,800 24,800
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 Btu/h (*1) 78,500 98,300
Cooling capacity Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 (*1) 23.0 28.8
kW kW
(*2) 2.2 2.8 3.6 4.5 5.6 (*2) 22.4 28.0
Power consumption kW 0.081 0.081 0.085 0.194 0.215 Power consumption kW 1.294 1.465
Casing Galvanised steel plate Casing Galvanised steel plate
m3/min 9/7.5/6.5 9/7.5/6.5 9.5/8/7 16/13/11 18/16.5/15 m3/min 58/50 72/62
Airflow rate (HH/H/L) Airflow rate (H/L)
cfm 318/265/230 318/265/230 335/282/247 565/459/388 635/582/530 cfm 2,047/1,765 2,542/2,189
1 1 1 1 1 1 1
External static pressure Pa 30-100 30-100 30-100 30-160 50-200 External static pressure Pa 132-221 191-270

Sound level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30 39/37/35 41/39/37 Sound level 220 V 48/45 48/45
dB(A)
(H/L) 240 V 49/46 49/46
Dimensions (HXWXD) mm 300X550X700 300X550X700 300X550X700 300X700X700 300X1,000X700
Dimensions (HXWXD) mm 470X1,380X1,100 470X1,380X1,100
Machine weight kg 25.0 25.0 25.0 28.0 36.0
Machine weight kg 137.0 137.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4
Piping Liquid (Flare) 9.5 9.5
connections Gas (Flare) mm 12.7 12.7 12.7 12.7 12.7
Piping
mm
Drain VP25 (External Dia, 32/Internal Dia, 25) connections Gas (Brazing) 19.1 22.2
Drain PS1B

MODEL FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE


Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
kcal/h (*1) 6,300 8,000 10,000 12,500 14,300 Ceiling Suspended Type
Btu/h (*1) 24,900 31,700 39,600 49,500 57,000
Cooling capacity MODEL FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE
(*1) 7.3 9.3 11.6 14.5 16.7
kW Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
(*2) 7.1 9.0 11.2 14.0 16.0
kcal/h(*1) 3,200 6,300 10,000
Power consumption kW 0.230 0.298/ 0.376 0.461 0.461
Btu/h(*1) 12,600 24,900 39,600
Casing Galvanised steel plate Cooling capacity
(*1) 3.7 7.3 11.6
m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32 kW
Airflow rate (HH/H/L) (*2) 3.6 7.1 11.2
cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
1 1 1 1 1 Power consumption kW 0.111 0.115 0.135
External static pressure Pa 50-200 50-200 50-200 50-200 50-140
Casing White (10Y9/0.5)
Sound level (HH/H/L) dB(A) 42/40/38 43/41/39 43/41/39 44/42/40 46/45/43
m3/min 12/10 17.5 /14 25/19.5
Dimensions (HXWXD) mm 300X1,000X700 300X1,000X700 300X1,400X700 300X1,400X700 300X1,400X700 Airflow rate (H/L)
cfm 424/353 618/494 883/688
Machine weight kg 36.0 36.0 46.0 46.0 47.0
Sound level (H/L) dB(A) 36/31 39/34 45/37
Liquid (Flare) 9.5 9.5 9.5 9.5 9.5
Piping Dimensions (HXWXD) mm 195X960X680 195X1,160X680 195X1,400X680
mm
connections Gas (Flare) 15.9 15.9 15.9 15.9 15.9
Machine weight kg 24.0 28.0 33.0
Drain VP25 (External Dia, 32/Internal Dia, 25)
Liquid (Flare) 6.4 9.5 9.5
Note: Specifications are based on the following conditions;
Piping
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. mm 12.7 15.9 15.9
(*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. connections Gas (Flare)
1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50- Drain VP20 (External Dia, 26/Internal Dia, 20)
125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static
pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P. Note: Specifications are based on the following conditions;
•Equivalent piping length: 7.5 m • Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
•Level difference: 0 m (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) 1: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure".
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. • Equivalent piping length: 7.5 m
During actual operation, these values are normally somewhat higher as a result of ambient conditions. • Level difference: 0 m
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
(FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

27 28
Specifications
VRV Indoor Units

Ceiling Mounted Duct Type Ceiling Mounted Duct Type


MODEL FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE MODEL FXMQ200MAVE FXMQ250MAVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Power supply 1-phase, 220- 240 V/220 V, 50/60 Hz
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 kcal/h(*1) 19,800 24,800
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 Btu/h (*1) 78,500 98,300
Cooling capacity Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 (*1) 23.0 28.8
kW kW
(*2) 2.2 2.8 3.6 4.5 5.6 (*2) 22.4 28.0
Power consumption kW 0.081 0.081 0.085 0.194 0.215 Power consumption kW 1.294 1.465
Casing Galvanised steel plate Casing Galvanised steel plate
m3/min 9/7.5/6.5 9/7.5/6.5 9.5/8/7 16/13/11 18/16.5/15 m3/min 58/50 72/62
Airflow rate (HH/H/L) Airflow rate (H/L)
cfm 318/265/230 318/265/230 335/282/247 565/459/388 635/582/530 cfm 2,047/1,765 2,542/2,189
1 1 1 1 1 1 1
External static pressure Pa 30-100 30-100 30-100 30-160 50-200 External static pressure Pa 132-221 191-270

Sound level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30 39/37/35 41/39/37 Sound level 220 V 48/45 48/45
dB(A)
(H/L) 240 V 49/46 49/46
Dimensions (HXWXD) mm 300X550X700 300X550X700 300X550X700 300X700X700 300X1,000X700
Dimensions (HXWXD) mm 470X1,380X1,100 470X1,380X1,100
Machine weight kg 25.0 25.0 25.0 28.0 36.0
Machine weight kg 137.0 137.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4
Piping Liquid (Flare) 9.5 9.5
connections Gas (Flare) mm 12.7 12.7 12.7 12.7 12.7
Piping
mm
Drain VP25 (External Dia, 32/Internal Dia, 25) connections Gas (Brazing) 19.1 22.2
Drain PS1B

MODEL FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE


Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
kcal/h (*1) 6,300 8,000 10,000 12,500 14,300 Ceiling Suspended Type
Btu/h (*1) 24,900 31,700 39,600 49,500 57,000
Cooling capacity MODEL FXHQ32MAVE FXHQ63MAVE FXHQ100MAVE
(*1) 7.3 9.3 11.6 14.5 16.7
kW Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
(*2) 7.1 9.0 11.2 14.0 16.0
kcal/h(*1) 3,200 6,300 10,000
Power consumption kW 0.230 0.298/ 0.376 0.461 0.461
Btu/h(*1) 12,600 24,900 39,600
Casing Galvanised steel plate Cooling capacity
(*1) 3.7 7.3 11.6
m3/min 19.5/17.5/16 25/22.5/20 32/27/23 39/33/28 46/39/32 kW
Airflow rate (HH/H/L) (*2) 3.6 7.1 11.2
cfm 688/618/565 883/794/706 1,130/953/812 1,377/1,165/988 1,624/1,377/1,130
1 1 1 1 1 Power consumption kW 0.111 0.115 0.135
External static pressure Pa 50-200 50-200 50-200 50-200 50-140
Casing White (10Y9/0.5)
Sound level (HH/H/L) dB(A) 42/40/38 43/41/39 43/41/39 44/42/40 46/45/43
m3/min 12/10 17.5 /14 25/19.5
Dimensions (HXWXD) mm 300X1,000X700 300X1,000X700 300X1,400X700 300X1,400X700 300X1,400X700 Airflow rate (H/L)
cfm 424/353 618/494 883/688
Machine weight kg 36.0 36.0 46.0 46.0 47.0
Sound level (H/L) dB(A) 36/31 39/34 45/37
Liquid (Flare) 9.5 9.5 9.5 9.5 9.5
Piping Dimensions (HXWXD) mm 195X960X680 195X1,160X680 195X1,400X680
mm
connections Gas (Flare) 15.9 15.9 15.9 15.9 15.9
Machine weight kg 24.0 28.0 33.0
Drain VP25 (External Dia, 32/Internal Dia, 25)
Liquid (Flare) 6.4 9.5 9.5
Note: Specifications are based on the following conditions;
Piping
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. mm 12.7 15.9 15.9
(*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. connections Gas (Flare)
1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50- Drain VP20 (External Dia, 26/Internal Dia, 20)
125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static
pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P. Note: Specifications are based on the following conditions;
•Equivalent piping length: 7.5 m • Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
•Level difference: 0 m (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.) 1: External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure".
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. • Equivalent piping length: 7.5 m
During actual operation, these values are normally somewhat higher as a result of ambient conditions. • Level difference: 0 m
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
(FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

27 28
Specifications
VRV Indoor Units

Wall Mounted Type Connection unit series indoor units


MODEL FXAQ20MAVE FXAQ25MAVE FXAQ32MAVE FXAQ40MAVE FXAQ50MAVE FXAQ63MAVE * A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data for details.
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz * Group control between Connection Unit series equipment within one system is possible. However, group control with the other
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 VRV indoor units is not possible.
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3
kW Ceiling Suspended Cassette Type
(*2) 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption kW 0.016 0.022 0.027 0.020 0.027 0.050
Indoor unit FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
Casing White (3.0Y8.5/0.5) MODEL
3
m /min 7.5/4.5 8/5 9/5.5 12/9 15/12 19/14 Connection unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE
Airflow rate (H/L)
cfm 265/159 282/177 318/194 424/318 530/424 671/494 Power supply 1-phase, 220-240 V, 50 Hz
Sound level (H/L) dB(A) 35/29 36/29 37/29 39/34 42/36 46/39 Kcal/h(*1) 7,100 10,000 12,500
Dimensions (HXWXD) mm 290X795X230 290X795X230 290X795X230 290X1,050X230 290X1,050X230 290X1,050X230 Btu/h(*1) 28,300 39,600 49,500
Cooling capacity
Machine weight kg 11.0 11.0 11.0 14.0 14.0 14.0 (*1) 8.3 11.6 14.5
kW
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 (*2) 8.0 11.2 14.0
Piping
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7 15.9 Power consumption kW 0.189 0.298 0.298
Drain VP13 (External Dia, 18/Internal Dia, 13) Casing White (10Y9/0.5)
3
m /min 19/14 29/21 32/23

Indoor unit
Airflow rate (H/L)
cfm 671/494 1,024/741 1,130/812
Sound level (H/L) 230 V dB(A) 40/35 43/38 44/39
Dimensions (HXWXD) mm 165X895X895 230X895X895 230X895X895
Floor Standing Type/Concealed Floor Standing Type Machine weight kg 25 31 31
Liquid 9.5 (Flare)
FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE Piping
MODEL connections
Gas mm 15.9 (Flare)
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Drain VP 20 (External Dia. 26/Internal Dia. 20)
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Note: Specifications are based on the following conditions;
• Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
FXLQ • Equivalent piping length: 7.5 m
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 • Level difference: 0 m
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
kW • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre.
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Power consumption kW 0.049 0.049 0.090 0.090 0.110 0.110


Casing FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate
m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12
Airflow rate (H/L)
FXNQ cfm 247/212 247/212 282/212 388/300 494/388 565/424
220 V 35/32 35/32 35/32 38/33 39/34 40/35
Sound level (H/L) dB(A)
240 V 37/34 37/34 37/34 40/35 41/36 42/37

Dimensions FXLQ 600X1,000X222 600X1,000X222 600X1,140X222 600X1,140X222 600X1,420X222 600X1,420X222


mm
(HXWXD) FXNQ 610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220
FXLQ 25.0 25.0 30.0 30.0 36.0 36.0
Machine weight kg
FXNQ 19.0 19.0 23.0 23.0 27.0 27.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5
Piping
mm 12.7 12.7 12.7 12.7 12.7 15.9
connections Gas (Flare)
Drain 21O.D.
Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
(*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Equivalent piping length: 7.5 m
•Level difference: 0 m
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: (FXAQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

29 30
Specifications
VRV Indoor Units

Wall Mounted Type Connection unit series indoor units


MODEL FXAQ20MAVE FXAQ25MAVE FXAQ32MAVE FXAQ40MAVE FXAQ50MAVE FXAQ63MAVE * A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data for details.
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz * Group control between Connection Unit series equipment within one system is possible. However, group control with the other
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 VRV indoor units is not possible.
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3
kW Ceiling Suspended Cassette Type
(*2) 2.2 2.8 3.6 4.5 5.6 7.1
Power consumption kW 0.016 0.022 0.027 0.020 0.027 0.050
Indoor unit FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
Casing White (3.0Y8.5/0.5) MODEL
3
m /min 7.5/4.5 8/5 9/5.5 12/9 15/12 19/14 Connection unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE
Airflow rate (H/L)
cfm 265/159 282/177 318/194 424/318 530/424 671/494 Power supply 1-phase, 220-240 V, 50 Hz
Sound level (H/L) dB(A) 35/29 36/29 37/29 39/34 42/36 46/39 Kcal/h(*1) 7,100 10,000 12,500
Dimensions (HXWXD) mm 290X795X230 290X795X230 290X795X230 290X1,050X230 290X1,050X230 290X1,050X230 Btu/h(*1) 28,300 39,600 49,500
Cooling capacity
Machine weight kg 11.0 11.0 11.0 14.0 14.0 14.0 (*1) 8.3 11.6 14.5
kW
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 (*2) 8.0 11.2 14.0
Piping
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7 15.9 Power consumption kW 0.189 0.298 0.298
Drain VP13 (External Dia, 18/Internal Dia, 13) Casing White (10Y9/0.5)
3
m /min 19/14 29/21 32/23

Indoor unit
Airflow rate (H/L)
cfm 671/494 1,024/741 1,130/812
Sound level (H/L) 230 V dB(A) 40/35 43/38 44/39
Dimensions (HXWXD) mm 165X895X895 230X895X895 230X895X895
Floor Standing Type/Concealed Floor Standing Type Machine weight kg 25 31 31
Liquid 9.5 (Flare)
FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE Piping
MODEL connections
Gas mm 15.9 (Flare)
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Drain VP 20 (External Dia. 26/Internal Dia. 20)
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Note: Specifications are based on the following conditions;
• Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
FXLQ • Equivalent piping length: 7.5 m
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 • Level difference: 0 m
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
kW • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre.
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Power consumption kW 0.049 0.049 0.090 0.090 0.110 0.110


Casing FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate
m3/min 7/6 7/6 8/6 11/8.5 14/11 16/12
Airflow rate (H/L)
FXNQ cfm 247/212 247/212 282/212 388/300 494/388 565/424
220 V 35/32 35/32 35/32 38/33 39/34 40/35
Sound level (H/L) dB(A)
240 V 37/34 37/34 37/34 40/35 41/36 42/37

Dimensions FXLQ 600X1,000X222 600X1,000X222 600X1,140X222 600X1,140X222 600X1,420X222 600X1,420X222


mm
(HXWXD) FXNQ 610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220
FXLQ 25.0 25.0 30.0 30.0 36.0 36.0
Machine weight kg
FXNQ 19.0 19.0 23.0 23.0 27.0 27.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5
Piping
mm 12.7 12.7 12.7 12.7 12.7 15.9
connections Gas (Flare)
Drain 21O.D.
Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
(*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Equivalent piping length: 7.5 m
•Level difference: 0 m
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Sound level: (FXAQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

29 30
Specifications
Residential Indoor Units with connection
to BP units

Residential indoor units with connection to BP units Ceiling Mounted Built-in Type
Residential indoor units can be connected to the VRVIII single outdoor unit series by BP units. MODEL FBQ60BV1 FBQ71BV1
Power supply 1-phase, 220-240 V, 50 Hz

Ceiling Mounted Cassette Type Airflow rates (H) m3/min (cfm) 17.0 (600) 19.0 (670)
Sound levels (H/L)* dB (A) 41/35
MODEL FCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE Fan speed 2 steps
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Temperature control Microcomputer control
Airflow rates (H) m3/min (cfm) 14.0 (494) 15.0 (530) 19.0 (671) Dimensions (HXWXD) mm 300X1,000X800
Sound levels (H/L)* dB (A) 33/29 35/30 Machine weight kg 41
Fan speed 2 steps Liquid (Flare) ø6.4 ø9.5
Piping
Temperature control Microcomputer control mm
connections Gas (Flare) ø12.7 ø15.9
Dimensions (HXWXD) mm 230X840X840 Drain I.D ø25XO.D ø32
Machine weight kg 24 Heat insulation Both liquid and gas pipes
Liquid (Flare) ø6.4 ø9.5 Model BYBS71DJW1
Piping
mm ø9.5 ø12.7 ø15.9 Panel
connections Gas (Flare) Colour White
(Option)
Drain I.D ø25XO.D ø32 Dimensions (HXWXD) mm 55X1,100X500
Heat insulation Both liquid and gas pipes Weight kg 4.5
Model BYC125K-W1 Note: * For 220 V operation.

Panel Colour White


(Option)
Dimensions (HXWXD) mm 40X950X950
Slim Ceiling Mounted Duct Type
Weight kg 5
Note: * For 220 V operation.
MODEL FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB
Power supply 1-phase, 220 -240 V/220 V, 50/60 Hz
Airflow rates (H) m3/min (cfm) 8.7 (307) 9.5 (335) 10.0 (353) 12.0 (424) 16.0 (565)

Ceiling Mounted Cassette (Compact Multi Flow) Type Sound levels (H/L/SL)* dB (A) 35/31/29 37/33/31 38/34/32
Fan speed 5 steps, quiet and automatic
600 x 600 MODEL FFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B Temperature control Microcomputer control
Power supply 1-phase, 220 - 240 V, 50 Hz Dimensions (HXWXD) mm 200X700X620 200X900X620 200X1,100X620
Airflow rates (H) m3/min (cfm) 9.0 (318) 10.0 (353) 12.0 (424) 15.0 (530) Machine weight kg 21 25 27 30
Sound levels (H/L)* dB (A) 29.5/24.5 32/25 36/27 41/32 Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
Fan speed 2 steps connections Gas (Flare)
Temperature control Microcomputer control Drain VP20 (External Dia. 26/Internal Dia. 20)
Dimensions (HXWXD) mm 286X575X575 Heat insulation Both liquid and gas pipes
Machine weight kg 17.5 External static pressure Pa 30 40
Liquid (Flare) ø6.4 Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa
Piping for FDKS-C. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C.
mm ø9.5 ø12.7
connections Gas (Flare)
Drain VP20 (External Dia. 26/Internal Dia. 20)
Heat insulation Both liquid and gas pipes
Model BYFQ60B8W1 Wall Mounted Type
Panel Colour White
(Option)
Dimensions (HXWXD) mm 55X700X700 MODEL FTKS25DVM FTKS35DVM FTKS50FVM FTKS60FVM FTKS71FVM
Weight kg 2.7 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher Front panel colour White
owing to ambient conditions.
Airflow rates (H) m3/min (cfm) 8.7 (307) 8.9 (314) 14.7 (519) 16.2 (572) 17.4 (614)
Sound levels (H/L/SL) dB (A) 37/25/22 39/26/23 43/34/31 45/36/33 46/37/34
Fan speed 5 steps, quiet and automatic
Temperature control Microcomputer control
Dimensions (HXWXD) mm 283X800X195 290X1,050X238
Machine weight kg 9 12
Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
connections Gas (Flare)
Drain ø18.0
Heat insulation Both liquid and gas pipes

31 32
Specifications
Residential Indoor Units with connection
to BP units

Residential indoor units with connection to BP units Ceiling Mounted Built-in Type
Residential indoor units can be connected to the VRVIII single outdoor unit series by BP units. MODEL FBQ60BV1 FBQ71BV1
Power supply 1-phase, 220-240 V, 50 Hz

Ceiling Mounted Cassette Type Airflow rates (H) m3/min (cfm) 17.0 (600) 19.0 (670)
Sound levels (H/L)* dB (A) 41/35
MODEL FCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE Fan speed 2 steps
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Temperature control Microcomputer control
Airflow rates (H) m3/min (cfm) 14.0 (494) 15.0 (530) 19.0 (671) Dimensions (HXWXD) mm 300X1,000X800
Sound levels (H/L)* dB (A) 33/29 35/30 Machine weight kg 41
Fan speed 2 steps Liquid (Flare) ø6.4 ø9.5
Piping
Temperature control Microcomputer control mm
connections Gas (Flare) ø12.7 ø15.9
Dimensions (HXWXD) mm 230X840X840 Drain I.D ø25XO.D ø32
Machine weight kg 24 Heat insulation Both liquid and gas pipes
Liquid (Flare) ø6.4 ø9.5 Model BYBS71DJW1
Piping
mm ø9.5 ø12.7 ø15.9 Panel
connections Gas (Flare) Colour White
(Option)
Drain I.D ø25XO.D ø32 Dimensions (HXWXD) mm 55X1,100X500
Heat insulation Both liquid and gas pipes Weight kg 4.5
Model BYC125K-W1 Note: * For 220 V operation.

Panel Colour White


(Option)
Dimensions (HXWXD) mm 40X950X950
Slim Ceiling Mounted Duct Type
Weight kg 5
Note: * For 220 V operation.
MODEL FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB
Power supply 1-phase, 220 -240 V/220 V, 50/60 Hz
Airflow rates (H) m3/min (cfm) 8.7 (307) 9.5 (335) 10.0 (353) 12.0 (424) 16.0 (565)

Ceiling Mounted Cassette (Compact Multi Flow) Type Sound levels (H/L/SL)* dB (A) 35/31/29 37/33/31 38/34/32
Fan speed 5 steps, quiet and automatic
600 x 600 MODEL FFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B Temperature control Microcomputer control
Power supply 1-phase, 220 - 240 V, 50 Hz Dimensions (HXWXD) mm 200X700X620 200X900X620 200X1,100X620
Airflow rates (H) m3/min (cfm) 9.0 (318) 10.0 (353) 12.0 (424) 15.0 (530) Machine weight kg 21 25 27 30
Sound levels (H/L)* dB (A) 29.5/24.5 32/25 36/27 41/32 Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
Fan speed 2 steps connections Gas (Flare)
Temperature control Microcomputer control Drain VP20 (External Dia. 26/Internal Dia. 20)
Dimensions (HXWXD) mm 286X575X575 Heat insulation Both liquid and gas pipes
Machine weight kg 17.5 External static pressure Pa 30 40
Liquid (Flare) ø6.4 Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa
Piping for FDKS-C. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C.
mm ø9.5 ø12.7
connections Gas (Flare)
Drain VP20 (External Dia. 26/Internal Dia. 20)
Heat insulation Both liquid and gas pipes
Model BYFQ60B8W1 Wall Mounted Type
Panel Colour White
(Option)
Dimensions (HXWXD) mm 55X700X700 MODEL FTKS25DVM FTKS35DVM FTKS50FVM FTKS60FVM FTKS71FVM
Weight kg 2.7 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher Front panel colour White
owing to ambient conditions.
Airflow rates (H) m3/min (cfm) 8.7 (307) 8.9 (314) 14.7 (519) 16.2 (572) 17.4 (614)
Sound levels (H/L/SL) dB (A) 37/25/22 39/26/23 43/34/31 45/36/33 46/37/34
Fan speed 5 steps, quiet and automatic
Temperature control Microcomputer control
Dimensions (HXWXD) mm 283X800X195 290X1,050X238
Machine weight kg 9 12
Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
connections Gas (Flare)
Drain ø18.0
Heat insulation Both liquid and gas pipes

31 32
Specifications Specifications
BP Units for connection to
residential indoor units
Specifications—Indoor Units
Outdoor Units

BP units for connection to residential indoor units single outdoor unit series
• A BP unit is an innovative development which allows VRVIII single outdoor unit series to be connected to
residential indoor units.
• A BP unit has the ability to precisely vary refrigerant volume to meet the cooling requirements of individual room
spaces.
• A BP unit is easy to disassemble, making repairing and recycling simple.

MODEL RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1


Power supply 3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h (*1) 19,400 24,300 29,000 34,600 39,000 42,400
Btu/h (*1) 76,800 96,200 115,000 137,000 155,000 168,000
MODEL BPMKS967B3B BPMKS967B2B Cooling capacity (*1)(*2)
(*1) 22.5 28.2 33.7 40.2 45.3 49.3
kW
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz (*2) 22.4 28.0 33.5 40.0 45.0 49.0
Power consumption (*2) kW 5.24 7.90 8.93 12.4 14.2 16.4
Number of ports 3 (connectable to 1-3 indoor units) 2 (connectable to 1-2 indoor units)
Capacity control % 20-100 14 -100 14 -100 10-100 10-100 9-100
Power consumption W 10
Casing colour Ivory white (5Y7.5/1)
Running current A 0.05 Type Hermetically sealed scroll type
Compressor
Dimensions (HXWXD) mm 180X294 (+356*)X350 Motor output kW 3.6X1 (1.4+4.5)X1 (1.8+4.5)X1 (1.4+4.5+4.5)X1 (2.7+4.5+4.5)X1 (2.8+4.5+4.5)X1
Airflow rate m3/min 180 185 233 233 233 239
Machine weight kg 8 7.5
Dimensions (HXWXD) mm 1,680X930X765 1,680X1,240X765
Number of wiring connections 3 for power supply (including earth wiring), 2 for interunit wiring (outdoor unit-BP, BP-BP), 4 for interunit wiring (BP-indoor unit) Machine weight kg 188 232 268 312 312 324
Main mm ø9.5X1 Sound level dB(A) 57 58 60 60 60 63
Liquid
Piping Branch mm ø6.4X3 ø6.4X2 Operation range °CDB –5 to 43
connections Type R-410A
(Brazing) Main mm ø19.1X1 Refrigerant
Gas Charge kg 4.7 4.9 6.0 6.3 6.5 6.7
Branch mm ø15.9X3 ø15.9X2 Piping Liquid 9.5 (Brazing) 9.5 (Brazing) 12.7 (Brazing) 12.7 (Brazing) 12.7 (Brazing) 15.9 (Brazing)
mm
Heat insulation Both liquid and gas pipes connections Gas 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing)
Connectable indoor units 2.5 kW class to 7.1 kW class residential indoor units Note: Specifications are based on the following conditions; • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. unit at a height of 1.5 m.
Min. rated capacity of (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. During actual operation, these values are normally somewhat higher as a
kW 2.5
connectable indoor units •Equivalent piping length: 7.5 m result of ambient conditions.
•Level difference: 0 m
Max. rated capacity of
kW 20.8 14.2
connectable indoor units
Note: * Total auxiliary piping length.

Outdoor unit combinations


Total capacity index of connectable indoor units*
Model name kW HP Capacity Maximum number of
Combination (%)*
index connectable indoor units
50% 100% 130%
RSXQ8PY1 22.4 8 HP 200 100 200 260 13
RSXQ10PY1 28.0 10 HP 250 125 250 325 16
RSXQ12PY1 33.5 12 HP 300 150 300 390 19
RSXQ14PY1 40.0 14 HP 350 175 350 455 22
RSXQ16PY1 45.0 16 HP 400 200 400 520 26
RSXQ18PY1 49.0 18 HP 450 225 450 585 29
* Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.

Total capacity index of the indoor units


Combination ratio =
Capacity index of the outdoor unit

33 34
Specifications Specifications
BP Units for connection to
residential indoor units
Specifications—Indoor Units
Outdoor Units

BP units for connection to residential indoor units single outdoor unit series
• A BP unit is an innovative development which allows VRVIII single outdoor unit series to be connected to
residential indoor units.
• A BP unit has the ability to precisely vary refrigerant volume to meet the cooling requirements of individual room
spaces.
• A BP unit is easy to disassemble, making repairing and recycling simple.

MODEL RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1


Power supply 3-phase 4-wire system, 380–415 V, 50 Hz
kcal/h (*1) 19,400 24,300 29,000 34,600 39,000 42,400
Btu/h (*1) 76,800 96,200 115,000 137,000 155,000 168,000
MODEL BPMKS967B3B BPMKS967B2B Cooling capacity (*1)(*2)
(*1) 22.5 28.2 33.7 40.2 45.3 49.3
kW
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz (*2) 22.4 28.0 33.5 40.0 45.0 49.0
Power consumption (*2) kW 5.24 7.90 8.93 12.4 14.2 16.4
Number of ports 3 (connectable to 1-3 indoor units) 2 (connectable to 1-2 indoor units)
Capacity control % 20-100 14 -100 14 -100 10-100 10-100 9-100
Power consumption W 10
Casing colour Ivory white (5Y7.5/1)
Running current A 0.05 Type Hermetically sealed scroll type
Compressor
Dimensions (HXWXD) mm 180X294 (+356*)X350 Motor output kW 3.6X1 (1.4+4.5)X1 (1.8+4.5)X1 (1.4+4.5+4.5)X1 (2.7+4.5+4.5)X1 (2.8+4.5+4.5)X1
Airflow rate m3/min 180 185 233 233 233 239
Machine weight kg 8 7.5
Dimensions (HXWXD) mm 1,680X930X765 1,680X1,240X765
Number of wiring connections 3 for power supply (including earth wiring), 2 for interunit wiring (outdoor unit-BP, BP-BP), 4 for interunit wiring (BP-indoor unit) Machine weight kg 188 232 268 312 312 324
Main mm ø9.5X1 Sound level dB(A) 57 58 60 60 60 63
Liquid
Piping Branch mm ø6.4X3 ø6.4X2 Operation range °CDB –5 to 43
connections Type R-410A
(Brazing) Main mm ø19.1X1 Refrigerant
Gas Charge kg 4.7 4.9 6.0 6.3 6.5 6.7
Branch mm ø15.9X3 ø15.9X2 Piping Liquid 9.5 (Brazing) 9.5 (Brazing) 12.7 (Brazing) 12.7 (Brazing) 12.7 (Brazing) 15.9 (Brazing)
mm
Heat insulation Both liquid and gas pipes connections Gas 19.1 (Brazing) 22.2 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing) 28.6 (Brazing)
Connectable indoor units 2.5 kW class to 7.1 kW class residential indoor units Note: Specifications are based on the following conditions; • Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. unit at a height of 1.5 m.
Min. rated capacity of (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. During actual operation, these values are normally somewhat higher as a
kW 2.5
connectable indoor units •Equivalent piping length: 7.5 m result of ambient conditions.
•Level difference: 0 m
Max. rated capacity of
kW 20.8 14.2
connectable indoor units
Note: * Total auxiliary piping length.

Outdoor unit combinations


Total capacity index of connectable indoor units*
Model name kW HP Capacity Maximum number of
Combination (%)*
index connectable indoor units
50% 100% 130%
RSXQ8PY1 22.4 8 HP 200 100 200 260 13
RSXQ10PY1 28.0 10 HP 250 125 250 325 16
RSXQ12PY1 33.5 12 HP 300 150 300 390 19
RSXQ14PY1 40.0 14 HP 350 175 350 455 22
RSXQ16PY1 45.0 16 HP 400 200 400 520 26
RSXQ18PY1 49.0 18 HP 450 225 450 585 29
* Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.

Total capacity index of the indoor units


Combination ratio =
Capacity index of the outdoor unit

33 34
Option List
VRV Indoor Units

Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Duct Type
No. Type FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P Type FXMQ20P FXMQ50P FXMQ100P FXMQ200MA
Item No. FXMQ25P FXMQ40P FXMQ63P FXMQ125P
1 Decoration panel BYCP125K-W1 Item FXMQ32P FXMQ80P FXMQ140P FXMQ250MA
2 Sealing member of air discharge outlet KDBH55K160F 1 Drain pump kit — KDU30L250VE
3 Panel spacer KDBP55H160FA
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
High efficiency filter unit 65% KAFP556B80 KAFP556B160 2 High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
High efficiency filter unit 90% KAFP557B80 KAFP557B160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160 3 Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 4 Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
4 Filter related
Filter chamber KDDFP55B160 5 Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
Long life replacement filter Non-woven type KAFP551K160
White KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
Ultra long-life filter KAFP55B160
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F —
Replacement ultra long-life filter KAFP55H160H
Without T shape and fan KDDP55B160 Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Chamber type
5 Fresh air intake kit With T shape without fan KDDP55B160K 7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
Direct installation type KDDP55X160
6 Branch duct chamber KDJP55B80 KDJP55B160
7 Chamber connection kit KKSJ55KA160
8 Insulation kit for high humidity KDTP55K80 KDTP55K160 Ceiling Suspended Type
No. Type FXHQ32MA FXHQ63MA FXHQ100MA
Item
Ceiling Mounted Cassette (Compact Multi Flow) Type 1 Drain pump kit KDU50N60VE KDU50N125VE
Type 2 Replacement long-life filter (Resin net) KAF501DA56 KAF501DA80 KAF501DA112
No. Item FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M
3 L-type piping kit (for upward direction) KHFP5MA63 KHFP5MA160
1 Decoration panel BYFQ60B8W1
2 Sealing member of air discharge outlet KDBH44BA60
3 Panel spacer KDBQ44BA60A
4 Replacement long-life filter KAFQ441BA60 Wall Mounted Type
5 Fresh air intake kit Direct installation type KDDQ44XA60 Type FXAQ20MA
No. Item FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MA
1 Drain pump kit K-KDU572EVE

Ceiling Mounted Cassette (Double Flow) Type


Type FXCQ20M Floor Standing Type
No. FXCQ25M FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M
Item FXCQ32M No. Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA
1 Decoration panel BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
Item
High efficiency filter 65% 1 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
High efficiency filter 90% 1 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160
2 Filter related
Filter chamber bottom suction KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160

Note:
Long life replacement filter
1 Filter chamber is required if installing high efficiency filter.
KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Concealed Floor Standing Type
No. Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
Item
Ceiling Mounted Cassette Corner Type 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71

No. Type FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


Item
Decoration panel BYK45FJW1 BYK71FJW1
1 Panel related
Panel spacer KPBJ52F56W KPBJ52F80W
Ceiling Suspended Cassette Type
Long life replacement filter KAFJ521F56 KAFJ521F80 Type
Air inlet and air No. Item FXUQ71MA FXUQ100MA FXUQ125MA
Air discharge grille K-HV7AW K-HV9AW
2 discharge outlet 1 Replacement long-life filter KAF495FA140
Air discharge blind panel KDBJ52F56W KDBJ52F80W
related 2 Sealing member of air discharge outlet (*1) KDBH49FA80 KDBH49FA140
Flexible duct (with shutter) KFDJ52FA56 KFDJ52FA80
3 Decoration panel for air discharge KDBT49FA80 KDBT49FA140
4 Vertical flap kit KDGJ49FA80 KDGJ49FA140
5 L-shape piping kit KHFP49MA140
Slim Ceiling Mounted Duct Type (700 mm width type) Note: (*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.
Type
No. FXDQ20PB FXDQ25PB FXDQ32PB
Item
1 Insulation kit for high humidity KDT25N32

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


Type
No. FXDQ40NB FXDQ50NB FXDQ63NB
Item
1 Insulation kit for high humidity KDT25N50 KDT25N63

35 36
Option List
VRV Indoor Units

Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Duct Type
No. Type FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P Type FXMQ20P FXMQ50P FXMQ100P FXMQ200MA
Item No. FXMQ25P FXMQ40P FXMQ63P FXMQ125P
1 Decoration panel BYCP125K-W1 Item FXMQ32P FXMQ80P FXMQ140P FXMQ250MA
2 Sealing member of air discharge outlet KDBH55K160F 1 Drain pump kit — KDU30L250VE
3 Panel spacer KDBP55H160FA
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
High efficiency filter unit 65% KAFP556B80 KAFP556B160 2 High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
High efficiency filter unit 90% KAFP557B80 KAFP557B160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160 3 Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 4 Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
4 Filter related
Filter chamber KDDFP55B160 5 Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
Long life replacement filter Non-woven type KAFP551K160
White KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
Ultra long-life filter KAFP55B160
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F —
Replacement ultra long-life filter KAFP55H160H
Without T shape and fan KDDP55B160 Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Chamber type
5 Fresh air intake kit With T shape without fan KDDP55B160K 7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
Direct installation type KDDP55X160
6 Branch duct chamber KDJP55B80 KDJP55B160
7 Chamber connection kit KKSJ55KA160
8 Insulation kit for high humidity KDTP55K80 KDTP55K160 Ceiling Suspended Type
No. Type FXHQ32MA FXHQ63MA FXHQ100MA
Item
Ceiling Mounted Cassette (Compact Multi Flow) Type 1 Drain pump kit KDU50N60VE KDU50N125VE
Type 2 Replacement long-life filter (Resin net) KAF501DA56 KAF501DA80 KAF501DA112
No. Item FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M
3 L-type piping kit (for upward direction) KHFP5MA63 KHFP5MA160
1 Decoration panel BYFQ60B8W1
2 Sealing member of air discharge outlet KDBH44BA60
3 Panel spacer KDBQ44BA60A
4 Replacement long-life filter KAFQ441BA60 Wall Mounted Type
5 Fresh air intake kit Direct installation type KDDQ44XA60 Type FXAQ20MA
No. Item FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MA
1 Drain pump kit K-KDU572EVE

Ceiling Mounted Cassette (Double Flow) Type


Type FXCQ20M Floor Standing Type
No. FXCQ25M FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M
Item FXCQ32M No. Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA
1 Decoration panel BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
Item
High efficiency filter 65% 1 KAFJ532G36 KAFJ532G56 KAFJ532G80 KAFJ532G160 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
High efficiency filter 90% 1 KAFJ533G36 KAFJ533G56 KAFJ533G80 KAFJ533G160
2 Filter related
Filter chamber bottom suction KDDFJ53G36 KDDFJ53G56 KDDFJ53G80 KDDFJ53G160

Note:
Long life replacement filter
1 Filter chamber is required if installing high efficiency filter.
KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Concealed Floor Standing Type
No. Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
Item
Ceiling Mounted Cassette Corner Type 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71

No. Type FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA


Item
Decoration panel BYK45FJW1 BYK71FJW1
1 Panel related
Panel spacer KPBJ52F56W KPBJ52F80W
Ceiling Suspended Cassette Type
Long life replacement filter KAFJ521F56 KAFJ521F80 Type
Air inlet and air No. Item FXUQ71MA FXUQ100MA FXUQ125MA
Air discharge grille K-HV7AW K-HV9AW
2 discharge outlet 1 Replacement long-life filter KAF495FA140
Air discharge blind panel KDBJ52F56W KDBJ52F80W
related 2 Sealing member of air discharge outlet (*1) KDBH49FA80 KDBH49FA140
Flexible duct (with shutter) KFDJ52FA56 KFDJ52FA80
3 Decoration panel for air discharge KDBT49FA80 KDBT49FA140
4 Vertical flap kit KDGJ49FA80 KDGJ49FA140
5 L-shape piping kit KHFP49MA140
Slim Ceiling Mounted Duct Type (700 mm width type) Note: (*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.
Type
No. FXDQ20PB FXDQ25PB FXDQ32PB
Item
1 Insulation kit for high humidity KDT25N32

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


Type
No. FXDQ40NB FXDQ50NB FXDQ63NB
Item
1 Insulation kit for high humidity KDT25N50 KDT25N63

35 36
Option List
Residential Indoor Units with connection
to BP units

Ceiling Mounted Cassette Type Wall Mounted Type


No. Type FCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE No. Type FTKS25DVM
Item Item FTKS35DVM FTKS50FVM FTKS60FVM FTKS71FVM
1 Decoration panel BYC125K-W1 1 Titanium apatite photocatalytic air-purifying filter KAF970A46 KAF952B42
2 Panel spacer KDBP55H160WA
Chamber Without T-shaped pipe and fan*1 KDDP55D160 Note: Filter is a standard accessory. It should be replaced approximately 3 years.
3 Fresh air intake kit type With T-shaped pipe, without fan*2 KDDP55D160K
Direct installation type*3 KDDJ55X160
(Colourimetric method 65%) KAFP556D80
4 High-efficiency filter
(Colourimetric method 90%) KAFP557D80
Replacement (Colourimetric method 65%) KAFP552H80
5
high-efficiency filter (Colourimetric method 90%) KAFP553H80
6 High-efficiency filter chamber KDDF55DA160
7 Replacement long-life filter KAF551KA160
8 Branch duct chamber KDJ55K80
Notes: *1. With a suction chamber. Fresh air intake is from 2 holes on the sides of the connection chamber. (This method should be selected if a wireless remote controller is used.)
*2. Without a suction chamber. Fresh air intake is from 2 holes on the connection chamber via a T-shaped pipe connection. (A wireless remote controller cannot be used in this case.)
*3. Without a suction chamber. Fresh air intake is directly from a hole on the main unit.

Ceiling Mounted Cassette (Compact Multi Flow) Type BP Units for connection to
residential indoor units

No. Type FFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B


Item
1 Decoration panel BYFQ60B8W1
2 Replacement long-life filter KAFQ441BA60 No. Type BPMKS967B2B BPMKS967B3B
3 Fresh air intake kit Direct installation type KDDQ44XA60 Item
4 Sealing member for air discharge outlet KDBH44BA60 1 REFNET joint KHRP26A22T
5 Panel spacer KDBQ44BA60A Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints.

Ceiling Mounted Built-in Type


No. Type FBQ60BV1 FBQ71BV1
Item
1 Decoration panel BYBS71DJW1
2 Service access panel KTBJ25L80W
(Colourimetric method 65%) KAF252LA80
3 High-efficiency filter
(Colourimetric method 90%) KAF253LA80
4 Replacement long-life filter Resin net KAFJ251K80
5 Filter chamber for bottom suction KAJ25LA80D
6 Filter chamber for rear suction KAJ25LA80B
7 Canvas duct KSAJ25K80
ø150 K-DG5DW
8 Discharge grille
ø200 K-DG9DW
9 Discharge chamber
ø150
ø200
K-DGC5D
K-DGC9D
Specifications—Indoor Units
Outdoor Units
10 Branch duct ø150 ø200 K-DDV20A
ø150 K-FDS151C(1m)/K-FDS152C(2m)/K-FDS153C(3m)/K-FDS154C(4m)/K-FDS155C(5m)/K-FDS156C(6m)
11 Flexible duct
ø200 K-FDS201C(1m)/K-FDS202C(2m)/K-FDS203C(3m)/K-FDS204C(4m)/K-FDS205C(5m)/K-FDS206C(6m)
12 Blind board KBBJ25KA80
13 Adaptor for discharge KDAJ25K71 Type
RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1
14 Flange for suction KDJ2507K80 Item
KHRP26M22H (Max. 4 branch) KHRP26M22H (Max. 4 branch)
REFNET header KHRP26M33H (Max. 8 branch)
KHRP26M33H (Max. 8 branch)
Distributive KHRP26M72H (Max. 8 branch)
piping
KHRP26A22T KHRP26A22T
REFNET joint KHRP26A33T
KHRP26A33T
KHRP26A72T
Auxiliary pipe set*1 KHFP22B8P KHFP22B10P KHFP22B12P KHFP22B16P KHFP22B18P
Slim Ceiling Mounted Duct Type
Central drain pan kit KWC26C280 KWC26C450
No. Type FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB
Item Digital pressure gauge kit BHGP26A1
1 Suction grille KDGF19A45 Note: *1. Auxiliary pipe sets are not attached to the outdoor units. If neccesary, use the optional accessories.
2 Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63

37 38
Option List
Residential Indoor Units with connection
to BP units

Ceiling Mounted Cassette Type Wall Mounted Type


No. Type FCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE No. Type FTKS25DVM
Item Item FTKS35DVM FTKS50FVM FTKS60FVM FTKS71FVM
1 Decoration panel BYC125K-W1 1 Titanium apatite photocatalytic air-purifying filter KAF970A46 KAF952B42
2 Panel spacer KDBP55H160WA
Chamber Without T-shaped pipe and fan*1 KDDP55D160 Note: Filter is a standard accessory. It should be replaced approximately 3 years.
3 Fresh air intake kit type With T-shaped pipe, without fan*2 KDDP55D160K
Direct installation type*3 KDDJ55X160
(Colourimetric method 65%) KAFP556D80
4 High-efficiency filter
(Colourimetric method 90%) KAFP557D80
Replacement (Colourimetric method 65%) KAFP552H80
5
high-efficiency filter (Colourimetric method 90%) KAFP553H80
6 High-efficiency filter chamber KDDF55DA160
7 Replacement long-life filter KAF551KA160
8 Branch duct chamber KDJ55K80
Notes: *1. With a suction chamber. Fresh air intake is from 2 holes on the sides of the connection chamber. (This method should be selected if a wireless remote controller is used.)
*2. Without a suction chamber. Fresh air intake is from 2 holes on the connection chamber via a T-shaped pipe connection. (A wireless remote controller cannot be used in this case.)
*3. Without a suction chamber. Fresh air intake is directly from a hole on the main unit.

Ceiling Mounted Cassette (Compact Multi Flow) Type BP Units for connection to
residential indoor units

No. Type FFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B


Item
1 Decoration panel BYFQ60B8W1
2 Replacement long-life filter KAFQ441BA60 No. Type BPMKS967B2B BPMKS967B3B
3 Fresh air intake kit Direct installation type KDDQ44XA60 Item
4 Sealing member for air discharge outlet KDBH44BA60 1 REFNET joint KHRP26A22T
5 Panel spacer KDBQ44BA60A Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints.

Ceiling Mounted Built-in Type


No. Type FBQ60BV1 FBQ71BV1
Item
1 Decoration panel BYBS71DJW1
2 Service access panel KTBJ25L80W
(Colourimetric method 65%) KAF252LA80
3 High-efficiency filter
(Colourimetric method 90%) KAF253LA80
4 Replacement long-life filter Resin net KAFJ251K80
5 Filter chamber for bottom suction KAJ25LA80D
6 Filter chamber for rear suction KAJ25LA80B
7 Canvas duct KSAJ25K80
ø150 K-DG5DW
8 Discharge grille
ø200 K-DG9DW
9 Discharge chamber
ø150
ø200
K-DGC5D
K-DGC9D
Specifications—Indoor Units
Outdoor Units
10 Branch duct ø150 ø200 K-DDV20A
ø150 K-FDS151C(1m)/K-FDS152C(2m)/K-FDS153C(3m)/K-FDS154C(4m)/K-FDS155C(5m)/K-FDS156C(6m)
11 Flexible duct
ø200 K-FDS201C(1m)/K-FDS202C(2m)/K-FDS203C(3m)/K-FDS204C(4m)/K-FDS205C(5m)/K-FDS206C(6m)
12 Blind board KBBJ25KA80
13 Adaptor for discharge KDAJ25K71 Type
RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1
14 Flange for suction KDJ2507K80 Item
KHRP26M22H (Max. 4 branch) KHRP26M22H (Max. 4 branch)
REFNET header KHRP26M33H (Max. 8 branch)
KHRP26M33H (Max. 8 branch)
Distributive KHRP26M72H (Max. 8 branch)
piping
KHRP26A22T KHRP26A22T
REFNET joint KHRP26A33T
KHRP26A33T
KHRP26A72T
Auxiliary pipe set*1 KHFP22B8P KHFP22B10P KHFP22B12P KHFP22B16P KHFP22B18P
Slim Ceiling Mounted Duct Type
Central drain pan kit KWC26C280 KWC26C450
No. Type FDKS25EAVMB FDKS35EAVMB FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMB
Item Digital pressure gauge kit BHGP26A1
1 Suction grille KDGF19A45 Note: *1. Auxiliary pipe sets are not attached to the outdoor units. If neccesary, use the optional accessories.
2 Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63

37 38
Control Systems

Individual Control Systems for VRV Indoor Units

Navigation remote controller (Wired remote controller) (Option) Wireless remote controller (Option)
The same operation modes and settings as with wired remote controllers are possible.
A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is
Large buttons and arrow keys for easy operation. included.
Guide on display gives an explanation of each setting. • A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted
Backlight and dot matrix LCD display for easy viewing. type is mounted into the indoor unit.
Weekly schedule timer can be set up easily. Signal receiver unit can be
10 display languages are available. installed on the panel
ex. Ceiling Mounted Cassette (Round Flow) type
(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch,
Russian and Turkish)
Signal receiver unit
(Separate type)
BRC1E61
Wireless remote Signal receiver unit
Wired remote controller (Option) Wired remote controller controller (Installed type)

with weekly schedule timer (Option) *Wireless remote controller and signal receiver unit are sold as a set.
Displays current airflow, swing, temperature,
*Refer to page 43 for the name of each model.
operating mode and timer settings. Adds weekly schedule timer function.

Simplified remote controller (Option)


The remote controller has
centralised its frequently used
operation selectors and
switches (on/off, operation
mode, temperature setting and
airflow volume), making itself
suitable for use in hotel rooms
or conference rooms.
BRC1C62 BRC1D61
The exposed type remote
Concealed type controller is fitted with a
Notes: 1. Standard remote controllers (BRC1C62) not required. (For hotel use) thermostat sensor.
2. If the BRC1D61 is connected to the centralised remote controllers (BRC3A61)
(DCS303A51, DCS302CA61, DCS301BA61, DST301BA61), the
Exposed type
schedule function is not available. The concealed type remote controller smartly fits into a
(BRC2C51)
night table or console panel in a hotel room.
Widewired
The variation
remote
of remote
controller
controllers
supportsfor
a wide
indoor
range
unitsof control functions

Wide variation of remote controllers for VRV


indoor
indoor
unitsunits
1 Control by two remote controller

Group control The indoor unit can be connected by the two FXFQ FXZQ FXCQ FXKQ FXDQ FXMQ FXHQ FXAQ FXL(N)Q FXUQ
One remote controller can remote controller, for example one in the room
Equipment and the other one in the control room, which
Outdoor
related to the control the operation of max.16
unit indoor units at the same time. can control the operation of indoor unit freely. Navigation remote controller
central control (Wired remote controller)
(The last command has a priority.) Of course, (BRC1E61)
the group control by two remote controller is
also possible.
Wired remote controller
(BRC1C62)
Indoor unit
Remote controller 2 Remote control
Remote controller
The wiring of remote controller can be Wired remote controller with
extended to max. 500 m and it is possible weekly schedule timer
to install the remote controllers for the (BRC1D61)
different indoor units in one place.
Remote
controller
Wireless remote controller*
3 Control for the combined operation (Installed type signal receiver unit)

Forced OFF
input The operation of the Heat Reclaim Ventilator
can be controlled by the remote controller of
Wireless remote controller*
Heat Reclaim the indoor unit. Of course, the remote controller (Separate type signal receiver unit)
Ventilator can display the time to clean the filter.
Remote controller Remote
controller Remote controller
Remote controller Remote controller
Simplified remote controller
4 Expansion of system control (Exposed type)
(BRC2C51)
1 2 3 4 The system can be expanded to add
several controllers, such as BMS, Forced
OFF input and etc. Simplified remote controller
(Concealed type: for Hotel use)
(BRC3A61)

*Refer to page 43 for the name of each model.

39 40
Control Systems

Individual Control Systems for VRV Indoor Units

Navigation remote controller (Wired remote controller) (Option) Wireless remote controller (Option)
The same operation modes and settings as with wired remote controllers are possible.
A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is
Large buttons and arrow keys for easy operation. included.
Guide on display gives an explanation of each setting. • A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted
Backlight and dot matrix LCD display for easy viewing. type is mounted into the indoor unit.
Weekly schedule timer can be set up easily. Signal receiver unit can be
10 display languages are available. installed on the panel
ex. Ceiling Mounted Cassette (Round Flow) type
(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch,
Russian and Turkish)
Signal receiver unit
(Separate type)
BRC1E61
Wireless remote Signal receiver unit
Wired remote controller (Option) Wired remote controller controller (Installed type)

with weekly schedule timer (Option) *Wireless remote controller and signal receiver unit are sold as a set.
Displays current airflow, swing, temperature,
*Refer to page 43 for the name of each model.
operating mode and timer settings. Adds weekly schedule timer function.

Simplified remote controller (Option)


The remote controller has
centralised its frequently used
operation selectors and
switches (on/off, operation
mode, temperature setting and
airflow volume), making itself
suitable for use in hotel rooms
or conference rooms.
BRC1C62 BRC1D61
The exposed type remote
Concealed type controller is fitted with a
Notes: 1. Standard remote controllers (BRC1C62) not required. (For hotel use) thermostat sensor.
2. If the BRC1D61 is connected to the centralised remote controllers (BRC3A61)
(DCS303A51, DCS302CA61, DCS301BA61, DST301BA61), the
Exposed type
schedule function is not available. The concealed type remote controller smartly fits into a
(BRC2C51)
night table or console panel in a hotel room.
Widewired
The variation
remote
of remote
controller
controllers
supportsfor
a wide
indoor
range
unitsof control functions

Wide variation of remote controllers for VRV


indoor
indoor
unitsunits
1 Control by two remote controller

Group control The indoor unit can be connected by the two FXFQ FXZQ FXCQ FXKQ FXDQ FXMQ FXHQ FXAQ FXL(N)Q FXUQ
One remote controller can remote controller, for example one in the room
Equipment and the other one in the control room, which
Outdoor
related to the control the operation of max.16
unit indoor units at the same time. can control the operation of indoor unit freely. Navigation remote controller
central control (Wired remote controller)
(The last command has a priority.) Of course, (BRC1E61)
the group control by two remote controller is
also possible.
Wired remote controller
(BRC1C62)
Indoor unit
Remote controller 2 Remote control
Remote controller
The wiring of remote controller can be Wired remote controller with
extended to max. 500 m and it is possible weekly schedule timer
to install the remote controllers for the (BRC1D61)
different indoor units in one place.
Remote
controller
Wireless remote controller*
3 Control for the combined operation (Installed type signal receiver unit)

Forced OFF
input The operation of the Heat Reclaim Ventilator
can be controlled by the remote controller of
Wireless remote controller*
Heat Reclaim the indoor unit. Of course, the remote controller (Separate type signal receiver unit)
Ventilator can display the time to clean the filter.
Remote controller Remote
controller Remote controller
Remote controller Remote controller
Simplified remote controller
4 Expansion of system control (Exposed type)
(BRC2C51)
1 2 3 4 The system can be expanded to add
several controllers, such as BMS, Forced
OFF input and etc. Simplified remote controller
(Concealed type: for Hotel use)
(BRC3A61)

*Refer to page 43 for the name of each model.

39 40
Control Systems

Advanced Control Systems for VRV Indoor Units


Communication functions in the user-friendly icon-based multilingual
PCMCIA
Flash
Memory DCS601C51 controller simplify centralised control of the VRV system.
Dio Unit Di Unit
Support for centralised control from elsewhere
DEC102A51 DEC101A51 Function 1 using a PC with a Web browser (Option)
• CSV output of power
proportional distribution
(Option) (Option) • Colour LCD touch panel icon display
results (Option)
Function 5 • Small manageable size Sending of e-mail alerts to a specified address
Function 2
Function 1 Input Input (Key signal - • Simplified engineering when malfunctions occur (Option)
System (Lights) General purpose ADP)
• Multi language (English, French, Italian, German, Spanish, Dutch, Built-in modem for connecting to Air Conditioning
Set temperature OFF
Remote monitor- Function 6
Portuguese, Chinese and Korean) Function 3
ing and control
change command command
Network Service System (Option)
• Yearly schedule Doubling of number of connectable indoor units by
• PPD (Power Proportional Distribution function) (Option) Function 4
adding a D -NET Plus Adaptor (Option)
Air Conditioning Network
Service System modem
Pi Port
• Auto heat/cool change-over
Function 2 for connections • Connection to power consumption Management of facilities/equipment other than
metre when using power proportional • Temperature limitation Function 5
Function 3
Via internet distribution function. (Option) D -NET A/C units (By adding Dio unit or Di unit)
Malfunction report
by E-mail
RS-232C
• Enhanced history function
System Simple Interlock Function
Mobile Phone PC Components Indoor Unit
Heat Reclaim Ventilator • Air Conditioning Network Service System (Optional Maintenance Service) Function 6
D -NET Plus Adaptor
ACC centre
• Air Conditioning Network Service System DCS601A52 (Option)
Function 4
• Simple Interlock Function
(Optional Maintenance Service) Number of indoor units expanded from 64 to 128.

Centralised Control Systems for VRV Indoor Units


Up to 64 groups of indoor units (128 units) can be centrally controlled. System integration with various air-conditioning peripheral
equipment, such as a Heat Reclaim Ventilator, is easy.
Optional controllers for centralised control can be combined freely, and Residential central remote controller* (Option)
system can be designed in accordance with building scale and purpose. Wiring can be run up to a total length of 2 km, and adapts easily to
Max. 16 groups of indoor units can be easily controlled with the large LCD panel.
large-scale system expansion.
• Max. 16 groups (128 indoor units) controllable • All indoor units can be turned on or off at once with
• Backlight and large LCD panel for easy readability “ALL” button.
• ON/OFF, temperature settings and scheduling can • Each group has a dedicated button for convenience.
be controlled individually for indoor units. • Outside temperature display
Unified on/off DCS303A51
controller
* For residential use only. Cannot be used with other centralised control equipment.
(DCS301BA61)
Connection of
up to 8 units
Independent
possible
and centralised Central remote controller (Option)
Address setting of central control can be control of a
performed from the remote controller. Heat Reclaim Max. 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.
Ventilator is
possible. • Max. 64 groups (128 indoor units) controllable • Airflow volume and direction can be controlled
• Max. 128 groups (128 indoor units) are controllable by individually for indoor units in each group
using 2 central remote controllers, which can control operation.
DCS302CA61 from 2 different places. • Ventilation volume and mode can be controlled
Connectable number of
centralised control • Zone control for the Heat Reclaim Ventilator.
equipment • Malfunction code display • Up to 4 ON/OFF pairs can be set per day by
• Max. wiring length 1,000 m (Total: 2,000 m) connecting a schedule timer.
Central remote Group control of up to 16 units is possible
controller 2 units • Connectable with Unified ON/OFF controller, schedule
(group control via automatic address setting)
timer and BMS system
Unified on / off
controller 8 units

Schedule timer 1 unit

Unified ON/OFF controller (Option)


System without remote control is also available.
Max. 16 groups of indoor units can be operated simultaneously/individually.
• Max. 16 groups (128 indoor units) controllable • Max. wiring length 1,000 m (Total: 2,000 m)
Forced • Compact size casing (Thickness: 16 mm)
• 2 remote controllers can be used to control from 2
shut-down
input different places. • Connectable with Central Remote controller,
Central control Wiring adaptor • Schedule timer and BMS system
for other air- Outdoor-air • Operating status indication (Normal operation, Alarm)
adaptor kit
conditioners processing DCS301BA61 • Centralised control indication
(DTA107A55)
(DTA103A51) unit can be
connected.
Central remote
controller Interface adaptor for SkyAir
(DCS302CA61) series (built-in indoor unit) Schedule timer (Option)
(DTA102A52)
Up to 2 units
connectable Max. 128 indoor units can be operated as programmed schedule.
• Max. 128 indoor units controllable • Max. 48 hours back up power supply
• When used in combination with a central remote • Max. wiring length 1,000 m (Total: 2,000 m)
6 cores 7 cores max. Interlink Building Management System controller, a maximum of 8 weekly schedule • Compact size casing (Thickness: 16 mm)
(host computer monitor panel) also possible patterns can be set, while the central controller can • Connectable with Central Remote controller,
Schedule timer (DST301BA61)
1 unit connection possible ; Unification adaptor for computerised DST301BA61 be used to select desired zones. Up to 2 ON/OFF Unified ON/OFF controller and BMS system
8 weekly schedule control patterns possible control (DCS302A52) pairs can be set per day.
• Certain indoor units limit the functions of some control systems.
For more details, please refer to the Engineering Data Book.

41 42
Control Systems

Advanced Control Systems for VRV Indoor Units


Communication functions in the user-friendly icon-based multilingual
PCMCIA
Flash
Memory DCS601C51 controller simplify centralised control of the VRV system.
Dio Unit Di Unit
Support for centralised control from elsewhere
DEC102A51 DEC101A51 Function 1 using a PC with a Web browser (Option)
• CSV output of power
proportional distribution
(Option) (Option) • Colour LCD touch panel icon display
results (Option)
Function 5 • Small manageable size Sending of e-mail alerts to a specified address
Function 2
Function 1 Input Input (Key signal - • Simplified engineering when malfunctions occur (Option)
System (Lights) General purpose ADP)
• Multi language (English, French, Italian, German, Spanish, Dutch, Built-in modem for connecting to Air Conditioning
Set temperature OFF
Remote monitor- Function 6
Portuguese, Chinese and Korean) Function 3
ing and control
change command command
Network Service System (Option)
• Yearly schedule Doubling of number of connectable indoor units by
• PPD (Power Proportional Distribution function) (Option) Function 4
adding a D -NET Plus Adaptor (Option)
Air Conditioning Network
Service System modem
Pi Port
• Auto heat/cool change-over
Function 2 for connections • Connection to power consumption Management of facilities/equipment other than
metre when using power proportional • Temperature limitation Function 5
Function 3
Via internet distribution function. (Option) D -NET A/C units (By adding Dio unit or Di unit)
Malfunction report
by E-mail
RS-232C
• Enhanced history function
System Simple Interlock Function
Mobile Phone PC Components Indoor Unit
Heat Reclaim Ventilator • Air Conditioning Network Service System (Optional Maintenance Service) Function 6
D -NET Plus Adaptor
ACC centre
• Air Conditioning Network Service System DCS601A52 (Option)
Function 4
• Simple Interlock Function
(Optional Maintenance Service) Number of indoor units expanded from 64 to 128.

Centralised Control Systems for VRV Indoor Units


Up to 64 groups of indoor units (128 units) can be centrally controlled. System integration with various air-conditioning peripheral
equipment, such as a Heat Reclaim Ventilator, is easy.
Optional controllers for centralised control can be combined freely, and Residential central remote controller* (Option)
system can be designed in accordance with building scale and purpose. Wiring can be run up to a total length of 2 km, and adapts easily to
Max. 16 groups of indoor units can be easily controlled with the large LCD panel.
large-scale system expansion.
• Max. 16 groups (128 indoor units) controllable • All indoor units can be turned on or off at once with
• Backlight and large LCD panel for easy readability “ALL” button.
• ON/OFF, temperature settings and scheduling can • Each group has a dedicated button for convenience.
be controlled individually for indoor units. • Outside temperature display
Unified on/off DCS303A51
controller
* For residential use only. Cannot be used with other centralised control equipment.
(DCS301BA61)
Connection of
up to 8 units
Independent
possible
and centralised Central remote controller (Option)
Address setting of central control can be control of a
performed from the remote controller. Heat Reclaim Max. 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.
Ventilator is
possible. • Max. 64 groups (128 indoor units) controllable • Airflow volume and direction can be controlled
• Max. 128 groups (128 indoor units) are controllable by individually for indoor units in each group
using 2 central remote controllers, which can control operation.
DCS302CA61 from 2 different places. • Ventilation volume and mode can be controlled
Connectable number of
centralised control • Zone control for the Heat Reclaim Ventilator.
equipment • Malfunction code display • Up to 4 ON/OFF pairs can be set per day by
• Max. wiring length 1,000 m (Total: 2,000 m) connecting a schedule timer.
Central remote Group control of up to 16 units is possible
controller 2 units • Connectable with Unified ON/OFF controller, schedule
(group control via automatic address setting)
timer and BMS system
Unified on / off
controller 8 units

Schedule timer 1 unit

Unified ON/OFF controller (Option)


System without remote control is also available.
Max. 16 groups of indoor units can be operated simultaneously/individually.
• Max. 16 groups (128 indoor units) controllable • Max. wiring length 1,000 m (Total: 2,000 m)
Forced • Compact size casing (Thickness: 16 mm)
• 2 remote controllers can be used to control from 2
shut-down
input different places. • Connectable with Central Remote controller,
Central control Wiring adaptor • Schedule timer and BMS system
for other air- Outdoor-air • Operating status indication (Normal operation, Alarm)
adaptor kit
conditioners processing DCS301BA61 • Centralised control indication
(DTA107A55)
(DTA103A51) unit can be
connected.
Central remote
controller Interface adaptor for SkyAir
(DCS302CA61) series (built-in indoor unit) Schedule timer (Option)
(DTA102A52)
Up to 2 units
connectable Max. 128 indoor units can be operated as programmed schedule.
• Max. 128 indoor units controllable • Max. 48 hours back up power supply
• When used in combination with a central remote • Max. wiring length 1,000 m (Total: 2,000 m)
6 cores 7 cores max. Interlink Building Management System controller, a maximum of 8 weekly schedule • Compact size casing (Thickness: 16 mm)
(host computer monitor panel) also possible patterns can be set, while the central controller can • Connectable with Central Remote controller,
Schedule timer (DST301BA61)
1 unit connection possible ; Unification adaptor for computerised DST301BA61 be used to select desired zones. Up to 2 ON/OFF Unified ON/OFF controller and BMS system
8 weekly schedule control patterns possible control (DCS302A52) pairs can be set per day.
• Certain indoor units limit the functions of some control systems.
For more details, please refer to the Engineering Data Book.

41 42
Option List
Control Systems

Operation Control System Optional Accessories System Configuration


For VRV indoor unit use No. Item Model No.
Note 3
Function
•Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF,
1 Residential central remote controller DCS303A51
Type temperature settings and scheduling can be controlled individually for indoor units.
No. FXFQ-P FXZQ-M FXCQ-M FXKQ-MA FXDQ-PB FXMQ-P FXMQ-MA FXHQ-MA FXAQ-MA FXLQ-MA FXUQ-MA
Item FXDQ-NB FXNQ-MA Note 2
2 Central remote controller DCS302CA61 •Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
Wireless type BRC7F635F BRC7E531W BRC7C67 BRC4C63 BRC4C66 BRC4C66 BRC4C64 BRC7EA66 BRC7EA619 BRC4C64 BRC7CA529W monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
1 Remote controller system.
Wired type BRC1C62 2-1 Electrical box with earth terminal (3 blocks) KJB311AA

2 Navigation remote controller (Wired remote controller) BRC1E61 3 Unified ON/OFF controller
Note 2
DCS301BA61
3 Wired remote controller with weekly schedule timer BRC1D61 •Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
3-1 Electrical box with earth terminal (2 blocks) KJB212AA operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
4 Simplified remote controller (Exposed type) — BRC2C51 — BRC2C51 —
5 Remote controller for hotel use (Concealed type) — BRC3A61 — BRC3A61 — 3-2 Noise filter (for electromagnetic interface use only) KEK26-1A
6 Adaptor for wiring KRP1C63 KRP1BA57 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 — KRP1B61 — Note 2 •Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
4 Schedule timer
DST301BA61 (128 units). Can turn units ON/OFF twice per day.
7-1 Wiring adaptor for electrical appendices (1) KRP2A62 KRP2A62 KRP2A61 KRP2A61 KRP2A53 KRP2A61 KRP2A61 KRP2A62 KRP2A61 KRP2A61 KRP2A62
5-room centralised controller Note 4
7-2 Wiring adaptor for electrical appendices (2) KRP4AA53 KRP4AA53 KRP4AA51 KRP4AA51 KRP4A54 KRP4AA51 KRP4AA51 KRP4AA52 KRP4AA51 KRP4AA51 KRP4AA53 5 For FTKS-D/F, FDKS-EA/C(A) KRC72 •Up to 5 indoor units can be controlled. This is a low cost system which can only control ON/OFF.
for residential indoor units
8 Remote sensor (for indoor temperature) KRCS01-4B KRCS01-1B KRCS01-4B KRCS01-1B For FTKS-D/F, FDKS-EA/C(A) KRP928BB2S
Interface adaptor for residential
Notes 2, 3 Notes 4, 6 Notes 2, 3 Notes 4, 6 Notes 2, 3 Note 3 Notes 2, 3 6
9 Installation box for adaptor PCB KRP1H98 KRP1BA101 KRP1B96 — KRP1BA101 KRP4A96 — KRP1CA93 KRP4AA93 — KRP1BA97 indoor units
For FCQ-B, FFQ-B, FBQ-B DTA112BA51 •Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
10 External control adaptor for outdoor unit DTA104A62 DTA104A62 DTA104A61 DTA104A61 DTA104A53 DTA104A61 DTA104A61 DTA104A62 DTA104A61 DTA104A61 — communication system adopted for the VRV System.
7 Interface adaptor for SkyAir-series For SkyAir, FD(Y)M-FA, FDY-KA
DTA102A52
11 Adaptor for multi tenant DTA114A61 — DTA114A61 — DTA114A61 — FDYB-KA, FVY(P)J-A, FXUQ-MA * To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
Notes: 1. Installation box is necessary for each adaptor marked . 8 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit. 9 Wiring adaptor for other air-conditioner DTA103A51
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
•Up to 1024 units can be centrally controlled in 64 different groups.
D -NET
10 DTA109A51 •Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
Expander Adaptor
apply to each adaptor.

10-1 Mounting plate KRP4A92 •Fixing plate for DTA109A51

Notes: 1. Installation box for adaptor must be obtained locally.


For Residential indoor unit use 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary. For residential indoor units, an interface adaptor (KRP928BB2S or DTA112BA51) is required for each indoor unit.
3. For residential use only. Cannot be used with other centralised control equipment.
4. A wiring adaptor (KRP413AB1S) is also required for each indoor unit.
Type FDKS-EA FTKS-D
No. FCQ-B FFQ-B FBQ-B
Item FDKS-C(A) FTKS-F
Wired typeNote 1 BRC1C61 —
1 Remote controller
Wireless type BRC7C613W BRC7E531W — — Note 2

Note 3 Note 4
2 Adaptor for wiring KRP1BA57 KRP1BA57 KRP1BA54 —

Note 3 Note 4
3 Wiring adaptor for electrical appendices KRP4AA51 —

4 Installation box for adaptor PCB


KRP4AA53
KRP1B98
KRP4AA53
KRP1BA101 —
Building Management System
5 Remote sensor (for indoor temperature) — KRCS01-1B — No. Item Model No. Function
Wiring adaptor for time clock/remote controller Note 5 1 Basic Hardware intelligent Touch Controller DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.
6 — KRP413AB1S
(Normal open pulse contact/normal open contact)
1-1 intelligent Touch Hardware DIII-NET plus adaptor DCS601A52 •Additional 64 groups (10 outdoor units) is possible.
7 Remote controller loss prevention chain — KKF917A4
1-2 Controller Option PPD DCS002C51 •PPD: Power Proportional Distribution function
Notes: 1. Wiring for wired remote controller should be obtained locally. Software
2. A wireless remote controller is a standard accessory for FDKS and FTKS models. 1-1
1-3 Web DCS004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
3. Installation box for adaptor PCB (KRP1B98) is necessary.
1-4 Electrical box with earth terminal (4 blocks) KJB411A •Wall embedded switch box.
4. Installation box for adaptor PCB (KRP1BA101) is necessary.
5. Time clock and other devices should be obtained locally. 128 units DAM602B52
256 units DAM602B51
Number of
2 Basic Hardware units to be 512 units DAM602B51x2 •Air conditioner management system that can be controlled by personal computers.
connected
768 units DAM602B51x3

intelligent Manager III 1024 units DAM602B51x4

2-1 PPD DAM002A51 •Power Proportional Distribution function

2-2 Option Software Web DAM004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.

2-3 ECONO DAM003A51 •ECONO (Energy saving functions.)

2-4 Optional DIII Ai unit DAM101A51 •External temperature sensor for intelligent Manager III.

2-5 Di unit DEC101A51 •8 pairs based on a pair of On/Off input and abnormality input.

2-6 Dio unit DEC102A51 •4 pairs based on a pair of On/Off input and abnormality input.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-

Communication line
3 *1 Interface for use in BACnet ®
DMS502B51 conditioning systems through BACnet communication.
®

•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
3-1 Optional DIII board DAM411B51 independently.
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
3-2 Optional Di board DAM412B51 independently.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
4 *2 Interface for use in LONWORKS ®
DMS504B51 conditioning systems through LONWORKS communication.
®

5 Parallel interface DPF201A51 •Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
Contact/analogue

Basic unit 4 units.


6 Temperature DPF201A52 •Enables temperature measurement output for 4 groups; 0-5VDC.
signal

measurement units
7 Temperature DPF201A53 •Enables temperature setting input for 16 groups; 0-5VDC.
setting units
8 Unification adaptor for DCS302A52 •Interface between the central monitoring board and central control units.
computerised control
®
Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS is a trademark of Echelon Corporation registered in the United States and other countries.
®

*3. Installation box for adaptor must be obtained locally.

43 44
Option List
Control Systems

Operation Control System Optional Accessories System Configuration


For VRV indoor unit use No. Item Model No.
Note 3
Function
•Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF,
1 Residential central remote controller DCS303A51
Type temperature settings and scheduling can be controlled individually for indoor units.
No. FXFQ-P FXZQ-M FXCQ-M FXKQ-MA FXDQ-PB FXMQ-P FXMQ-MA FXHQ-MA FXAQ-MA FXLQ-MA FXUQ-MA
Item FXDQ-NB FXNQ-MA Note 2
2 Central remote controller DCS302CA61 •Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
Wireless type BRC7F635F BRC7E531W BRC7C67 BRC4C63 BRC4C66 BRC4C66 BRC4C64 BRC7EA66 BRC7EA619 BRC4C64 BRC7CA529W monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
1 Remote controller system.
Wired type BRC1C62 2-1 Electrical box with earth terminal (3 blocks) KJB311AA

2 Navigation remote controller (Wired remote controller) BRC1E61 3 Unified ON/OFF controller
Note 2
DCS301BA61
3 Wired remote controller with weekly schedule timer BRC1D61 •Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
3-1 Electrical box with earth terminal (2 blocks) KJB212AA operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
4 Simplified remote controller (Exposed type) — BRC2C51 — BRC2C51 —
5 Remote controller for hotel use (Concealed type) — BRC3A61 — BRC3A61 — 3-2 Noise filter (for electromagnetic interface use only) KEK26-1A
6 Adaptor for wiring KRP1C63 KRP1BA57 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 — KRP1B61 — Note 2 •Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
4 Schedule timer
DST301BA61 (128 units). Can turn units ON/OFF twice per day.
7-1 Wiring adaptor for electrical appendices (1) KRP2A62 KRP2A62 KRP2A61 KRP2A61 KRP2A53 KRP2A61 KRP2A61 KRP2A62 KRP2A61 KRP2A61 KRP2A62
5-room centralised controller Note 4
7-2 Wiring adaptor for electrical appendices (2) KRP4AA53 KRP4AA53 KRP4AA51 KRP4AA51 KRP4A54 KRP4AA51 KRP4AA51 KRP4AA52 KRP4AA51 KRP4AA51 KRP4AA53 5 For FTKS-D/F, FDKS-EA/C(A) KRC72 •Up to 5 indoor units can be controlled. This is a low cost system which can only control ON/OFF.
for residential indoor units
8 Remote sensor (for indoor temperature) KRCS01-4B KRCS01-1B KRCS01-4B KRCS01-1B For FTKS-D/F, FDKS-EA/C(A) KRP928BB2S
Interface adaptor for residential
Notes 2, 3 Notes 4, 6 Notes 2, 3 Notes 4, 6 Notes 2, 3 Note 3 Notes 2, 3 6
9 Installation box for adaptor PCB KRP1H98 KRP1BA101 KRP1B96 — KRP1BA101 KRP4A96 — KRP1CA93 KRP4AA93 — KRP1BA97 indoor units
For FCQ-B, FFQ-B, FBQ-B DTA112BA51 •Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
10 External control adaptor for outdoor unit DTA104A62 DTA104A62 DTA104A61 DTA104A61 DTA104A53 DTA104A61 DTA104A61 DTA104A62 DTA104A61 DTA104A61 — communication system adopted for the VRV System.
7 Interface adaptor for SkyAir-series For SkyAir, FD(Y)M-FA, FDY-KA
DTA102A52
11 Adaptor for multi tenant DTA114A61 — DTA114A61 — DTA114A61 — FDYB-KA, FVY(P)J-A, FXUQ-MA * To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
Notes: 1. Installation box is necessary for each adaptor marked . 8 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit. 9 Wiring adaptor for other air-conditioner DTA103A51
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
•Up to 1024 units can be centrally controlled in 64 different groups.
D -NET
10 DTA109A51 •Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
Expander Adaptor
apply to each adaptor.

10-1 Mounting plate KRP4A92 •Fixing plate for DTA109A51

Notes: 1. Installation box for adaptor must be obtained locally.


For Residential indoor unit use 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary. For residential indoor units, an interface adaptor (KRP928BB2S or DTA112BA51) is required for each indoor unit.
3. For residential use only. Cannot be used with other centralised control equipment.
4. A wiring adaptor (KRP413AB1S) is also required for each indoor unit.
Type FDKS-EA FTKS-D
No. FCQ-B FFQ-B FBQ-B
Item FDKS-C(A) FTKS-F
Wired typeNote 1 BRC1C61 —
1 Remote controller
Wireless type BRC7C613W BRC7E531W — — Note 2

Note 3 Note 4
2 Adaptor for wiring KRP1BA57 KRP1BA57 KRP1BA54 —

Note 3 Note 4
3 Wiring adaptor for electrical appendices KRP4AA51 —

4 Installation box for adaptor PCB


KRP4AA53
KRP1B98
KRP4AA53
KRP1BA101 —
Building Management System
5 Remote sensor (for indoor temperature) — KRCS01-1B — No. Item Model No. Function
Wiring adaptor for time clock/remote controller Note 5 1 Basic Hardware intelligent Touch Controller DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.
6 — KRP413AB1S
(Normal open pulse contact/normal open contact)
1-1 intelligent Touch Hardware DIII-NET plus adaptor DCS601A52 •Additional 64 groups (10 outdoor units) is possible.
7 Remote controller loss prevention chain — KKF917A4
1-2 Controller Option PPD DCS002C51 •PPD: Power Proportional Distribution function
Notes: 1. Wiring for wired remote controller should be obtained locally. Software
2. A wireless remote controller is a standard accessory for FDKS and FTKS models. 1-1
1-3 Web DCS004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
3. Installation box for adaptor PCB (KRP1B98) is necessary.
1-4 Electrical box with earth terminal (4 blocks) KJB411A •Wall embedded switch box.
4. Installation box for adaptor PCB (KRP1BA101) is necessary.
5. Time clock and other devices should be obtained locally. 128 units DAM602B52
256 units DAM602B51
Number of
2 Basic Hardware units to be 512 units DAM602B51x2 •Air conditioner management system that can be controlled by personal computers.
connected
768 units DAM602B51x3

intelligent Manager III 1024 units DAM602B51x4

2-1 PPD DAM002A51 •Power Proportional Distribution function

2-2 Option Software Web DAM004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.

2-3 ECONO DAM003A51 •ECONO (Energy saving functions.)

2-4 Optional DIII Ai unit DAM101A51 •External temperature sensor for intelligent Manager III.

2-5 Di unit DEC101A51 •8 pairs based on a pair of On/Off input and abnormality input.

2-6 Dio unit DEC102A51 •4 pairs based on a pair of On/Off input and abnormality input.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-

Communication line
3 *1 Interface for use in BACnet ®
DMS502B51 conditioning systems through BACnet communication.
®

•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
3-1 Optional DIII board DAM411B51 independently.
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
3-2 Optional Di board DAM412B51 independently.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
4 *2 Interface for use in LONWORKS ®
DMS504B51 conditioning systems through LONWORKS communication.
®

5 Parallel interface DPF201A51 •Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
Contact/analogue

Basic unit 4 units.


6 Temperature DPF201A52 •Enables temperature measurement output for 4 groups; 0-5VDC.
signal

measurement units
7 Temperature DPF201A53 •Enables temperature setting input for 16 groups; 0-5VDC.
setting units
8 Unification adaptor for DCS302A52 •Interface between the central monitoring board and central control units.
computerised control
®
Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS is a trademark of Echelon Corporation registered in the United States and other countries.
®

*3. Installation box for adaptor must be obtained locally.

43 44
Memo
Memo
PCV1131

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or VRV indoor units combine with
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion. residential indoor units, all in one system
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

Single outdoor unit series


—suitable for homes, offices, shops, and middle-sized buildings

Catalogue No: VRV3-0315-A


Cooling Only 50 Hz