Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or VRV indoor units combine with
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion. residential indoor units, all in one system
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Specifications...............................page 24
Outdoor units...........................page 38
Control Systems...........................page 39
BP units...................................page 33
Outdoor units...........................page 34
SHOPS
1
HOMES 2
Contents
Specifications...............................page 24
Outdoor units...........................page 38
Control Systems...........................page 39
BP units...................................page 33
Outdoor units...........................page 34
SHOPS
1
HOMES 2
Main Features
BP unit BP unit
Connection unit
VRV indoor units 15 types 73 models Residential indoor units with connection to BP units 7 types 21 models
20 25 32 40 50 63 80 100 125 140 200 250 25 35 50 60 71
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP Type Model Name Rated Capacity 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW
Capacity Index 20 25 31.25 40 50 62.5 80 100 125 140 200 250 Capacity Index 29 40 55 68 79
Ceiling Mounted
Ceiling Mounted
Cassette FXFQ-PVE FCQ-BVE
Cassette
(Round Flow)
Ceiling Mounted Ceiling Mounted
Cassette FXZQ-MVE Cassette FFQ-BV1B
(Compact Multi Flow) (Compact Multi Flow)
Ceiling Mounted
Ceiling Mounted
Cassette FXCQ-MVE FBQ-BV1
Built-in
(Double Flow)
Ceiling Mounted
FXKQ-MAVE FDKS-EAVMB
Cassette Corner (700 mm width type)
Slim Ceiling
Mounted Duct
FXDQ-PBVE FDKS-C(A)VMB
(with drain pump)
(900/1,100 mm width type)
Note: BP units are necessary for residential indoor units. Refer to page 33 for BP unit details.
FXDQ-NBVET (900/1,100 mm width type)
(without drain pump)
FXMQ-PVE
Ceiling Mounted
Duct Outdoor units
FXMQ-MAVE The new VRVIII single outdoor unit series single outdoor unit series
offers 6 models to select from, providing
Ceiling Suspended FXHQ-MAVE the power that suits your needs.
Concealed
Floor Standing FXNQ-MAVE
8, 10 HP 12, 14, 16, 18 HP
Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system. Outdoor unit lineup
VRV indoor units connection unit series
Model Name RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1
71 100 125
Capacity Range 3 HP 4 HP 5 HP
Type Model Name HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
Capacity Index 71 100 125 Capacity
Connection Unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE Range
kW 22.4 kW 28.0 kW 33.5 kW 40.0 kW 45.0 kW 49.0 kW
Ceiling Suspended
Note:
Cassette FXUQ-MAV1 Capacity Index 200 250 300 350 400 450
Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.
3 4
Main Features
BP unit BP unit
Connection unit
VRV indoor units 15 types 73 models Residential indoor units with connection to BP units 7 types 21 models
20 25 32 40 50 63 80 100 125 140 200 250 25 35 50 60 71
Type Model Name Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP 5 HP 6 HP 8 HP 10 HP Type Model Name Rated Capacity 2.5 kW 3.5 kW 5.0 kW 6.0 kW 7.1 kW
Capacity Index 20 25 31.25 40 50 62.5 80 100 125 140 200 250 Capacity Index 29 40 55 68 79
Ceiling Mounted
Ceiling Mounted
Cassette FXFQ-PVE FCQ-BVE
Cassette
(Round Flow)
Ceiling Mounted Ceiling Mounted
Cassette FXZQ-MVE Cassette FFQ-BV1B
(Compact Multi Flow) (Compact Multi Flow)
Ceiling Mounted
Ceiling Mounted
Cassette FXCQ-MVE FBQ-BV1
Built-in
(Double Flow)
Ceiling Mounted
FXKQ-MAVE FDKS-EAVMB
Cassette Corner (700 mm width type)
Slim Ceiling
Mounted Duct
FXDQ-PBVE FDKS-C(A)VMB
(with drain pump)
(900/1,100 mm width type)
Note: BP units are necessary for residential indoor units. Refer to page 33 for BP unit details.
FXDQ-NBVET (900/1,100 mm width type)
(without drain pump)
FXMQ-PVE
Ceiling Mounted
Duct Outdoor units
FXMQ-MAVE The new VRVIII single outdoor unit series single outdoor unit series
offers 6 models to select from, providing
Ceiling Suspended FXHQ-MAVE the power that suits your needs.
Concealed
Floor Standing FXNQ-MAVE
8, 10 HP 12, 14, 16, 18 HP
Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system. Outdoor unit lineup
VRV indoor units connection unit series
Model Name RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1 RSXQ16PY1 RSXQ18PY1
71 100 125
Capacity Range 3 HP 4 HP 5 HP
Type Model Name HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
Capacity Index 71 100 125 Capacity
Connection Unit BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE Range
kW 22.4 kW 28.0 kW 33.5 kW 40.0 kW 45.0 kW 49.0 kW
Ceiling Suspended
Note:
Cassette FXUQ-MAV1 Capacity Index 200 250 300 350 400 450
Note: BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.
3 4
Main Features
Operation sound level selectable from 3 steps for the night mode
Mode 1. Automatic mode
2 Heat exchanger 3 Compact aero box
Set on the outdoor PCB. Time of maximum
temperature is memorised. The low Mode 1. Automatic mode
Thanks to an optimised e-Pass heat exchanger, heat Realises a compact casing by stacking the Inverter and
operating mode will initiate 8 hours*1 after the change effectiveness has been increased, thus control PCBs plus optimising the internal design to suit
peak temperature in the daytime, and normal contributing to a high COP. airflow speed. This achieves low noise and reduces the
operation will resume 10 hours*2 after that. power required by the large-diameter fanned outdoor unit.
Operation sound dB(A) Load % Capacity %
The operation sound level for the night mode Peak in outdoor temperature (For 10 HP outdoor unit)
100
can be selected from 55 dB(A) (Step 1),
50 dB(A) (Step 2) and 45 dB(A) (Step 3). 4 Smooth sine wave DC Inverter 5 DC fan motor
8 hrs 10 hrs
(Initial setting) (Initial setting)
50 • Efficiency improvement by approximately 40% especially at
By adoption of the Sine Wave, which smoothes the
rotation of the motor, operation efficiency is improved low speed.
Mode 2. Manual mode
sharply. DC fan motor DC motor efficiency
Starting time and ending time can be input. 0 Night Mode structure (comparison with AC motor)
(An external control adaptor for outdoor unit, 58 100
Step 1 max. - 3dB(A) Step 1: 55 dB(A) DC motor
DTA104A53/61/62, and a locally obtained 55 80
Efficiency (%)
timer are necessary.) Step 2 max. - 8dB(A) Step 2: 50 dB(A)
50 60 Approx.
40%
increase
Mode 3. Combined mode Step 3 max. - 13dB(A) Step 3: 45 dB(A) 40
45 AC motor
Combinations of modes 1 and 2 can be used Night mode starts Night mode ends 20
depending on your needs. 8:00 12:00 16:00 20:00 0:00 4:00 8:00
0
200 300 400 500 600 700 800 900 1000
*1. Initial setting. Can be selected from 6, 8 and 10 hours. Notes: • This function is available in setting at site. Motor speed (rpm)
*2. Initial setting. Can be selected from 8, 9 and 10 hours. • The relationship of outdoor temperature (load) and time shown in the Note: Data are based on studies conducted under controlled conditions
graph is just an example. at a Daikin laboratory.
The capacity reduction rate differs depending on the operation sound level step selected.
5 6
Main Features
Operation sound level selectable from 3 steps for the night mode
Mode 1. Automatic mode
2 Heat exchanger 3 Compact aero box
Set on the outdoor PCB. Time of maximum
temperature is memorised. The low Mode 1. Automatic mode
Thanks to an optimised e-Pass heat exchanger, heat Realises a compact casing by stacking the Inverter and
operating mode will initiate 8 hours*1 after the change effectiveness has been increased, thus control PCBs plus optimising the internal design to suit
peak temperature in the daytime, and normal contributing to a high COP. airflow speed. This achieves low noise and reduces the
operation will resume 10 hours*2 after that. power required by the large-diameter fanned outdoor unit.
Operation sound dB(A) Load % Capacity %
The operation sound level for the night mode Peak in outdoor temperature (For 10 HP outdoor unit)
100
can be selected from 55 dB(A) (Step 1),
50 dB(A) (Step 2) and 45 dB(A) (Step 3). 4 Smooth sine wave DC Inverter 5 DC fan motor
8 hrs 10 hrs
(Initial setting) (Initial setting)
50 • Efficiency improvement by approximately 40% especially at
By adoption of the Sine Wave, which smoothes the
rotation of the motor, operation efficiency is improved low speed.
Mode 2. Manual mode
sharply. DC fan motor DC motor efficiency
Starting time and ending time can be input. 0 Night Mode structure (comparison with AC motor)
(An external control adaptor for outdoor unit, 58 100
Step 1 max. - 3dB(A) Step 1: 55 dB(A) DC motor
DTA104A53/61/62, and a locally obtained 55 80
Efficiency (%)
timer are necessary.) Step 2 max. - 8dB(A) Step 2: 50 dB(A)
50 60 Approx.
40%
increase
Mode 3. Combined mode Step 3 max. - 13dB(A) Step 3: 45 dB(A) 40
45 AC motor
Combinations of modes 1 and 2 can be used Night mode starts Night mode ends 20
depending on your needs. 8:00 12:00 16:00 20:00 0:00 4:00 8:00
0
200 300 400 500 600 700 800 900 1000
*1. Initial setting. Can be selected from 6, 8 and 10 hours. Notes: • This function is available in setting at site. Motor speed (rpm)
*2. Initial setting. Can be selected from 8, 9 and 10 hours. • The relationship of outdoor temperature (load) and time shown in the Note: Data are based on studies conducted under controlled conditions
graph is just an example. at a Daikin laboratory.
The capacity reduction rate differs depending on the operation sound level step selected.
5 6
Main Features
a
b c d
e f g h i
First indoor branch
VRV indoor units
Max.
50 m k Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
Max. Refer to page 34 for the maximum number of connectable indoor units.
j 15 m
When a mixed combination of VRV and Colours in the diagram below are merely for identifying
pipes referenced with symbols such as a .
residential indoor units is connected
7 8
Main Features
a
b c d
e f g h i
First indoor branch
VRV indoor units
Max.
50 m k Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.
Max. Refer to page 34 for the maximum number of connectable indoor units.
j 15 m
When a mixed combination of VRV and Colours in the diagram below are merely for identifying
pipes referenced with symbols such as a .
residential indoor units is connected
7 8
Indoor Unit Lineup
VRV Indoor Units
Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type
FXZQ-M 20/25 32 40 50
There are areas of There are much fewer (H/L) 240 V 32/26 34/28 37/29 42/35
uneven temperature. areas of uneven temperature.
* As of April 2004, the release date for Japan.
All models are lighter than the conventional ones. Comfortable airflow
Ex: Models FXFQ25P-50P are 4.5 kg lighter
1 Wide discharge angle: 0° to 60°
(reduced from 24 kg to 19.5 kg).
Auto swing Fixed angles: 5 levels
Drain pump is equipped as
standard accessory, and the
850 mm
lift height has been improved 0° 0° 0° 0°
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.
9 10
Indoor Unit Lineup
VRV Indoor Units
Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Cassette (Compact Multi Flow) Type
FXZQ-M 20/25 32 40 50
There are areas of There are much fewer (H/L) 240 V 32/26 34/28 37/29 42/35
uneven temperature. areas of uneven temperature.
* As of April 2004, the release date for Japan.
All models are lighter than the conventional ones. Comfortable airflow
Ex: Models FXFQ25P-50P are 4.5 kg lighter
1 Wide discharge angle: 0° to 60°
(reduced from 24 kg to 19.5 kg).
Auto swing Fixed angles: 5 levels
Drain pump is equipped as
standard accessory, and the
850 mm
lift height has been improved 0° 0° 0° 0°
Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.
9 10
Indoor Unit Lineup
VRV Indoor Units
Ceiling Mounted Cassette (Double Flow) Type Ceiling Mounted Cassette Corner Type
Downward discharge
500 mm
Designed with higher airflow suitable for
high ceiling application up to 3 metres. Air discharge grille (Option)
swing mechanism realises even distribution Two types of optional high-efficiency filter are Main body
of airflow and room temperature. available (65% and 95%, colourimetric method).
11 12
Indoor Unit Lineup
VRV Indoor Units
Ceiling Mounted Cassette (Double Flow) Type Ceiling Mounted Cassette Corner Type
Downward discharge
500 mm
Designed with higher airflow suitable for
high ceiling application up to 3 metres. Air discharge grille (Option)
swing mechanism realises even distribution Two types of optional high-efficiency filter are Main body
of airflow and room temperature. available (65% and 95%, colourimetric method).
11 12
Indoor Unit Lineup
VRV Indoor Units
FXAQ20MA/FXAQ25MA
FXHQ32MA / FXHQ63MA
FXAQ32MA/FXAQ40MA
FXHQ100MA
FXAQ50MA/FXAQ63MA
* Remote controllers are an optional accessory. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details. Refer to page 39 for remote controller details.
Turbulent flow Quiet stream fan Drain pan and air filter can be kept clean by
is produced
Straightening vane
mildew-proof polystyrene.
Low operation sound level (dB(A)) Washable grille, the front grille can be easily
FXHQ-MA 32 63 100 removed for washing.
Sound level
36/31 39/34 45/37
(H/L)
Auto-swing realises efficiency of air
distribution. The louvre closes automatically
Installation is easy
when the unit stops.
Drain pump kit (option) can be easily
incorporated.
5 steps of discharge angle can be set by
600 mm
remote controller.
Maintenance is easy
Discharge angle is automatically set at the Drain pump kit is available as optional
Drain pump kit Non-dew Flap with no implanted bristles
(built inside main unit) Bristle-free Flap minimises
same angle as the previous operation when accessory, which lifts the drain 1,000 mm from
contamination and makes restarting. (Initial setting: 10˚ for cooling) the bottom of the unit.
cleaning simpler.
Wide air discharge openings produce a Non-dew Flap
Height of drain-up
Easy-to-clean flat design Flexible installation
spreading 100° airflow.
Maintenance is easier because everything can Drain pipe can be fitted to from either left or
be performed from below the unit. right sides.
1,000 mm
15 16
Indoor Unit Lineup
VRV Indoor Units
FXAQ20MA/FXAQ25MA
FXHQ32MA / FXHQ63MA
FXAQ32MA/FXAQ40MA
FXHQ100MA
FXAQ50MA/FXAQ63MA
* Remote controllers are an optional accessory. * Remote controllers are an optional accessory.
Refer to page 39 for remote controller details. Refer to page 39 for remote controller details.
Turbulent flow Quiet stream fan Drain pan and air filter can be kept clean by
is produced
Straightening vane
mildew-proof polystyrene.
Low operation sound level (dB(A)) Washable grille, the front grille can be easily
FXHQ-MA 32 63 100 removed for washing.
Sound level
36/31 39/34 45/37
(H/L)
Auto-swing realises efficiency of air
distribution. The louvre closes automatically
Installation is easy
when the unit stops.
Drain pump kit (option) can be easily
incorporated.
5 steps of discharge angle can be set by
600 mm
remote controller.
Maintenance is easy
Discharge angle is automatically set at the Drain pump kit is available as optional
Drain pump kit Non-dew Flap with no implanted bristles
(built inside main unit) Bristle-free Flap minimises
same angle as the previous operation when accessory, which lifts the drain 1,000 mm from
contamination and makes restarting. (Initial setting: 10˚ for cooling) the bottom of the unit.
cleaning simpler.
Wide air discharge openings produce a Non-dew Flap
Height of drain-up
Easy-to-clean flat design Flexible installation
spreading 100° airflow.
Maintenance is easier because everything can Drain pipe can be fitted to from either left or
be performed from below the unit. right sides.
1,000 mm
15 16
Indoor Unit Lineup
VRV Indoor Units
Connection unit series indoor units
Floor Standing Type Ceiling Suspended Cassette Type
as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Wall hanging Floor installation
FXNQ20MA / FXNQ25MA
FXNQ32MA/FXNQ40MA
FXNQ50MA / FXNQ63MA
Designed to be concealed in the perimeter skirting-wall Connection unit Connection unit is the device for connecting above indoor unit to VRV III.
BEVQ71MA/BEVQ100MA/BEVQ125MA
The unit is concealed in skirting-wall of perimeter, that enables
Refrigerant piping layout External wiring layout *1 Maximum piping length
to create high class interior design. Connection unit for indoor unit Model between the BEV unit
and the indoor unit.
The connecting port faces VRV series FXUQ-MA 5m
outdoor unit
Notes:
downward, greatly facilitating BEVQ-MA Super wiring ( DIII-NET ) • When connecting centralised-control device, it is
Liquid Gas pipe necessary to install an interface adaptor for an
on-site piping work. Connecting pipe Single-phase 220-240 V
power supply indoor unit (DTA102A52).
port • Connection unit BEVQ-MA is necessary for each
Indoor unit indoor unit.
A long-life filter (maintenance Refrigerant
• The refrigerant piping height difference between
the indoor units and the BEV unit must be within
free up to one year*) is equipped piping 4 m.
• The BEV unit must be installed within a
as standard accessory. Piping length*1 Indoor unit maximum height difference between indoor units
of 15 m.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Applies also to Floor Standing type (FXLQ-MA).
Remote controller • Branching of the refrigerant piping is not
possible downstream of the BEV unit.
17 18
Indoor Unit Lineup
VRV Indoor Units
Connection unit series indoor units
Floor Standing Type Ceiling Suspended Cassette Type
as standard accessory.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Wall hanging Floor installation
FXNQ20MA / FXNQ25MA
FXNQ32MA/FXNQ40MA
FXNQ50MA / FXNQ63MA
Designed to be concealed in the perimeter skirting-wall Connection unit Connection unit is the device for connecting above indoor unit to VRV III.
BEVQ71MA/BEVQ100MA/BEVQ125MA
The unit is concealed in skirting-wall of perimeter, that enables
Refrigerant piping layout External wiring layout *1 Maximum piping length
to create high class interior design. Connection unit for indoor unit Model between the BEV unit
and the indoor unit.
The connecting port faces VRV series FXUQ-MA 5m
outdoor unit
Notes:
downward, greatly facilitating BEVQ-MA Super wiring ( DIII-NET ) • When connecting centralised-control device, it is
Liquid Gas pipe necessary to install an interface adaptor for an
on-site piping work. Connecting pipe Single-phase 220-240 V
power supply indoor unit (DTA102A52).
port • Connection unit BEVQ-MA is necessary for each
Indoor unit indoor unit.
A long-life filter (maintenance Refrigerant
• The refrigerant piping height difference between
the indoor units and the BEV unit must be within
free up to one year*) is equipped piping 4 m.
• The BEV unit must be installed within a
as standard accessory. Piping length*1 Indoor unit maximum height difference between indoor units
of 15 m.
* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3 Applies also to Floor Standing type (FXLQ-MA).
Remote controller • Branching of the refrigerant piping is not
possible downstream of the BEV unit.
17 18
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units
Ceiling Mounted Cassette Type Ceiling Mounted Cassette (Compact Multi Flow) Type
FCQ35B/FCQ50B/FCQ60B/FCQ71B FFQ25B/FFQ35B/FFQ50B/FFQ60B
Min. 245 mm
Drain pump is equipped as (Set on site) 35° between 0° and 35° 35° between 0° and 35°
19 20
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units
Ceiling Mounted Cassette Type Ceiling Mounted Cassette (Compact Multi Flow) Type
FCQ35B/FCQ50B/FCQ60B/FCQ71B FFQ25B/FFQ35B/FFQ50B/FFQ60B
Min. 245 mm
Drain pump is equipped as (Set on site) 35° between 0° and 35° 35° between 0° and 35°
19 20
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units
FBQ60B/FBQ71B
FDKS25EA/FDKS35EA
FDKS25CA/FDKS35CA/FDKS50C/FDKS60C
Option
Note: Remote controller
cables not included. Standard accessory
Cables should be Note: Remote controllers
obtained locally. other than the standard
accessory wireless remote
controller cannot be used.
Flexible air discharge unit to fit various forms of space Slim and smooth design suits your shallow ceiling
The indoor unit can be installed in rooms with as Options 7 High-performance filter Models in the FDKS-EA series are only 700 mm Low operation sound level (H/L/SL)
little as 350 mm between the drop ceiling and 1 Decorative panel 8 Inspection panel
in width and 21 kg in weight, so are easily
ceiling slab. It also works with both flexible and
2 Air discharge opening adaptor 9 Rear intake blocking pad FDKS25 FDKS35 FDKS50 FDKS60
3 Canvas bellows and air intake panel 10 Air discharge opening flange installed in limited spaces. Just 200 mm in height,
Flexible duct Rear intake filter chamber
ordinary ducts. 4
Air discharge grille
11
all models can be installed in rooms with as little 35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
5 12 Branch duct
6 Air discharge chamber 13 Low-draft filter chamber
as 240 mm depth between the drop ceiling and
ceiling slab, making them ideal for even shallow
Home Leave Operation prevents large rises or
Standard installation examples With high-efficiency filter ceilings.
In crawl space With canvas bellows and air intake panel (sold separately) falls in the indoor temperature by continuing
2 Air conditioner
6 2 Air conditioner 2 Air conditioner 4 540 mm or more FDKS-EA operation* while you are sleeping or out of your
4 350 mm or more
4 6
13 7
Great for
6
Long-life filter 3
425 mm or more 3
home. This means that an air-conditioned
5 1
5 1 hotel use!
Air blow
Air intake Long-life filter 5
Air blow Air intake
1 Air blow Air intake welcome awaits when you wake or return. It also
45 mm
means that the indoor temperature can quickly
Ceiling return Ceiling return with high-efficiency filter With ordinary ducts
return to your favourite comfort setting.
Ordinary duct Ordinary duct
2 Air conditioner 2 Air conditioner 540 mm or more Air conditioner
(procured locally) (procured locally) * Home Leave Operation can be selected for any temperature from 18 to
6
4
Long-life filter Air intake
450 mm or more
6 4 11
Air intake
10
460 mm or more
200 mm 32˚C for cooling operation and 10 to 30˚C for heating operation.
9 7 9
* Home Leave Operation function must be set using the remote controller
5 8
5 8
8
Air intake
Only 700 mm when going to sleep or leaving the house, and after waking up or returning
Air blow Air blow
Air blow home.
Notes:
Option 1. To prevent an increase in operation noise, avoid
installing the air suction grille directly below the
suction chamber.
Low operation sound level (H/L)
2. Grilles, piping connections, ducts, and installation
parts should be obtained locally. Slim Ceiling
Mounted Duct type FDKS models do not have
FBQ60B FBQ71B Suction grille (KDGF19A45) drain-up pumps.
3. The signal receiver unit must be located near the
Signals from the wireless remote controller are air suction inlet, because the unit includes a
L-shaped room U-shaped room Long room 41/35 dB (A) 41/35 dB (A) transmitted to the signal receiver.
sensor that detects room temperature.
21 22
Indoor Unit Lineup
Residential Indoor Units with connection
to BP units
FBQ60B/FBQ71B
FDKS25EA/FDKS35EA
FDKS25CA/FDKS35CA/FDKS50C/FDKS60C
Option
Note: Remote controller
cables not included. Standard accessory
Cables should be Note: Remote controllers
obtained locally. other than the standard
accessory wireless remote
controller cannot be used.
Flexible air discharge unit to fit various forms of space Slim and smooth design suits your shallow ceiling
The indoor unit can be installed in rooms with as Options 7 High-performance filter Models in the FDKS-EA series are only 700 mm Low operation sound level (H/L/SL)
little as 350 mm between the drop ceiling and 1 Decorative panel 8 Inspection panel
in width and 21 kg in weight, so are easily
ceiling slab. It also works with both flexible and
2 Air discharge opening adaptor 9 Rear intake blocking pad FDKS25 FDKS35 FDKS50 FDKS60
3 Canvas bellows and air intake panel 10 Air discharge opening flange installed in limited spaces. Just 200 mm in height,
Flexible duct Rear intake filter chamber
ordinary ducts. 4
Air discharge grille
11
all models can be installed in rooms with as little 35/31/29 dB (A) 35/31/29 dB (A) 37/33/31 dB (A) 38/34/32 dB (A)
5 12 Branch duct
6 Air discharge chamber 13 Low-draft filter chamber
as 240 mm depth between the drop ceiling and
ceiling slab, making them ideal for even shallow
Home Leave Operation prevents large rises or
Standard installation examples With high-efficiency filter ceilings.
In crawl space With canvas bellows and air intake panel (sold separately) falls in the indoor temperature by continuing
2 Air conditioner
6 2 Air conditioner 2 Air conditioner 4 540 mm or more FDKS-EA operation* while you are sleeping or out of your
4 350 mm or more
4 6
13 7
Great for
6
Long-life filter 3
425 mm or more 3
home. This means that an air-conditioned
5 1
5 1 hotel use!
Air blow
Air intake Long-life filter 5
Air blow Air intake
1 Air blow Air intake welcome awaits when you wake or return. It also
45 mm
means that the indoor temperature can quickly
Ceiling return Ceiling return with high-efficiency filter With ordinary ducts
return to your favourite comfort setting.
Ordinary duct Ordinary duct
2 Air conditioner 2 Air conditioner 540 mm or more Air conditioner
(procured locally) (procured locally) * Home Leave Operation can be selected for any temperature from 18 to
6
4
Long-life filter Air intake
450 mm or more
6 4 11
Air intake
10
460 mm or more
200 mm 32˚C for cooling operation and 10 to 30˚C for heating operation.
9 7 9
* Home Leave Operation function must be set using the remote controller
5 8
5 8
8
Air intake
Only 700 mm when going to sleep or leaving the house, and after waking up or returning
Air blow Air blow
Air blow home.
Notes:
Option 1. To prevent an increase in operation noise, avoid
installing the air suction grille directly below the
suction chamber.
Low operation sound level (H/L)
2. Grilles, piping connections, ducts, and installation
parts should be obtained locally. Slim Ceiling
Mounted Duct type FDKS models do not have
FBQ60B FBQ71B Suction grille (KDGF19A45) drain-up pumps.
3. The signal receiver unit must be located near the
Signals from the wireless remote controller are air suction inlet, because the unit includes a
L-shaped room U-shaped room Long room 41/35 dB (A) 41/35 dB (A) transmitted to the signal receiver.
sensor that detects room temperature.
21 22
Indoor Unit Lineup Specifications
Residential Indoor Units with connection
to BP units VRV Indoor Units
and Horizontal Result certificate: No. 012553-1 and 012553-2 Weight kg 2.7 2.7 2.7 2.7 2.7
Testing organisation: Japan Spinners Inspecting Foundation
Auto-Swing to Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
circulate air to every • Equivalent piping length: 7.5 m
• Level difference: 0 m
part of a room for •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
uniform cooling of even During actual operation, these values are normally somewhat higher as a result of ambient conditions.
large spaces.
* This function is available for A uniform temperature
FTKS50/60/71F. is achieved throughout
the entire room.
23 24
Indoor Unit Lineup Specifications
Residential Indoor Units with connection
to BP units VRV Indoor Units
and Horizontal Result certificate: No. 012553-1 and 012553-2 Weight kg 2.7 2.7 2.7 2.7 2.7
Testing organisation: Japan Spinners Inspecting Foundation
Auto-Swing to Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
circulate air to every • Equivalent piping length: 7.5 m
• Level difference: 0 m
part of a room for •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
uniform cooling of even During actual operation, these values are normally somewhat higher as a result of ambient conditions.
large spaces.
* This function is available for A uniform temperature
FTKS50/60/71F. is achieved throughout
the entire room.
23 24
Specifications
VRV Indoor Units
Ceiling Mounted Cassette (Double Flow) Type Slim Ceiling Mounted Duct Type (700 mm width type)
with
MODEL FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE drain pump FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
MODEL without
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET
drain pump
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 8,000 12,500 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 31,700 49,500 kcal/h(*1) 2,000 2,500 3,200
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 9.3 14.5
kW Btu/h(*1) 7,800 9,900 12,600
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0 Cooling capacity
(*1) 2.3 2.9 3.7
Power consumption kW 0.077 0.092 0.092 0.130 0.130 0.161 0.209 0.256 kW
(*2) 2.2 2.8 3.6
Casing Galvanised steel plate
Power consumption
m3/min 7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25 kW 0.086 0.086 0.089
(FXDQ-PBVE)
Airflow rate (H/L)
cfm 247/177 318/230 318/230 424/318 424/318 582/459 918/741 1,165/883 Power consumption
kW 0.067 0.067 0.070
(FXDQ-PBVET)
220 V 32/27 34/28 34/28 34/29 34/29 37/32 39/34 44/38
Sound level (H/L) dB(A) Casing Galvanised steel plate
240 V 34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40
m3/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Dimensions (HXWXD) mm 305X775X600 305X775X600 305X775X600 305X990X600 305X990X600 305X1,175X600 305X1,665X600 305X1,665X600 Airflow rate (HH/H/L)
cfm 282/254/226 282/254/226 282/254/226
Machine weight kg 26.0 26.0 26.0 31.0 32.0 35.0 47.0 48.0
External static pressure Pa 30-10 1
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 9.5 9.5
Piping Sound level (HH/H/L) 2 3 dB(A) 33/31/29 33/31/29 33/31/29
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9
Dimensions (HXWXD) mm 200X700X620 200X700X620 200X700X620
Drain VP25 (External Dia, 32/Internal Dia, 25)
Machine weight kg 23.0 23.0 23.0
Model BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
Liquid (Flare) 6.4 6.4 6.4
Panel Colour White (10Y9/0.5) Piping
mm
(Option) Dimensions (HXWXD) mm 53X1,030X680 53X1,030X680 53X1,030X680 53X1,245X680 53X1,245X680 53X1,430X680 53X1,920X680 53X1,920X680 connections Gas (Flare) 12.7 12.7 12.7
Drain VP20 (External Dia, 26/Internal Dia, 20)
Weight kg 8.0 8.0 8.0 8.5 8.5 9.5 12.0 12.0
Ceiling Mounted Cassette Corner Type Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
MODEL FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE with
drain pump FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz MODEL without
kcal/h (*1) 2,500 3,200 4,000 6,300 drain pump FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
Btu/h (*1) 9,900 12,600 16,000 24,900 Power supply 1-phase, 220 -240 V/220 V, 50/60 Hz
Cooling capacity
(*1) 2.9 3.7 4.7 7.3 kcal/h (*1) 4,000 5,000 6,300
kW
(*2) 2.8 3.6 4.5 7.1 Btu/h(*1) 16,000 19,800 24,900
Cooling capacity
Power consumption kW 0.066 0.066 0.076 0.105 (*1) 4.7 5.8 7.3
kW
Casing Galvanised steel plate (*2) 4.5 5.6 7.1
m3/min 11/9 11/9 13/10 18/15 Power consumption
Airflow rate (H/L) kW 0.160 0.165 0.181
cfm 388/318 388/318 459/353 635/530 (FXDQ-NBVE)
220 V 38/33 38/33 40/34 42/37 Power consumption
Sound level (H/L) kW 0.147 0.152 0.168
dB(A) (FXDQ-NBVET)
240 V 40/35 40/35 42/36 44/39
Casing Galvanised steel plate
Dimensions (HXWXD) mm 215X1,110X710 215X1,110X710 215X1,110X710 215X1,310X710
Machine weight kg 31.0 31.0 31.0 34.0 m3/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Airflow rate (HH/H/L)
Liquid (Flare) 6.4 6.4 6.4 9.5 cfm 371/335/300 441/388/353 583/512/459
Piping External static pressure Pa 44-15 1
Gas (Flare) mm 12.7 12.7 12.7 15.9
connections
Drain VP25 (External Dia, 32/Internal Dia, 25) Sound level (HH/H/L) 2 3 dB(A) 34/32/30 35/33/31 36/34/32
Model BYK45FJW1 BYK71FJW1 Dimensions (HXWXD) mm 200X900X620 200X900X620 200X1,100X620
Panel Colour White (10Y9/0.5) Machine weight kg 27.0 28.0 31.0
(Option) Dimensions (HXWXD) mm 70X1,240X800 70X1,240X800 70X1,240X800 70X1,440X800
Liquid (Flare) 6.4 6.4 9.5
Weight kg 8.5 8.5 8.5 9.5 Piping
mm
Note: Specifications are based on the following conditions; connections Gas (Flare) 12.7 12.7 15.9
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Drain VP20 (External Dia, 26/Internal Dia, 20)
•Equivalent piping length: 7.5 m • Level difference: 0 m
Note: Specifications are based on the following conditions;
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
3: Values are based on the following conditions: external static pressure of 10 Pa.
• Equivalent piping length: 7.5 m • Level difference: 0 m
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
25 26
Specifications
VRV Indoor Units
Ceiling Mounted Cassette (Double Flow) Type Slim Ceiling Mounted Duct Type (700 mm width type)
with
MODEL FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE drain pump FXDQ20PBVE FXDQ25PBVE FXDQ32PBVE
MODEL without
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz FXDQ20PBVET FXDQ25PBVET FXDQ32PBVET
drain pump
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 8,000 12,500 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 31,700 49,500 kcal/h(*1) 2,000 2,500 3,200
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 9.3 14.5
kW Btu/h(*1) 7,800 9,900 12,600
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0 Cooling capacity
(*1) 2.3 2.9 3.7
Power consumption kW 0.077 0.092 0.092 0.130 0.130 0.161 0.209 0.256 kW
(*2) 2.2 2.8 3.6
Casing Galvanised steel plate
Power consumption
m3/min 7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25 kW 0.086 0.086 0.089
(FXDQ-PBVE)
Airflow rate (H/L)
cfm 247/177 318/230 318/230 424/318 424/318 582/459 918/741 1,165/883 Power consumption
kW 0.067 0.067 0.070
(FXDQ-PBVET)
220 V 32/27 34/28 34/28 34/29 34/29 37/32 39/34 44/38
Sound level (H/L) dB(A) Casing Galvanised steel plate
240 V 34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40
m3/min 8.0/7.2/6.4 8.0/7.2/6.4 8.0/7.2/6.4
Dimensions (HXWXD) mm 305X775X600 305X775X600 305X775X600 305X990X600 305X990X600 305X1,175X600 305X1,665X600 305X1,665X600 Airflow rate (HH/H/L)
cfm 282/254/226 282/254/226 282/254/226
Machine weight kg 26.0 26.0 26.0 31.0 32.0 35.0 47.0 48.0
External static pressure Pa 30-10 1
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4 9.5 9.5 9.5
Piping Sound level (HH/H/L) 2 3 dB(A) 33/31/29 33/31/29 33/31/29
mm
connections Gas (Flare) 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9
Dimensions (HXWXD) mm 200X700X620 200X700X620 200X700X620
Drain VP25 (External Dia, 32/Internal Dia, 25)
Machine weight kg 23.0 23.0 23.0
Model BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1
Liquid (Flare) 6.4 6.4 6.4
Panel Colour White (10Y9/0.5) Piping
mm
(Option) Dimensions (HXWXD) mm 53X1,030X680 53X1,030X680 53X1,030X680 53X1,245X680 53X1,245X680 53X1,430X680 53X1,920X680 53X1,920X680 connections Gas (Flare) 12.7 12.7 12.7
Drain VP20 (External Dia, 26/Internal Dia, 20)
Weight kg 8.0 8.0 8.0 8.5 8.5 9.5 12.0 12.0
Ceiling Mounted Cassette Corner Type Slim Ceiling Mounted Duct Type (900/1,100 mm width type)
MODEL FXKQ25MAVE FXKQ32MAVE FXKQ40MAVE FXKQ63MAVE with
drain pump FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz MODEL without
kcal/h (*1) 2,500 3,200 4,000 6,300 drain pump FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET
Btu/h (*1) 9,900 12,600 16,000 24,900 Power supply 1-phase, 220 -240 V/220 V, 50/60 Hz
Cooling capacity
(*1) 2.9 3.7 4.7 7.3 kcal/h (*1) 4,000 5,000 6,300
kW
(*2) 2.8 3.6 4.5 7.1 Btu/h(*1) 16,000 19,800 24,900
Cooling capacity
Power consumption kW 0.066 0.066 0.076 0.105 (*1) 4.7 5.8 7.3
kW
Casing Galvanised steel plate (*2) 4.5 5.6 7.1
m3/min 11/9 11/9 13/10 18/15 Power consumption
Airflow rate (H/L) kW 0.160 0.165 0.181
cfm 388/318 388/318 459/353 635/530 (FXDQ-NBVE)
220 V 38/33 38/33 40/34 42/37 Power consumption
Sound level (H/L) kW 0.147 0.152 0.168
dB(A) (FXDQ-NBVET)
240 V 40/35 40/35 42/36 44/39
Casing Galvanised steel plate
Dimensions (HXWXD) mm 215X1,110X710 215X1,110X710 215X1,110X710 215X1,310X710
Machine weight kg 31.0 31.0 31.0 34.0 m3/min 10.5/9.5/8.5 12.5/11.0/10.0 16.5/14.5/13.0
Airflow rate (HH/H/L)
Liquid (Flare) 6.4 6.4 6.4 9.5 cfm 371/335/300 441/388/353 583/512/459
Piping External static pressure Pa 44-15 1
Gas (Flare) mm 12.7 12.7 12.7 15.9
connections
Drain VP25 (External Dia, 32/Internal Dia, 25) Sound level (HH/H/L) 2 3 dB(A) 34/32/30 35/33/31 36/34/32
Model BYK45FJW1 BYK71FJW1 Dimensions (HXWXD) mm 200X900X620 200X900X620 200X1,100X620
Panel Colour White (10Y9/0.5) Machine weight kg 27.0 28.0 31.0
(Option) Dimensions (HXWXD) mm 70X1,240X800 70X1,240X800 70X1,240X800 70X1,440X800
Liquid (Flare) 6.4 6.4 9.5
Weight kg 8.5 8.5 8.5 9.5 Piping
mm
Note: Specifications are based on the following conditions; connections Gas (Flare) 12.7 12.7 15.9
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. Drain VP20 (External Dia, 26/Internal Dia, 20)
•Equivalent piping length: 7.5 m • Level difference: 0 m
Note: Specifications are based on the following conditions;
• Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting
(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.)
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
3: Values are based on the following conditions: external static pressure of 10 Pa.
• Equivalent piping length: 7.5 m • Level difference: 0 m
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
• Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
25 26
Specifications
VRV Indoor Units
Sound level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30 39/37/35 41/39/37 Sound level 220 V 48/45 48/45
dB(A)
(H/L) 240 V 49/46 49/46
Dimensions (HXWXD) mm 300X550X700 300X550X700 300X550X700 300X700X700 300X1,000X700
Dimensions (HXWXD) mm 470X1,380X1,100 470X1,380X1,100
Machine weight kg 25.0 25.0 25.0 28.0 36.0
Machine weight kg 137.0 137.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4
Piping Liquid (Flare) 9.5 9.5
connections Gas (Flare) mm 12.7 12.7 12.7 12.7 12.7
Piping
mm
Drain VP25 (External Dia, 32/Internal Dia, 25) connections Gas (Brazing) 19.1 22.2
Drain PS1B
27 28
Specifications
VRV Indoor Units
Sound level (HH/H/L) dB(A) 33/31/29 33/31/29 34/32/30 39/37/35 41/39/37 Sound level 220 V 48/45 48/45
dB(A)
(H/L) 240 V 49/46 49/46
Dimensions (HXWXD) mm 300X550X700 300X550X700 300X550X700 300X700X700 300X1,000X700
Dimensions (HXWXD) mm 470X1,380X1,100 470X1,380X1,100
Machine weight kg 25.0 25.0 25.0 28.0 36.0
Machine weight kg 137.0 137.0
Liquid (Flare) 6.4 6.4 6.4 6.4 6.4
Piping Liquid (Flare) 9.5 9.5
connections Gas (Flare) mm 12.7 12.7 12.7 12.7 12.7
Piping
mm
Drain VP25 (External Dia, 32/Internal Dia, 25) connections Gas (Brazing) 19.1 22.2
Drain PS1B
27 28
Specifications
VRV Indoor Units
Indoor unit
Airflow rate (H/L)
cfm 671/494 1,024/741 1,130/812
Sound level (H/L) 230 V dB(A) 40/35 43/38 44/39
Dimensions (HXWXD) mm 165X895X895 230X895X895 230X895X895
Floor Standing Type/Concealed Floor Standing Type Machine weight kg 25 31 31
Liquid 9.5 (Flare)
FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE Piping
MODEL connections
Gas mm 15.9 (Flare)
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Drain VP 20 (External Dia. 26/Internal Dia. 20)
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Note: Specifications are based on the following conditions;
• Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
FXLQ • Equivalent piping length: 7.5 m
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 • Level difference: 0 m
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
kW • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre.
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 During actual operation, these values are normally somewhat higher as a result of ambient conditions.
29 30
Specifications
VRV Indoor Units
Indoor unit
Airflow rate (H/L)
cfm 671/494 1,024/741 1,130/812
Sound level (H/L) 230 V dB(A) 40/35 43/38 44/39
Dimensions (HXWXD) mm 165X895X895 230X895X895 230X895X895
Floor Standing Type/Concealed Floor Standing Type Machine weight kg 25 31 31
Liquid 9.5 (Flare)
FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE Piping
MODEL connections
Gas mm 15.9 (Flare)
FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Drain VP 20 (External Dia. 26/Internal Dia. 20)
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Note: Specifications are based on the following conditions;
• Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.
kcal/h (*1) 2,000 2,500 3,200 4,000 5,000 6,300 (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.
FXLQ • Equivalent piping length: 7.5 m
Btu/h (*1) 7,800 9,900 12,600 16,000 19,800 24,900 • Level difference: 0 m
Cooling capacity
(*1) 2.3 2.9 3.7 4.7 5.8 7.3 • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)
kW • Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre.
(*2) 2.2 2.8 3.6 4.5 5.6 7.1 During actual operation, these values are normally somewhat higher as a result of ambient conditions.
29 30
Specifications
Residential Indoor Units with connection
to BP units
Residential indoor units with connection to BP units Ceiling Mounted Built-in Type
Residential indoor units can be connected to the VRVIII single outdoor unit series by BP units. MODEL FBQ60BV1 FBQ71BV1
Power supply 1-phase, 220-240 V, 50 Hz
Ceiling Mounted Cassette Type Airflow rates (H) m3/min (cfm) 17.0 (600) 19.0 (670)
Sound levels (H/L)* dB (A) 41/35
MODEL FCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE Fan speed 2 steps
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Temperature control Microcomputer control
Airflow rates (H) m3/min (cfm) 14.0 (494) 15.0 (530) 19.0 (671) Dimensions (HXWXD) mm 300X1,000X800
Sound levels (H/L)* dB (A) 33/29 35/30 Machine weight kg 41
Fan speed 2 steps Liquid (Flare) ø6.4 ø9.5
Piping
Temperature control Microcomputer control mm
connections Gas (Flare) ø12.7 ø15.9
Dimensions (HXWXD) mm 230X840X840 Drain I.D ø25XO.D ø32
Machine weight kg 24 Heat insulation Both liquid and gas pipes
Liquid (Flare) ø6.4 ø9.5 Model BYBS71DJW1
Piping
mm ø9.5 ø12.7 ø15.9 Panel
connections Gas (Flare) Colour White
(Option)
Drain I.D ø25XO.D ø32 Dimensions (HXWXD) mm 55X1,100X500
Heat insulation Both liquid and gas pipes Weight kg 4.5
Model BYC125K-W1 Note: * For 220 V operation.
Ceiling Mounted Cassette (Compact Multi Flow) Type Sound levels (H/L/SL)* dB (A) 35/31/29 37/33/31 38/34/32
Fan speed 5 steps, quiet and automatic
600 x 600 MODEL FFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B Temperature control Microcomputer control
Power supply 1-phase, 220 - 240 V, 50 Hz Dimensions (HXWXD) mm 200X700X620 200X900X620 200X1,100X620
Airflow rates (H) m3/min (cfm) 9.0 (318) 10.0 (353) 12.0 (424) 15.0 (530) Machine weight kg 21 25 27 30
Sound levels (H/L)* dB (A) 29.5/24.5 32/25 36/27 41/32 Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
Fan speed 2 steps connections Gas (Flare)
Temperature control Microcomputer control Drain VP20 (External Dia. 26/Internal Dia. 20)
Dimensions (HXWXD) mm 286X575X575 Heat insulation Both liquid and gas pipes
Machine weight kg 17.5 External static pressure Pa 30 40
Liquid (Flare) ø6.4 Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa
Piping for FDKS-C. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C.
mm ø9.5 ø12.7
connections Gas (Flare)
Drain VP20 (External Dia. 26/Internal Dia. 20)
Heat insulation Both liquid and gas pipes
Model BYFQ60B8W1 Wall Mounted Type
Panel Colour White
(Option)
Dimensions (HXWXD) mm 55X700X700 MODEL FTKS25DVM FTKS35DVM FTKS50FVM FTKS60FVM FTKS71FVM
Weight kg 2.7 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher Front panel colour White
owing to ambient conditions.
Airflow rates (H) m3/min (cfm) 8.7 (307) 8.9 (314) 14.7 (519) 16.2 (572) 17.4 (614)
Sound levels (H/L/SL) dB (A) 37/25/22 39/26/23 43/34/31 45/36/33 46/37/34
Fan speed 5 steps, quiet and automatic
Temperature control Microcomputer control
Dimensions (HXWXD) mm 283X800X195 290X1,050X238
Machine weight kg 9 12
Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
connections Gas (Flare)
Drain ø18.0
Heat insulation Both liquid and gas pipes
31 32
Specifications
Residential Indoor Units with connection
to BP units
Residential indoor units with connection to BP units Ceiling Mounted Built-in Type
Residential indoor units can be connected to the VRVIII single outdoor unit series by BP units. MODEL FBQ60BV1 FBQ71BV1
Power supply 1-phase, 220-240 V, 50 Hz
Ceiling Mounted Cassette Type Airflow rates (H) m3/min (cfm) 17.0 (600) 19.0 (670)
Sound levels (H/L)* dB (A) 41/35
MODEL FCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE Fan speed 2 steps
Power supply 1-phase, 220 - 240 V/220 V, 50/60 Hz Temperature control Microcomputer control
Airflow rates (H) m3/min (cfm) 14.0 (494) 15.0 (530) 19.0 (671) Dimensions (HXWXD) mm 300X1,000X800
Sound levels (H/L)* dB (A) 33/29 35/30 Machine weight kg 41
Fan speed 2 steps Liquid (Flare) ø6.4 ø9.5
Piping
Temperature control Microcomputer control mm
connections Gas (Flare) ø12.7 ø15.9
Dimensions (HXWXD) mm 230X840X840 Drain I.D ø25XO.D ø32
Machine weight kg 24 Heat insulation Both liquid and gas pipes
Liquid (Flare) ø6.4 ø9.5 Model BYBS71DJW1
Piping
mm ø9.5 ø12.7 ø15.9 Panel
connections Gas (Flare) Colour White
(Option)
Drain I.D ø25XO.D ø32 Dimensions (HXWXD) mm 55X1,100X500
Heat insulation Both liquid and gas pipes Weight kg 4.5
Model BYC125K-W1 Note: * For 220 V operation.
Ceiling Mounted Cassette (Compact Multi Flow) Type Sound levels (H/L/SL)* dB (A) 35/31/29 37/33/31 38/34/32
Fan speed 5 steps, quiet and automatic
600 x 600 MODEL FFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B Temperature control Microcomputer control
Power supply 1-phase, 220 - 240 V, 50 Hz Dimensions (HXWXD) mm 200X700X620 200X900X620 200X1,100X620
Airflow rates (H) m3/min (cfm) 9.0 (318) 10.0 (353) 12.0 (424) 15.0 (530) Machine weight kg 21 25 27 30
Sound levels (H/L)* dB (A) 29.5/24.5 32/25 36/27 41/32 Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
Fan speed 2 steps connections Gas (Flare)
Temperature control Microcomputer control Drain VP20 (External Dia. 26/Internal Dia. 20)
Dimensions (HXWXD) mm 286X575X575 Heat insulation Both liquid and gas pipes
Machine weight kg 17.5 External static pressure Pa 30 40
Liquid (Flare) ø6.4 Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa
Piping for FDKS-C. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C.
mm ø9.5 ø12.7
connections Gas (Flare)
Drain VP20 (External Dia. 26/Internal Dia. 20)
Heat insulation Both liquid and gas pipes
Model BYFQ60B8W1 Wall Mounted Type
Panel Colour White
(Option)
Dimensions (HXWXD) mm 55X700X700 MODEL FTKS25DVM FTKS35DVM FTKS50FVM FTKS60FVM FTKS71FVM
Weight kg 2.7 Power supply 1-phase, 220-240 V/220 V, 50/60 Hz
Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher Front panel colour White
owing to ambient conditions.
Airflow rates (H) m3/min (cfm) 8.7 (307) 8.9 (314) 14.7 (519) 16.2 (572) 17.4 (614)
Sound levels (H/L/SL) dB (A) 37/25/22 39/26/23 43/34/31 45/36/33 46/37/34
Fan speed 5 steps, quiet and automatic
Temperature control Microcomputer control
Dimensions (HXWXD) mm 283X800X195 290X1,050X238
Machine weight kg 9 12
Liquid (Flare) ø6.4
Piping
mm ø9.5 ø12.7 ø15.9
connections Gas (Flare)
Drain ø18.0
Heat insulation Both liquid and gas pipes
31 32
Specifications Specifications
BP Units for connection to
residential indoor units
Specifications—Indoor Units
Outdoor Units
BP units for connection to residential indoor units single outdoor unit series
• A BP unit is an innovative development which allows VRVIII single outdoor unit series to be connected to
residential indoor units.
• A BP unit has the ability to precisely vary refrigerant volume to meet the cooling requirements of individual room
spaces.
• A BP unit is easy to disassemble, making repairing and recycling simple.
33 34
Specifications Specifications
BP Units for connection to
residential indoor units
Specifications—Indoor Units
Outdoor Units
BP units for connection to residential indoor units single outdoor unit series
• A BP unit is an innovative development which allows VRVIII single outdoor unit series to be connected to
residential indoor units.
• A BP unit has the ability to precisely vary refrigerant volume to meet the cooling requirements of individual room
spaces.
• A BP unit is easy to disassemble, making repairing and recycling simple.
33 34
Option List
VRV Indoor Units
Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Duct Type
No. Type FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P Type FXMQ20P FXMQ50P FXMQ100P FXMQ200MA
Item No. FXMQ25P FXMQ40P FXMQ63P FXMQ125P
1 Decoration panel BYCP125K-W1 Item FXMQ32P FXMQ80P FXMQ140P FXMQ250MA
2 Sealing member of air discharge outlet KDBH55K160F 1 Drain pump kit — KDU30L250VE
3 Panel spacer KDBP55H160FA
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
High efficiency filter unit 65% KAFP556B80 KAFP556B160 2 High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
High efficiency filter unit 90% KAFP557B80 KAFP557B160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160 3 Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 4 Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
4 Filter related
Filter chamber KDDFP55B160 5 Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
Long life replacement filter Non-woven type KAFP551K160
White KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
Ultra long-life filter KAFP55B160
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F —
Replacement ultra long-life filter KAFP55H160H
Without T shape and fan KDDP55B160 Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Chamber type
5 Fresh air intake kit With T shape without fan KDDP55B160K 7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
Direct installation type KDDP55X160
6 Branch duct chamber KDJP55B80 KDJP55B160
7 Chamber connection kit KKSJ55KA160
8 Insulation kit for high humidity KDTP55K80 KDTP55K160 Ceiling Suspended Type
No. Type FXHQ32MA FXHQ63MA FXHQ100MA
Item
Ceiling Mounted Cassette (Compact Multi Flow) Type 1 Drain pump kit KDU50N60VE KDU50N125VE
Type 2 Replacement long-life filter (Resin net) KAF501DA56 KAF501DA80 KAF501DA112
No. Item FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M
3 L-type piping kit (for upward direction) KHFP5MA63 KHFP5MA160
1 Decoration panel BYFQ60B8W1
2 Sealing member of air discharge outlet KDBH44BA60
3 Panel spacer KDBQ44BA60A
4 Replacement long-life filter KAFQ441BA60 Wall Mounted Type
5 Fresh air intake kit Direct installation type KDDQ44XA60 Type FXAQ20MA
No. Item FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MA
1 Drain pump kit K-KDU572EVE
Note:
Long life replacement filter
1 Filter chamber is required if installing high efficiency filter.
KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Concealed Floor Standing Type
No. Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
Item
Ceiling Mounted Cassette Corner Type 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
35 36
Option List
VRV Indoor Units
Ceiling Mounted Cassette (Round Flow) Type Ceiling Mounted Duct Type
No. Type FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P Type FXMQ20P FXMQ50P FXMQ100P FXMQ200MA
Item No. FXMQ25P FXMQ40P FXMQ63P FXMQ125P
1 Decoration panel BYCP125K-W1 Item FXMQ32P FXMQ80P FXMQ140P FXMQ250MA
2 Sealing member of air discharge outlet KDBH55K160F 1 Drain pump kit — KDU30L250VE
3 Panel spacer KDBP55H160FA
65% KAF372AA36 KAF372AA56 KAF372AA80 KAF372AA160 KAFJ372L280
High efficiency filter unit 65% KAFP556B80 KAFP556B160 2 High efficiency filter
90% KAF373AA36 KAF373AA56 KAF373AA80 KAF373AA160 KAFJ373L280
High efficiency filter unit 90% KAFP557B80 KAFP557B160
Replacement high efficiency filter 65% KAFP552B80 KAFP552B160 3 Filter chamber KDDF37AA36 KDDF37AA56 KDDF37AA80 KDDF37AA160 KDJ3705L280
Replacement high efficiency filter 90% KAFP553B80 KAFP553B160 4 Long life replacement filter KAF371AA36 KAF371AA56 KAF371AA80 KAF371AA160 KAFJ371L280
4 Filter related
Filter chamber KDDFP55B160 5 Long life filter chamber kit KAF375AA36 KAF375AA56 KAF375AA80 KAF375AA160
Long life replacement filter Non-woven type KAFP551K160
White KTBJ25K36W KTB25KA56W KTB25KA80W KTB25KA160W
Ultra long-life filter KAFP55B160
6 Service panel Fresh white KTBJ25K36F KTBJ25K56F KTBJ25K80F KTBJ25K160F —
Replacement ultra long-life filter KAFP55H160H
Without T shape and fan KDDP55B160 Brown KTBJ25K36T KTBJ25K56T KTBJ25K80T KTBJ25K160T
Chamber type
5 Fresh air intake kit With T shape without fan KDDP55B160K 7 Air discharge adaptor KDAJ25K36A KDAJ25K56A KDAJ25K71A KDAJ25K140A
Direct installation type KDDP55X160
6 Branch duct chamber KDJP55B80 KDJP55B160
7 Chamber connection kit KKSJ55KA160
8 Insulation kit for high humidity KDTP55K80 KDTP55K160 Ceiling Suspended Type
No. Type FXHQ32MA FXHQ63MA FXHQ100MA
Item
Ceiling Mounted Cassette (Compact Multi Flow) Type 1 Drain pump kit KDU50N60VE KDU50N125VE
Type 2 Replacement long-life filter (Resin net) KAF501DA56 KAF501DA80 KAF501DA112
No. Item FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M
3 L-type piping kit (for upward direction) KHFP5MA63 KHFP5MA160
1 Decoration panel BYFQ60B8W1
2 Sealing member of air discharge outlet KDBH44BA60
3 Panel spacer KDBQ44BA60A
4 Replacement long-life filter KAFQ441BA60 Wall Mounted Type
5 Fresh air intake kit Direct installation type KDDQ44XA60 Type FXAQ20MA
No. Item FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MA
1 Drain pump kit K-KDU572EVE
Note:
Long life replacement filter
1 Filter chamber is required if installing high efficiency filter.
KAFJ531G36 KAFJ531G56 KAFJ531G80 KAFJ531G160
Concealed Floor Standing Type
No. Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
Item
Ceiling Mounted Cassette Corner Type 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
35 36
Option List
Residential Indoor Units with connection
to BP units
Ceiling Mounted Cassette (Compact Multi Flow) Type BP Units for connection to
residential indoor units
37 38
Option List
Residential Indoor Units with connection
to BP units
Ceiling Mounted Cassette (Compact Multi Flow) Type BP Units for connection to
residential indoor units
37 38
Control Systems
Navigation remote controller (Wired remote controller) (Option) Wireless remote controller (Option)
The same operation modes and settings as with wired remote controllers are possible.
A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is
Large buttons and arrow keys for easy operation. included.
Guide on display gives an explanation of each setting. • A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted
Backlight and dot matrix LCD display for easy viewing. type is mounted into the indoor unit.
Weekly schedule timer can be set up easily. Signal receiver unit can be
10 display languages are available. installed on the panel
ex. Ceiling Mounted Cassette (Round Flow) type
(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch,
Russian and Turkish)
Signal receiver unit
(Separate type)
BRC1E61
Wireless remote Signal receiver unit
Wired remote controller (Option) Wired remote controller controller (Installed type)
with weekly schedule timer (Option) *Wireless remote controller and signal receiver unit are sold as a set.
Displays current airflow, swing, temperature,
*Refer to page 43 for the name of each model.
operating mode and timer settings. Adds weekly schedule timer function.
Group control The indoor unit can be connected by the two FXFQ FXZQ FXCQ FXKQ FXDQ FXMQ FXHQ FXAQ FXL(N)Q FXUQ
One remote controller can remote controller, for example one in the room
Equipment and the other one in the control room, which
Outdoor
related to the control the operation of max.16
unit indoor units at the same time. can control the operation of indoor unit freely. Navigation remote controller
central control (Wired remote controller)
(The last command has a priority.) Of course, (BRC1E61)
the group control by two remote controller is
also possible.
Wired remote controller
(BRC1C62)
Indoor unit
Remote controller 2 Remote control
Remote controller
The wiring of remote controller can be Wired remote controller with
extended to max. 500 m and it is possible weekly schedule timer
to install the remote controllers for the (BRC1D61)
different indoor units in one place.
Remote
controller
Wireless remote controller*
3 Control for the combined operation (Installed type signal receiver unit)
Forced OFF
input The operation of the Heat Reclaim Ventilator
can be controlled by the remote controller of
Wireless remote controller*
Heat Reclaim the indoor unit. Of course, the remote controller (Separate type signal receiver unit)
Ventilator can display the time to clean the filter.
Remote controller Remote
controller Remote controller
Remote controller Remote controller
Simplified remote controller
4 Expansion of system control (Exposed type)
(BRC2C51)
1 2 3 4 The system can be expanded to add
several controllers, such as BMS, Forced
OFF input and etc. Simplified remote controller
(Concealed type: for Hotel use)
(BRC3A61)
39 40
Control Systems
Navigation remote controller (Wired remote controller) (Option) Wireless remote controller (Option)
The same operation modes and settings as with wired remote controllers are possible.
A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is
Large buttons and arrow keys for easy operation. included.
Guide on display gives an explanation of each setting. • A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow,
Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted
Backlight and dot matrix LCD display for easy viewing. type is mounted into the indoor unit.
Weekly schedule timer can be set up easily. Signal receiver unit can be
10 display languages are available. installed on the panel
ex. Ceiling Mounted Cassette (Round Flow) type
(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch,
Russian and Turkish)
Signal receiver unit
(Separate type)
BRC1E61
Wireless remote Signal receiver unit
Wired remote controller (Option) Wired remote controller controller (Installed type)
with weekly schedule timer (Option) *Wireless remote controller and signal receiver unit are sold as a set.
Displays current airflow, swing, temperature,
*Refer to page 43 for the name of each model.
operating mode and timer settings. Adds weekly schedule timer function.
Group control The indoor unit can be connected by the two FXFQ FXZQ FXCQ FXKQ FXDQ FXMQ FXHQ FXAQ FXL(N)Q FXUQ
One remote controller can remote controller, for example one in the room
Equipment and the other one in the control room, which
Outdoor
related to the control the operation of max.16
unit indoor units at the same time. can control the operation of indoor unit freely. Navigation remote controller
central control (Wired remote controller)
(The last command has a priority.) Of course, (BRC1E61)
the group control by two remote controller is
also possible.
Wired remote controller
(BRC1C62)
Indoor unit
Remote controller 2 Remote control
Remote controller
The wiring of remote controller can be Wired remote controller with
extended to max. 500 m and it is possible weekly schedule timer
to install the remote controllers for the (BRC1D61)
different indoor units in one place.
Remote
controller
Wireless remote controller*
3 Control for the combined operation (Installed type signal receiver unit)
Forced OFF
input The operation of the Heat Reclaim Ventilator
can be controlled by the remote controller of
Wireless remote controller*
Heat Reclaim the indoor unit. Of course, the remote controller (Separate type signal receiver unit)
Ventilator can display the time to clean the filter.
Remote controller Remote
controller Remote controller
Remote controller Remote controller
Simplified remote controller
4 Expansion of system control (Exposed type)
(BRC2C51)
1 2 3 4 The system can be expanded to add
several controllers, such as BMS, Forced
OFF input and etc. Simplified remote controller
(Concealed type: for Hotel use)
(BRC3A61)
39 40
Control Systems
41 42
Control Systems
41 42
Option List
Control Systems
2 Navigation remote controller (Wired remote controller) BRC1E61 3 Unified ON/OFF controller
Note 2
DCS301BA61
3 Wired remote controller with weekly schedule timer BRC1D61 •Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
3-1 Electrical box with earth terminal (2 blocks) KJB212AA operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
4 Simplified remote controller (Exposed type) — BRC2C51 — BRC2C51 —
5 Remote controller for hotel use (Concealed type) — BRC3A61 — BRC3A61 — 3-2 Noise filter (for electromagnetic interface use only) KEK26-1A
6 Adaptor for wiring KRP1C63 KRP1BA57 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 — KRP1B61 — Note 2 •Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
4 Schedule timer
DST301BA61 (128 units). Can turn units ON/OFF twice per day.
7-1 Wiring adaptor for electrical appendices (1) KRP2A62 KRP2A62 KRP2A61 KRP2A61 KRP2A53 KRP2A61 KRP2A61 KRP2A62 KRP2A61 KRP2A61 KRP2A62
5-room centralised controller Note 4
7-2 Wiring adaptor for electrical appendices (2) KRP4AA53 KRP4AA53 KRP4AA51 KRP4AA51 KRP4A54 KRP4AA51 KRP4AA51 KRP4AA52 KRP4AA51 KRP4AA51 KRP4AA53 5 For FTKS-D/F, FDKS-EA/C(A) KRC72 •Up to 5 indoor units can be controlled. This is a low cost system which can only control ON/OFF.
for residential indoor units
8 Remote sensor (for indoor temperature) KRCS01-4B KRCS01-1B KRCS01-4B KRCS01-1B For FTKS-D/F, FDKS-EA/C(A) KRP928BB2S
Interface adaptor for residential
Notes 2, 3 Notes 4, 6 Notes 2, 3 Notes 4, 6 Notes 2, 3 Note 3 Notes 2, 3 6
9 Installation box for adaptor PCB KRP1H98 KRP1BA101 KRP1B96 — KRP1BA101 KRP4A96 — KRP1CA93 KRP4AA93 — KRP1BA97 indoor units
For FCQ-B, FFQ-B, FBQ-B DTA112BA51 •Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
10 External control adaptor for outdoor unit DTA104A62 DTA104A62 DTA104A61 DTA104A61 DTA104A53 DTA104A61 DTA104A61 DTA104A62 DTA104A61 DTA104A61 — communication system adopted for the VRV System.
7 Interface adaptor for SkyAir-series For SkyAir, FD(Y)M-FA, FDY-KA
DTA102A52
11 Adaptor for multi tenant DTA114A61 — DTA114A61 — DTA114A61 — FDYB-KA, FVY(P)J-A, FXUQ-MA * To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
Notes: 1. Installation box is necessary for each adaptor marked . 8 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit. 9 Wiring adaptor for other air-conditioner DTA103A51
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
•Up to 1024 units can be centrally controlled in 64 different groups.
D -NET
10 DTA109A51 •Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
Expander Adaptor
apply to each adaptor.
Note 3 Note 4
2 Adaptor for wiring KRP1BA57 KRP1BA57 KRP1BA54 —
Note 3 Note 4
3 Wiring adaptor for electrical appendices KRP4AA51 —
2-2 Option Software Web DAM004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
2-4 Optional DIII Ai unit DAM101A51 •External temperature sensor for intelligent Manager III.
2-5 Di unit DEC101A51 •8 pairs based on a pair of On/Off input and abnormality input.
2-6 Dio unit DEC102A51 •4 pairs based on a pair of On/Off input and abnormality input.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
Communication line
3 *1 Interface for use in BACnet ®
DMS502B51 conditioning systems through BACnet communication.
®
•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
3-1 Optional DIII board DAM411B51 independently.
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
3-2 Optional Di board DAM412B51 independently.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
4 *2 Interface for use in LONWORKS ®
DMS504B51 conditioning systems through LONWORKS communication.
®
5 Parallel interface DPF201A51 •Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
Contact/analogue
measurement units
7 Temperature DPF201A53 •Enables temperature setting input for 16 groups; 0-5VDC.
setting units
8 Unification adaptor for DCS302A52 •Interface between the central monitoring board and central control units.
computerised control
®
Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS is a trademark of Echelon Corporation registered in the United States and other countries.
®
43 44
Option List
Control Systems
2 Navigation remote controller (Wired remote controller) BRC1E61 3 Unified ON/OFF controller
Note 2
DCS301BA61
3 Wired remote controller with weekly schedule timer BRC1D61 •Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
3-1 Electrical box with earth terminal (2 blocks) KJB212AA operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
4 Simplified remote controller (Exposed type) — BRC2C51 — BRC2C51 —
5 Remote controller for hotel use (Concealed type) — BRC3A61 — BRC3A61 — 3-2 Noise filter (for electromagnetic interface use only) KEK26-1A
6 Adaptor for wiring KRP1C63 KRP1BA57 KRP1B61 KRP1B61 KRP1B56 KRP1C64 KRP1B61 KRP1BA54 — KRP1B61 — Note 2 •Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
4 Schedule timer
DST301BA61 (128 units). Can turn units ON/OFF twice per day.
7-1 Wiring adaptor for electrical appendices (1) KRP2A62 KRP2A62 KRP2A61 KRP2A61 KRP2A53 KRP2A61 KRP2A61 KRP2A62 KRP2A61 KRP2A61 KRP2A62
5-room centralised controller Note 4
7-2 Wiring adaptor for electrical appendices (2) KRP4AA53 KRP4AA53 KRP4AA51 KRP4AA51 KRP4A54 KRP4AA51 KRP4AA51 KRP4AA52 KRP4AA51 KRP4AA51 KRP4AA53 5 For FTKS-D/F, FDKS-EA/C(A) KRC72 •Up to 5 indoor units can be controlled. This is a low cost system which can only control ON/OFF.
for residential indoor units
8 Remote sensor (for indoor temperature) KRCS01-4B KRCS01-1B KRCS01-4B KRCS01-1B For FTKS-D/F, FDKS-EA/C(A) KRP928BB2S
Interface adaptor for residential
Notes 2, 3 Notes 4, 6 Notes 2, 3 Notes 4, 6 Notes 2, 3 Note 3 Notes 2, 3 6
9 Installation box for adaptor PCB KRP1H98 KRP1BA101 KRP1B96 — KRP1BA101 KRP4A96 — KRP1CA93 KRP4AA93 — KRP1BA97 indoor units
For FCQ-B, FFQ-B, FBQ-B DTA112BA51 •Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
10 External control adaptor for outdoor unit DTA104A62 DTA104A62 DTA104A61 DTA104A61 DTA104A53 DTA104A61 DTA104A61 DTA104A62 DTA104A61 DTA104A61 — communication system adopted for the VRV System.
7 Interface adaptor for SkyAir-series For SkyAir, FD(Y)M-FA, FDY-KA
DTA102A52
11 Adaptor for multi tenant DTA114A61 — DTA114A61 — DTA114A61 — FDYB-KA, FVY(P)J-A, FXUQ-MA * To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.
Notes: 1. Installation box is necessary for each adaptor marked . 8 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit. 9 Wiring adaptor for other air-conditioner DTA103A51
4. Up to 2 installation boxes can be installed for each indoor unit.
5. Installation box is necessary for second adaptor.
6. Installation box is necessary for each adaptor.
•Up to 1024 units can be centrally controlled in 64 different groups.
D -NET
10 DTA109A51 •Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
Expander Adaptor
apply to each adaptor.
Note 3 Note 4
2 Adaptor for wiring KRP1BA57 KRP1BA57 KRP1BA54 —
Note 3 Note 4
3 Wiring adaptor for electrical appendices KRP4AA51 —
2-2 Option Software Web DAM004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
2-4 Optional DIII Ai unit DAM101A51 •External temperature sensor for intelligent Manager III.
2-5 Di unit DEC101A51 •8 pairs based on a pair of On/Off input and abnormality input.
2-6 Dio unit DEC102A51 •4 pairs based on a pair of On/Off input and abnormality input.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
Communication line
3 *1 Interface for use in BACnet ®
DMS502B51 conditioning systems through BACnet communication.
®
•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
3-1 Optional DIII board DAM411B51 independently.
•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
3-2 Optional Di board DAM412B51 independently.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
4 *2 Interface for use in LONWORKS ®
DMS504B51 conditioning systems through LONWORKS communication.
®
5 Parallel interface DPF201A51 •Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
Contact/analogue
measurement units
7 Temperature DPF201A53 •Enables temperature setting input for 16 groups; 0-5VDC.
setting units
8 Unification adaptor for DCS302A52 •Interface between the central monitoring board and central control units.
computerised control
®
Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS is a trademark of Echelon Corporation registered in the United States and other countries.
®
43 44
Memo
Memo
PCV1131
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or VRV indoor units combine with
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion. residential indoor units, all in one system
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.