Safety Testing of Electrical and Electronics Instruments
Safety Testing of Electrical and Electronics Instruments
Submitted by
PARUSHNI SINGH
VIII Semester
Id – BTBTL14575
Banasthali University, Rajasthan
Under Supervision of
Department Of Electronics
Banasthali Vidyapith
Banasthali - 304022
Session: 2014-18
ABOUT THE ORGANIZATION
2
CERTIFICATE
This is to certify that Ms. Parushni Singh has carried out the project work titled
“Saftey Testing Of Electrical And Electronics Instruments” from 1st January
2018 to 30th May 2018 for the award of the B.Tech ( Electrical and
Electronics ) from Safety Lab, STQC under my supervision. The thesis
embodies result of original work and studies carried out by Student herself and the
contents of the thesis do not form the basis for the award of any other degree to
the candidate or to anybody else.
3
CERTIFICATE
The project on evaluation fulfils all the stated criteria and the student’s findings
are her original work. I hereby certify her work good to the best of my knowledge
& wish her best of luck for her future.
4
ACKNOWLEDGEMENT
I would also like to express my sincere thanks to DEEPIKA GAHLOT mam for
her support and for providing me with the required facilities to carry out my
project.
Parushni singh
5
ABSTRACT
6
TABLE OF CONTENTS
1. Introduction
1.1. Objective
1.2. Calibration
1.3. Durability and environmental testing
2. Hazard
2.1. Introduction
2.2. Hazardous voltage
2.3. Hazardous energy level
3. Important features during testing
3.1. General instructions
3.2. Marking
3.3. Selection of Electrical Test Instruments
4. Terminologies used
4.1. DC mains supply
4.2. AC mains supply
4.3. Mains supply
4.4. Rated voltage
4.5. Rated current
4.6. Rated frequency
4.7. Normal load
4.8. Rated operating time
4.9. Rated resting time
4.10. Classes of equipment
4.11. Primary circuit
4.12. Secondary circuit
4.13. ELV circuit
4.14. SELV circuit
4.15. Limited current voltage
7
4.16. TNV circuit
4.17. Working voltage
4.18. Functional earthing
4.19. Touch current
4.20. Power interface
4.21. Input current
4.22. Neutral conductor
5. Testing instrument review
5.1. High voltage test
5.2. Insulation Resistance Test
5.3. Earth continuity test
5.4. Leakage current test
5.5. Ball pressure test
5.6. Determine the Temperature of Winding under Short Circuit
5.7. Heat deflection test
5.8. Clearances, Creepage distance and Solid insulation
5.9. Dielectric Strength Tests
5.10. Leakage Current
5.11. TestsGlow Wire Test
5.12. Cables testing
6. Major work
6.1. Switching adapter
6.2. Test of cable
6.3. Printer
6.4. Electric fence
6.5. Control gear
7. Conclusion
8. Reference
8
TABLE OF FIGURES
Title of Figure
9
LIST OF TABLES
Title of table Pg No
10
Chapter 1: Introduction
1.1 GENERAL
The manufacturer must maintain accurate records to ensure it builds products with
the same materials and processes on a continuous basis. The manufacturer must
notify the safety agency of any changes to the material, design, or process used in
producing its product. If the manufacturer makes a change, safety agencies may
amend the safety certification; in some cases, the product may need to be
recertified .
11
UL/IEC Harmonized Standards
STANDARD DISCRIPTION
(Table 1.1)
1.2 OBJECTIVE
1.2.1 Electrical safety testing is essential to ensure safe operating standards for
any product that uses electricity. Various governments and agencies have
12
developed stringent requirements for electrical products that are sold world-wide.
In most markets it is mandatory for a product to conform to safety
standards promulgated by safety and standard agencies such as
UL, CE, VDE,CSA, BSIand so on. To conform to such standards, the product
must pass safety tests such as the high voltagetest (also called as Dielectric
voltage-withstand test or high potential test), Insulation Resistance Test, Ground
(Earth) Bond & Ground Continuity Test & Leakage Current Test (also called as
Line Leakage Test, Earth Leakage Current Test, Enclosure Leakage Current Test
or Patient Leakage Current Test).
In general, IEC 60335 is the most widely applied standard for electrical safety
testing, especially for domestic appliances. Many safety testing standards in the
world have been based on it. To safeguard workplace health and safety, many
sections of the Occupational Health and Safety Regulation provide guidelines on
electrical safety and the appropriate equipment required to work on low and high
voltage electrical appliances.
1.3 CALIBRATION
13
instrument also involves adjusting its precision and accuracy so that its readings
come in accordance with the established .
1.3.2Types of Calibration
Barometers
Digital Indicators
14
Digital Pressure Gauges
Test Gauges
Transmitters
Chambers
Dial Thermometers
Infrared Meters
Thermal Cameras
Thermometers/Thermocouples
Weather Stations
Electrical calibration
Clamp Meters
Data Loggers
15
Electrical meters
Insulation Testers
Multi-meters
Oscilloscopes
Accelerometers
Scales/Balances
1.3.3 Process
The exact process of equipment calibration shall vary according to the type of
instrument, how critical its role is in the operation and standards that are followed
for the calibration purpose. Mentioned below is a typical process that needs to be
followed for equipment calibration.
16
Check tolerance value: Tolerance value of the instrument should be taken
in regard. It may be noted that every calibrator has a particular tolerance
level this is due to the normal variations in the instrumentation and quality
control process. The tolerance level will vary according to several factors
including the industry sector and even the country in which the calibration
process is to be carried out.
17
1.4 DURABILITY AND ENVIRONMENTAL TESTING
Shock Testing : laboratories are equipped with shock machines that enable
product damage boundary analysis, and vibration testing equipment to
determine product resonant frequency analysis and response. equipment is
specified to deliver synthesized shock up to 20G. Free fall shock machine
up to 500G (depending on pulse energy) .
18
Chapter 2: Hazards
2.1. Introduction
Application of a safety standard is intended to reduce the risk of injury or damage
due to the following:
electric shock;
energy related hazards;
fire;
heat related hazards;
mechanical hazards;
radiation;
chemical hazards
Electric shock
Electric shock is due to current passing through the human body. The resulting
physiological effects depend on the value and duration of the current andhazards
the path it takes through the body. The value of the current depends on the applied
voltage, the impedance of the source and the impedance of the body. The body
impedance depends in turn on the area of contact, moisture in the area of contact
and the applied voltage and frequency. Currents of approximately half a
milliampere can cause a reaction in persons in good health and may cause injury
indirectly due to involuntary reaction. Higher currents can have more direct
effects, such as burn or muscle tetanization leading to inability to let go or to
ventricular fibrillation.
Steady state voltages up to 42,4 V peak, or 60 V d.c., are not generally regarded as
hazardous under dry conditions for an area of contact equivalent to a human hand.
Bare parts that have to be touched or handled should be at earth potential or
properly insulated.
19
single fault, including any consequential faults, should not create a shock hazard.
However, provision of additinal protective measures, such as protective earthing
or supplementary insulation, is not considered a substitute for, or a relief from,
properly designed BASIC INSULATION. Harm may result from:
(Table 2.1.)
Harm may result from Examples of measures to reduce
risks
Contact with bare parts normally at Prevent user access to parts at
hazardous voltages hazardous voltages by fixed or locked
covers, safety interlocks, etc. discharge
accessible capacitors that are at
hazardous voltages.
20
insulation Insulation that is accessible to the user
should have adequate mechanical and
electrical strength to reduce the
likelihood of contact with hazardous
voltages
Touch current (leakage current) Limit touch current to a specified
flowing from parts at hazardous value, or provide a high integrity
voltages to accessible parts, or failure protective earthing connection.
of a protective earthing connection.
touch current may include current
due to emc filter components
connected between primary circuits
and accessible parts
Energy related hazards Injury or fire may result from a short-circuit between
adjacent poles of high current supplies or high capacitance circuits, causing:
Burns;
Arcing;
Ejection of molten metal.
Even circuits whose voltages are safe to touch may be hazardous in this respect.
Examples of measures to reduce risks include:
Separation;
Shielding;
Provision of safety interlocks.
Fire Risk of fire may result from excessive temperatures either under normal
operating conditions or due to overload, component failure, insulation breakdown
or loose connections. Fires originating within the equipment should not spread
beyond the immediate vicinity of the source of the fire, nor cause damage to the
surroundings of the equipment. Examples of measures to reduce risks include:
providing overcurrent protection;
using constructional materials having appropriate flammability properties
for their purpose;
21
selection of parts, components and consumable materials to avoid high
temperature which might cause ignition;
limiting the quantity of combustible materials used;
shielding or separating combustible materials from likely ignition
sources;
using enclosures or barriers to limit the spread of fire within the
equipment;
using suitable materials for enclosures so as to reduce the likelihood of
fire spreading from the equipment.
Heat related hazards Injury may result from high temperatures under normal
operating conditions, causing:
burns due to contact with hot accessible parts
degradation of insulation and of safety-critical components;
ignition of flammable liquids. Examples of measures to reduce risks
include:
taking steps to avoid high temperature of accessible parts;
avoiding temperatures above the ignition point of liquids;
provision of markings to warn USERS where access to hot parts is
unavoidable.
22
Radiation Injury to users and to service persons may result from some forms of
radiation emitted by equipment. examples are sonic (acoustic), radio frequency,
infra-red, ultraviolet and ionizing radiation, and high intensity visible and
coherent light (lasers). Examples of measures to reduce risks include:
limiting the energy level of potential radiation sources; − screening
radiation sources;
provision of safety interlocks;
provision of markings to warn users where exposure to the radiation
hazard is unavoidable.
Chemical hazards Injury may result from contact with some chemicals or from
inhalation of their vapours and fumes. Examples of measures to reduce risks
include:
avoiding the use of constructional and consumable materials likely to
cause injury by contact or inhalation during intended and normal
conditions of use;
avoiding conditions likely to cause leakage or vaporization;
provision of markings to warn users about the hazards
Voltage exceeding 42,4 V peak, or 60 V d.c., existing in a circuit that does not
meet the requirements for either a LIMITED CURRENT CIRCUIT or a TNV
CIRCUIT.
23
Chapter 3: Important Features During Testing
Mark Description
VDE
The VDE Mark indicates conformity with the VDE standards or
European or internationally harmonized standards resp. and
confirms compliance with protective requirements of the
applicable EC Directive(s). The VDE Mark is a symbol for
electrical, mechanical, thermal, toxic, radiological and other
hazards.
For appliances in compliance with standards for
electromagnetic compatibilityThe VDE EMC Mark expresses
24
the conformity of a product with applicable standards for
electromagnetic compatibility. The reliable function of the
product in its electromagnetic environment is also included.
For cables, insulated cords, installation conduits and ducts,
the VDE Cable Mark is applicable.
For cables and cords, the VDE Identification Thread may be used.
Underwriters Laboratories Inc.
UL Listing Mark
This is one of the most common UL Marks. If a product carries
this Mark, it means UL found that samples of this product met
UL's safety requirements.. This type of Mark is seen commonly
on appliances and computer equipment, furnaces and heaters,
fuses, electrical panelboards, smoke and carbon monoxide
detectors, fire extinguishers and sprinkler systems, personal
flotation devices like life jackets and life preservers, bullet
resistant glass, and thousands of other products.
C-UL Listing Mark
This mark is applied to products for the Canadian market. The
products with this type of mark have been evaluated to Canadian
safety requirements, which may be somewhat different from U.S.
safety requirements. This type of Mark on appliances and
computer equipment, vending machines, household burglar
alarm systems, lighting fixtures, and many other types of
products.
Classification Mark
This mark appears on products which UL has also evaluated.
Products carrying this mark have been evaluated for specific
properties, a limited range of hazards, or suitability for use under
limited or special conditions.. Examples of types of equipment
Classified by UL include immersion suits, fire doors, protective
gear for fire fighters and industrial trucks.
25
Recognized Component Mark and Canadian Recognized
Component Mark
These are marks consumers rarely see because they are
specifically used on component parts that are part of a larger
product or system. These components may have restrictions on
their performance or may be incomplete in construction. The
Component Recognition marking is found on a wide range of
products, including some switches, power supplies, printed
wiring boards, some kinds of industrial control equipment and
thousands of other products. Products intended for Canada carry
the Recognized Component mark "C."
International "emc-Mark"
The International "emc-Mark" appears on products meeting the
electromagnetic compatibility requirements of Europe, the
United States, Japan, Australia, or any combination of the four.
In the United States, some types of products can't be sold without
proof of compliance to U.S. electromagnetic compatibility
requirements. The types of products that are subject to EMC
testing include medical and dental equipment, computers,
microwave ovens, televisions, radios, transmitters, and radio-
controlled equipment.
26
CSA International
The CSA mark may appear alone or with indicators. If it appears
alone, it means that the product is certified for the Canadian
market, to the applicable Canadian standards.
CGA"Script"
The Canadian Gas Association (CGA) "Script" for components
of gas appliances and other liquid petroleum products indicates
certification to applicable Canadian standards.
A.G.A. Blue Star
The American Gas Association (A.G.A.) "Blue Star" mark for
gas appliances and other liquid petroleum products indicates
certification to applicable U.S. standards.
CSA Blue Star
The CSA Blue Star Mark for gas appliances and other liquid
petroleum products indicates certification to applicable U.S.
standards.
CSA Blue Flame
The CSA Blue Flame Mark for gas appliances and other liquid
petroleum products indicates certification to applicable Canadian
standards.
NEMKO
Shows that the product is Safety Certified and when relevant, that
the product is also compliant with the EMC Directive.The well-
known N-mark is a certification mark based on Nemko's own
testing or results from testing performed by often labratory
according to multi-national or bi-lateral agreement or by otherwise
Nemko accepted labratories including all authorized
manufacturers. The mark itself signifies that Nemko has tested or
certified the product according to national standards official safety
regulations in Norway. (which in principle are aquivalent to those
of the other European EU/EEA states)
DEMKO
27
DEMKO's D-Mark represents electrical product safety for a great
majority of consumers.
The D-Mark demonstrates that, from a safety point of view, the
tested product complies with:
FIMKO
The SGS Fimko FI mark is a well-known and respected impartial
certification mark indicating the safety and quality of a product..
The FI mark can appear on the certified product, in the User’s
Manual and Installation Guide, in product catalogues and, for
example in newspaper, TV and radio advertisements.) More
information about the use of the FI mark can be found in
FIMKO’s FI handbook and on a diskette which can be obtained
free of charge.
SGS Fimko’s EMC mark can be granted to all products which are
in accordance with European standards, for example household
appliances, switches for household appliances, lighting fittings,
measurement instruments, electromedical equipment, IT
equipment, office machines, hand-held tools and consumer
electronics.
SEMKO
The S marking, which is volontary today, means that SEMKO as
an impartial testing laboratory certifies that the product fulfils
valid safety requirements.
The safety requirements include checking of e.g.
electrical safety
fire protection
mechanical hazards
radiation risks, e.g. of CD players and solaria
28
VARIOUS
Lighting
Components for lampholders
IT
Electric office equipment
Safety isolating transformers
Isolating transformers and separating transformers
Power supply units
Switches
29
The GS-Mark is the German national mark that demonstrates that
a product has been tested and found to comply with the standards
for the product. The GS-Mark is very well recognised by German
consumers; so well recognised that certain products are nearly
impossible to sell without the GS-Mark.
For manufacturers and importers wishing to sell their electrical
products in Germany, it is a good idea to have a GS-Mark. There
are three particular areas where a GS-Mark is nearly a necessity:
tools, IT equipment and electromedical equipment.
Manufacturers of tools often have a hard, if not impossible, time
selling their products in Germany without a GS-Mark because
such marking is supported by consumers and the trade unions. IT
equipment is also effected by the requirement for GS-Marking;
the mark is a requirement if you wish to sell major companies or
institutions.
The third area where the GS-Mark is particularly important is
electromedicine because a GS-Mark is a prerequisite for a grant to
the institution in question from the German authorities.
ETL Listed Mark
ETL Listed Mark represents compliance to United States and/or
Canadian product safety standards. You will find the ETL Listed
Mark on electrical-gas-, or oil- fired products.
30
3.2. Marking
1. Maker's or responsible vendor's name, trade mark or identification mark;
2. Model number or type reference;
3. The symbol for class ii for apparatus without functional earth
for class ii apparatus with functional earth
4. Nature of supply:
– a.c. Only with the symbol:
– d.c. Only with the symbol:
– a.c. Or d.c. With the symbol:
– for three-phase systems;
5. Rated supply voltage or range of the rated supply voltages which can be
applied without operating a voltage setting device. Apparatus which can be set
to different rated supply voltages or ranges of rated
supply voltages shall be so constructed that the indication of the voltage or
range of voltages to which the apparatus is set, is discernible on the apparatus
when ready for use. A solidus shall be used for user selectable ratings, for
example “110/230 v” and a hyphen shall be used for a rating range, for
example “110-230 v”;
6. Rated current consumption or rated power consumption of apparatus which
can be supplied by supply apparatus for general use. As an alternative the
information may be given in the instruction manual. The measured
consumption at rated supply voltage shall not exceed the marked value by
more than 10 %;
7. Rated current consumption or rated power consumption for apparatus intended
for connection to an a.c. Mains supply. The measured consumption at rated
supply voltage shall not exceed the marked value by more than 10 %.
31
Minimizing such risks requires that everyone working in electrical environments
has safety equipment as required. They need correctly rated gloves, eye
protection, and electrical test instruments that provide appropriate protection.
Having the correct electrical test and measurement instruments and using the
correct procedures can improve job safety.
In connection with this, a quick review of the four category (CAT) ratings is in
order:
32
outlets with "short" connections to service entrance. The peak impulse transient
range is from 600 to 8,000 volts with a 2-ohm source.
3.3.1.Overvoltage categories
33
2. cases where the reliability and the availability of the equipment is subject
to requirement.
3.3.2.Pulltion degrees
34
POLLUTION DEGREE 4: continuous conductivity occurs due to conductive
dust, rain or other wet conditions.
3.3.3.Classes of insulation
Class II: Equipment in which protection against electric shock does not rely
on basic insulation only, but in which additional safety precautions, such as
double insulation or reinforced insulation, are provided, there being no
reliance on either protective earthing or installation conditions
When isolation is used to enable the system to function properly, but not
necessarily to serve as a barrier against shock, it is called functional
isolation.
35
Chapter 4: Terminologies Used
36
its lower and upper rated voltages .This means that the equipment is designed to
be connected to anAC mains supply having any voltage between 220 V and 240
V.
4.7.Normal load
Mode of operation, used for testing purposes, which represents as closely as
possible the most severe conditions of normal use which can reasonably be
expected If the conditions of actual use can reasonably be expected to be more
severe than the maximum load conditions recommended by the manufacturer,
including rated operating time and rated resting time, a mode of operation is used
that represents these more severe conditions.
4.10.Classes of equipment
37
providing a means of connection to the protective earthing
conductor in the building wiring those conductive parts that are
otherwise capable of assuming hazardous voltages if the basic
insulation fails note class I equipment may have parts with double
insulation or reinforced insulation.
Class II equipment equipment in which protection against electric shock
does not rely on basic insulation only, but in which additional safety
precautions, such as double insulation or reinforced insulation are provided,
there being no reliance on protective earthing
4.11.Primary circuit
circuit that is directly connected to the AC mains supply It includes, for example,
the means for connection to the AC mains supply, the primary windings of
transformers, motors and other loading devices.
4.12.Secondary circuit
circuit that has no direct connection to a primary circuit and derives its power
from a
transformer, converter or equivalent isolation device, or from a battery.
4.13.ELV circuit
Secondary circuit with voltages between any two conductors of the circuit, and
between any
one such conductor and earth , not exceeding 42,4 v peak, or 60 v d.c.,
undernormal operating conditions, which is separated from hazardous voltage by
basicinsulation, and which neither meets all of the requirements for an selv circuit
nor meets allof the requirements for a limited current circuit
38
4.14.SELV circuit
Secondary circuit that is so designed and protected that under normal operating
conditions
and single fault conditions, its voltages do not exceed a safe value.The limit
values of voltages under normal operating conditions and single fault conditions
are :
General requirements
SELV circuits shall exhibit voltages that are safe to touch both under normal
operating conditions and after a single fault. If no external load is applied to the
SELV circuit (open circuit), the voltage limits shall not be exceeded.
NOTE 1a circuit that meets the above requirements, but that is subject to
overvoltages from a
telecommunication network or a cable distribution system, is a TNV-1 circuit.
NOTE 2 For normal conditions, the SELV circuit voltage limit is the same for an
ELV circuit; an SELV circuitmay be regarded as an ELV circuit with additional
protection under fault conditions.
39
"hiccup" mode), additional pulses exceeding V1 (but not exceeding V2) are
permitted under
the following conditions:
− ift1 ≤ 20 ms, t2 shall be greater than 1 s;
− ift1 >20 ms, t2 shall be greater than 3 s;
− t1 shall not exceed 200 ms
SELV circuit obtains its supply conductively from a secondary circuit that is
separated
from a hazardous voltage circuit by either:
double insulation or reinforced insulation;
an earthed conductive screen that is separated from the hazardous voltage
circuit by
basicinsulation,theselv circuit shall be considered as being separated from the
hazardous voltage circuitby the same method.
(Figure 4.1)
40
circuit that is so designed and protected that, under both normal operating
conditions and
single fault conditions, the current that can be drawn is not hazardous.
4.16.TNV circuits
TNV circuit that is in the equipment and to which the accessible area of contact is
limited and that is so designed and protected that, under normal operating
conditions and single fault conditions , the voltages do not exceed specified limit
values. A TNV circuit is considered to be a secondary circuit in the meaning of
this standard.
41
4.17.Working voltage highest voltage to which the insulation or the component
under consideration is, or can be, subjected when the equipment is operating
under conditions of normal use.
42
S means the protective function is provided by a conductor
separate from the neutral or from the earthed line (or in a.c.
systems, earthed phase) conductor,
C means the neutral and protective functions are combined in a
single conductor
4.21.Input current The steady state input current of the equipment shall not
exceed the rated current by more than 10 % under normal load.
4.22.Neutral conductor The neutral conductor, if any, shall be insulated from
earth and from the BODY throughout the equipment as if it were a line conductor.
Components connected between neutral and earth shall be rated for the line-to-
neutral voltage.
43
Chapter 5: Testing Instrument Review
This test is carried out by applying a significantly higher than operating voltage to
the device under test. In this test, the insulation of a product, stressed to a greater
extent than under normal operating conditions, should not be breached for the
product to pass. In most cases, the device is stressed to twice its normal operating
voltage. During type testing, i.e. testing during designing a product or for a double
insulated product, however, much larger voltage may be applied. For all electrical
products, the high voltage test is a universal test, meaning that every unit should
pass before it can be used.
(figure 5.1)
44
(figure5.2)
This test is performed by measuring the resistance between the third pin (ground)
and outside metal body of the product under test. The maximum acceptable value
is generally 0.5 ohms although certain standards may specify 0.1 ohms. This test
is generally carried out at a slightly higher current
(e.g. 25–60 A) so that the ground bond circuit maintains safe voltages on the
chassis of the product, even at a high current, before the circuit breaker trips. This
test is essential so that the product does not cause an electric shock resulting from
insulation failure. In India current specified is 16 A so the test is done at double of
the current i.e. 32 A.
Figure(5.3)
This test is to measure the undesirable leakage current that flows through or across
the surface of the insulation or the dielectric of a capacitor. This test is generally
carried out at 100%-110% of the rated input voltage of the product under test. The
45
maximum acceptable limit of a leakage current is generally 210 micro amperes.
At first, this test was mandatory for medical devices only.
46
remove the pressure ball from the test specimen and within 10 s immerse
the test specimen in cold water.
Immediately thereafter keep immersion for 6 min-2 min.Now remove the
test specimen from the water and eliminate all traces of water.Within 3
min of removal from the water measure dimension d, toone decimal place
using the profile projector or optical measuring instrumentDimensiondis
the greatest dimension across the indentation caused by the pressure ball.
The diameter of the impression caused by the ball shall not exceed 2mm
(figure 5.4)
5. Then connect Voltage leads (U+ & U-) on both the Ends of naked conductor
fixed on the bench exact at 1 meter.
6. Press the measure button on the Micro-Ohm Meter and Record the observed
resistance in or m.
47
7. Measure the cold resistance or initial resistance of primary &Secondary
windings in turns and record their values Pri, Sec.1, Sec.2 etc.
10. Immediately after completion of test, power off the DUT , and again measure
the resistance or Final resistance of primary & Secondary windings in turns
and record their values Pri, Sec.1, Sec.2 etc& also record the Temp. T2 at the
time of measrement.
11. Now scratch sligthly the winding wire to ensure the type of winding wire or
from available data whether winding wire used is Aluminium or Copper
(equation 5.1)
where
Δt is the temperature rise of the winding;
R1 is the resistance at the beginning of the test;
R2 is the resistance at the end of the test;
k is equal to 234,5 for copper windings and 225 for aluminium windings;
t1 is the room temperature at the beginning of the test;
t2 is the room temperature at the end of the test.
48
(equation 5.2)
where
F is the load, in newtons;
is the flexural stress, in megapascals, at the test-specimen surface;
B is the width, in millimetres, of the test specimen;
H is the thickness, in millimetres, of the test specimen;
L is the span, in millimetres, between the supports.
1. Set the temperature of Vicat Tester to 130 2 C’.
2. If specimen flat wise, set the span between support 64 mm and centrally
place one specimen each one of the plateform.
3. Now apply the load on each specimen by calculated load.
4. Immerse the platefom side the oil bath and slowly align the dial gauge
micrometer to zero..
5. As the temperature start increasing towards set temp. , needle of dial gauge
unit keep on moving.
(figure5.5)
49
5.8.Clearances, Creepage distance and Solid insulation
In allocation of the equipment to an installation category, the following factors
shall be taken into account
● Overvoltages which can enter the equipment from outside across the terminals.
● Overvoltages generated in the equipment itself and occurring at the terminals.
5.8.1.Insulation parameters
The following insulation parameters apply to:
Installation category I : Equipment is intended for use only in appliances
or installation parts, in which no overvoltages can occur. Equipment in
this installation category in normally operated at extra low voltage.
Installation category II : Equipment is intended for use in installations or
parts of installations, in which lightning overvoltages need not be
considered. Overvoltages caused by switching must be taken into account.
This includes for example domestic appliances.
Installation category III: Equipment is intended for use in installations or
parts of installations, in which lightning overvoltages need not be
considered, but which are subject to particular requirements with regard to
the safety and availability of the equipment and its supply systems. This
includes equipment for fixed installation such as protective devices,
relays, switches and sockets.
Installation category IV: Equipment is intended for use in installations or
parts of installations, in which lightning overvoltages must be taken into
account. This includes equipment for connection to overhead lines such as
omnidirectional control receivers and meters.
50
[The degrees of pollution 3 and 4 are in this case not considered, as they are not
relevant for the connectors shown in this catalogue].
5.8.2.Clearance: The clearance is defined as shortest distance through the air
between two conductive elements. Clearance.
(figure5.6)
(table 5.2)
(figure5.7)
51
To identify the creepage distance
● Define the installation category
● Define the degree of pollution expected
● From the nominal voltage and the type of supply system select the rated voltage
from table 00.03 a/b
● From the rated voltage and degree of pollution select the minimum creepage
required in table 00.04 [For the dimensioning of the creepage distance the tracking
formation of the insulating material has to be considered. If not indicated contrary,
the CTI value of the insulating material is III a/b].
voltage can be used, if the creepage, the installation category and the degree of
pollution are known:
(table5.3)
The best voltage for a DC hipot is normally higher than the AC test voltage by a
factor of 1.414. A product that would be tested at 1500V AC would be tested at
2121V DC. For double-insulated products, the required test voltages may be much
52
higher, such as 2500 VAC or even 4000 VAC for a 120 VAC power tool. The
voltage is applied between the operating circuits and the chassis or ground (the
parts of a product that a consumer might touch or otherwise come in contact
with).The purpose of the test is to make sure that consumers do not receive an
electrical shock when they use the product, which might be caused by a
breakdown of the electrical insulation.
5.9.1.Arcing
53
arcing graph(figure 5.9)
Agency requirements specify a maximum current limit for a successful hipot test,
but they do not specify any minimum level. Omission of such a requirement,
however, means that under some conditions it is possible for a tester to pass
defective DUTs. Setting a maximum (high) current limit tells the hipot tester to
shut down when that current level is reached. Any value above the high current
limit is considered a Fail and any value below the set high limit is considered a
Pass. Setting
a minimum (low) current limit tells the hipottester to shut down if there is not the
specified minimum amount of current after the test is initiated Any value above
the low current limit is considered a Pass and any value below the set low limit is
considered a Fail.
54
Current v/s time for minimum current test pass and fail (figure 5.10)
All products that use an AC line source aspower have some associated leakage
current when the device is turned on and operating. This leakage current normally
flows from the AC line source through the ground path in theproduct and back to
earth ground through theground blade on the power cord. On products without a
ground blade or those in which the ground is malfunctioning, a potential can
develop on metal surfaces of the product.
If an individual then comes in contact with the exposed metal surface, this
individual then becomes the ground path for the product.Under this condition, a
certain amount of leakage current flows through the person exposed to the metal
surface. If the leakage current is extremely low, typically less than 0.5mA, the
person should not notice he/she is in the path of the current flow. At levels higher
than this, the person can experience a startle reaction or worse. For this reason,
products that do not use a ground on the power cord generally are limited to a
maximum leakage current of 0.5mA or less. Products that exceed this level
normally have a ground on the power cord to conduct the leakage current back to
ground, thereby protecting a person who comes in contact with any exposed metal
on the product. Limits on leakage current are significantly less on medical
products.
The leakage current discussed here is different from the measurement of leakage
current during a dielectric withstand or hipot test. During a dielectric withstand
test, a high voltage generally greater than 1000V is applied between the hot and
neutral lines and the ground of the DUT. The leakage current is then measured. In
a leakage current test, the product is on and operating via standard line voltage,
such as 120VAC. The leakage current is then measured using a special circuit that
simulates the impedance of the human body.
55
Test procedure to simulate the effect of thermal stresses which may be produced
by heat sources such as glowing elements or overloaded resistors, for short
periods, in order to assess the fire hazard by simulation technique.
The test specimen is considered to have satisfactorily withstood the test if there is
no ignition of the test specimen, or
a) if flames or glowing of the test specimen extinguish within 30 s after removal
of the glow wire and
b) there is no ignition of the wrapping tissue.
5.12.Cables Testing
5.12.1.Polyvinyl chloride compound (PVC)[ insulating and sheathing
materials]
Combination of materials suitably selected, proportioned and treated, of which the
characteristic constituent is the plastomer polyvinyl chloride or one of its
copolymers. The same term also designates compounds containing both polyvinyl
chloride and certain of its polymers.
5.12.2.Definitions relating to the tests
Type tests (symbol T)
56
Tests made on samples of completed cable or components taken from a completed
cable, adequate to verify that the finished product meets the design specifications.
Rated voltage
U○ being the r.m.s value between any insulated conductor and "earth" (metal
covering of the cable or the surrounding medium);
U being the r.m.s value between any two-phase conductors of multicore cable or
of a systemof single-core cables.
5.12.3 Marking
Cables shall be provided with an indication of the manufacturer, which shall be
either an identification thread or a repetitive marking of the manufacturer's name
or trade-mark.
Cables for use at a conductor temperature exceeding 70°C shall also be marked
either with the code designation or with the maximum conductor temperature.
Marking may be printed or by reproduction in relief on or in the insulation or
sheath. Each specified mark shall be regarded as continuous if the distance
between the end of the mark and beginning of the next identical mark does not
exceed
-550mm if the marking is on the outer sheath of the cable;
-275mm if the marking is
a) on the insulation of an unsheathed cable;
b) on the insulation of sheathed cable;
c) on a tape within a sheathed cable.
5.12.4.Legibility
All marking shall be legible .The colours of the identification threads shall be easy
to recognize or safety made recognizable, if necessary, by cleaning with petrol or
other suitable solvent.
5.12.5.Core identification
Ientification of the cores of a cable shall be achieved by the use of coloured
insulation or other suitable method. Each core of a cable shall have only one
colour, except the core identification by combinations of the colours green-and-
yellow.The colours red, grey, white and when not in combination, green and
yellow, shall not be used for any multicore cable.Colours scheme
The preferred colour scheme for flexible cables and single-core cables is :
(table 5.4)
57
Cable type Color
single-core cable no preferred cable colour scheme
two-core cable no preferred colour scheme
three-core cable either green-and-yellow, light blue,
brown, or light blue, black brown;
5.12.6. Filter
For each type of cable, the particular specificationspecify whether that cable
includes filters or whether the sheath or inner covering may penetrate between the
cores, thus forming a filling.
The filters shall fill the spaces between the cores giving the assembly a practically
circular shape. The filters shall not adhere to the cores. The assembly of cores and
filters may be held together by a film or a tape.
5.12.7 Thickness
The mean value of the thickness shall not be less than the specified value for each
type and size of cable shown in the tables of particular specifications However,
the thickness at any place may be less than the specified value provided that the
difference does not exceed 0.1mm+ 15% of the specified value, unless otherwise
specified
Cable tests
(table 5.5)
58
Set Min. IR value 2MΩ.
Value of insulation is calculated by
R= 0.0367*log10(D/d)
2 Provision covering constructional and dimensional characteristics
59
Chapter 6: Major Work
6.1.Switching adapter
Switching adapter is tested under IEC 60950-1 at different clauses according to
adapter manufacturing.
1. (Cl. No.1.5).Components
C1, Capacitor bridging primary & secondary insulation is used which is safety
certified. Discharge of capacitors in equipment is not in primary since no
capacitor in d.c mains supply.Resistors bridging double insulation or
reinforced insulations s used between the a.c. mains supply and circuits
connected to an antenna or coaxial cable.Components used in equipment for
IT power distribution systems.
60
Figure 6.1.1.1 internal view of adapter
Power rating and identification markings are shown Input 130-270V, 50Hz,
50Hz, 0.3A. Power outlets on the equipment is not used. Rated voltage(s) or
voltage ranges(s) (V) are 130-270Vac. Rated current (mA or A) is 1000mA.
61
multiple power sources is not needed due to single supply. Marking is durable
and legible on adapter.
TNV circuit that is in the equipment and to which the accessible area of
contact is limited and that is so designed and protected that, under normal
operating conditions and single fault conditions , the voltages do not exceed
specified limit values i.e. no TNV circuit is required.
6. (Cl. No.2.5).Limited power sources
Limited current 0.7mA peak, Peak working voltage 381V peak, RMS working
voltage 270V~ max. observed by supplying rated voltage at raped frequency.
Different current ,voltage and power ratings are are noted at by varrying
parameters to get Maximum and Minimum output voltage (V), Maximum and
Minimum output current (A) and Maximum and Minimum apparent power (VA)
values as well as r.m.s and peak values of current and voltage.
Functional earthing is not available due tothe Functional earthing either separated
from hazardous voltages by double or reinforced insulation or by protectively
earthed screen or conductive part separated by at least basic insulation, or safely
connected to Protective Bonding Conductorr. In adapt no such insulation is present.
Under this clause basic requirements: The built-in device fuse provides over
current protection. OR The equipment is protected by the built-in circuit
breaker.
Short-circuit backup protection is measured from multimeter in case fault
simulated.
62
Multimeter
No safety interlock provided for moving parts, switches and relays and their related
circuits, separation distances for contact gaps and their related circuits,
electric strength test, mechanical actuators.
63
the surface of the insulation . One additional term that is related to these
definitions in a high voltage design is “bounding surface.”
Creepage and clearance are measured by digital vernier caliper which gives
accurate measure of distance.
Solid insulation consider for PCB & Enclosure is Thin sheet material Used in
sealed type transformer. Uncoated printed boards are used.
Current rating and overcurrent protection have Adequate cross sectional area of
wire used interconnecting cable (SELV Connection). Means of connection to
an a.c. mains supply is direct plug in Switching Adapter and no d.c. mains
64
supply. Wiring terminals for connection of external conductors of switching
Adaptor is direct plug in equipment.
Appliance inlets: Are so Located that parts at hazardous voltage are not
accessible during insertion or removal of the connector, connector can be
inserted without difficulty and after insertion of the connector, the equipment is
not supported by the connector for any position of normal use on a flat surface
( appliance inlets complying with IEC 60309 or IEC 60320 considered to
comply with this requirement.
A unit having a mass of 7 kg or more shall not fall over when tilted to an
angle of 10° from its normal upright position. Alternatively, the unit is
placed in its intended position of use on a plane, inclined at an angle of
10° to the horizontal, and then rotated slowly through an angle of 360°
about its normal vertical axis.
65
A floor-standing unit shall not fall over when a constant downward force
of 800 N is applied at the point of maximum moment to any horizontal
surface of at least 125 mm by at least 200 mm, at a height up to 1 m
from the floor.
Fall test/ Drop test is very essential since many times movable/portable
specimens fall so it is tested weather specimen will break in short fall
or not. Hence at 4-5m of height specimen is droped.
66
No ionizing radiation generated
Flammable liquids not used
No Human exposure to ultraviolet radiation used
No lasers or laser diodes used
Low Power LED for indication
67
Parts not requiring a fire enclosure for Motors, Transformer, PVC Cable
Enclosure material passing the glow-wire test at 550 °C according to
IEC 60695-2-11 is acceptable as an alternative to check the cover
weather it will catch flame or not.
Plastic materials of a FIRE ENCLOSURE located less than 13mm
through air from non-arcing parts which, under any condition of normal
or abnormal operation, could attain a temperature sufficient to ignite the
material, shall be capable of passing the test of IEC 60695-2-20.
The average time to ignition of the samples shall be not less than 15sec.
If the sample melts through without igniting, the time at which this
occurs is not considered to be the time to ignition.
This test is carried under HVDC for dielectric test. For plastic body 1.5kv-3kv
and for metal body 1kv-2kv is supplied for 60seconds. This will show the
specimen will bear the high voltage.
During the tests no flame in the equipment, no molten metal emitted. After the
tests Meet the Electric strength test.
6.2.Test of cable
This test id used for measure the Checking of the durability of colors and
markings by rubbing with wool cloth. Measurement of insulation thickness of
sheath is done by Profile projector or measuring microscope of at least 10 x
magnification.
68
Profile Projector
Piece is placed between the mid of the profile projector then dimensions are
taken.
Inside the piece surface is not smooth so dimensions are measured from
broad and narrow sides. Different readings are taken by rotating at 60°. 5-6
measurements are noted .Average of measured dimension should be in range
of 0.642 to 0.455mm.through this test radius is calculated which give area of
conductor(A).
𝐴 = 𝑁𝜋𝑟 2
Where N= no. of conduction wires
69
Now wire resistance is measured
R20= Rt*Kt*1000/L
Where,
K=0.984(constant)
R20 = Resistance at 20C
Rt = Resistance at room temperaturC
Kt = Correction factor corresponding to room temperature C
70
Bath tub
71
Check sample if cracked sample is failed if not then place it in heat for 20h
and weight(w2)
= ………..N
where:
k is a coefficient which shall be specified in the standard for the type of cable if a
value is given, or, if a value is not specified in the cable standard, shall be k = 0.6
for flexible cords and cores of flexible cables
= average thickness of the test piece, in mm,
D = mean outer diameter of the test piece, in mm
Impression of blade shall not exceed 50%
72
There shall not be any cracks over insulation after pre conditioning for16 hr at –
15 C. wire is rolled over mandrel tightly and then crack is checked on insulation.
if any crack occur then test is fail otherwise fail .These cracks are due to change in
temperature %age Elongation at break shall be 20%min.
In this test a hammer is placed on wire rolled on mandrl and again cracks are
measured since in cold area when air or other circumstances press the wire
with force/pressure then wire will resist that or not.
There shall not be any cracks over insulation.
73
11. Mechanical strength of completed cable (flexing test)
12. Tensile Strength & Elongation at Break (Before & after ageing) Insulation
Accelerated ageing takes place in ovens using prescribed temperature, air flow
and air disturbance. The temperature and duration of ageing is dependent on the
type of compound and its temperature rating, for example, a V-90 compound will
be aged at 115 ± 2°C for 504 hours.
Test is done with different samples of 10mm length. copper wire is removed
from inside. The test consists of a comparison of the physical characteristics of
tensile and elongation compound based on before- and after-ageing values,
effectively reporting loss in mechanical properties.
74
This test is done in sense of climatic conditions which a wire will bear when
used.
Cable of 10mm
6.3 Printer
The sample of thermal printer , model th200i is complying with all relevant
clauses of is IS 13252 (part 1) and IEC 60950.
1. (Cl. No.1.5).component
75
Internal View Of Printer PCB With Component
76
Marking On Printer
No access with test finger to hazardous voltage circuit. Voltages under fault
conditions are in SELV limits not exceeded under normal condition
Safety Sign
TNV circuit that is in the equipment and to which the accessible area of
contact is limited and that is so designed and protected that, under normal
operating conditions and single fault conditions , the voltages do not exceed
specified limit values i.e. no TNV circuit is required.
77
EUT is Class III appliance, working at SELV supply derived from Safety
certified AC-DC adapter. Secondary functional earthing is separated to primary
by reinforced or double insulation
PE connections make earlier and break later than the supply connections in
following:
a plug on a power supply cord;
an appliance coupler.
Safety certified AC/DC adapter used in printer all other parts are working at
SELV supply. Considered Pollution degree II
Creepage distances and Clearances Safety certified AC/DC adapter used.
78
Insulation part of safety certified AC/DC adapter used. Minimum Thickness
of insulation 0.4mm in wound components. Uncoated printed boards of PCB.
Appliance inlets: Are so Located that parts at hazardous voltage are not
accessible during insertion or removal of the connector, connector can be
inserted without difficulty and after insertion of the connector, the equipment is
not supported by the connector for any position of normal use on a flat surface
( appliance inlets complying with IEC 60309 or IEC 60320 considered to
comply with this requirement.
Rated current (A), cross-sectional area (mm²) is 6A, 0.75 mm2 respectively.
Current rating and overcurrent protection have Adequate cross sectional area of
wire used interconnecting cable (SELV Connection). Means of connection to
an a.c. mains supply is direct plug in Switching Adapter and no d.c. mains
supply. Wiring terminals for connection of external conductors of switching
Adaptor is direct plug in equipment.
79
11. (Cl. No.3.4). Disconnection From The Mains Supply
To disconnect device or a device shall be provided to disconnect the
equipment from the mains supply for servicing is direct plug in Switching
Adaptor. It is not a three phase equipment so No parts remains energized
when the disconnect devices is removed,
A unit having a mass of 7 kg or more shall not fall over when tilted to an
angle of 10° from its normal upright position. Alternatively, the unit is
placed in its intended position of use on a plane, inclined at an angle of 10°
to the horizontal, and then rotated slowly through an angle of 360° about its
normal vertical axis.
A floor-standing unit shall not fall over when a constant downward force of
800 N is applied at the point of maximum moment to any horizontal surface
of at least 125 mm by at least 200 mm, at a height up to 1 m from the floor.
80
Adequate mechanical strength with no hazards when subjected to
unexpected handling.
Steady force test, 10 N
Steady force test, 30 N
Steady force test, 250 N
Fall test/ Drop test is very essential since many times movable/portable
specimens fall so it is tested weather specimen will break in short fall
or not. Hence at 4-5m of height specimen is droped.
81
No hazardous moving part in operator access area.
No misconnection likely to create hazard all are tightly attached and stick
with glue with full insulation.
Low power LEDs are used for indication purpose
82
Enclosure material passing the glow-wire test at 550 °C according to
IEC 60695-2-11 is acceptable as an alternative to check the cover
weather it will catch flame or not.
Plastic materials of a FIRE ENCLOSURE located less than 13mm
through air from non-arcing parts which, under any condition of normal
or abnormal operation, could attain a temperature sufficient to ignite the
material, shall be capable of passing the test of IEC 60695-2-20.
The average time to ignition of the samples shall be not less than 15sec.
If the sample melts through without igniting, the time at which this
occurs is not considered to be the time to ignition.
This test is carried under HVDC for dielectric test. For plastic body 1.5kv-3kv
and for metal body 1kv-2kv is supplied for 60seconds. This will show the
specimen will bear the high voltage.
During the tests no flame in the equipment, no molten metal emitted. After the
tests Meet the Electric strength test.
6.4.Electric Fence
Electric fence takes electric energy from fence energiser and delivers to fence as
pulses under IEC 60335-1:2010 (Fifth Edition).
83
stream flows through the body of the animal and back through the ground to
the earth return terminal of the energiser.
84
Marking On Fence Enerzisser
For fixed appliances, name, trademark or identification mark and model or type
reference visible after installation according to the instructions. No earthing
symbol present show below:
Supply terminals for connection of the battery clearly indicated by symbols IEC
60417-5005 are + & - symbols are present for connection to battery
85
4. (Cl. No.7.12). Instructions for safe use provided
Instructions for class III appliances state that it must only be supplied at
SELV, unless it is a battery-operated appliance, the battery being charged
outside the appliance.Suitable for connection to the mains consisting of an
impulse generating circuit (battery).It is stated that during charging, batteries
must be placed in a well-ventilated area.
Stationary appliances not fitted with means for disconnection from the supply
mains having a contact separation in all poles that provide full disconnection
under overvoltage category III, the instructions state that means for
disconnection must be incorporated in the fixed wiring in accordance with the
wiring rules. Operated by battery or solar energy/Not to be connected to
mains.
86
through openings in earthed metal enclosures having a non-conductive
coating: no contact with live parts
Accessible part not considered live if safety extra-low a.c. voltage:
peak value not exceeding 42.4 V or safety extra-low d.c. voltage: not
exceeding 42.4 V.
Live parts protected at least by basic insulation before installation or
assembly.
Class II appliances and constructions constructed so that there is
adequate protection against accidental contact with basic insulation
and metal parts separated from live parts by basic insulation only
Largest type of battery is used and discharged at 0.75 times nominal value.
Temperature rises, other than of windings, determined by thermocouples.
During this temperature rise atleast 2 temperature rise are noted by giving
load through applying 2 different high resistances.
87
Motor-operated appliances operated under normal operation at most
unfavourable voltage between 0.94 and 1.06 times rated voltage (V) operated
at 12.72V DC.
Leakage current not excessive and electric strength adequate due to Not a
mains operated appliance. Hence Heating appliances operated at 1.15 times
the rated power input (W) and Protective impedance and radio interference
filters disconnected before carrying out the tests.
For class 0, class II and class III appliances, and class II constructions,
leakage current measured by means of the circuit described in figure 4 of
IEC 60990.[ Metal Encase Class II Appliance].
88
No trace of water on insulation which can result in a reduction of clearances
or creepage distances below values specified in clause 29. Water valves
containing live parts in external hoses for connection of an appliance to the
water mains tested as specified for IPX7 appliances.
Spillage of liquid does not affect the electrical insulation. Spillage solution
comprising water containing approximately 1% NaCl and 0.6 % rinsing
agent.
Leakage current not excessive and electric strength adequate at 0.07A and
1kV. This test is carried by HVDC instrument. Tests carried out at room
temperature and not connected to the supply. Single-phase appliances: test
voltage 1.06 times rated voltage (V): Class II appliance is working at 12V DC
Supply. Test voltage applied between the supply cord and inlet bushing and
cord guard and cord anchorage as specified.
89
Operating 168 h at – 15 °C (500 Ω load for 84 h) and + 50 °C (500 Ω load for
84 h) with O/P terminals are loaded with a non inductive resistor of 500 Ω.
Measured characteristics as specified in 22.108 are within ± 10 %.
90
This fault condition is not applied between the two circuits of an optocoupler.
Each low power circuit is short-circuited by connecting the low-power point to the
pole of the supply source from which the measurements were made.
91
All edges or corners are rounded and smoothed. No exposed pointed
ends of self-tapping screws or other fasteners, likely to be touched by
the user in normal use or during user maintenance.
20. (Cl. No.22.2). Appliance provided with pins: no undue strain on socket-
outlets
Applied torque not exceeding 0.25 Nm i.e. no pins in appliance. Pull force of
50 N to each pin after the appliance has being placed in the heating cabinet;
when cooled to room temperature the pins are not displaced by more than 1
mm.
No risk of electric shock when touching the pins of the plug, for appliances
having a capacitor with rated capacitance equal to or greater than 0.1 F,
appliance being disconnected from the supply at the instant of peak voltage
34V.
Axial force 15 N applied for 1minute to parts, the shape being so that an axial
pull is unlikely to be applied.
92
No damage after 10 000 flexings for conductors flexed during normal
use
Adequate insulating lining provided inside a coiled spring, the turns
of which touch one another.
Not more than 10 % of the strands of any conductor broken .
no breakdown when a voltage of 2000 V is applied for 15 min
between the conductor and metal foil wrapped around the insulation .
Components not tested and found to comply with relevant IEC standard and
components not marked or not used in accordance with its marking, tested
under the conditions occurring in the appliance.Components can comply with
the requirements for clearances and creepage distances for functional
insulation in the relevant component standard. Capacitors likely to be
permanently subjected to the supply voltage and used for radio interference
suppression or for voltage dividing, comply with IEC 60384-14
93
Internal view of Fence Energizer
Clearances not less than the values specified in table 16, taking into account
the rated impulse voltage for the overvoltage categories for basic insulation
and functional insulation they comply with the impulse voltage test of clause
14. However, if the distances are affected by wear, distortion, movement of
the parts or during assembly, the clearances for rated impulse voltages of
1500V and above are increased by 0.5 mm and the impulse voltage test is not
applicable.
94
Clearances of reinforced insulation not less than those specified for basic
insulation , using the next higher step for rated impulse voltage. Clearances for
functional insulation are the largest values determined from rated impulse
voltage 500V.
95
Siren for Fence Energizer
6.5.Control Gear
This standard specifies performance requirements for electronic control gear for
use on d.c. supplies up to 1 000 V and a.c. supplies up to 1 000 V at 50 Hz with an
output frequency which can deviate from the supply frequency, associated with
LED modules according to IS 16103 (Part 1) : 2012 ‘LED modules for general
lighting: Part 1 Safety requirements’. Control gear for LED modules specified in
this standard are designed to provide constant voltage or current. Deviations from
the pure voltage and current types do not exclude the gear from this standard.
1. (Cl.No.2.1).Construction
96
Prepare a test specimen having thickness of at least 2.5 mm.Set the
temperature of oven to as specified in the specification, within tolerance ..
Place the test specimen on the approximate centre of the test specimen
support so that its upper surface is horizontal and the spherical part of
apparatus is pressed against this surface with a force of 20N.
Gently lower the pressure ball on to the approximate centre of the test
specimen. After 1 hour, remove the pressure ball from the test specimen
and within 10 s immerse the test specimen in cold water.
Immediately thereafter keep immersion for 6 min-2 min.Now remove the
test specimen from the water and eliminate all traces of water.Within 3
min of removal from the water measure dimension d, toone decimal place
using the profile projector or optical measuring instrument dimensiondis
the greatest dimension across the indentation caused by the pressure ball.
3. (Cl.No.5.1). Classification
4. (Cl.No.6.0). Marking
97
Mandatory Marking on Control gear shall be clearly marked as follows:
Circuit power factor, for example λ = 0.9 If the power factor is less than 0.95
leading, it shall be followed by the letter ‘C’, for example λ = 0.9 C.
A symbol which indicates that the control gear is a short-circuit proof type
(the symbol is underconsideration).
Marking Plate
For control gear having a non-stabilised output voltage, when supplied with
the rated supply voltage, the output voltage shall not differ by more than ±10
percent from the rated voltage of the LED modules; for control gear having a
stabilised output voltage when supplied at any supply voltage between 92
percent and 106 percent of the rated supply voltage ,t he output voltage shall
not differ by more than ±10 percent from the rated voltage of the LED
98
modules. Multiple load control gear shall be tested with both the minimum
and maximum load.
If the LED module or any additional control unit connected to the convertor
contain capacitors for control and/or driving circuitry on the modules, current
pulses may be generated when connecting the LED module to the control gear.
This shall not disturb the control gear overcurrent detection nor the starting
process of the control gear. Compliance requirement when connecting the
measurement circuit to the control gear, the detection device shall not trip.
Voltage surges superimposed on the output voltage shall not exceed the
values specified (values under consideration).
At rated voltage, the total circuit power shall not be more than 110 percent of
the value declared by the manufacturer, when the control gear is operated with
LED module(s).
The measured circuit power factor shall not be less than the marked value by
more than 0.05 when the control gear is operated on its rated wattage with
LED module(s) and the whole combination is supplied with rated voltage and
frequency.
99
At rated voltage, the supply current shall not differ by more than +10 percent
from the value marked on the control gear or declared in the manufacturer’s
literature, when that control gear is operated on its rated wattage with LED
module(s).
Control gear marked with the audio frequency symbol shall be tested in
accordance with A-3 using the circuit For every signal frequency between
400 Hz and 2 000 Hz, the impedance of the control gear when operated with
the rated LED module load at rated voltage and frequency shall be inductive in
characteristic. Its impedance in ohms shall be at least equal to the resistance of
the resistor which would dissipate the same power as the LED module control
gear combination when operating at its rated voltage and frequency.
The control gear impedance is measured with a signal voltage equal to 3.5
percent of the rated supply voltage(220-240 V) of the control gear. Between
250 Hz and 400 Hz, the impedance shall be at least equal to half the minimum
value required for frequencies between 400 Hz and 2 000 Hz.
13. (Cl. No.11.0). Operational Tests For Abnormal Conditions
a) Test without LED Module(s) Inserted : The control gear shall be supplied
with rated voltage for 1 h without LED module(s) inserted. At the end of this
test, the LED module(s) operate normally.
b)Tests for Short-Circuit Proof Control Gear : The control gear is short-
circuited for 1 h or until a protecting device opens the circuit. After these tests
and after restoration of a possible protecting device, the control gear function
normally.
100
The control gear shall be subjected to a temperature cycling shock test and a
supply voltage switching test as follows:
c) Supply Voltage Switching Test : At rated supply voltage the control gear shall
be switched on and off for 30 s. The cycling shall 4 IS 16104 : 2012 be
repeated 200 times with no load and 800 times with maximum load
conditions. LED modules failing during this test shall be replaced
immediately.
At the end of these tests the control gear shall operate an appropriate LED
module or LED modules correctly for 15 min.
d) Test Voltage and Frequency : Unless otherwise specified, the control gear to
be tested shall be operated at its rated supply voltage and frequency. When a
control gear is marked for use on a range of supply voltages, or has different
separate rated supply voltages, any voltage for which it is intended may be
chosen as the rated voltage.
e) Stability of Supply Voltage and Frequency : During the tests, the supply
voltage and the frequency shall be maintained constant within ±0.5 percent.
However, during the actual measurement, the voltage shall be adjusted to
within ±0.2 percent of the specified testing value.
Control gear pass all the test successfully. Only markimg plate has some
data and certified sign were missing that will be corrected by manufacturer.
101
Chapter 7: Conclusion
102
Chapter 8: References
[1] file:///C:/Users/kk/Downloads/60227-2.pdf
[2]https://www.google.co.in/search?biw=1366&bih=613&ei=SeYXW5XZNseo9
QPqz5DwD
A&q=testing+of++pvc+cables+according+to+iec60227&oq=testing+of++pvc+ca
bles+according+to+iec60227&gs_l=psy-ab.3...194067.195983.0.196801.5
[3] http://www.intertek.com/blog/2011/07-04-iec-60601-1/
[4] http://www.bis.org.in/sf/etd/ETD_WC_06072017
[5] http://www.stqc.gov.in/content/electronics-and-electrical-testing
[6] https://en.wikipedia.org/wiki/Consumer_electronics
[7]http://10.newegg.com/UploadFilesForNewegg/itemintelligence/ClearPond/is.1
6104.20121401470272583.pdf
Standards studied:
103