Submittal - (2019-01) SDS - Intelligent Touch Manager PDF
Submittal - (2019-01) SDS - Intelligent Touch Manager PDF
MODEL COMPATIBILITY:
Compatible with VRV and VRV LifeTM indoor unit models: FXAQ, FXDQ, FXEQ, FXFQ, FXHQ, FXLQ, FXMQ, FXMQ_MF,
FXNQ, FXSQ, FXTQ, FXUQ, FXZQ, CXTQ, VAM*
Compatible with SkyAir indoor unit models: FAQ, FBQ, FCQ, FHQ, FTQ
Compatible with Single Zone/Multi Zone/SkyAir system indoor unit models:
FDMQ, FFQ_Q
FFQ_LVJU with the use of the Interface Adaptor DTA112BA51.
FTXS, CTXS, CTXG, FTXG, FDXS, CDXS, FVXS with the use of the DIII-Net Adapter KRP928BB2S
FTX, FTXN, FTK, and FTKN with the use of the DIII-Net Adapter KRP928BB2S and an Interface adaptor
KRP067A41E/KRP980B1/KRP980B2E
* iTM BACnet Server Gateway Option is not compatible with VAM unit
* The outdoor operational data is available for the following VRV IV outdoor unit models only: RXYQ_TATJU, RXYQ_TAYDU,
REYQ_TATJU, and REYQ_TAYDU
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 1 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
OPTIONS:
Software Options:
(1)
o Power Proportional Distribution (PPD) Option (DCM002A71)
o BACnet Client Option Software (DCM009A51)
(2)(3)
o BACnet/IP Server Gateway Option (DCM014A51)
Hardware Options:
o iTM Plus Adapter (DCM601A72) for expanding indoor unit groups up to 512 groups (1024 indoor units)
o WAGO I/O basic kit (60359653) and I/O modules for controlling/ monitoring of external equipment via Di, Do, Ai,
Ao and Pi
o Digital Input (DEC101A51-US2) for monitoring of external equipment
o Digital Input/Output (DEC102A51-US2) for controlling / monitoring of external equipment
Notes:
(1) The Power Proportional Distribution (PPD) option supplies the user with a reasonably calculated apportionment of the total
power consumption by the Daikin air-conditioning system to individual units on the system. Because input to the PPD
includes measured pulses in the refrigerant system and because the air-conditioning system includes a number of variables,
to include operating temperatures and pressures, piping lengths, heat exchange rates and others, no meter-type
apportionment of individual user’s consumption can be made. However, the PPD feature provides an apportionment
methodology that uses highly advanced technology as applied to the many variables in the air-conditioning system.
(2) The BACnet Server Gateway option cannot use together with the BACnet Client software option and the PPD option.
(3) BACnet/IP Server Gateway option is not compatible with the VAM unit.
FEATURES:
1. Management size - up to 512 indoor unit groups (1024 indoor units).
a. The iTM can manage one (1) DIII-Net system which can have up to 64 indoor unit groups (128 indoor units).
b. The iTM can manage up to eight (8) DIII-Net systems with the addition of the iTM Plus Adapter which can manage
one (1) DIII-Net system each. This means up to seven (7) iTM adapters can be daisy chained to the iTM.
2. Control / Monitoring
a. Independent Cool and Heat setpoints
i. Setpoint tracking for full range of setpoint differentials
b. Independent Cool and Heat Setback setpoints (unoccupied)
i. Adjustable timed override
o
c. Room temperature displayed in 0.1 F
d. Scheduling: 7, 5+2, 5+1+1, 1 (Everyday) weekly patterns
i. Optimum Start
e. Auto-changeover: Fixed, Individual, Average, and Vote
i. Weighted demand (0-3) configurable for Average and Vote methods
o
ii. Adjustable (1-4 F) Primary and Secondary changeover bands
3. Web Accessibility
a. Web and Alert Email function standard with iTM
b. All iTM configuration/setup can be done through Web Option or touch screen
4. Visual Navigation Screen
a. Floor plan layout view is available
b. Graphical User Interface (GUI) for BACnet IP Client management points
5. Easy installation
a. Wall mount and flush mount installation.
b. Automatic indoor unit registration and indoor unit model detection.
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 2 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
6. Easy Engineering
a. iTM can be configured off site via Pre-setting Tool.
b. All data can be uploaded and downloaded by USB flash drive.
7. Building facilities management
a. The iTM is equipped with 3 digital/pulse inputs and the iTM Plus Adapter comes equipped with 4 digital/pulse
inputs.
b. Building ancillary equipment can be connected by using the WAGO I/O system (optional).
i. I/O configuration for Digital Input, Digital Output, Analog Input, Analog Output and Pulse Input.
c. BACnet IP Client management points with BACnet Client option (optional).
i. AI, AO, AV, BI, BO, BV, MI, MO and MV
d. Tenant billing with PPD option (optional).
8. BACnet Client (Optional)
a. Monitor and control equipment and sensors connected to a BACnet server via BACnet IP.
i. Up to 50 BACnet IP servers can be connected
9. BACnet Server Gateway (Optional)
1. Provide function to monitor outdoor units and control indoor units by BMS via BACnet IP.
i. Up to 128 BACnet Device IDs (including indoor unit groups and outdoor units)
ii. Up to 4000 BACnet objects
iii. Virtual BACnet router function embedded
i. Individual and configurable Device ID for each indoor unit group and/or outdoor unit system.
10. History
a. All errors, operations, automatic controls and status changes are stored in history (up to 500,000 items).
11. D-Net compatible (Service option)
a. Remote monitoring of VRV equipment status and reporting
12. Operation Data
a. Operation data are stored in the iTM every minute for the last 5 days.
i. Indoor and outdoor unit operation data.
ii. BACnet Client management data points (AI, AO, AV, BI, BO, BV, MI, MO and MV).
iii. WAGO IO system data points (External DI, DIO, PI, AI and AO).
b. The operation data can be exported through the iTM web browser or a USB drive based on a specified period.
(See iTM BACnet Server points list below for IDU/ODU operational data list)
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 3 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
WIRING SPECIFICATION:
Specifications of Communication Cabling
DIII-Net
Type 2-conductor, stranded, non-shielded copper cable / PVC of vinyl jacket
Size AWG 18-2
Total Length Maximum wiring distance between units 3,280 ft. Total wire length 6,560 ft.
iTM Plus Adapter
Type 2-conductor, stranded, non-shielded copper cable / PVC of vinyl jacket
Size AWG 18-2
RS485 Length Maximum distance between iTM and furthest iTM Plus Adapter 150 ft.
Total Length Maximum wiring distance between units 3,280 ft. Total wire length 6,560 ft.
WAGO
Type 2-conductor, stranded, non-shielded copper cable / PVC of vinyl jacket (CPEV or FCPEV)
Size 2 Wire AWG 24 - 18 stranded
Total Length Maximum wiring distance between iTM and Bus Coupler 1640 ft.
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 4 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
Indoor unit monitoring points (one set of points per indoor unit group):
Point Name Point Description
Unit On_Off Status Monitors if the indoor unit fan is On or Off
Monitors whether or not the indoor unit is operating normally, and issues an alarm if the indoor
Alarm Status
unit has a malfunction. Error Code is shown in the description.
Room Temperature Monitors and displays the room temperature.
Unit On Details Indoor unit details operation Off - Normal (ON) - Override - Setback
Filter Sign Status Monitors filter run time and provides service alert.
Indoor Fan Status Monitors if the indoor unit fan is On or Off
Communication Status Monitor if the communication is Normal or in Alarm
Thermo-on Status Monitors whether or not the indoor unit is actively cooling or heating.
Compressor Status Monitors if the compressor of the outdoor unit is On/Off/Defrost
Aux Heater Status Monitors if the external heater controlled by the indoor unit is operating.
Changeover Option Monitor if iTM changeover logic is Active.
Return Air Temperature Monitors and displays the return air temperature.
Discharge Air Temperature Monitors and displays the discharge air temperature of the FXMQ_PB indoor unit only.
Liquid Pipe Temperature Monitors and displays the liquid pipe temperature.
Gas Pipe Temperature Monitors and displays the gas pipe temperature.
EV Position Monitors and displays the expansion valve position.
Monitors if the freeze protection is active (For FXEQ_P, FXFQ_T, FXTQ_TA, FXUQ_P,
Freeze Protection
FXZQ_TA, FXSQ_TA, CXTQ_TA indoor unit only).
Indoor unit monitoring and control points (one set of points per indoor unit group):
Point Name Point Description
Occupancy Mode Set the occupancy of the indoor unit Occupied , Unoccupied or Standby
Operation mode Set Cool - Heat -Fan -Dry operation mode. for the indoor unit and monitors the latest mode
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 5 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
Occ Cooling Setpoint Sets the occupied cooling setpoint of the indoor unit and monitors the latest setpoint value.
Occ Heating Setpoint Sets the occupied heating setpoint of the indoor unit and monitors the latest setpoint value.
Unocc Cooling Setpoint Sets the unoccupied cooling setpoint of the indoor unit and monitors the latest setpoint value.
Unocc Heating Setpoint Sets the occupied heating setpoint of the indoor unit and monitors the latest setpoint value.
Max Cooling Setpoint Sets the maximum cooling setpoint of the indoor unit and monitors the latest setpoint value.
Min Cooling Setpoint Sets the minimum cooling setpoint of the indoor unit and monitors the latest setpoint value.
Max Heating Setpoint Sets the maximum Heating setpoint of the indoor unit and monitors the latest setpoint value.
Min Heating Setpoint Sets the minimum heating setpoint of the indoor unit and monitors the latest setpoint value.
Min Setpoint Differential Set the minimum differential value between cooling and heating setpoint and monitor the
(Cooling & Heating) latest differential value.
Cooling & Heating Setpoint
Enable or disable iTM setpoint tracking mode.
Tracking Mode
Fan speed Sets the indoor unit fan speed and monitors the latest setting
Timed Override Operation Enable or disable iTM override timer
Remote Controller Prohibit
Permits or prohibits the remote controller to control the indoor unit's On/Off.
(On_Off)
Remote Controller Prohibit
Permits or prohibits the remote controller to control the indoor unit's Operation mode.
(Operation Mode)
Remote Controller Prohibit
Permits or prohibits the remote controller to control the indoor unit's Setpoint.
(Setpoint)
Filter Sign Reset Clears the filter sign status.
Forced Thermo-off Force the indoor unit to stop actively cooling or heating.
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 6 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
M_Evaporating Temperature Monitors and displays the evaporating temperature (Master Module)
M_Inverter Compressor 1 Speed Monitors and displays the speed of the inverter compressor1 (Master Module)
M_Inverter Compressor 2 Speed Monitors and displays the speed of the inverter compressor2 (Master Module)
M_Fan Step Monitors and displays the fan step (Master Module)
M_EV Position 1 Monitors and displays the position of the expansion valve1 (Master Module)
M_EV position 2 Monitors and displays the position of the expansion valve2 (Master Module)
M_Hot Gas Temperature (Compressor 1) Monitors and displays the hot gas temperature of the compressor1 (Master Module)
M_Hot Gas Temperature (Compressor 2) Monitors and displays the hot gas temperature of the compressor2 (Master Module)
M_Liquid Pipe Temperature Monitors and displays the liquid pipe temperature (Master Module)
M_Liquid Pipe Temperature (HX Upper) Monitors and displays the liquid pipe temperature for the upper HX (Master Module)
M_Liquid Pipe Temperature (HX Lower) Monitors and displays the liquid pipe temperature for the lower HX (Master Module)
M_Liquid Pipe Temperature (De-Icer) Monitors and displays the liquid pipe temperature for the de-icer (Master Module)
M_Gas Pipe Temperature (HX Upper) Monitors and displays the gas pipe temperature for the upper HX (Master Module)
M_Gas Pipe Temperature (HX Lower) Monitors and displays the gas pipe temperature for the lower HX (Master Module)
M_Suction Temperature Monitors and displays the suction temperature (Master Module)
M_Compressor Suction Temperature Monitors and displays the compressor’s suction temperature (Master Module)
M_Subcool Inlet Temperature Monitors and displays the subcool inlet temperature (Master Module)
M_Subcool Outlet temperature Monitors and displays the subcool outlet temperature (Master Module)
M_Subcool EV Position Monitors and displays the subcool expansion valve position (Master Module)
S1_Condensing Pressure Monitors and displays the condensing pressure (Sub Module1)
S1_Evaporating Pressure Monitors and displays the evaporating pressure (Sub Module1)
S1_Condensing Temperature Monitors and displays the condensing temperature (Sub Module1)
S1_Evaporating Temperature Monitors and displays the evaporating temperature (Sub Module1)
S1_Inverter Compressor 1 Speed Monitors and displays the speed of the inverter compressor1 (Sub Module1)
S1_Inverter Compressor 2 Speed Monitors and displays the speed of the inverter compressor2 (Sub Module1)
S1_Fan Step Monitors and displays the fan step (Sub Module1)
S1_EV Position 1 Monitors and displays the position of the expansion valve1 (Sub Module1)
S1_EV position 2 Monitors and displays the position of the expansion valve2 (Sub Module1)
S1_Hot Gas Temperature (Compressor 1) Monitors and displays the hot gas temperature of the compressor1 (Sub Module1)
S1_Hot Gas Temperature (Compressor 2) Monitors and displays the hot gas temperature of the compressor2 (Sub Module1)
S1_Liquid Pipe Temperature Monitors and displays the liquid pipe temperature (Sub Module1)
S1_Liquid Pipe Temperature (HX Upper) Monitors and displays the liquid pipe temperature for the upper HX (Sub Module1)
S1_Liquid Pipe Temperature (HX Lower) Monitors and displays the liquid pipe temperature for the lower HX (Sub Module1)
S1_Liquid Pipe Temperature (De-Icer) Monitors and displays the liquid pipe temperature for the de-icer (Sub Module1)
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 7 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
S1_Gas Pipe Temperature (HX Upper) Monitors and displays the gas pipe temperature for the upper HX (Sub Module1)
S1_Gas Pipe Temperature (HX Lower) Monitors and displays the gas pipe temperature for the lower HX(Sub Module1)
S1_Suction Temperature Monitors and displays the suction temperature (Sub Module1)
S1_Compressor Suction Temperature Monitors and displays the compressor’s suction temperature (Sub Module1)
S1_Subcool Inlet Temperature Monitors and displays the subcool inlet temperature (Sub Module1)
S1_Subcool Outlet temperature Monitors and displays the subcool outlet temperature (Sub Module1)
S1_Subcool EV Position Monitors and displays the subcool expansion valve position (Sub Module1)
S2_Condensing Pressure Monitors and displays the condensing pressure (Sub Module2)
S2_Evaporating Pressure Monitors and displays the evaporating pressure (Sub Module2)
S2_Condensing Temperature Monitors and displays the condensing temperature (Sub Module2)
S2_Evaporating Temperature Monitors and displays the evaporating temperature (Sub Module2)
S2_Inverter Compressor 1 Speed Monitors and displays the speed of the inverter compressor1 (Sub Module2)
S2_Inverter Compressor 2 Speed Monitors and displays the speed of the inverter compressor2 (Sub Module2)
S2_Fan Step Monitors and displays the fan step (Sub Module2)
S2_EV Position 1 Monitors and displays the position of the expansion valve1 (Sub Module2)
S2_EV position 2 Monitors and displays the position of the expansion valve2 (Sub Module2)
S2_Hot Gas Temperature (Compressor 1) Monitors and displays the hot gas temperature of the compressor1 (Sub Module2)
S2_Hot Gas Temperature (Compressor 2) Monitors and displays the hot gas temperature of the compressor2 (Sub Module2)
S2_Liquid Pipe Temperature Monitors and displays the liquid pipe temperature (Sub Module2)
S2_Liquid Pipe Temperature (HX Upper) Monitors and displays the liquid pipe temperature for the upper HX (Sub Module2)
S2_Liquid Pipe Temperature (HX Lower) Monitors and displays the liquid pipe temperature for the lower HX (Sub Module2)
S2_Liquid Pipe Temperature (De-Icer) Monitors and displays the liquid pipe temperature for the de-icer (Sub Module2)
S2_Gas Pipe Temperature (HX Upper) Monitors and displays the gas pipe temperature for the upper HX (Sub Module2)
S2_Gas Pipe Temperature (HX Lower) Monitors and displays the gas pipe temperature for the lower HX(Sub Module2)
S2_Suction Temperature Monitors and displays the suction temperature (Sub Module2)
S2_Compressor Suction Temperature Monitors and displays the compressor’s suction temperature (Sub Module2)
S2_Subcool Inlet Temperature Monitors and displays the subcool inlet temperature (Sub Module2)
S2_Subcool Outlet temperature Monitors and displays the subcool outlet temperature (Sub Module2)
S2_Subcool EV Position Monitors and displays the subcool expansion valve position (Sub Module2)
* Supported outdoor unit models (RXYQ_TATJU, RXYQ_TAYDU, REYQ_TATJU, and REYQ_TAYDU) only.
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 8 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
DIMENSIONS:
iTM:
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)
Page 9 of 10
Submittal Data Sheet
DCM601A71 – intelligent Touch Manager
Project Name:
Location: Approval:
Engineer: Date:
Submitted to: Construction:
Submitted by: Unit #:
Reference: Drawing #:
DOCUMENTATION:
Documentation available on www.daikincity.com and/or www.daikinac.com:
Submittal
Sales Brochure
Guide Specs
Installation Manual
Operation Manual
iTM BACnet Server Gateway
o Design Guide
o Sales Flyer
o Quick User Guide
iTM BACnet Client
o Sales Flyer
WAGO I/O basic kit and modules
o Submittal
o Installation Manual
o Sales Flyer
Daikin North America LLC, 5151 San Felipe, Suite 500, Houston TX, 77056
www.daikinac.com www.daikincity.com
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations)