Transformer
Transformer
0311
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 1 of 204
POWER TRANSFORMERS
ERECTION, COMMISSIONING,
OPERATION AND MAINTENANCE
MANUAL
FOR
POWER TRANSFORMERS
abcd
NAINI WORKS, P.O. NAINI,
ALLAHABAD - 211008
(UTTAR PRADESH, INDIA)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 2 of 204
POWER TRANSFORMERS
CONTENTS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 3 of 204
POWER TRANSFORMERS
1.0 GENERAL
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 4 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 5 of 204
POWER TRANSFORMERS
• Construction of the tank and cover are such that pockets for water
collection is avoided.
• The tank and cover are designed such that these can be transported
by railways/road/water as per customer specification.
1.1.5 CONSERVATOR
• Conservator is provided to take care of the expansion and
contraction of transformer oil, which takes place during normal
operation of the transformer.
• Wherever specified flexible separators or air cell if provided in the
conservator can prevent direct contact of air with the transformer oil.
• A smaller oil expansion vessel is provided for the On Load Tap
Changer.
• Magnetic oil level gauge is fitted on the main conservator which can
give alarm / trip in the event of the oil level falling below the pre-set
levels due to any reason.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 6 of 204
POWER TRANSFORMERS
internal pressure. Some times the explosion vent is provided with
double diaphragm such that the outer one remains intact even after
the inner one is ruptured. Rupturing of inside diaphragm can be
checked by viewing through the oil level gauge provided in between
the diaphragms.
1.1.7 GAS & OIL ACTUATED (BUCHHOLZ) RELAY
• Gas and oil actuated relay is fitted in the feed pipe from the
transformer tank to the expansion vessel for collection of gas, if
generated in the oil. The relay operates on the fact that almost every
type of fault in an oil immersed transformer gives rise to generation
of gas. This gas is collected in the body of the relay, and is used to
close the alarm switch. In the event of any severe fault, the sudden
increase in oil pressure causes an oil surge towards the expansion
vessel and this is used to close the trip contacts. This oil surge will
impinge on the flap fitted to the trip element causing it to rotate about
its axis and thus bringing the mercury switch to the closed circuit
position, which in turn operates the tripping device.
• In the event of serious oil loss from the transformer, both alarm and
trip elements operate in turn in the manner previously described for
gas collection.
• Two brass petcocks are fitted at the top of the relay body, the outlets
of which are threaded to take a bleed pipe if required for collection of
gas samples.
• In the pipe connection between On Load Tap Changer and its oil
expansion vessel a single float Oil Surge Relay is fitted. This relay
operates on the principle of oil surge impinging on a flap causing
operation of the mercury switch connected to the trip circuit. Gas
actuated alarm switch is eliminated because the gas generated
during normal tap changing operation will give unnecessary alarm.
1.1.8 SILICAGEL BREATHER
• Expansion and contraction of oil cause breathing action. The
silicagel-dehydrating breather absorbs any humidity in the air
breathed. An oil seal in the air intake prevents external moisture
being absorbed when no breathing occurs.
• The breather container is filled with silicagel crystals. It is arranged
such that the air breathed must pass through it. The desiccant
contains blue and white crystals. When the silicagel is fully active,
the blue crystals will have a deep blue colour and changes to pink as
it absorbs moisture. When saturated with moisture and the charge
contained should be replaced. The gel removed from the breather
may be arranged for regeneration and preserved for future use.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 7 of 204
POWER TRANSFORMERS
• The size of the breather is chosen such that it can operate effectively
over a period of six months approximately. The factors, which
influence the selection of size of the silicagel breather required for a
particular transformer, depend on many factors like, the oil quantity
in the transformer, the adsorption capacity of silicagel, the loading
pattern and the atmospheric conditions prevailing at site. The
loading pattern and the site conditions are difficult for the transformer
manufacturer to assess. Hence, the selection of breather is based
on certain assumptions and it is difficult to fix up a time schedule for
the regeneration of silicagel. It is advisable to have a periodic
inspection (say monthly) of the indicator so that the gel can be
regenerated or replaced as soon it is saturated with moisture.
1.1.9 WINDING TEMPERATURE INDICATORS
• The winding temperature relay indicates the winding temperature of
the transformer and operates the alarm, trip and cooler control
contacts. This instrument operates on the principle of thermal
imaging and it is not an actual measurement.
• Winding temperature indicator consists of a sensor bulb placed in oil
filled pocket in the transformer tank cover. The bulb is connected to
the instrument housing by means of two flexible capillary tubes. One
capillary is connected to the measuring bellow of the instrument and
the other to a compensation bellow. The measuring system is filled
with a liquid, which changes its volume with rising temperature.
Inside the instrument is fitted with a heating resistance which is fed
by a current proportionate to the current flowing through the
transformer winding.
• The instrument is provided with a maximum temperature indicator.
The heating resistance is fed by a current transformer associated to
the loaded winding of the transformer. (The heating resistance is
made out of the same material as that of the winding) The increase
in the temperature of the resistance is proportionate to that of the
winding. The sensor bulb of the instrument is located in the hottest
oil of the transformer, therefore, the winding temperature indicates a
temperature of hottest oil plus the winding temperature rise above
hot oil i.e. the hot spot temperature.
1.1.10 OIL TEMPERATURE INDICATOR
• The oil temperature indicator consists of a sensor bulb, capillary tube
and a dial thermometer, the sensor bulb is fitted at the location of
hottest oil. The sensor bulb and capillary tube are fitted with an
evaporation liquid. The vapour pressure varies with temperature and
is transmitted to a bourden tube inside the dial thermometer, which
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 8 of 204
POWER TRANSFORMERS
moves in accordance with the changes in pressure, which is
proportional to the temperature.
1.1.11 BUSHINGS
• The high voltage connections pass from the windings to terminal
bushings. Terminal bushings upto 36 kV class, 3150 Amps, are
normally of plain porcelain and oil communicating type. Higher
current rated bushings and bushings of 52 kV class and above will
be of oil impregnated paper condenser type. The oil inside the
condenser bushings will not be communicating with the oil inside the
transformer. Oil level gauge is provided on the expansion chambers
of the condenser bushings.
• Oil in the condenser bushing is hermetically sealed and it should not
be disturbed in normal operation. Oil level may be checked regularly
and any oil leakage should be reported to the bushing manufacturer
for immediate attention.
1.1.12 TAP CHANGER
• Tap changers of power transformer are specifically of two types-
1. On Load Tap changer
• In the case of off circuit tap changer, the tap changing takes place
only when the transformer is de-energised, but in the case of on load
tap changers the tap changing takes place when the transformer is
in operation. The tap changer can be designed for changing the
taps.
a. Manually
b. Automatically &
c. From remote
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 9 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 10 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 11 of 204
POWER TRANSFORMERS
♦ Do not apply any voltage or even high voltage megger when the
equipment is under vacuum.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 12 of 204
POWER TRANSFORMERS
1.2.2.2 MERCURY
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 13 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 14 of 204
POWER TRANSFORMERS
þ Attach the caution tags "DO NOT OPERATE THE SWITCHES"
while working on units, which are energised.
þ Make sure that the fire fighting equipment are available at the oil
treatment equipment as well as workplace and adjacent to the
transformer.
þ Fire fighting equipment should be checked regularly and should
have sufficient quantity of extinguishant.
þ Transformer tank, control cabinets etc. as well as oil treatment
equipment shall be connected with permanent earthing system
of the station.
þ Check and thoroughly investigate the transformer whenever any
alarm or protective device is operated.
þ Check air cell in conservator.
þ Attend leakage on the bushings.
þ Examine the bushings for dirt deposits and clean them
periodically.
þ Check the oil in transformer and OLTC for dielectric strength
and moisture content and take suitable action for restoring
quality.
þ Check the oil level in oil cup and ensure air passages are free in
breather. If oil is less make up the oil.
þ If inspection covers are removed or any gasket joint is to be
tightened, then tighten the bolts evenly to avoid uneven
pressure.
þ Check and clean the relay and alarm contacts. Check also their
operation and accuracy and if required change the setting.
þ Check the protection circuits periodically.
þ Check the pointers of all gauges for their free movement.
þ Clean the oil conservator thoroughly before erecting.
þ Check the OTI and WTI pockets and replenish the oil if required.
þ Gas filled storage of transformer at site should be limited to a
maximum of 3 months.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 15 of 204
POWER TRANSFORMERS
þ Check the door seal of the Marshalling box. Change the rubber
lining if required.
þ Ensure proper tightness of top terminal of condenser bushings
to avoid entry of rainwater.
þ Check oil level in condenser bushing, any discrepancy should
be reported immediately to the manufacturer.
þ Do jacking only at jacking pad.
1.3.2 DON'TS
x Do not take any fibrous material such as cotton waste inside
while repairing.
x Do not drop any tools / material in side.
x Do not stand on leads / cleats.
x Do not weld, braze or solder inside the tank.
x Do not weld any thing to the tank wall from outside.
x Do not weld any thing to the conservator vessel if Air cell bag is
inside.
x Do not smoke near the transformer.
x Do not use fibrous material for cleaning as it can deteriorate the
oil when mixed with it.
x Do not energise without thorough investigation of the
transformer whenever any alarm of protection has operated.
x Do not re-energise the transformer unless the Buchholz gas is
analysed.
x Do not re-energise the transformer without conducting all pre-
commissioning checks. The results must be compared with
factory test results.
x Do not handle the off circuit tap switch when the transformer is
energised.
x Do not energise the transformer unless the off circuit tap switch
handle is in locked position.
x Do not leave off circuit tap switch handle unlocked.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 16 of 204
POWER TRANSFORMERS
x Do not use low capacity lifting jacks / slings on transformer for
jacking / slinging.
x Do not change the setting of WTI and OTI alarm and trip
frequently. Setting should be done as per manufacturer's
instructions.
x Do not leave any connection loose.
x Do not meddle with the protection circuits.
x Do not leave marshalling box doors open, they must be locked.
x Do not switch off the heater in marshalling box except to be
periodically cleaned.
x Do not allow unauthorised entry near the transformer.
x Do not close any valve in pump circuit for taking stand by pump
and motor into circuit.
x Do not allow water pressure to exceed the oil pressure in oil to
water heat exchangers.
x Do not mix transformer oils of different make/ base, unless oil is
new and conforms fully to IS: 335.
x Do not continue with pink (wet) silicagel, this should immediately
be changed or reactivated.
x Do not store transformer in gas filled condition for more than
three months after reaching site. If storage is required for longer
duration, the main body should be filled up with oil.
x Do not leave tertiary terminals unprotected outside the tank.
x Do not allow WTI / OTI temperature to exceed 70°C during dryout of
transformer and filter machine temperature beyond 75°C
x Do not parallel transformers, which do not fulfil the conditions for
paralleling.
x Do not over load the transformers beyond limit specified in IS:6600.
x Do not leave secondary terminals of any CT open.
x Do not measure insulation resistance by using megger when the
transformer is under vacuum.
x Do not stand on any vessel, which is under vacuum.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 17 of 204
POWER TRANSFORMERS
2.1 GENERAL
• Depending on the restriction imposed by the weight and transport
dimensions, the transformer will be despatched either in oil filled or
nitrogen gas filled condition.
• In case of transformer despatched without oil, the transformer will be
pressurised with dry nitrogen gas to minimise the likelihood of
condensation or moisture entering the tank.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 18 of 204
POWER TRANSFORMERS
• Accessories and cooler are despatched separately. All oil pipes and
chambers are despatched in sealed condition to avoid entry of water
during transportation and storage.
2.2 PACKING
• When any internal part like tap changer, CT's etc. are removed from
the main body for transportation, they shall be despatched in tanks
filled with oil or dry nitrogen gas or suitable measures are taken so
that they do not absorb moisture.
• All fragile parts such as temperature indicators, oil level gauges etc.
shall be carefully packed to avoid breakage in transit.
• Air cell type conservator shall be despatched with air cell mounted
inside the conservator and inflated with air at a slightly positive
pressure so that it remains fully tight inside the conservator. This is
to avoid relative movement of air cell inside the conservator during
transit and to avoid damages to air cell during handling.
• All blanking plates, valves guards etc., which are used exclusively
for transportation are painted with a different colour shade than the
transformer (normally post office red) and shall be preserved for
future use.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 19 of 204
POWER TRANSFORMERS
2.3.2 JACKING
• For the purpose of jacking, only the jacking pads provided on the
tank are to be used. Capacity of Jacks should be at least 1.5 times
the weight of transformer. Put sufficient wooden/steel packing below
the jack to support the weight. Do not lift more than 30 mm at a time.
Use all jacks simultaneously. Jacks should not be left in the loaded
position for long time. Transformer should be handled only in the
normal upright position.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 20 of 204
POWER TRANSFORMERS
2.3.3 LASHING
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 21 of 204
POWER TRANSFORMERS
FIG. – 2.3
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 22 of 204
POWER TRANSFORMERS
• When oil is transported in tankers, there should be storage tanks of
sufficient capacity available at site. Such tanks should be fitted with
dehydrating breathers.
FIG. - 2.4
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 23 of 204
POWER TRANSFORMERS
(ii) For each stylus measure the length of the trace from centre line
in one direction to the end of the arc that extends farthest from
the centre line.
(iii) Use the table below to find equivalent 'g' levels in the designated
column (X column for 'x' axis shocks etc.)
X Y Z
mm space 2g 6g 6g 2g 6g
3 1 0.4 1.7 1.4 0.4 1.2
6 2 0.8 3.3 2.8 0.8 2.5
9 3 1.3 5.0 4.2 1.3 3.7
12 4 1.7 6.3 5.5 1.7 5.0
15 5 2.1 8.2 6.9 2.1 6.2
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 24 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 25 of 204
POWER TRANSFORMERS
3.0 STORAGE
3.1 RECEIVING MAIN UNIT AND ACCESSORIES
• When a transformer arrives at site a careful external inspection must
be made of the unit, its cooling system and all sealed components,
referring to the general arrangement drawing and the shipping list.
• Inspect all packing cases and loose components for damage or
missing items.
• Check whether the transformer has arrived at site with a positive gas
pressure in case of despatch without oil. In case of despatch of main
body in oil filled condition, the oil level should be checked. One
transport oil level gauge is welded near the top of the tank for
indicating the level of oil in the tank.
• Should the transformer arrive at site without pressure (owing to gas
leakage) it must be assumed that moisture has entered the tank and
that the moisture will have to be driven out. In such cases the
manufacturer’s advice must be sought.
• Confirm that case numbers match with the packing list. Check their
contents tally with the packing list if the packing case is damaged.
IMPORTANT:
• If any scratches or damage to the paint is noticed on receipt of Main
body or Accessories, touchup painting should be done immediately
over the damaged area. For procedures of touchup painting, refer to
“ Clause 4.22: Touchup Painting at site”.
3.1.1 REPORT OF DAM AGE PARTS ETC.
• If any damage is noticed, claim must be lodged with the insurance
agency and the matter must be reported promptly to the
manufacturer. The report should contain sufficient details of
damaged parts and extent of damage so that the cost of
replacement /rectification can be worked out.
3.1.2 INSPECTION OF MAIN UNIT GAS FILLED
• After receipt of consignment at site, gas pressure inside the tank and
the temperature at the time of measurement should be recorded.
The value obtained should be compared with the gas pressure
versus temperature chart furnished in the instruction manual. (Refer
fig.– 2.1 of chapter 2)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 26 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 27 of 204
POWER TRANSFORMERS
• Sufficient space is provided underneath for free flow of air and also
for lifting, jacking etc.
3.4 GAS FILLED STORAGE
• It is recommended to keep the transformer oil filled immediately after
receipt. If oil can not be filled immediately after receipt of main body,
it must be retained with dry nitrogen gas filled at a positive pressure
of 0.2 kg/ cm2 at about 200C. (Please ref. Fig.– 1 of Chapter 2 for
Pressure Vs Temperature Chart).
• The duration of gas filled storage should be limited to 3 months from
the receipt of main body at site.
• If the pressure of gas inside drops due to leakage, the leakage point
may be detected by using soap water. The matter shall be reported
to the manufacturer for immediate corrective action.
1. Cylinder Key.
2. Top sampling valve of
transformer.
3. Gauge for reading gas pressure
inside the transformer
4. Adapter.
5. Gauge to indicate gas pressure in
the cylinder
6. Gas pressure regulator.
7. Gauge to indicate gas pressure
from the regulator
8. Pneumatic pressure hose.
9. Hose clip.
10. Nitrogen cylinder.
FIG. — 3.1
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 28 of 204
POWER TRANSFORMERS
• Should it not be possible to rectify the leak immediately, the
transformer must be covered by putting a tarpaulin sheet over the
whole tank until remedial measures can be carried out.
• Gasket must not be tightened indiscriminately as this could result in
loss of gasket property due to over compression.
• The arrangement for gas filled storage is shown in fig. - 3.1
• Pressure inside the transformer should be monitored on daily basis
and any pressure drop should be made up by opening the cylinder
and operating the pressure regulator. The cylinder should be kept
closed.
• Before deciding on loss of pressure, the pressure versus
temperature chart (Fig. –2.1) shall be referred to.
• If the storage period of transformer at site is expected to be beyond
3 months, it is recommended to keep it filled with transformer oil.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 29 of 204
POWER TRANSFORMERS
Fig. 3.2
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 30 of 204
POWER TRANSFORMERS
• If erection work is not likely to commence immediately the boxes,
which are opened for inspection, should be repacked and the
packing list retained for future reference and records.
• All packing cases should be kept above ground on suitable support
so as to allow free circulation of air underneath. Water should not
collect in the storage area. There should be sufficient space for
inspection, handling and transport.
• All fragile items and instruments should be stored indoors.
• All crates should be kept as per the markings provided on the crates
by manufacturer. As a general rule, all control boxes such as RTCC
Panel, Marshalling Box, Drive Mechanism etc. should be kept
indoors in vertical position.
• Crates should not be stacked one over the other.
• Strictly adhere to the specific storage instruction provided by the
manufacturer for specific items.
• Table - 1 may be referred to for further guidelines for storage and
periodical inspection of transformer accessories.
Table- 1
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 31 of 204
POWER TRANSFORMERS
4.0 INSTALLATION
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 32 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 33 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 34 of 204
POWER TRANSFORMERS
25 a) 3 Phase, 440
Volts, 50 Hz.
Electric Power
Supply for
Operating the
vacuum pump
and filter machine
b) Water Supply if
Purifier is water
cooled.
26 Pulling winches/ 2 Sets Please refer section 4.3.
Pulleys each
27 Hydraulic/Mechanical 4 Nos. 50% of total weight of main
Screw Jacks with body with oil.
Locking facility
28 Measuring Tapes 2 Nos. 10 meter long.
29 Spirit Level/Level tube 1 No.
(Plastic)
30 Dry Air Generator (For 1 No. Capacity; 4~5 m3/hr. Dew
Transformers of 400 Point –40° C Temperature
kV class and above) 25 ± 5°C, Outlet pressure 200
Aq.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 35 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 36 of 204
POWER TRANSFORMERS
FIG. — 4.1
• When jacking (e.g. to remove steel plates), position the jacks under
specified jacking pads only. When jacking, ensure that all four jacks
are operated simultaneously.
• Before lowering, clean all grease dirt etc. from the under base of the
transformer.
4.4 OIL RECEIVING AND FILTERING
FIG. – 4.2
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 37 of 204
POWER TRANSFORMERS
• Quality of transformer oil must be checked before it is filled into the
transformer. Oil samples should be taken from 5 drums at random.
Samples should be collected from the bottom of the drums as shown
in fig.–4.2 for testing.
FIG. – 4.3
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 38 of 204
POWER TRANSFORMERS
• Dry air of dew point –400C or better must be fed through the inside
of tank when covers are removed in case of 400 kV and higher class
of transformers to avoid direct contact of winding insulation with
moist air outside.
I. HV – Earth (Tank)
II. LV/ IV – Earth (Tank)
III. HV – LV/ IV
IV. Core Frame – Earth (Tank)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 39 of 204
POWER TRANSFORMERS
ASSEMBLE COOLERS .
ASSEMBLE CONSERVATOR .
ASSEMBLE HV BUSHINGS .
ASSEMBLE ACCESSORIES .
CONTROL WIRING
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 40 of 204
POWER TRANSFORMERS
FIG. – 4.4
• Attach a transparent vinyl hose to indicate the level of oil being filled
in the transformer.
• Open the top filter valve or any other bolted covers on topmost point
on the transformer for releasing dry gas at the time of oil filling.
• Open the bottom filter valve on the transformer and top air release
valve on the oil storage tank.
• Oil should be filled upto a level above the top insulation of
transformer winding.
• A small gas space (approx. 5~10%) should be left above oil for
expansion of oil.
• During oil filling, if the filter press stops due to any reason, the top
filter valve and any other opening on the top of the transformer
should be closed immediately to prevent air getting into the
transformer.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 41 of 204
POWER TRANSFORMERS
• Oil level shall be continuously monitored during oil filling.
• After filling oil, if the storage is expected to be for a long period, dry
gas should be filled above the oil at a pressure of 0.1 ~ 0.2 kg/cm2.
• Assembling work should start from the bottom of the tank so that
after initial oil filling, oil need not be drained again for assembling
work.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 42 of 204
POWER TRANSFORMERS
• Tightness of all inside connection should be checked and proper
locking shall be provided.
• Persons working inside the transformer or top of the transformer
should not wear wristwatches, pen, coins etc.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 43 of 204
POWER TRANSFORMERS
• Check and ensure that level of all the foundations for cooler support
are in same level as that of the top surface of rails. Level difference
should be compensated by putting shims if the level is lower and
chipping the concrete foundation if the level is higher.
• Fix cooler header mounting frames as per dimensions shown in
General arrangement and Foundation Plan drawing.
• Mount cooler headers loosely. Final tightening to be done only after
proper alignment.
• Top and bottom butterfly valves of all radiators should be in the
vertical line. This should be confirmed by a plumb.
• Remove blanking plates from the butterfly valves.
• Tighten the cooler frame foundation bolt, and clamping bolts of
cooler headers and pipe connections.
• While mounting the oil pump and oil flow indicators, care should be
taken to ensure the arrows indicating the oil flow direction are
towards the transformer tank.
• While mounting radiators care should be taken to ensure that the
weight is balanced.
• Ensure that a fresh gasket is used while mounting the radiators.
• In case of separately mounted coolers, the oil pipes are provided
with expansion joints. Tack welded bars on expansion joints should
be removed.
• Fix the fan mounting frames and fans as indicated in the general
arrangement drawing.
• Fan & mounting frame shall be connected to the earth grid.
4.11 CONSERVATOR
• Mount the conservator as shown in G.A.. Drawing.
• Very often the small conservator for on load tap changer is attached
to the main conservator.
• Usually the main conservator is provided with Magnetic Oil level
Gauge having low oil level alarm contacts and OLTC conservator is
provided with oil sight window.
• Magnetic oil level gauge shall be mounted after attaching the float to
the gauge. Check and confirm free movement of float arm and
proper locking of float to the float arm.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 44 of 204
POWER TRANSFORMERS
• Mount all valves as shown in GA drawing on the conservator.
• Mount the connecting pipe with Buchholz relay from the main tank to
the conservator. Ensure direction of Buchholz Relay by the direction
of arrow on Buchholz Relay towards conservator.
• Mount connecting pipe with oil surge relay from OLTC to the
conservator.
• Mount breather connecting pipes and silica gel breathers for the
main tank and OLTC conservators.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 45 of 204
POWER TRANSFORMERS
• Keep air release valves open. Fix air filling adapter on breather pipe
and inflate the air cell at an air pressure indicated on the
INSTRUCTION PLATE affixed on the transformer and hold air
pressure.
• Open the air release valves and start oil filling from the bottom filter
valve of the transformer.
• Observe the air release valves and as soon as oil starts overflowing,
close the air release valves one by one. Stop oil filling when all air
release valves are closed.
• Remove the air filling adapter.
• Continue oil filling and observe the Magnetic Oil Level Gauge
(MOLG)
• Stop the filling when the needle of MOLG shows the level
corresponding to the ambient temperature at the time of filling.
• Fix silica gel breather.
CAUTION:
Ø Do not open any of the air release valves after completion of oil
filling. If air release valve is opened, air will enter and oil level will
drop.
Ø The plain oil level gauge on the end cover of the conservator
should indicate full oil level always. If air enters the conservator, it
can be seen by a fall in the oil level in plain oil level gauge.
Ø The plain oil level gauge should be monitored on regular basis.
FILLING PROCEDURE UNDER VACUUM IN CONSERVATOR
The conservator, with its separator, being set up and plugged in above
the transformer, is connected to its oil filling reserve by a pipe in its
lower part.
Proceed as follows :
• Create a vacuum in separator.
• With the same source of vacuum, create a vacuum in the
conservator.
• Open the oil filling valve of the transformer. Because of the vacuum
in the conservator, the oil level rises automatically.
• Stop the oil filling once the required volume in the conservator is
attained.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 46 of 204
POWER TRANSFORMERS
• While maintaining the conservator under vacuum, allow Dry Air or
Nitrogen gas to enter into the internal part of the separator. Then,
the separator inflates by itself, and takes all the free space due to
the fact that the conservator was not completely full. In particular,
during the operation, the oil is going to rise to the top of the
conservator.
• Inflate the separator at a maximum as shown in the INSTRUCTION
PLATE.
• Check on the vent-holes, and confirm that there is no more air in the
conservator or, if necessary, adjust the level.
CAUTION:
The above mentioned CAUTION regarding the opening of air
release valve after completion of oil filling, is applicable for this
case also.
FIG.— 4.5
METHOD OF LIFTING CONDENSER BUSHINGS FROM PACKING
CASE AND MOUNTING ON THE TRANSFORMER AT AN ANGLE
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 47 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 48 of 204
POWER TRANSFORMERS
• If holes are not provided in the CT terminal box for fixing cable
glands, suitable holes shall be drilled and cable glands assembled.
• Fix all air release pipes between bushing turrets and Buchholz relay
connecting pipe. Please refer to the part marking drawing for
respective part numbers of air release pipes.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 49 of 204
POWER TRANSFORMERS
some manufacturers adopt oil filled gear box. Oil, if required, shall be
filled as per the manufacturer's instructions.
• Coupling up of drive mechanism and OLTC bevel gear shall be done
only after ensuring that both are at the same tap position. Normally
the transformer is despatched from the factory at rated Tap position.
• Operate the DM manually from rated tap to tap no. 1 and then to the
other extreme tap position and bring back to rated tap.
• Operate DM electrically. Check and confirm that for each impulse
given in both raise and lower directions, diverter switch operation
sound is heard before the motor stops. After hearing the sound, the
travel of the tap position indicating disc upto the green band shall be
equal in both forward and backward crank operation.
• Verify the ratios on all taps using ratio meter or digital voltmeter.
4.16 CABLE BOX ASSEMBLY
• If cable box is provided, the assembly shall be carried out referring
to the cable box assembly drawing provided in the Instruction
Manual.
• Cable sealing ends shall be fitted on to the end of the cable before it
is inserted and bolted on to the cable box.
• Cable box assembly may be bolted to the disconnecting chamber on
the transformer tank.
• Flexible connections shall be made between bushings and cable box
bus bars through the Inspection Cover.
4.17 INSTRUCTIONS REGARDING USAGE OF GASKETS
• Gasket materials used are either Synthetic Rubber Bonded Cork
(SRBC) sheet or nitrile rubber.
• SRBC material conforms to RC-70C of IS : 4253(Part II); thickness
used are 6.0 mm and 10.0 mm.
• Gaskets should be stored in stress free condition and must be
protected from moisture, oil and grease.
• Synthetic rubber bonded cork sheets once used should not be used
again.
• Gasket seating surfaces should be smooth and free from scratches,
oil, grease, dirt etc.
• Gasket should be properly located before tightening.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 50 of 204
POWER TRANSFORMERS
• Gasket joints are designed with 40~50% compression.
• Gasket joints should be tightened evenly with a diametrically
opposite sequence.
• Full compression should not be achieved in one go.
• Over tightening will cause the gasket material to loose its properties
and under tightening may not prevent oil leakage.
4.18 CHECKING LEAK RATE UNDER VACUUM
• Drain oil & create vacuum of 200 torr inside the tank, close the valve
between vacuum pump and tank and stop the pump and hold the
vacuum. There should be no appreciable loss of vacuum over one
minute.
• If there is leak, find out the leak and rectify.
• Start the pump and open the valves and continue till a vacuum of 10
torr is achieved.
• Close vacuums valve and stop the pump.
• There should not be an increase of pressure of more than 1 torr over
half an hour.
• IF the rise in pressure is more, find out leak and rectify.
• If results are satisfactory, restart the vacuum pump open the valves
and continue pumping to obtain a vacuum of 1 torr or better and
maintain this vacuum for more than 24 hrs. before and during
subsequent oil filling operations.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 51 of 204
POWER TRANSFORMERS
• Open all valves between conservator, main tank and OLTC.
• Fill oil in the transformer upto 1/3 rd of the conservator through oil
filter.
• Apply a gas pressure above the oil such that the pressure at the
base of the tank is between 0.7 kg/cm² to 1.0 kg/cm².
• Check for oil leakage at all bolted and welded joints by keeping the
pressure for 12 Hrs.
• If any leakage is noticed, rectify the leak and continue the test.
• Break pressure and reassemble breathers, PRD, explosion vent etc.
4.21 VACUUM OIL INJECTION
• Oil injection shall be made under full vacuum (1.0 torr or better) for
transformers above 66kV. 380 mm Hg or better vacuum is required
for transformers rated for 66kV and below. The vacuum shall
preferably be measured by using McLeod Vacuum Gauge.
• After draining the oil completely from the transformer, vacuum
should be pulled from the oil filling hole on main conservator. If the
conservator is fitted with air cell, pressure equalising connection is
required to avoid damage to the air cell.
• For facilitating evacuation of main transformer and diverter switch
compartment of OLTC simultaneously, an equaliser pipe (Refer GA
drawing for item number & location) is supplied. This is to be fitted
during evacuation and removed after vacuum oil filling.
• Before starting vacuum, all bolted connections shall be checked.
• Radiator valves shall be kept open.
• A transparent vinyl hose shall be connected to the bottom sampling
valve (Refer Fig. – 4.4) for indicating the oil level.
• If explosion vent is provided, the pressure shall be equalised on
either side of the diaphragm to avoid damage to the diaphragm.
• Vacuum shall be maintained for 6 hours.
• Oil may be injected through the bottom filter valve until the level
reaches 350C marking on the Magnetic Oil Level Gauge of the
conservator.
• Initial oil filling shall be done at a slow rate. Rise in oil level per hour
inside the transformer shall be limited to 300 mm.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 52 of 204
POWER TRANSFORMERS
• Natural rubber hose shall not be used as sulphur in the rubber may
react with oil.
• Oil inlet valve shall be closed and after one hour the vacuum shall be
broken.
• Oil level indicating vinyl hose can be removed by closing the bottom
sampling valve.
• Vacuum gauges may be detached and breathers assembled in its
position.
• Pressure equalising connection provided for explosion vent
diaphragm and OLTC diverter chamber shall be removed.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 53 of 204
POWER TRANSFORMERS
(v) Total dry film thickness after final coating: as per data sheet
(80 ~ 100 microns if not specified)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 54 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 55 of 204
POWER TRANSFORMERS
FIG.— 5.1
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 56 of 204
POWER TRANSFORMERS
6.0 COMMISSIONING
6.1 POST ERECTION CHECKS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 57 of 204
POWER TRANSFORMERS
• Remove the cap provided at the bottom of silicagel breather for the
transportation purpose.
• Arcing horns if provided are set to the specified gap
• All earthing connections are tightened properly.
• Anti condensation heaters are functioning correctly.
• Rating and connection diagram plates and other marking labels are
fitted properly.
• All isolating switches are set at ON position.
• Cooler control switch is set to AUTO.
• All alarm circuits are reset.
• OLTC to Transformer equalising pipe shall be removed after oil filling
under vacuum and the opening shall be coverd by blanking plate
supplied with the transformer.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 58 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 59 of 204
POWER TRANSFORMERS
• Convert the resistances to 750C.
• For copper windings:
• R (75) = R (measured) x (234.5 + 75)
(234.5 + Oil temperature at the time of measurement)
• Compare the values with factory test results.
6.9 TAN DELTA AND CAPACITANCE
• Measure tan delta and capacitance of Condenser bushings of 52 kV
and above and compare with the factory test results (Refer to
"INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE OF
OIP CONDENSER BUSHINGS" provided elsewhwhere in this
Manual).
• Compare the values with factory test results.
6.10 OPERATION CHECKS
• Check signalling circuits for pump fail/fans fail etc., and reset.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 60 of 204
POWER TRANSFORMERS
• Open the petcock quickly and allow air full flow with surge. Record
the minimum pressure required to operate the surge contacts.
• Release all the air trapped in the Buchholz relay.
6.12 WINDING TEMPERATURE INDICATOR CALIBRATION
• Rotate the indicator pointer slowly and confirm that the alarm signal
is received at the set temperature.
• Rotate the pointer slowly and confirm that the trip signal is received
at the set temperature.
• For set values of alarm and trip contacts, please refer to the
instruction manual.
• Repeat the test for all winding temperature indicators if more than
one indicator is provided.
• Remove the thermal sensing bulb from the transformer cover and
insert in hot oil bath.
• Check the readings with clinical thermometer.
• Replace the sensing element in transformer pocket and check the
readings or remote winding temperatures if provided.
• For any adjustment if needed please refer to the instrument
supplier's catalogue.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 61 of 204
POWER TRANSFORMERS
APPENDIX - A
SIGNED .......…...........………….
DATE .......................………..
1. DOCUMENTATION CHECK
2. RECEIPT OF TRANSFORMER
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 62 of 204
POWER TRANSFORMERS
Observation
Marshalling box inspected ___________ _________
Observation
Quantities tally with shipping list ___________ _________
Any shortages/
Observation ___________ _________
4. ERECTION
Observation
Radiators internally inspected ___________ _________
Observation
All valves fitted on main tank ___________ _________
Observation
Inside surface of condenser
Bushing pipe inspected ___________ _________
Observation
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 63 of 204
POWER TRANSFORMERS
Buchholz relay
installed at correct angle ___________ _________
5. OIL FILLING
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 64 of 204
POWER TRANSFORMERS
6. CABLING
Cabling/Wiring visually
Satisfactory ___________ _________
7. BREATHERS
9. KIOSK/DRIVING MECHANISM
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 65 of 204
POWER TRANSFORMERS
Cabinet clean & tidy ___________ _________
10. GENERAL
2 IV Bushings ……………kV
3 LV Bushings ……………kV
8 Buchholz Relay
11 Oil Pump
12 Cooling Fan
16
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 66 of 204
POWER TRANSFORMERS
APPENDIX B
2. GENERAL CHECKS HV IV LV
a. Arcing horns positioned correctly
b. Arcing horns gaps
c. Arching horns gaps
d. Oil levels in bushing correct
e. Air release plugs vent
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 67 of 204
POWER TRANSFORMERS
3. GENERAL TESTS
a. Insulation Resistance:
(i) Core frame/Tank at ______ 0C m?
(ii) Windings at _____ 0C with _____ kV megger
HV - E Core frame m?
IV - E earthed to m?
LV - E tank m?
HV - IV m?
HV - LV m?
IV - LW m?
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 68 of 204
POWER TRANSFORMERS
l Ratio checked at all taps and continuity checked during each tap
changing.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 69 of 204
POWER TRANSFORMERS
LV – LV1
A-a2 A-b2 A-c2
B-a2 B-b2 B-c2
C-a2 C-b2 C-c2
HV – LV2 (Tertiary)
A-a2 A-b2 A-c2
B-a2 B-b2 B-c2
C-a2 C-b2 C-c2
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 70 of 204
POWER TRANSFORMERS
Note: The above checks shall apply to individual motors and each phase of
individual overload devices. The values shall be maximum for any type of
motor.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 71 of 204
POWER TRANSFORMERS
e. Buchholz Device :
Main Tap changer
Make ________ __________
Manufacturer
Serial No.
Type/Model
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 72 of 204
POWER TRANSFORMERS
Ratio Checked
WTI Temp 0C
Indicator
Reading 0C
Repeater WTI
Reading 0C
Repeater
Reading 0C
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 73 of 204
POWER TRANSFORMERS
a. Insulation
Checked to Revision
4. OPERATIONAL TESTS
a. Tap changer Equipment Raise Lower
Max. interval between operating times of
diverter switches of single phase tap changes.
Local raising and lowering (full range)
Remote raising and lowering (full range)
Local/Remote switch
Hand operation and handle interlock switch
Check circuit for correct sequence.
Limit switch operates.
Mechanical position indicator
Remote electrical position indicator
Tap change incomplete alarm
Tap change counter operates correctly
Tap change counter reading initial/final
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 74 of 204
POWER TRANSFORMERS
Cooler A Cooler B
Cooler control Switch
Auto Control from WTI
Time delay for pumps (Auto) sec.
Manual
Pump failure alarm
Auto start of stand by pump
Stand by pump running indication
Cooler fail alarm
Fuse ratings correct
Differential pressure alarm
5. MARSHALLING KIOSK
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 75 of 204
POWER TRANSFORMERS
6. ALARM SIGNALS
Check the following indicators are enunciated:
CAUTION :
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 76 of 204
POWER TRANSFORMERS
2. For electronic instruments/repeaters, TPI & WTI FACIA, please check the
voltage to be applied (AC/DC, 110/220 Volts) & also potential free contacts,
before energising the circuit. Incorrect voltage or polarity of supply may
damage the instrument.
3. For connecting digital repeater instruments independent screened or
armoured cables should be used. Resistance of cable should be kept
minimum to avoid any drop in signal.
8. OIL TESTS
Oil supplier _________________________
Oil sample should be taken after commissioning and prior to energising the
unit and at every three months thereafter.
paper combinations
5. Arcing of oil and H2, C 2H2, CO, CO2, C 2H4
paper combinations
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 77 of 204
POWER TRANSFORMERS
9. Tests on CTS
(a) Sl. No.
(b) Ratio
(c) Polarity
(d) Magnetising current
(e) Knee point voltage
(f) Winding resistance
(g) Ambient Temp. at the time of measurement
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 78 of 204
POWER TRANSFORMERS
7.0 OPERATION
• Check and confirm that tap position indicators is same in local and
remote indicators.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 79 of 204
POWER TRANSFORMERS
• While temperature is rising, confirm that fans and pumps are
switched on automatically at the preset temperatures.
• While temperature is falling, observe that the pumps and fans are
switched off at preset temperature.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 80 of 204
POWER TRANSFORMERS
Note:
] ]
Duration of surface repainting depends on the level of
pollution prevailing at site. If pollution is more, a frequent
repainting schedule may have to be worked out.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 81 of 204
POWER TRANSFORMERS
8.0 MAINTENANCE
Maintenance Schedule
• For transformers of voltage class upto 245 kV, if the moisture content is
found to have increased beyond 25 ppm oil should be filtered.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 82 of 204
POWER TRANSFORMERS
8.1.3 Acidity
• It the acidity is increased beyond 0.5 mg KOH/g, than the oil needs
filtration.
• After draining the oil completely from the transformer, core, winding,
insulation and interior of tank should be washed by hot oil jet. The oil
being used for washing of internal body also must be drained
completely.
8.2.2 Procedure
• The sampling bottles shall be labelled and marked with information like
source of sample, date and time & sample temperature.
• Sample bottle shall not be opened before it is needed for testing.
• Sampling point should be cleaned by using sponge.
• Blanking plate of sampling valve shall be removed by using spanner.
• Clean the silicon rubber tubing thoroughly and fit to sampling point
nipple.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 83 of 204
POWER TRANSFORMERS
• Rinse the bottle in oil stream and reduce the rate of oil flow to 1
litre/minute.
• Put the end of rubber tubing to sampling bottle and fill the bottle from
bottom.
• No air bubble shall be introduced into the bottle.
• The bottle is allowed to overflow before it is closed.
• Measure and record the temperature of oil sample as soon as it is
taken.
• Put back and tighten the blanking plate.
• Remove all tools, excess oil container and oil sample from the area.
• Arrange for testing oil sample at laboratory.
8.3.2 Procedures
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 84 of 204
POWER TRANSFORMERS
8.3.3 Calibration
• Remove the thermal sensing bulbs from the transformer and insert it
into the hot oil bath.
• Check the winding temperature readings up and down the scale at
intervals of 5 °C.
• Confirm from control room that remote temperature readings are
tallying with the local readings.
• Replace the sensing element into the transformer pocket.
For any adjustment, see the manufacturer's catalogue.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 85 of 204
POWER TRANSFORMERS
• Bucket
• 10 mm polythene tube, 10 meters.
8.4.1 Procedure
• The purpose of this test is to ensure correct operation of Buchholz
relay.
• Transformer shall be isolated and earthed.
• Connect nitrogen cylinder to the top petcock of Buchholz relay.
• Open the other petcock.
• Allow gas to enter the relay.
• Check and confirm from control room that alarm signal is received.
• Check continuity of alarm contact by using multimeter.
• Close petcock on gas supply side and release all gases trapped in
relay casing.
• Increase the gas pressure to approx. 2 kg/cm² (30 psi)
• Open the test petcock and allow full surge of gas to enter the relay
casing.
• Check and confirm from control room that trip signal has been
received.
• Check continuity of trip contacts by using multimeter.
• Close Buchholz relay test cocks.
• If relay has not operated, increase gas pressure and repeat the test.
• If the relay is found faculty replace it with a new one.
• Open conservator shut off valve and release all gases trapped.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 86 of 204
POWER TRANSFORMERS
• Transformer shall be isolated and earthed.
• Note the tap position.
• Operate the tap changer through operating handle through entire range
of tap positions.
• Return to the original tap position.
• Set the local selector switch to LOCAL.
• Press RAISE button and release. Check and confirm the tap position
indication has changed and that limit switch stops the tap changing at
preset tap.
• Repeat.
• Press the LOWER button and release. Check and confirm that limit
switch has operated and tap position indication has changed.
• Repeat till the tap position has returned to the original value.
• Set the local selector switch to REMOTE.
8.6 OIL FILTRATION
• Purpose of this maintenance is to improve the unsatisfactory condition
of oil found during sampling.
• Transformer shall be isolated and earthed.
8.6.2 Procedure
• Remove the blanking plate from filter valves and connect the oil inlet
hose to top filter valve and oil outlet hose to the bottom filter valve.
• Open the filter valves and start circulation of hot oil. Oil temperature
shall be 55°C to 70°C.
• Circulate the oil for 4 full passes.
• Re sample and arrange to test.
ISSUE/ REVISION 99/07 01/11 02/08 03/11
© This document and any Information or Descriptive Matter set out herein are the Confidential and Copyright Property of ALSTOM
and must not be disclosed, loaned, copied or used for Manufacturing, Tendering or for any other purpose without written permission.
ERECTION, COMMISSIONING, Ref. No. TRM. 0311
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 87 of 204
POWER TRANSFORMERS
• Continue until oil condition is acceptable.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 88 of 204
POWER TRANSFORMERS
8.9.2 Procedure
• Transformer shall be isolated and earthed.
• Set the cooler supply isolator of OFF.
• Close the inlet and outlet valves if radiator are mounted on a separate
cooler tank.
• Close the top and bottom isolating valves of radiator.
• Open the top air release plug.
• Remove the bottom drain plug and drain the oil to oil container under
gravity.
• Sling the radiator with jib crane.
• Remove the radiator clamping bolts.
• Remove radiator.
• Blank off the radiator and header openings.
• Close the air release and drain plugs.
• For Re fitting the Radiator.
• Remove the blanking plates.
• Fix new gaskets.
• Assemble the radiator and tighten the clamping bolts.
• Open the top header air release plug.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 89 of 204
POWER TRANSFORMERS
• Open the bottom radiator isolating valve.
• If the radiator is on a separate cooler bank, oil shall be filled into the
radiator bank through the bottom header valve by using the filter
machine. If the radiator is tank mounted, the oil from the oil tank should
be pumped into the tank by using the filter machine.
• Close the air release plug on top as soon as oil starts flowing through
the air release plug.
• Shut down the oil filter machine
• Open top header isolating valve.
• In case of separate cooler banks, air should be released through the
top common header air release plugs.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 90 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 91 of 204
POWER TRANSFORMERS
9.2 PUMPS
9.3 FANS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 92 of 204
POWER TRANSFORMERS
Boiling of Simultaneous
water in occurrence of a
exceptional heat producing
cases fault and entry
of water into
the tank .
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 93 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 94 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 95 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 96 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 97 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 98 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 99 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 100 of 204
POWER TRANSFORMERS
O2 (Oxygen)
N2 (Nitrogen)
CO2 (Carbon dioxide)
CO (Carbon monoxide)
H2 (Hydrogen)
CH4 (Methane)
C2H2 (Acetylene)
C2H4 (Ethylene)
C2H6 (Ethane)
C3H6 (Propylene)
C3H8 (Propane)
Table 9.6
"Normal" Values of Dissolved Key Gas Concentration Limits in oil of
Power Transformers in Service [Parts Per Million – ppm].
(Ref. FIST 3-30 tt : October 2000)
Status H2 CH4 C2H2 C2H4 C2H6 CO CO2* TDCG**
Condition 1 100 120 35 50 65 350 2500 720
Condition 2 101~ 121~ 36~ 51~ 66~ 351~ 2500~ 721~
700 400 50 100 100 570 4000 1920
Condition 3 701~ 401~ 51~ 101~ 101~ 571~ 4001~ 1921~
1800 1000 80 200 150 1400 10000 4630
Condition 4 >1800 >1000 >80 >200 >150 >1400 >10000 >4630
tt
Ref.: FIST 3-30 (Transformer Maintenance; Facilities, Instructions, Standards
and Techniques by United States Department of the Interior Bureau of
Reclamation, Denver, Colorado).
* CO2 is not considered in the calculations for TDCG, because it is not a
combustible gas
** TDCG means Total Dissolved Combustible Gas.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 101 of 204
POWER TRANSFORMERS
Condition - 1
Total Dissolved Combustible Gas (TDCG) and any individual combustible gas
below this level indicates normal operation of the transformer. If any gas
exceeds the specified level, it needs investigation.
Condition - 2
TDCG and any individual combustible gas in this range indicate greater than
normal combustible gas level. A fault may be present. Further monitoring is
required.
Condition - 3
TDCG and any individual combustible gas in this range indicate a high level of
decomposition of cellulose insulation and / or oil.
Condition - 4
TDCG and any individual combustible gas in this range indicate excessive
decomposition of cellulose insulation and / or oil. Continued operation could
result in failure of the transformer.
Note:
A sudden increase in key gases and the rate of gas generation are more
important in evaluating a transformer than the amount of gas.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 102 of 204
POWER TRANSFORMERS
Table 9.7
Action based on Dissolved Combustible Gas concentration.
Conditions TDCG Level or TDCG Sampling Intervals and Operating Actions for
Highest Generation Gas Generation Rates
Individual Gas Rates Sampling Operating Procedures
(Ref. Table 9.5) (ppm / day) Interval
Condition 1 720 ppm of Annually/ 6 Continue normal operation
TDCG or < 10 Monthly for
highest EHV
condition based Trans.
on individual 10 ~ 30 Quarterly
gas from Table Exercise caution. Analyse
9.5 > 30 Monthly individual gases to find cause.
Determine load dependence.
Condition 2 < 10 Quarterly Exercise caution. Analyse
10 ~ 30 Monthly individual gases to find cause.
> 30 Monthly Determine load dependence.
Condition 3 < 10 Monthly Exercise caution. Analyse
10 ~ 30 Weekly individual gases to find cause.
> 30 Weekly Plan outage. Contact
manufacturer for advice.
Condition 4 < 10 Weekly Exercise caution. Analyse
individual gases to find cause.
10 ~ 30 Daily Plan outage. Contact
manufacturer for advice.
> 30 Daily Consider removal from service.
Contact manufacturer for advice
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 103 of 204
POWER TRANSFORMERS
Table –9.8
Transformer Fault Types and the gases they produce.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 104 of 204
POWER TRANSFORMERS
C2H2 (acetylene /hydrogen): >2 & C 2H2 >30 ppm indicates possibility
H2 of tap changer oil leaking into main tank
Note:
Ratios are to be calculated only if the concentrations of both the
gases are above the detection levels.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 105 of 204
POWER TRANSFORMERS
TRANSFORMER
DATA GATHERING
TRIPPED OR MONITOR
TABLES 2 AND 3
MALFUNCTIONED
YES NO
PROBLEM RETURN TO SERVICE
YES DAMAGE NO
TESTING
IS
TABLE 4 AND TABLE 5
OBVIOUS
NO
ANALYZE TEST
TESTING
SCRAP RESULTS
TABLE 4 AND TABLE 5
APPENDIX A
NO YES
FURTHER
TESTING
YES
FIELD
REPAIR
NO
NO FACTORY YES
TEARDOWN-TABLE 10
REPAIR
ANALYZE-SECTION 6
DECISION
FIG. — 9
NOTE : For further details please refer to IEEE Std. C . 57. 125 - 1991
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 106 of 204
POWER TRANSFORMERS
Reactors.
dielectric tests.
transformers.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 107 of 204
POWER TRANSFORMERS
strips.
without gaps.
Protection
fasteners.
(M5 to M64)
(M5 to M64)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 108 of 204
POWER TRANSFORMERS
(M5 to M64)
atmosphere 24 kV Bushings.
atmosphere 36 kV Bushings.
atmospheres.
steel
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 109 of 204
POWER TRANSFORMERS
Transformers
transformers.
Rectangular Conductors.
priming.
pack).
1100 V.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 110 of 204
POWER TRANSFORMERS
kV
transformers; 12 kV ~ 36 kV.
IS 13947 (Part1) : 1993 Low voltage Switch Gear and Control Gear -
General rules.
36 kV bushings.
Transformers.
purpose application.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 111 of 204
POWER TRANSFORMERS
transformers.
transformers.
Voltage transformers.
10.1.4 TRANSFORMER BUSHING
IS 1885 (Part54) : 1993 Electro Technical Vocabulary - Insulators.
1000 V.
bushings.
bushing 12 kV to 36 kV.
electrical equipment.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 112 of 204
POWER TRANSFORMERS
10.1.5 REACTORS
IS 5553 (Part1) : 1989 Reactors - General.
earthing reactors.
IS 1448 (Part 10) : 1970 Method for test for petroleum and its
IS 1448 (Part 21) : 1992 Petroleum and its Products - Flash point by
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 113 of 204
POWER TRANSFORMERS
Viscosity.
equipment.
method.
liquids.
of insulating oils.
electrical equipment.
beaker method.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 114 of 204
POWER TRANSFORMERS
oils.
ordination.
measurements.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 115 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 116 of 204
POWER TRANSFORMERS
air.
short circuit.
sound levels.
above 1000 V
performance.
electrical equipment.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 117 of 204
POWER TRANSFORMERS
transformers.
equipment.
electrical purposes.
IEC 60567 (1992) Guide for the sampling of gases and of oil
transformers.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 118 of 204
POWER TRANSFORMERS
Transformer.
application.
application.
********************
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 119 of 204
POWER TRANSFORMERS
TRANSFORMER
ACCESSORIES
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 120 of 204
POWER TRANSFORMERS
TEMPERATURE INDICATOR
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 121 of 204
POWER TRANSFORMERS
1. APPLICATION
The Temperature indicator is used as an Oil Temperature Indicator (OTI) or
as Winding Temperature Indicator (WTI) for the protection of liquid immersed
power transformer. In the case of dry type transformers it is used as
Temperature Indicator (T.I.) to monitor the temperature of the windings.
2. SCOPE OF SUPPLY
OTI & TI: Instrument with specified Range, Number of control switches, length
of capillary and sensing bulb.
WTI: Same as 2.1 but fitted with specified thermal image device.
TRANSMITTER (OPTIONAL): A precision potentiometer is mounted inside
the case of OTI or WTI (2.1 or 2.2) to transmit the measured temperature to
remote point(s).
REPEATER (OPTIONAL): Analog indicator supplied separately for remote
indication of the temperature measured by OTI or WTI (2.1 or 2.2)
3. OPERATION
The instrument operates as OTI when its sensing bulb is mounted in an oil
filled pocket located in the hottest oil of an oil immersed transformer.
The instrument operates as TI when its sensing bulb is exposed to the
medium adjacent to the windings of a dry type transformer.
When a proportionate load current of the transformer is passed through the
thermal image device, the instrument operates as a WTI integrating the
simulated temperature rise of the thermal image device and the top oil
temperature measured by the sensing bulb.
Remote indication of the temperature measured by the OTI or WTI is provided
by connecting the transmitter to the repeater either directly or through a
resistance transducer (resistance to current converter).
4. CONSTRUCTION
LIQUID-FILLED SYSTEM (Refer Fig. 1): A sensing bulb (25), a measuring
bellows (2) and a small bore capillary tube (24) connecting the two, form the
measuring system. A second bellows (16-compensating bellows)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 122 of 204
POWER TRANSFORMERS
connected with a second capillary (24) running parallel to the first capillary
and terminated at the head of the bulb from the temperature compensating
system. Both the systems are completely filled with the same liquid (other
than mercury). The two bellows are linked to a compensating lever (15) in
such a manner that the effect of ambient temperature changes on the
capillary line and measuring bellows is compensated. The movement of the
measuring bellows is related only to the temperature being measured by the
sensing bulb. This movement is amplified by the link and lever mechanism
(6), which directly drives the rotating disc (21) carrying the control switches.
The same mechanism moves, through rack and pinion a separately mounted
indicating pointer (Fig. 2, 11) over a calibrated dial. Head compensation is
provided by sealing both the systems under initial pressure, which is greater
than the possible head pressure due to differences in the elevation between
the bulb and indicator.
MAXIMUM POINTER (RED COLOURED) located on the indicator lid, is
resettable from outside the case by a screw driver blade. Unscrew and
remove black cap to reach the screw driver-slot.
CAUTION: Never use the switch testing knob for setting the maximum
pointer. If used, the switch contacts will close and initiate the external control
circuits when the instrument is in operation.
SWITCH TESTING KNOB: It is fitted on the indicator lid to check mercury
switches setting and potentiometer operation. This knob when rotated moves
the indicating pointer, switch mechanism and potentiometer wiper together
and facilitates testing these circuits without opening the lid. Rotate the knob
slowly and steadily for an accurate check. Never allow the knob to spring back
suddenly or quickly, as this will cause damage.
THERMAL IMAGE DEVICE (Refer Fig. 1): A heater coil (3-Bellows Heater) is
fitted around the measuring bellow (2) and supplied from a current
transformer in the load circuit of transformer. The heater coil simulates hot-
spot temperature of the winding over top oil temperature for a given load. The
measuring bellows reacts to this simulated temperature rise in addition to the
top oil temperature measured by the sensing bulb and the instrument
functions as a WTI displaying the hottest spot temperature of the winding. An
adjustable shunt resistor (17-calibrating shunt) is provided for shunting portion
of the current through the heater coil to obtain precise thermal image.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 123 of 204
POWER TRANSFORMERS
FIG. 1
INDICATOR
(LID & DIAL REMOVED)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 124 of 204
POWER TRANSFORMERS
5. PRE-INSTALLATION TESTING
EQUIPMENT:
1. Controlled constant temperature bath with continuously stirred liquid.
2. Certified Standard Thermometer.
3. A continuity test circuit.
4. High voltage breakdown tester.
5. A constant current source.
Note: Calibration baths are generally suitable for use only in workshop. If
required for use in the field, they should be used under cover and in a non
hazardous environment.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 125 of 204
POWER TRANSFORMERS
PRE-CONDITIONING: Before commencing any tests check the following: -
1. The instrument is as per purchaser specification.
2. The instrument is not damaged in any way and any such damage is
rectified before testing.
3. The instrument is mounted correctly. (Refer 6.1)
4. The shipping stop (22 - Fig. 1) is removed.
SPAN ADJUSTMENT: Use this adjustment for correcting reading near the
maximum scale value. Referring to Fig. 1, slacken the shoulder screw (7) half
a turn but do not remove the same. Turn the range adjuster screw (8)
anticlockwise or clockwise to increase or decrease respectively the sweep of
the pointer. Make the adjustment in small increments and carefully. Half a turn
in either direction may correspond to approximately 0.5° reading. After
adjustment, retighten the shoulder screw.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 126 of 204
POWER TRANSFORMERS
Ensure that the lock nut (4) and shoulder screw (7) are properly tightened after
the above adjustments. Repeat the tests in cold and hot bath until the
accuracy limit of ± 1.5% f.s.d. is achieved.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 127 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 128 of 204
POWER TRANSFORMERS
mounting and removing the bulb without sharp bend at the joint. Wind in spiral
(minimum dia. 150 mm) the possible excess length of capillary close to the
indicator or the bulb.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 129 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 130 of 204
POWER TRANSFORMERS
CONTENTS
I. General
2. Applications
3. Advantages
4. Construction
5. Functional Test
6. Electrical Connection
7. Installation and Maintenance
8. Basic Characteristics
9. Function
10. Operating Characteristics
11. Relays for use in areas of Seismic Disturbances
12. Specifications of Relays
13. Overall Dimensional drawing
14. Dimensions and ratings
PREFACE
The ever increasing demand for electrical energy goes together with the demand for
more and more efficient and reliable "protection devices'' for power, distribution and
supply facilities. In the field of power supply, transformers represent key installations
that demand effective protection to ensure the constant availability of electrical
energy.
One of the most essential devices to protect a transformer is a Buchholz relay. For
more than 20 years, Buchholz relays have been manufactured in India. They are
made by an experienced staff of skilled workers, highly qualified technicians and
engineers ensuring a high degree of precision and quality.
A wide range of type corresponding to the BIS & International Standards are
available to meet the many requirements of manufacturers and users of
transformers.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 131 of 204
POWER TRANSFORMERS
1. GENERAL
Protective devices in the ideal case must be sensitive to all faults, simple in
operation, robust for service and economically feasible. Considering liquid
immersed transformers, a near-ideal 'protective device' is available in the form
of Gas and Oil relay described here. The relay operates on the well-known
fact that almost every type of electric fault in a `liquid immersed transformer'
gives rise to gas. This gas is collected in the body of the relay and is used in
some way or other to close the alarm or the tripping circuit
The principle of the Gas and Oil relay was first successfully demonstrated and
utilised by 'Buchholz' many years back. In a series of experiments carried out
extensively in Germany it was proved that the Relay is capable of bringing to
light incipient fault thereby preventing further spreading of the fault and
extensive damage and thus saving expensive and protracted repairs. So
successful is the principle of this Relay that despite the continued search for
better protective devices in other electrical fields the Gas-and-Oil Relay is still
on its own in providing protection against a variety of faults.
2. APPLICATIONS
b) Shorted laminations
c) Bad contacts
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 132 of 204
POWER TRANSFORMERS
The alarm element will also operate in the event of oil leakage, or if air gets
into the oil system.
The trip element will be operated by an oil surge in the event of more serious
fault such as -
a) Earth faults
c) Puncture of bushings
The trip element will also be operated if a rapid loss of oil occurs. Single
element relays can be used to detect either incipient or major faults in oil filled
potential transformers, reactors, capacitors etc. A special single element relay
is available for the protection of on load tap-change equipment.
3. ADVANTAGES
b) Unique internal design of 'housing' prevents false air traps on top of the
relay.
e) Built in test facility for checking continuity of both Alarm and Trip
circuits.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 133 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 134 of 204
POWER TRANSFORMERS
4. CONSTRUCTION
The front inspection glass is provided with a graduation (100 to 300 cm³) to
allow readings the accumulated volume of gas and observe colour of gas for
fault analysis.
For checking the function of the inserted assembly a Test Key (1.3) is
provided. There is also a visual indication on the scale (1.4) of service and
Test/Locking position, in the form of movement of red indicator on the reading
scale. This allows the testing of the alarm and Trip circuits before installation
and even when the transformer is in service.
Just above the inspection glass an arrow shows the specified direction of flow
of the insulation liquid to the conservator. Enclosure 1 and its inserted
Assembly cover are made out of Cast Iron.
5. FUNCTIONAL TEST
5.1 Testing the relay Function with the test key.
A test system is provided in the Buchholz relay that allows the functional test
of the upper and lower switching system.
To test the relay function loosen the nut (1.5) on the Test Key (1.3) and rotate
the key with a screwdriver in the Anticlockwise direction till the SLOT on the
TEST.
Key points towards the T/L position. Both the alarm (upper switching system)
and Trip (lower switching system) will show continuity.
On bringing the SLOT on the Test Key to S (service) position by rotating the
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 135 of 204
POWER TRANSFORMERS
'key' clockwise the Alarm and Trip circuits will not show continuity. The circuits
will be actuated to 'ON' position only when there will be a fault in the
transformer.
5.2 Testing the relay Function with the Test Pump. Screw the test pump/Air bottle
to the test cock. Open the test cock and pump air gently into the Buchholz
relay until the upper switching system operates.
For operating the lower switching system air has to be pumped suddenly with
a jerk which will in turn operated the lower switching system.
6. ELECTRICAL CONNECTION
To allow installation of the 'signal wire' open the terminal box cover
comprising of the nameplate and the instruction sticker on the backside. Then
pass the wire through one of the two-conduit screwings (1.6) into the terminal
box. By using either one or the other openings, facility is given for the cable
to enter the terminal box from the left or right. The upper two studs are
terminals for the Alarm switching circuit and are denoted by A. Likewise
the lower two studs are terminals or the Trip switching circuit and are
denoted by T.
7. INSTALLATION
- See that the Buchholz relay is positioned with the arrow pointing towards
the conservator, the connection box is in the Y plane (vertical) and to Test
cock. (1.7) and air vent cock (1.8) are at the top.
- Mount the Buchholz relay as close as possible to the tank in the pipeline
between transformer and conservator.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 136 of 204
POWER TRANSFORMERS
- Make sure pipe ascends to the conservator at angle between three degree
to seven degrees.
- See that the relay enclosure is not subjected to stress. If necessary, use
expansion compensators.
- Ensure that he slot on the Test Key remains in the T/L (Test/Locking)
position during storage or loose transportation of the relay.
- Ensure that the slot on the Test Key remains in the 'S' (Service) position
and the Test Key Bolt is Tightened just before commissioning of the relay.
- Remove the protective acorn nut (1.9) from the air vent cock.
- Open the air vent cock to let air escape until insulation liquid emerges.
7.3 Maintenance
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 137 of 204
POWER TRANSFORMERS
8. Basic Characteristics
The Gas and Oil relay provide protection against a number of internal faults
but it also is able to indicate in several cases the type of fault. This is possible
because the gas collected in relay can, from its colour, odour and
composition, indicate where the fault may be and what its nature is. By
examining the gases collected it is possible to infer the nature of fault.
Thus :
a. If the gas is colourless and odourless or with only a faint odour of oil, the
gas is air trapped in the oil or the insulation.
b. If the gas is Greyish White with sharp and penetrating odour and non-
inflammable it is due to overheated or faulty insulation (fuller board etc.)
d. lf the gas is dark Grey and inflammable it may be due to a flashover in oil
or due to excessive overheating of the oil caused by a fault in the winding
or the core.
On the operation of the alarm if investigation of the collected gas does not
indicate a serious fault it is possible to leave the transformer in service till it is
convenient to carry out a through inspection. This occurrence is possible on a
newly commissioned transformer due to air trapped in the oil or the insulation.
On repeated and frequent alarm signals the transformer should be taken out
of service for thorough check up.
9. FUNCTION
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 138 of 204
POWER TRANSFORMERS
In the event some fault in the interior of the transformer tank gas bubbles are
produced and accumulate in the Buchholz relay on the way to the
conservator. In consequence, the oil level in the relay enclosure drops which
in turn lowers the upper bucket.
The lower bucket does not change its position, because when the gas
reaches the upper inside wall of the pipe it can escape into the conservator.
Hence, minor fault in the transformer tank will not trigger the lower switching
assembly and will not trip the transformer.
In case the liquid continues to drop due to loss of oil, the lower also goes
down. In consequence lower switching system operates if the level of oil goes
below the bottom level of the pipe connected to the relay.
The lower bucket, does not change its position, because when the gas
reaches the upper inside wall of the pipe it can escape into the conservator.
Hence, minor fault in the transformer tank will not trigger the lower switching
assembly and will not trip the transformer.
In case the liquid continues to drop due to loss of oil, the lower also goes
down. In consequence lower switching system operates if the level of oil goes
below the bottom level of the pipe connected to the relay.
Alternately in the event the liquid flow exceeds a specific value (which is
continuously adjustable, by means of a flap) the lower bucket is forced down,
thus triggering the lower switching system to operate.
As the liquid flow rate decreases or the level of the liquid rises the bucket
returns to its original position. The single element relay has only one operating
element and it responds to either gas collection or oil surges. The method of
operation is similar to that described for double element relay. Single element
relays are suitable for the protection of oil filled reactors, capacitors and
potential transformers. The single element oil Surge relay has been
specifically designed for use with on load tap change equipment and it will
bypass normal amounts of gas which are generated by tap change operations
and will only respond to oil surges and loss of oil.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 139 of 204
POWER TRANSFORMERS
Relays of the double element type are made in three sizes. The sizes are
distinguished by the numerical prefix 1, 2 or 3. This refers to the diameter of
the bore of the oil pipe connecting the transformer to the conservator tank.
They are referred to as Type GOR 1, GOR 2 and GOR 3, where the
Alphabets indicate 'Gas and Oil Operated Relay' and the number refers to the
pipe bore diameter as 25, 50 and 80 mm. respectively.
The implications of the various Type Nos. and their operating conditions can
be listed as follows: -
GOR 1
GOR 3
The symbol /VO following their type markings indicate that the relays contain
Reed switches and normally open type
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 140 of 204
POWER TRANSFORMERS
The symbol /S following their type markings of all relays mentioned indicate
that the relays are suitable for Silicon Oil normally used in Electro static
precipitator transformers.
All relays mentioned above are normally open types. Normally closed type
relays can also be supplied on request.
When transformers are required for use in areas subject to earthquakes or for
traction applications, we can supply special relays, which use magnetically
operated Reed Switches instead of mercury switches.
The outward appearance of these relays are exactly the same as those with
mercury switches but they are distinguished from them by the symbol /VO
following their type marking. The latter V (for vibration) indicates that the relay
contains reed switches and the latter O that the contacts are normally open.
Thus a Type GOR 2/VO signifies a 50 mm. (pipe size). Double float relay with
normally open Reed Switches.
OPERATION
In the double element relay, collection of gas causes the oil level within the
relay to fall. This in turn causes the upper element to rotate on its pivots,
bringing the magnet it carries into a position where it operates the Alarm
Switch.
An oil surge through the relay will cause the lower element to rotate about its
pivots and its magnet into a position so as to operate the tripping switch.
CONNECTIONS
The terminal box and the terminals are the same as that of mercury switch
type relays. In the reed switch relays, each reed switch is protected by, an
inductor in series. These inductors are intended to protect the reed switch
contacts from the effects of capacitive loads, such as are imposed by long
leads or pilot cables, and must not be removed from relays in service.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 141 of 204
POWER TRANSFORMERS
Protection of reed switch contacts against the effects of inductive loads, such
as those imposed by contactors and Electro-Magnetic relays, is achieved by
means of a diode wired across each load. This diode must be rated with
forward current at least as high as the steady load current and connected
observing polarity so as to absorb the back e.m.f.. These diodes are not
provided with the relay.
The Mounting position and Testing on site procedure are same as that of
'Mercury Switch type' Buchholz relay.
OPERATING CHARACTERISTICS
All double element relays are adjusted so that their performances lie within
the limits given in table 14. In addition the Reed Switch Relay is capable of
withstanding shocks of up to 4g. Such shocks will not of themselves cause the
relay to operate.
SWITCH DATA:
TYPE ---------------------------------------------------------- Normally Open
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 142 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 143 of 204
POWER TRANSFORMERS
Frequency 50 HZ 0 to 60 HZ
Assembled relays are pressure tested with transformer oil at 3kg/cm² for 60 minutes.
Electrical circuits are tested at 2000 volts R.M.S. for one minute.
Insulation resistance measured at 500 volts is not less than 10 Megaohms in air.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 144 of 204
POWER TRANSFORMERS
IMPORTANT
The various part of a relay including the body, form one complete calibrated unit and
must not be inter changed with those of other relays.
We strongly recommend that relay should not be taken apart, and under no
circumstances should any alteration be made to the angle of the flap on the trip
element. This has been correctly adjusted during manufacturing.
RELAY
TYPE
GOR 1
RELAY
TYPE
SR1
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 145 of 204
POWER TRANSFORMERS
INSTRUCTIONS
FOR
INSTALLATION, OPERATION
AND MAINTENANCE
OF OIP CONDENSER TYPE
BUSHINGS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 146 of 204
POWER TRANSFORMERS
CONTENTS
5. Installation
9. Safety
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 147 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 148 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 149 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 150 of 204
POWER TRANSFORMERS
open the top cover of the wooden case and inspect the bushings thoroughly
for any transit damage. Ensure all the accessories are received in good
condition and report, in case found to be missing.
Note: Any damage or shortages should be reported immediately.
Bushing should be handled only with mechanical lifting arrangements, such
as the illustrated in Fig. 5.
When bushings are taken out of the packing case, they must not be allowed
to rest on the lower part of the bushing. The operation is best carried out two
lifting gears and two ropes as shown in Fig. 6. One rope is slung around the
lower end of the metallic flange and let directly to the hook of the first crane
and the other passed around the shell, between two sheds and then led to the
hook of the second crane. The bushing is raised sufficiently in the same
inclination angle as in the packing case with hoists and then lowered at the
flange end. When positioning the bushing upright (Fig. 7), care should be
taken to avoid any shocks, jerks or scratch to the oil end porcelain and bottom
stress shield. On no account the bushing should be balanced on rope, passed
around the porcelain at it’s centre of gravity.
4. CHECKS BEFORE INSTALLATION:
i) Mount the bushing vertically on a suitable stand and clean the surface
thoroughly with a dry cloth, particularly the oil end. Inspect the bushing
physically for any leakage or damage on the porcelains. The oil end and
inner portion of the central tube should be further cleaned with transformer
oil. Care should be taken to prevent scratching of the painted surface of
the bottom stress shield / base plate.
ii) Check oil level of the bushing in vertical position. The oil level should be
such that the oil level is clearly visible through the oil sight glass provided
on the bushing. The oil level is filled in the factory upto the mid point of the
sight glass, which is considered to be the normal oil level. The oil in the
prismatic type sight glass can be identified by the
highlighting of the red colour reflector at any position mounted from vertical
upto a maximum of 30 degrees.
iii) Ensure the top terminal is tightened firmly with its gasket provided to avoid
water / moisture entry into the transformer.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 151 of 204
POWER TRANSFORMERS
iv) Measure and record the IR values of the bushing with a 2.5 kV meggar.
The recommended values are:
• 4000 Meg ohms (Min) between oil end terminal or top and test tap.
• 1500 Meg ohms (Min) between test tap and flange with 1 kV meggar.
The IR values may vary due to the atmospheric condition (humidity), surface
cleanliness of the porcelains, dryness of test tap etc. In such cases,
preheating of porcelains, terminals test tap etc., with hot air is recommended.
This is only an indicative test, however, the healthiness of the bushings can
be known only after measurement of Tan delta & capacitance values.
v) Capacitance and Tan delta values of the bushing should be measured
between the top terminal and test tap at 2 kV to 10 kV (Maximum). The
measurement should be preferably carried out indoors with RH not exceeding
60% and at ambient temperature, with the facilities and procedure as
described as described below:
• Schering Bridge
• Standard loss free capacitor
• High voltage supply
• Necessary screened connecting leads.
Place the bushing vertically on suitable stand. Remove the threaded test tap
cover. Insert a plug / clip into the central stud of the test tap and connect to
the Schering Bridge through a screened cable. The flange body should be
grounded. Connect the high voltage supply to the top terminal. Measure the
capacitance & tan delta value of bushing upto a maximum of 10 kV.
Note:
• The voltage applied on the bushing should be limited to 10 kV, when the
bottom end is not immersed in oil. Utmost care should be taken to avoid
any contact with the bushing during testing as this may result in fatal
injury to the personnel.
• The test tap should be dry, free from any moisture condensation and dirt
deposition. The threaded test tap cover should be fixed back to the test
tap, immediately after the test.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 152 of 204
POWER TRANSFORMERS
Factory test values of tan delta and capacitance are indicated in the test
report of individual bushing at working voltages. However, site values may
vary, as they do not resemble factory test conditions. The site values recorded
at the time of commissioning should be taken as the reference values for
comparison with future measurements. The bushing can be commissioned, if
tan delta value measured is less than or equal to 0.007, and capacitance
value as per the factory test value with maximum variation of 10%. If higher
values are obtained, please contact ALSTOM, Customer Service Department
giving full details of testing arrangement, for further advice.
Note:
The bushing should be kept vertical or mounted on transformer for a
minimum period of 24 hours before application of voltage.
5. INSTALLATION:
Please refer to Fig. 8
The bushing is suitable for
installation for a maximum angle of
30 degrees from vertical. During the
lowering of the bushing into the
transformer, extreme care should
be taken to prevent the lower
porcelain hitting the wall of the tank.
The bushing should be so mounted
on the transformer that the oil sight
glass is visible from the ground
level. Ensure the visibility of the oil
level to the naked eye.
Maximum stress experienced by the
bushing is at the bottom stress
shield during testing. Hence
sufficient care should be taken to
avoid any flashover from the stress
shield to the wall of the
turret. The flashover voltage depends on the clearance maintained in oil
between the stress shield and turret, oil
quality, surface smoothness, presence of barriers,
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 153 of 204
POWER TRANSFORMERS
shape of the stress shield and turret etc. The recommended size of the turret
to be maintained for various voltage class of bushings is given in the
manufacturer’s booklet / respective drawings.
BUSHING WITH DRAW LEAD CONNECTION:
Please refer to Fig. 9.
Each bushing is supplied with a top
terminal (12), cable bolt (9), cable bolt
pin and a gasket placed separately in
the packing case.
Drill a hole of suitable diameter based
on the size of the flexible transformer
cable at the bottom end of the cable
bolt and braze the cable into it. Insert
an M8 bolt at the upper end of the
cable bolt and tie a wire or a fish cord
on to it.
Clean the gasket seating surface on
top face of the transformer and place
the gasket in position. Lift the bushing
above the transformer turret and clean
the bottom end of the bushing.
Lower the bushing slowly into the
transformer, simultaneously pull the transformer cable brazed with cable bolt
through the central tube with the help of the fish cord. Secure the cable bolt to
the central tube with the cable bolt pin. Remove the fish cord. Bolt the bushing
into position taking care to correctly position the gasket joint. Ensure the
threads on the terminal and the cable bolt are clean. Tighten the terminal to
the cable bolt ensuring full thread engagement for proper current transfer.
Sometimes the cable bolt is supplied along with the brazed flexible lead upto
the flange seat with a half connector at bottom end. In such cases the flexible
lead from the transformer winding should be brazed to the other half
connector and should be fastened with the draw lead connector of the
bushing using bolts and nuts.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 154 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 155 of 204
POWER TRANSFORMERS
• The threaded test tap cover should be fixed back to the test tap
immediately after the test.
• The bushing should be kept vertical mounted on the transformer for a
minimum of 24 hours before energisation.
CAUTION:
THE TEST TAP WILL ALWAYS BE EARTHED AS LONG AS THE
THREADED CAP IS FIXED (Fig. 2a). HENCE THE CAP SHOULD NEVER
BE KEPT OPEN.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 156 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 157 of 204
POWER TRANSFORMERS
SILICAGEL
BREATHER
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 158 of 204
POWER TRANSFORMERS
MAINTENANCE
Inspect the breather on monthly basis; more frequently, if found necessary by
experience (eg. highly humid atmosphere).
When the breather is first installed, the crystals have a blue tint, and after a
period of operation, the colour of the tinted crystals gradually changes to pink;
this is an indication that the silicagel is becoming saturated and losing its
absorbent properties. When there is a preponderance of pink crystals the geI
should be changed or reactivated.
Silicagel may be reactivated by heating in a shallow pan at a temperature of
150° C to 200° C for two to three hours when the crystals should have
regained their original blue tint.
Before filling the container with silicagel, clean and dry all parts of the
breather. Verify that the oil Level in the oil cup is correct when reassembling.
Ensure that the breather is not choked and is free for passage of air.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 159 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 160 of 204
POWER TRANSFORMERS
SILICAGEL BREATHER
TYPE 2
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 161 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 162 of 204
POWER TRANSFORMERS
Fig. 1
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 163 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 164 of 204
POWER TRANSFORMERS
APPLICATION
This model of indicator is manufactured considering Transformer application.
It can also be used as Content Gauge on other tanks where level of liquid
inside the tank is required to be indicated continuously on a dial.
CONSTRUCTION, WORKING & FEATURES
A float is used as sensor of liquid level inside the conservator (tank). Swing of
hinged float due to change in liquid level is utilised to indicate level on a
calibrated dial and to operate a switch for external alarm unit.
Use of magnetic coupling in the indicator achieves complete sealing off of
liquid inside the conservator from surrounding atmosphere. This results in
avoiding any leakage of costly oil and avoiding contamination of insulating oil
due to seepage of surrounding air in the conservator.
The glass mercury switch is nylon encapsulated to avoid breakage and
spilling of mercury. Switch is accessible for servicing while indicator is
mounted on the conservator without any necessity of draining the oil.
CALIBRATION
The standard calibration of dial is Empty, 1/4, 1/2, 3/4, Full. Calibration of
marks Empty & Full is done after leaving 65 mm from bottom and top of
conservator to avoid striking of float to conservator wall. Different calibrations
are done to suit customer's needs.
MOUNTING
In fig. 2, indicator is shown mounted by keeping dial and mounting pad in
vertical position. However, indicator can be mounted in titled position towards
ground (max 30°) for easy viewing by fixing mounting pad at desired angle.
The position of indicator on the conservator can be selected to suit site
condition. Float mechanism passes through the hole in pad (see Fig. 2).
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 165 of 204
POWER TRANSFORMERS
SPECIFICATIONS
1. Operating Liquid : Transformer Oil to IS: 335
2. Working Temperature : 0 to 100° C of Oil
3. Working Pressure : 0 to 4 kg/cm²
4. Environment : For Indoor & Outdoor use
5. Size : See Fig. 2 & 3
6. Weight : 6.6 Kg. with Float & Float-arm
7. Mounting Specifications : See Fig. 2 & 3
8. Float Travel : Float moves in right angle plane to
seating face (See Fig.2)
9. Electrical witch : One SPST Mercury Switch
10. Contact Rating : 5 Amps 240 V.AC. 50 Hz. 1.2 Amps
240 V.DC.
11. Switch Setting : Normally Open Closes when oil level
drops to Empty level.
Switch opens automatically when oil
level rises.
12. Dial Size : 250 mm dia.
13. Dial Position : Vertical or Inclined
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 166 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 167 of 204
POWER TRANSFORMERS
GLOSSARY OF TERMS
1. APPLICATION:
This PRV is designed to be used on Power Transformer. When pressure in
the tank rises above predetermined safe limit this valve operates and
performs following functions.
l Allows the pressure to drop by instantaneously opening a port of about
150 mm diameter.
l Gives visual indication of valve operation by rising a flag.
l Operates a micro switch.
This switch has 1 NO and 1 NC contacts (Four terminals). Hence switch can
be effectively used in control circuit.
2. SPECIFlCATIONS:
See Drg. No. CS-601-R-3.
3. TESTS:
Tests are carried out as per test certificate attached to this leaflet.
4. CONSTRUCTION & WORKING:
(Refer Drg. CS-601-R-3)
This PRV has an integral flange with six holes for mounting. The valve can be
mounted vertically or horizontally on the tank. The PRV has got a port of
about 150 mm dia. This port is sealed by a stainless steel diaphragm. The
diaphragm rests on an 'O' ring (3) and is kept pressed by two heavy-duty
springs, thereby keeping the port closed. The other side of the diaphragm is
exposed to tank pressure. Whenever the pressure in the tank rises due to any
reason, the same pressure acts on the diaphragm from inside. When pressure
rises above predetermined safe limit the diaphragm gets lifted from its seat.
This lifting is instantaneous and allows vapours, gases or liquid to come out of
tank depending upon the position of valve on tank.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 168 of 204
POWER TRANSFORMERS
The diaphragm restores its position as soon as pressure in the tank drops
below set limit. The lift of the diaphragm is utilised to operate flag ( 10) and
micro switch ( 11) with the help of rod (8). The flag and switch remain
operated until they are reset manually.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 169 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 170 of 204
POWER TRANSFORMERS
7. INSTALLATION
Each valve should be cleaned from inside (tank side) with compressed air jet.
All particles should be removed from tank side. While cleaning, care should
be taken that the jet does not attack the switch and the flag mechanism. The
PRV should be installed considering the following aspects.
The indicating flag (10) is easily seen from distance, The valve is accessible
for manual resetting and for routine manual checking. While installing remove
dirt and clean the mounting surface, remove all traces of oil, grease.
The rubber gasket supplied with the valve should be properly cleaned & be
located properly in the recess carefully.
All the bolts should be tightened evenly so that equal pressure is exerted on
gasket and base.
Connect control circuits to terminal plate provided in the switch box through
cable gland (14).
As per wiring diagram (ref. fig. 1 drg. CS-601-R-3), check the operation of flag
and switch by lifting operating rod (8) and confirm that both controls operate
as required.
The PRV can be put to service.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 171 of 204
POWER TRANSFORMERS
9. GENERAL NOTES:
Store the valve on its base duly packed in polythene bag to ensure that dirt
or other solid particles do not enter the valve port from tank side.
Do not remove the protection cover on flag box and switch box when it is
stored.
Keep the flat gasket (2) duly tied to the valve. Remove it only when it is to be
installed. This gasket should be kept dry.
After installation of valve on transformer, test periodically the functioning of
switch operation and flag operation by lifting the operating rod manually.
This will ensure the switch operation and flag operation when valve opens
due to rise in pressure inside the tank.
It is not possible to change the operating pressure at site.
The valve gaskets are of entirely different nature for synthetic liquid and
transformer oil. Hence use proper valve for liquid as described on product
label.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 172 of 204
POWER TRANSFORMERS
EXHAUST FAN
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 173 of 204
POWER TRANSFORMERS
COOLING FANS
GENERAL
Exhaust type cooling fans used on transformers are designed to operate
outdoors in all weather conditions. Generally the following sizes of fans are
used.
MOTORS
The fans are powered by totally enclosed, squirrel cage induction motors. The
motors are adequately rated to give reliable service for many years.
IMPELLER
The impeller is designed to give maximum volume at minimum noise level
with minimum power consumption.
For reducing vibrations, special shoes made of rubber are provided at fixing
points of fan lugs.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 174 of 204
POWER TRANSFORMERS
MOUNTING
1. The arm is secured by the resilient mounting caps, which are placed
over the rubber sockets and secured to the diaphragm with 8 screws,
nuts and washers provided. The lock washers should be fitted under
the heads of the screws.
2. Rubber sockets fitted to arms. To be fitted so that flat side will come in
contact with the diaphragm.
3. Arms to be secured to motor by the 4 screws in motor carton.
NOTE: Lock washers are supplied and should be fitted.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 175 of 204
POWER TRANSFORMERS
CONSTRUCTIONAL DETAILS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 176 of 204
POWER TRANSFORMERS
FLOW INDICATORS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 177 of 204
POWER TRANSFORMERS
FLOW INDICATORS
FUNCTION
Flow indicators included in this catalogue are mainly designed as a safety device
looking to the need of an electrical signal on failure of forced circulation of liquid in
pipeline. They perform following functions:
1. Indicate the rate of full flow in proper direction in specified pipe.
2. Operate one or two mercury switches when rate of flow drops near to 70% of
specified full flow.
These switches can be used to initiate precautionary systems or safety
devices.
APPLICATION
Consider the case of furnace transformer in which one Flow Indicator can be
mounted on suitable member of oil circulating pipe and one on water circulating pipe
of heat exchanger. The pointer of respective Flow Indictor will indicate whether
desired rate of flow is maintained or not and switch will operate if the flow drops near
to 70% to initiate precautionary system. For similar purpose it can be used on liquid
circulating pipes in chemical processes, heavy-duty bearings, compressors, etc.
MOUNTING
To introduce these Flow Indicators in a pipe line a `T-Mounting’ is necessary. In this
catalogue we have tabulated dimensions of 'T-Mounting' for range of size from 40
mm (1.5") to 250 mm (10") N.B. Pipes. But customer can always specify if his
requirement is different than the tables on page 8.
CONSTRUCTION & WORKING
A suspended vane is used as sensor. Its surface is kept at right angle to direction of
flow. When liquid starts flowing through pipe, the vane gets deflected along with
vane shaft. This deflection is used to indicate flow inside the pipe and to operate
mercury switch or switches as follows:
A pair of permanent magnets is used as gland-less coupling. The driving magnet is
connected with vane, therefore it rotates with vane and remains in liquid. The
follower magnet, separated by a non-magnetic wall, is kept outside in air and
acquires position corresponding to driving magnet. The follower magnet carries a
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 178 of 204
POWER TRANSFORMERS
pointer and a cam. The pointer is set to read the specified rate of full flow and the
cam is set to operate one or two mercury switches when flow drops near to 70%.
A return spring is used which acts in the opposite direction of flow. Hence any steady
position of pointer is the result of equilibrium of force due to impinging liquid on vane,
spring tension & weight of vane. The pointer does not remain steady for unsteady
flows. The size and shape of vane and tension on return spring is adjusted to suit
specified full flow. The vane occupies very small area out of full cross section of pipe
at NO-FLOW position. At full flow it becomes almost parallel to flow. Hence there is
practically no head-loss across Flow Indicator.
DIAL MARKING
The spread of flow indicating portion of dial is only about 70°. Hence it is not possible
to print more markings. Usually PUMP ON-PUMP OFF or FULL FLOW-NO FLOW
type of limit markings is printed. Intermediate markings such as ALARM. TRIP is also
printed if required. Besides, specifications such as value of full flow, liquid, pipe size
and direction of flow are also printed. The background of dial is white. Direction
indicating arrow is in red colour and all other markings in black colour.
SWITCHES
One or two mercury switches of SPST type are provided. The contact position can
be set to No or NC at full flow. If required, switch can be changed from NO to NC or
vice versa at site.
In case of single switch, it is set to operate near 70% when flow is falling. In case of
two switches, both are mounted on same plate. Hence both operate at same rate of
flow. But in order to satisfy design requirements, one switch can be set to operate
near 80% and the other near 70% or one near 70% and the other near 60%. It is not
possible to set a switch to operate at lower value than 60%. Even when both
switches are set to operate at lower value than 60%. Even when both switches are
set to operate at same rate of flow, some switching differentiate is observed due to
use of mercury as switching element, We can modify setting suitably if switching
requirements are clearly specified.
WIRING
Leads from mercury switch/switches are brought into a terminal box positioned at
the bottom of indicator. A two-way or four-way terminal strip is provided. Terminals
are accessible for wiring after removing cover. A hole with conduit threads is
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 179 of 204
POWER TRANSFORMERS
provided for fixing cable gland to box. Terminals are marked. Wiring should be done
as per respective wiring diagrams.
SETTING
Full Flow- Each indicator is set in water-flowing condition. Pipe size, pipe position,
direction of flow is maintained. By adjusting a valve in pipeline, the specified rate of
full flow is established, then the pointer is set to read the full flow mark. This method
of setting gives very accurate results as it is based on equilibrium of vane at full flow.
In case of liquids other than water, proportional rate of flow of water is maintained for
setting.
Switch - After setting of pointer at full flow, switches are set in the sequence ordered
by customer. Flow is reduced to check operation of switch & increased to check
automatic resetting. The rate of flow at which switching occurs is approximate. The
switch position is kept adjustable to compensate difference in pipe gradient at site.
TESTING
Static Pressure: At 7 kg/cm².
Flow: Indicator is mounted on pipe. Water is allowed to flow in specified direction.
Rate of flow is checked when pointer reads full flow. For Liquids other than water
proportional rate of flow of water is checked.
Switch: Switch operation is checked by reducing and increasing flow in pipeline.
Contact rating: Switches are tested in laboratory at 5A.24OV.AC
Dielectric strength: Live terminals are checked at 2 kV with body.
A test Certificate is provided with each instrument.
DESIGN FEATURES
1. Switch contacts are not affected by dust, humidity or corrosive atmosphere.
2. Switches can be serviced without need of stopping flow.
3. Causes negligible head-loss.
4. Low maintenance cost.
5. Robust construction & trouble free service.
6. Does not get damaged due to excess flow or reverse flow.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 180 of 204
POWER TRANSFORMERS
Fig. 1 SCHEMATIC
Item Description
1 - Pointer & Dial
2 - Mercury Switch
3 - Switch Operating Cam
4 - Return Spring
5 - Vane Shaft
6 - Vane
7 - Main Pipe
8 - Driving Magnet
9 - Non-magnetic Wall
10 - Follower Magnet
Item Description
1 - Main Pipe
2 - T - Mounting
3 - Connecting Flanges
4 - Flow Indicator
5 - Flange of indicator
Horizontal Pipe
Vertical Pipe
NOTES:
I. Flow indicators are not interchangeable for different liquids, pipe dia.,
direction of flow or rate of full flow. Hence they should be ordered
separately.
2. The rate of full flow is not adjustable.
3. The switch operation point is not adjustable.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 181 of 204
POWER TRANSFORMERS
Accessories
(Supplied at extra cost if agreed)
T-Mounting, Weldable connection,
Flanges, hardware.
Part List
No. Description
1 – Cover for terminal box
2 – Base with mounting holes
3 – Vane shaft
4 – Vane
5 – Product label
6 – Cable entry
7 – Terminals
8 – Mercury switch
9 – Nut for adjusting switch
10 – Cover for switch box
Weight - 3.8 kg.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 182 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 183 of 204
POWER TRANSFORMERS
Fig. 5
Details of vane orientation common to Series 4021 & 4022
Fig. 5 above shows vane positions at no-flow as seen from dial side of indictor.
Indicators are set for any one direction out of four illustrated in Fig. 5. T figure also
shows direction of forces acting on vane due to impinging liquid and return spring
(gravitational force not shown).
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 184 of 204
POWER TRANSFORMERS
Accessories
(Supplied at extra cost if agreed)
T-Mounting, Weldable connection,
flanges, hardware.
Part List
No. Description
1 – Cover for terminal box
2 – Base with mounting holes
3 – Vane shaft
4 – Vane
5 – Product label
6 – Cable entry
7 – Terminals
8 – Mercury switch
9 – Nut for adjusting switch
10 – Cover for switch box
Weight - 4.0 kg.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 185 of 204
POWER TRANSFORMERS
Accessories
(Supplied at extra cost if agreed)
T-Mounting, Weldable connection,
flanges, hardware.
Part List
No. Description
1 – Cover for terminal box
2 – Base with mounting holes
3 – Vane shaft
4 – Vane
5 – Product label
6 – Cable entry
7 – Terminals
8 – Mercury switch
9 – Nut for adjusting switch
10 – Cover for switch box
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 186 of 204
POWER TRANSFORMERS
Other Parts
Dial Body, switch housing, terminal box, covers Aluminium
Dial shield Tough glass
Terminals Brass
Mercury switch Hg in hard glass
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 187 of 204
POWER TRANSFORMERS
Fig. 10
Details of vane orientation common to Series 4031 & 4032
Fig. 10 above shows vane positions at no-flow as seen from dial side of indictor.
Indicators are set for any one direction out of four illustrated in Fig. 5. T figure also
shows direction of forces acting on vane due to impinging liquid and return spring
(gravitational force not shown).
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 188 of 204
POWER TRANSFORMERS
Accessories
(Supplied at extra cost if agreed)
T-Mounting, Weldable connection,
flanges, hardware.
Part List
No. Description
1 – Cover for terminal box
2 – Base with mounting holes
3 – Vane shaft
4 – Vane
5 – Product label
6 – Cable entry
7 – Terminals
8 – Mercury switch
9 – Nut for adjusting switch
10 – Cover for switch box
Weight - 4.8 kg.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 189 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 190 of 204
POWER TRANSFORMERS
GENERAL CONSTRUCTION
PUMP
The pump set is a single stage axial flow gland-less type, integral with the drive
motor. It has been specifically designed for forced circulation of oil through the
cooling system of large transformer & allows thermo syphonic flow.
It is designed for flange mounting directly to the pipe circuit of transformers in either
horizontal or vertical position.
All the moving parts are completely enclosed and gasket thus permitting open air
installation, without any need for protective cover. It is compact in design.
The Nameplate gives details of pump and motor output along with respective
connecting pipe size.
MOTOR
The motor is of squirrel cage induction type suitable for 3 PHASE A.C. Power supply.
It is coaxial with the pump and is designed to operate in hot transformer oil. The
bearings are lubricated by transformer oil.
PRECAUTIONS
1. Store the unit in clean and dry place.
2. Do not remove the M. S. end covers till the pump set is to be installed in pipe
circuit. These are meant to protect the internal components against dirt and
dust during transit and storage.
3. It is important that all pipe work must be supported independently so that it
imposes no under strain in bending or torsion on the pump flanges.
4. The bearings are lubricated by the transformer oil and hence the pump should
not run dry, to avoid damage to bearings.
5. Keep the entire pipe circuit perfectly clean and free from moisture and foreign
material.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 191 of 204
POWER TRANSFORMERS
6. Ensure that the electrical supply available is suitable for data given on the
pump rating plate.
7. Care should be taken that the valves are in the 'open' position, when the
pump set is operated, because the pump works correctly only when all valves
are fully opened. The oil filled pump will produce Pressure even with the
valves closed, but there is no circulation, there will be oil churning inside the
pump set and the pump motor might also get overheated.
INSTALLATION
Before mounting on pipeline check the following:
1. Remove the terminal box cover (8), and check the insulation resistance of the
set with a meggar to ensure minimum resistance of 10 meg-ohms.
2. Remove end covers and check for free rotation of the rotor. Ensure that
Impeller (5) and locking screw (19) with washer are in their proper position.
3. Connect the supply terminals and ensure rotation of impeller as per 'Arrow
Mark' on the Impeller Housing i.e. anti-clockwise rotation when looking
through the impeller housing opening.
NOTE: In case of wrong direction of rotation of impeller, there will be no discharge.
OPERATION
After installation on the pipe circuit, start filling the system with clean transformer oil
until it completely fills the pump unit, Release all air by the air vent plug initial
continuous air free oil seeps out. It is important that no air is trapped in the pump. It
is always a good practice to allow the pump to run for about 30 minutes before
energising the transformer, to ensure that any air not removed by venting has been
pumped out.
MAINTENANCE
Check periodically the behaviour regarding leakage, vibration, noise, and
current/power consumption of the pump set. In case the pump is to be removed,
allow the unit to cool and drain the oil completely from the set and replace the end
covers. Store as prior installation.
Dismantling of Pump and Motor may be carried out as detailed on Page 201.
TROUBLE SHOOTING
Trouble Checks
1) Reduced or No delivery : a) Casing Suction Pipe not filled with liquid
b) Discharge head too high.
c) Wrong direction of rotation.
d) Air not vented out.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 192 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 193 of 204
POWER TRANSFORMERS
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 194 of 204
POWER TRANSFORMERS
CONSTRUCTIONAL FEATURES
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 195 of 204
POWER TRANSFORMERS
The pump set is a single stage radial flow gland-less type, integral with a squirrel
cage type induction motor suitable for three phase AC Power supply. The pump and
motor are coaxial and suitable for operation in hot transformer oil.
A well balanced impeller is co-axially mounted on the motor shaft through a key and
positively locked in position. A cast iron volute casing mounted on the stator case
through a spigot joint and sealing ring houses the impeller and imparts direction to
the flow of oil as indicated by an arrow cast on it.
Centrifugal type transformer oil pumps are used for circulating transformer oil
through windings and heat exchanger of oil immersed transformer. These type of oil
pumps are not suitable for natural cooling of transformer and hence these are used
only in association with oil to water heat exchanger where natural cooling is not
applicable. Normally oil to water heat exchangers are used on transformers where
water is available in plenty like hydroelectric stations or on transformers used for
furnace applications.
SPECIFICATIONS
MOTOR : 4.3 HP and 7.5 HP
STATOR : 3 Phase, 50 Hz, Induction Type
ROTOR : Squirrel Cage Type
BEARING : Ball Type, Lubricated by transformer oil itself.
COOLING : By circulating transformer oil itself.
PERFORMANCE : To IS: 325-1996; 3 Phase Induction Motor
PUMPS
CASING : Cast Iron
IMPELLER : Cast Aluminium/Bronzed keyed to the shaft
SEALING RINGS : Neoprene rubber
FRAME : Cast Iron totally enclosed integral part of the pump
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 196 of 204
POWER TRANSFORMERS
EL4.3R 220 100 180 18 18 4 220 100 180 18 18 460 220 125 290 195 360 71 111
EL7.5R 285 150 240 23 20 8 285 150 240 23 20 525 227 152 360 210 410 91 131
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 197 of 204
POWER TRANSFORMERS
FLEXIBLE SEPARATOR
(AIR CELL)
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 198 of 204
POWER TRANSFORMERS
FLEXIBLE SEPARATOR
1. INTRODUCTION
Flexible separator (Air Cell) is provided inside the conservator of power
transformers for avoiding direct contact of air with the transformer oil. Air Cell
provides a permanent, flexible and non porous barrier between the
atmosphere and the transformer oil without affecting the operational function
of the system.
The basic construction of the separator is a highly resistant fabric coated
externally to resist transformer oil and internally to Ozone and weather
resistant. Flexible separators offer the following advantages :-
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 199 of 204
POWER TRANSFORMERS
4. INSTALLATION PROCEDURE
1 Connection to the
inside of Air Cell
2 Connection to the
inside of
Conservator
3 Magnetic Oil
Level Gauge
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 200 of 204
POWER TRANSFORMERS
• The conservator with Air Cell is pressure tested and despatched from the
factory at a slightly positive pressure. Confirm that there is no oil leakage.
• Fix three numbers air release valves on the conservator.
• Keep air release valves open. Fix air filling adapter on breather pipe and
inflate the air cell at an air pressure indicated on the INSTRUCTION
PLATE affixed on the transformer and hold air pressure.
DO NOT APPLY EXCESS AIR PRESSURE AS IT MAY
DAMAGE THE AIR CELL.
• Open air release valves and start oil filling from the bottom of the
conservator.
• Observe the air release valves and as soon as oil starts overflowing, close
the air release valves one by one. Stop oil filling when all air release
valves are closed.
• Remove the air filling adapter.
• Continue oil filling and observe the Magnetic Oil Level Gauge (MOLG)
• Stop the filling when the needle of MOLG shows the level corresponding to
the ambient temperature at the time of filling.
• Fix silica gel breather.
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 201 of 204
POWER TRANSFORMERS
CAUTION:
Ø Do not open any of the air release valves after completion of oil
filling. If air release valve is opened, air will enter and oil level will
drop.
Ø The plain oil level gauge on the end cover of the conservator
should indicate full oil level always. If air enters the conservator, it
can be seen by a fall in the oil level in plain oil level gauge.
Ø The plain oil level gauge should be monitored on regular basis.
6. FILLING PROCEDURE UNDER VACUUM IN
CONSERVATOR
The conservator, with its separator, being set up and plugged in above
the transformer, is connected to its oil filling reserve by a pipe in its lower
part.
Proceed as follows:
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 202 of 204
POWER TRANSFORMERS
THERMOSIPHON
FILTER
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 203 of 204
POWER TRANSFORMERS
1. INTRODUCTION
Thermosiphon filter is provided on large capacity, oil filled Power
Transformers for keeping the moisture level of insulating oil at a very low
level. At the time of initial erection and commissioning of transformer, most of
the moisture present in the oil is removed by hot oil circulation. The moisture
absorption of oil is eliminated by directing the air breathed in by the
transformer during its operation through silica gel desiccant. Air cell in
conservator avoids direct contact of oil with air and thereby eliminating the
chance of moisture absorption.
However, it is a well known fact that water is released to the oil from the paper
insulation due to ageing process. Thermosiphon filter helps in removing this
moisture from oil. When the transformer is on load, the thermosiphonic action
of liquid causes circulation of oil through the filter. The adsorbent filled in the
Thermosiphon filter adsorbs moisture and keeps the oil dry.
2. CONSTRUCTION
abcd
OPERATION AND MAINTENANCE
MANUAL FOR
Page 204 of 204
POWER TRANSFORMERS
4. MONITORING
The periodicity of oil testing and acceptance criteria is explained in the
Instruction Manual of the Transformer. However, the same is reproduced here
for your ready reference.