This document provides input data and results for anchor bolt calculations for 12 anchor bolts in concrete. The anchor bolts are M33 steel bolts with a nominal diameter of 33 mm. Load combinations are considered including dead loads, variable loads, and seismic loads. The maximum tension force in an anchor is 60,591 N. The maximum concrete compressive strain is 0.14‰ and stress is 4.26 N/mm2. The resulting tension and compression forces are also provided. Concrete properties, bolt properties, and geometry are defined for calculating anchor bolt capacities.

Uploaded by

Dan Bitca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
363 views13 pages

Anchor Cage Documents

This document provides input data and results for anchor bolt calculations for 12 anchor bolts in concrete. The anchor bolts are M33 steel bolts with a nominal diameter of 33 mm. Load combinations are considered including dead loads, variable loads, and seismic loads. The maximum tension force in an anchor is 60,591 N. The maximum concrete compressive strain is 0.14‰ and stress is 4.26 N/mm2. The resulting tension and compression forces are also provided. Concrete properties, bolt properties, and geometry are defined for calculating anchor bolt capacities.

Uploaded by

Dan Bitca
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Company: Page: 1

Address: Specifier: David


Phone I Fax: | E-Mail:
Design: C-1A S-1A_CASO1_V0 Date: 03/09/2019
Fastening Point:

Specifier's comments:

1 Input data
Anchor type and size: (8.8) M33
Item number: (mortar)

Effective embedment depth: hef,act = 775.0 mm (hef,limit = - mm)


Material: 8.8
Approval No.:
Issued I Valid: -|-
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 30.0 mm

Baseplate :
R lx x ly x t = 1,480.0 mm x 1,480.0 mm x 30.0 mm; (Recommended plate thickness: not calculated)

Profile: Pipe, ; (L x W x T) = 1,200.0 mm x 1,200.0 mm x 12.0 mm


Base material: 2
uncracked concrete, C25/30, fc,cube = 30.00 N/mm ; h = 1,500.0 mm, Temp. short/long: 70/43 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
www.hilti.es
Company: Page: 2
Address: Specifier: David
Phone I Fax: | E-Mail:
Design: C-1A S-1A_CASO1_V0 Date: 03/09/2019
Fastening Point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Load case 1 N = -314.483; Vx = 0.000; Vy = -31.875; no no
Mx = 451.065; My = 0.000; Mz = 0.000;

2 Load case 2 N = -232.950; Vx = 0.000; Vy = -31.875; no no


Mx = 451.065; My = 0.000; Mz = 0.000;

3 Load case 3 N = -314.483; Vx = 0.000; Vy = 0.000; no no


Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces


Controlling load case: 2 Load case 2

Load case 1 (1.35·dead load + 1.50·variable load)


Load case 2 (1.0·dead load + 1.50·variable load)
4y
Load case 3 (1.35·dead load)
5 3

Anchor reactions [kN]


Tension force: (+Tension, -Compression) 6 Tension 2
Anchor Tension force Shear force Shear force x Shear force y
1 22.132 2.656 0.000 -2.656
2 41.362 2.656 0.000 -2.656 7 x 1
3 55.439 2.656 0.000 -2.656
4 60.591 2.656 0.000 -2.656
5 55.439 2.656 0.000 -2.656 8 12
6 41.362 2.656 0.000 -2.656
7 22.132 2.656 0.000 -2.656
9 11
8 2.902 2.656 0.000 -2.656
10
9 0.000 2.656 0.000 -2.656 Compression
10 0.000 2.656 0.000 -2.656
11 0.000 2.656 0.000 -2.656
12 2.902 2.656 0.000 -2.656

max. concrete compressive strain: 0.14 [‰]


max. concrete compressive stress: 4.26 [N/mm ]
2

resulting tension force in (x/y)=(0.0/436.0): 304.261 [kN]


resulting compression force in (x/y)=(0.0/-592.7): 537.211 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
DATA

# Anchor Bolts
Nominal diameter dnom 33.00 mm NhEd 60591 N
Core diameter da 28.71 mm NgEd 304261 N
Head bolt diameter under concrete dh 50.00 mm eN,x 0 mm
Number 12 eN,y 115 mm
Bolt Grade 8.8
fuk 800 N/mm2 VhEd 2656 N
fyb 640 N/mm2 VgEd 31872 N
Tensile strenght NRk,s 414320 N eV 0 mm

Average Distance between center of bolts y S1 223.33 mm


Average Distance between center of bolts x S2 223.33 mm
Distance to edge y C1 1200
Distance to edge x C2 1200
Minimum distance to edge C 1200 mm

hef 775 mm

# Concrete
fck 30 N/mm2
Concrete thickness H 1100 mm

TENSILE LOAD CALCULATIONS

# 1. Concrete cone failure


γMC 1.50
K1 12.70

N0Rk,c 1500780 N
SCr,N 2325 mm
CCr,N 1162.5 mm
A0C,N 5405625 mm2
AC,N 9933395 mm2
γS,N 1.01
γre,N 1.00
γec,Nx 1.00
γec,Ny 0.91
γec,N 0.91
γM,N 1.20
1.20
Z 935 mm
NRk,C 3041137 N
NRd,C 2027425 N > NgEd OK
15.01 %

# 2. Glissement of the fixation failure


γMP 1.50
K2 10.5

Ah 1316 mm2
NRk,p 414578 N
NRd,p 276385 N > NhEd OK
21.92 %

# 3. Combined failure concrete cone + glissement of the fixation

Not required for mechanical fixations


# 4. Failure for crack on concrete
hmin 841 mm
Ccr,sp 841 mm
Scr,sp 1682 mm
CALCULATION NOT REQUIRED

# 5.Pry-out failure

hef 775 mm
C 1200 mm
CALCULATION NOT REQUIRED

Applied when

SHEAR FORCE CALCULATIONS

# 1. Concrete cone failure with lever arm


γMC 1.5
K8 2
AC,N 10549644 mm2

NRk,C 3229804 N
VRk,cp 6459607 N
VRd,cp 4306405 N > VgEd OK
0.74 %

# 2. Failure of the concrete side

γMC 1.50
K9 2.4
lf 264 mm
αV 0º

α 0.05
β 0.05
V0Rk,c 844874 N
A0c,V 6480000 mm2
h 775 mm
Ac,V 1860000 mm2
γS,V 0.90
γh,V 1.52
γec,V 1.00
γα,V 1.00
γre,V 1.00
VRk,c 332627 N
VRd,c 221752 N > VgEd OK
14.37 %
Company: Page: 1
Address: Specifier: David
Phone I Fax: | E-Mail:
Design: C-1A S-1A_CASO2_V0 Date: 03/09/2019
Fastening Point:

Specifier's comments:

1 Input data
Anchor type and size: (8.8) M33
Item number: (mortar)

Hilti Filling Set or any suitable annular gap filling solution


Effective embedment depth: hef,act = 775.0 mm (hef,limit = - mm)
Material: 8.8
Approval No.:
Issued I Valid: -|-
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: eb = 0.0 mm (no stand-off); t = 30.0 mm

Baseplate :
R lx x ly x t = 1,480.0 mm x 1,480.0 mm x 30.0 mm; (Recommended plate thickness: not calculated)

Profile: Pipe, ; (L x W x T) = 1,200.0 mm x 1,200.0 mm x 12.0 mm


Base material: 2
uncracked concrete, C25/30, fc,cube = 30.00 N/mm ; h = 1,500.0 mm, Temp. short/long: 70/43 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Company: Page: 2
Address: Specifier: David
Phone I Fax: | E-Mail:
Design: C-1A S-1A_CASO2_V0 Date: 03/09/2019
Fastening Point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combinación 1 N = -311.610; Vx = 0.000; Vy = -64.520; no no
Mx = 1,235.850; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces


Load case: Design loads

Anchor reactions [kN]


Tension force: (+Tension, -Compression) 4y
Anchor Tension force Shear force Shear force x Shear force y 5 3
1 75.965 5.377 0.000 -5.377
2 136.779 5.377 0.000 -5.377 6 2
Tension
3 181.298 5.377 0.000 -5.377
4 197.593 5.377 0.000 -5.377
5 181.298 5.377 0.000 -5.377
7 x 1
6 136.779 5.377 0.000 -5.377
7 75.965 5.377 0.000 -5.377
8 15.151 5.377 0.000 -5.377
8 12
9 0.000 5.377 0.000 -5.377
10 0.000 5.377 0.000 -5.377
11 0.000 5.377 0.000 -5.377 9 11
12 15.151 5.377 0.000 -5.377 10
Compression

max. concrete compressive strain: 0.41 [‰]


max. concrete compressive stress: 12.19 [N/mm ]
2

resulting tension force in (x/y)=(0.0/423.8): 1,015.978 [kN]


resulting compression force in (x/y)=(0.0/-606.6): 1,327.588 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2018 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
DATA

# Anchor Bolts
Nominal diameter dnom 33.00 mm NhEd 197593 N
Core diameter da 28.71 mm NgEd 1015978 N
Head bolt diameter under concrete dh 50.00 mm eN,x 0 mm
Number 12 eN,y 115 mm
Bolt Grade 8.8
fuk 800 N/mm2 VhEd 5377 N
fyb 640 N/mm2 VgEd 64524 N
Tensile strenght NRk,s 414320 N eV 0 mm

Average distance between center of bolts y S1 223.33 mm


Average distance between center of bolts x S2 223.33 mm
Distance to edge y C1 1200
Distance to edge x C2 1200
Minimum distance to edge C 1200 mm

hef 775 mm

# Concrete
fck 30 N/mm2
Concrete thickness H 1100 mm

TENSILE LOAD CALCULATIONS

# 1. Concrete cone failure


γMC 1.50
K1 12.70

N0Rk,c 1500780 N
SCr,N 2325 mm
CCr,N 1162.5 mm
A0C,N 5405625 mm2
AC,N 9933395 mm2
γS,N 1.01
γre,N 1.00
γec,Nx 1.00
γec,Ny 0.91
γec,N 0.91
γM,N 1.20
1.20
Z 935 mm
NRk,C 3041137 N
NRd,C 2027425 N > NgEd OK
50.11 %

# 2. Glissement of the fixation failure


γMP 1.50
K2 10.5

Ah 1316 mm2
NRk,p 414578 N
NRd,p 276385 N > NhEd OK
71.49 %

# 3. Combined failure concrete cone + glissement of the fixation

Not required for mechanical fixations


# 4. Failure for crack on concrete
hmin 841 mm
Ccr,sp 841 mm
Scr,sp 1682 mm
CALCULATION NOT REQUIRED

# 5.Pry-out failure

hef 775 mm
C 1200 mm
CALCULATION NOT REQUIRED

Applied when

SHEAR FORCE CALCULATIONS

# 1. Concrete cone failure with lever arm


γMC 1.5
K8 2
AC,N 10549644 mm2

NRk,C 3229804 N
VRk,cp 6459607 N
VRd,cp 4306405 N > VgEd OK
1.50 %

# 2. Failure of the concrete side

γMC 1.50
K9 2.4
lf 264 mm
αV 0º

α 0.05
β 0.05
V0Rk,c 844874 N
A0c,V 6480000 mm2
h 775 mm
Ac,V 1860000 mm2
γS,V 0.90
γh,V 1.52
γec,V 1.00
γα,V 1.00
γre,V 1.00
VRk,c 332627 N
VRd,c 221752 N > VgEd OK
29.10 %