Product Catalog

Split System Air Conditioners


Odyssey™ ™
Heat Pump Condenser — 5 to 16.7 Tons — 50 Hz
Air Handler — 4.6 to 16.7 Tons — 50 Hz

July 2018 SSP-PRC024K-EN


Introduction
Trane’s reputation for providing quality comfort solutions continues with the development of the
next generation Light Commercial Odyssey Split Systems.
With wide network availability, flexible applications, installation ease, built-in reliability and easy
servicing, Odyssey will meet any number of customer applications. Add to that Trane’s
outstanding customer service and you have the formula to make Odyssey the clear choice for
continued customer satisfaction.

Wide network availability


A broad distribution network provides owners, maintenance personnel, contractors, etc., the
means to get their hands on equipment when they need it. Whether it’s an emergency
replacement or a new construction project in its infancy stages, Odyssey products meet an array
of needs at the right time and right price.

Flexible applications
No matter what the application, Odyssey provides the solution. A broad array of models and
tonnages are available with single or dual compressors, single or dual circuits and numerous
accessories. Condensing units can be installed on the ground or on a rooftop along with
extended piping runs, while air handlers can be free discharge on the ground or horizontally
suspended with long duct runs from a ceiling. Should application challenges arise, Odyssey
delivers.

Easy to install
Small footprints and low weights combined with factory installed components like TXVs, filter
driers, etc., reduce installation time and cost. Colored and numbered wiring and factory tested
units make Odyssey the right choice.

Built-in reliability
Keeping in mind that productivity only occurs when equipment is operational,Trane has taken
the steps to ensure that Odyssey is up and running. Early indicators such as phase/reversal
monitors and loss of charge protection provide diagnostics which prevent failure and provide
years of worry-free service and operation.

Easy to service
When preventive maintenance or service is required, technicians will find efficient access to both
air handlers and condensers. Panels provide complete, easy access coupled with standardized
cabinets in which all components are located in proximity. Odyssey’s improved design results in
minimum service times and costs.
With these capabilities, Odyssey provides customers high efficiency and superior performance
for the best all-around value in the market today.

Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

©2018 Ingersoll Rand SSP-PRC024K-EN


Introduction

Revision History
• Weights, dimensional drawings have been updated to reflect that service valves are no longer
a factory installed feature.
• Running edits included.

SSP-PRC024K-EN 3
Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Split System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Standard and Optional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Standard and Optional Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
180° Blower Rotation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Cooling Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Heating Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Air Delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19


Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
General Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Gross Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Gross Heating Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
ReliaTel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Electromechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Air Handler (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

4 SSP-PRC024K-EN
Table of Contents

Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Weights. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Heat Pump Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104


Condensing Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Air Handlers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

SSP-PRC024K-EN 5
Features
Split System Overview
Unlike typical split systems on the market, Odyssey offers easy servicing, built-in reliability, ease
of installation and outstanding customer service. And because today’s owners are very cost-
conscious when it comes to service and maintenance, the Odyssey Split System was designed
with direct input from service contractors. This valuable information helped to design a product
that would get the service person off the job quicker and save the owner money.

Flexible Applications
Odyssey offers outstanding standard features enhanced by a variety of factory and field installed
options, multiple control options, rigorously tested proven designs and superior product and
technical support. Because of this, Odyssey offers ultimate flexibility. Units are built to order in
our standard “shortest in the industry” ship cycle time. Odyssey is available with single, dual and
manifolded compressor options. Single compressor outdoor units feature a single refrigeration
circuitry, lowering job installation costs by requiring only one set of refrigerant lines.
Equally important, Odyssey offers single refrigerant circuit/capacity unloading models. The
unloading units feature dual manifolded scroll compressors with two stages of capacity
modulation and a single refrigeration circuit. Dual compressor/dual circuit models give true
stand-by protection - if one compressor fails, the second will automatically start-up. Also, the first
compressor can be serviced without shutting down the unit since the refrigerant circuits are
independent. Dual compressor models also save on energy costs. During light load conditions,
only one compressor will operate to save energy.

Unmatched Product Support


One of our finest assets, Trane Sales Representatives are a support group that can assist you
with:
• Product
• Application
• Service
• Training
• Special Applications
• Specifications
• Computer Programs and much more

Rigorous Testing
Our units are rigorously rain tested to ensure water integrity. Actual shipping tests are performed
to determine packaging requirements. Units are test shipped around the country to determine
the best packaging. Factory shake and drop tests are used as part of the package design process
to help assure that the unit arrives at the job site in top condition. Rigging tests include lifting a
unit into the air and letting it drop one foot, assuring that the lifting lugs and rails hold up under
stress. A 100% coil leak test is performed at the factory. The condenser coils are leak tested at 660
psig and evaporators to 450 psig. All parts are inspected at the point of final assembly. Sub-
standard parts are identified and rejected immediately. Every unit receives a 100% unit run test
before leaving the production line to ensure it lives up to rigorous Trane requirements.

6 SSP-PRC024K-EN
Features

Standard and Optional Features


Figure 1. Compressors Figure 2. Belt drive motor Figure 3. Easy access to terminal board

A i r f l o w D i s t r i b u t i o n — Odyssey can replace an older machine with old ductwork and, in many
cases, improve the comfort through better air distribution.
A n t i - S h o r t C y c l e T i m e r — Provides a 3 minute minimum “ON” time and 3 minute “OFF” time
for compressors to enhance compressor reliability by assuring proper oil return.
B e l t D r i v e M o t o r s — For additional static requirements, Odyssey Split Systems offer standard
belt drive motors to meet and exceed a wide range of airflow needs.
B l a c k E p o x y P r e - C o a t e d C o n d e n s e r C o i l s — The pre-coated coils are an economical option for
protection in mildly corrosive environments.
C o l o r e d A n d N u m b e r e d W i r i n g — Save time and money tracing wires and diagnosing the unit.
C o m p r e s s o r s — Odyssey Split Systems contain the best compressor technology available to
achieve the highest possible performance. Dual compressors perform very well under part load
cooling conditions and system back- up applications. Dual compressors are available on 4.6-20.9
ton models and allow for efficient cooling utilizing 2-stages of compressor operation.
C o n v e r t i b l e U n i t s — The air handlers ship in a horizontal configuration. They can be easily
converted to vertical by simply repositioning the drain pan. Units come complete with duct
flanges so the contractor doesn’t have to field fabricate them. These duct flanges are a time and
cost saver.
C r a n k c a s e H e a t e r s — These band heaters provide improved compressor reliability by warming
the oil to prevent migration during off-cycles or low ambient conditions.
D u a l S l o p e d D r a i n P a n s — Every Odyssey unit has a non-corrosive, removable, double sloped
drain pan that’s easy to clean and reversible to allow installation of drain trap in two positions on
either side of the unit.
E a s y A c c e s s L o w V o l t a g e T e r m i n a l B o a r d — Odyssey’s Low Voltage Terminal Board is
external to the line voltage electrical cabinet. It is extremely easy to locate and attach the
thermostat wire and test operation of all unit functions. This is another cost and time saving
installation feature.
E l e c t r i c H e a t e r s — Electric heat modules are available in a variety of voltages and capacities.
F o i l F a c e d I n s u l a t i o n — All internal air handler surfaces have cleanable foil-faced insulation. All
edges are either captured or sealed to ensure insulation fibers do not get into the airstream.
H a i l / V a n d a l G u a r d s — These coil guards shall be either factory or field installed for condenser
coil protection. This feature protects the condenser coil from vandalism and/or hail damage.
When ordered factory installed, it also adds additional shipping protection.
H i g h / L o w S t a t i c M o t o r — Available on many models, this high static motor accessory extends
the capability of the standard unit.
H i g h P r e s s u r e C o n t r o l — All units include High Pressure Control as standard.
L o w A m b i e n t — Provides ability to cool space when outdoor ambient is below 50°F. Choice of
fan on/off or modulating control.

SSP-PRC024K-EN 7
Features

L o w A m b i e n t C o o l i n g — All Odyssey microprocessor units have cooling capabilities down to 0°


F as standard.
L o w V o l t a g e C o n n e c t i o n s — The wiring of the low voltage connections to the unit and the zone
sensors is as simple as 1-1, 2-2, and 3-3. This simplified system makes it easy for the installer to
wire.
P h a s e M o n i t o r / R e v e r s a l P r o t e c t i o n — Phase monitor shall provide 100% protection for motors
and compressors against problems caused by phase loss, phase imbalance, and phase reversal.
Phase monitors are equipped with an LED that provides an ON or FAULT indicator.
Q u i c k - A c c e s s P a n e l s — Remove a few screws for access to the standardized internal
components and wiring.
S i n g l e P o i n t P o w e r — A single electrical connection powers the unit.
S i n g l e S i d e S e r v i c e — Single side service is standard on all units.
S t a n d a r d i z e d C o m p o n e n t s — Components are placed in the same location on all Odyssey
units. Because of these standardized components throughout the Odyssey line, contractors/
owners can stock fewer parts.
T h e r m a l E x p a n s i o n V a l v e w i t h B y p a s s C h e c k V a l v e s — This feature is standard on all indoor
units.
U n i t C a b i n e t — The compact cabinet takes up less room and is less costly to ship. It’s cabinet
design also ensures water integrity.
Table 1. Odyssey features – standard and optional
Options(a)
Standard Factory Field
Features Installed Installed
1-year Limited Parts Warranty X
5-year Limited Compressor Warranty X
Anti-Short Cycle Timer X
Belt Drive Motors X
Black Epoxy Pre-Coated Coils X
Colored and Numbered Wiring X
Compressor Discharge Temperature Limit (DTL) X
Convertible Airflow X
Crankcase Heaters X
Easy Access Low Voltage Terminal Board (LTB) X
Electric Heaters X
Filters X
Foil-Faced and Edge Captured Insulation X
Hail/Vandal Guards X X
High Pressure Control X
High Static Motor Kit(b) X
IAQ Dual Sloped and Removable Drain Pans X
Liquid Line Refrigerant Drier X
Low Ambient Cooling X
Low Ambient Cooling to 50°F on Electromechanical Models X
Low Pressure Control X
Low Static Motor Kit(b) X
Low Voltage Circuit Protection X
Phase Loss/Reversal Monitor X
Quick Access Panels X
Scroll Compressors X
Single Point Power X

8 SSP-PRC024K-EN
Features

Table 1. Odyssey features – standard and optional (continued)


Options(a)
Standard Factory Field
Features Installed Installed
Single Side Service X
Standardized Components X
Thermal Expansion Valve X
Vibration Isolators X
(a) Refer to model number description for option availability or contact Product Support.
(b) Available on standard units only. See Accessories chapter for more information.

Standard and Optional Controls


™ Controls
ReliaTel™
Figure 4. ReliaTel board

ReliaTel controls provide unit control for heating, cooling, and ventilating, utilizing input from
sensors that measure outdoor and indoor temperature. ReliaTel also provides outputs for
building automation systems and expanded diagnostics. Quality and reliability are enhanced
through ReliaTel control and logic:
• Prevents the unit from short cycling, considerably improving compressor life.
• Ensures the compressor will run for a specific amount of time which allows oil to return for
better lubrication, enhancing the reliability of the compressor.
• Reduces the number of components required to operate the unit, reducing possibilities for
component failure.

ReliaTel Makes Installing and Servicing Easy


ReliaTel eliminates the need for field-installed, anti-short cycle timer and time delay relays. The
wiring of the low voltage connections to the unit and the zone sensors is as easy as 1-1, 2-2, and
3-3. This simplified system makes wiring easier for the installer.

ReliaTel Makes Testing Easy


ReliaTel requires no special tools to run the unit through its paces. Simply place a jumper
between Test 1 and Test 2 terminals on the Low Voltage Terminal Board and the unit will walk
through its operational steps automatically. The unit automatically returns control to the zone
sensor after stepping through the test mode a single time, even if the jumper is left on the unit.
As long as the unit has power and the “system on” LED is lit, ReliaTel is operational. The light
indicates that the controls are functioning properly. ReliaTel features expanded diagnostic
capabilities when utilized with Trane Integrated Comfort™ Systems. Some zone sensor options
have central control panel lights which indicate the mode the unit is in and possible diagnostic
information (dirty filters for example).

ReliaTel Has Other Benefits


• The ReliaTel built-in anti-shortcycle timer, time delay relay and minimum “on” time control
functions are factory tested to assure proper operation.
• ReliaTel softens electrical “spikes” by staging on fans, compressors and heaters.

SSP-PRC024K-EN 9
Features

• Intelligent Fallback is a benefit to the building occupant. If a component goes astray, the unit
will continue to operate at predetermined temperature setpoint.
• Intelligent Anticipation is a standard feature. It functions continuously as ReliaTel and zone
sensor(s) work together in harmony to provide much tighter comfort control than
conventional electromechanical thermostats.
• The ReliaTel design is standardized across the board, ensuring a lower cost to owners.

Additional Controls
V a r i T r a c ® B u i l d i n g A u t o m a t i o n S y s t e m — When Trane’s changeover VAV System for light
commercial applications is coupled with the unit, it provides the latest in technological advances
for comfort management systems and can allow thermostat control in every zone served by
VariTrac.

T r a n e C o m m u n i c a t i o n I n t e r f a c e ( T C I ) — This module, when applied with ReliaTel, easily


interfaces with the Trane Integrated Comfort System™.
F r o s t a t ™ — This control utilizes a capillary bulb embedded in the face of the evaporator coil
which monitors coil temperature to inhibit evaporator icing and protect the compressor.
Recommended for applications with low leaving air temperatures, low airflow and/or high latent
load applications.
L o n T a l k ® C o m m u n i c a t i o n s I n t e r f a c e — The LonTalk communications interface allows the unit
to communicate as a Tracer™ LCI-V device or directly with generic LonTalk Network Building
Automation System Controls.
B A C n e t ® C o m m u n i c a t i o n I n t e r f a c e ( B C I ) — The BACnet Communication Interface allows the
unit to communicate directly with a generic open protocol BACnet MS/TP Network Building
Automation Control System.
Z o n e S e n s o r s / T h e r m o s t a t s — Available in wireless, programmable, automatic and manual
styles.

10 SSP-PRC024K-EN
Features

Table 2. Odyssey control options – standard and optional


Options(a)
Standard Factory Field
Features Installed Installed
BACnet Communication Interface (BCI) X
Froststat - Evaporator Defrost Control (EDC) X
LonTalk Communications Interface (LCI) X X
ReliaTel Microprocessor Controls X X
Thermostat X
Trane Communications Interface (TCI) X
Wireless Zone Sensor X
Zone Sensor X
(a) Refer to model number description for option availability or contact Product Support.

SSP-PRC024K-EN 11
Accessories
Heat Pump Condenser
Table 3. TWA Accessories
Model Used With
Coil (Hail/Vandal) Guard
BAYGARD058* TWA0604*A, TWA0764*A
BAYGARD059* TWA060**D, TWA076**D
BAYGARD060* TWA101
BAYGARD061* TWA156, TWA201
Rubber Isolators
BAYISLT005* (black) TWA060, TWA076, TWA101
BAYISLT009* (red) TWA156
BAYISLT010* (green) TWA201
Steel Spring Isolators
BAYISLT023* (red) TWA060, TWA076, TWA101
BAYISLT024* (black) TWA156
BAYISLT025* (yellow) TWA201
Service Valve Kit
BAYVALV001A TWA0604*A, TWA1014*A
BAYVALV002A TWA0764*A
BAYVALV003A TWA0604*D, TWA0764*D, TWA1014*D
BAYVALV006A TWA1564*D, TWA2014*D
Low Ambient — On/Off Fan Control (External mount, small cabinets)(a) (b) (c)
BAYLOAMU01* (External Mount, small cabinets)(d) TWA060**A, TWA076**A
BAYLOAMU02* (Internal mount, large cabinets) TWA101, TWA156, TWA201
Head Pressure Control(b)
BAYLOAM435*, 50Hz TWA060*DA/D, TWA076*DA/D
BAYLOAM436*, 50Hz TWA101*DA/D, TWA156*DD, TWA201*DD
Transducer Kit for Head Pressure Control (BAYLOAM435, 436, 437)
BAYLOTR001*(e) TWA060**D, TWA076**D, TWA101**D
Trane Communication (3/4 Communications Interface)(f)
BAYICSI003* All Models
LonTalk Communications Interface(f)
BAYLTCI002* All Models
(a) Cycles fan on/off (no modulating).
(b) Quantity of 1 required for each fan (2 total for 13 ton and larger).
(c) ReliaTel™ requires onboard EDC function to be disabled when BAYLOAM is used, remove OA sensor from terminal J8-1&2
(d) Kit mounts external to the outdoor unit and operates by sensing ambient and liquid line temperatures.
(e) BAYLOTR001 required when modulating BAYLOAM kits used with units that have 2 compressors (dual circuit) and 1 condenser fan.
(f) BAYWRKT003 must also be installed when using BAYICSI003 or the BAYLTCI002 on the 13–16.7T Split System Heat Pump units

12 SSP-PRC024K-EN
Accessories

Air Handler
Table 4. TWE Accessories
Model Used With
Base (Subbase)
BAYBASE009* TWE051
BAYBASE0010* TWE072, TWE076
BAYBASE0011* TWE101
BAYBASE0012* TWE126, TWE156
BAYBASE0013* TWE201, TWE251
Drip Kit
BAYDRKT006* TWE051
BAYDRKT007* TWE072, TWE076
BAYDRKT008* TWE101
BAYDRKT009* TWE126, TWE156
BAYDRKT010* TWE201, TWE251
High Static Motor Kits(a)
BAYHSMT105* — 1.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE051*DA
BAYHSMT108* — 1.5HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE072*DB, TWE076*DA/B
BAYHSMT110* — 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE072*DB, TWE076*DA/B
BAYHSMT112* — 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE101*DA/B
BAYHSMT114* — 2.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE126*DB
BAYHSMT117* — 3.0HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE126*DB
BAYHSMT120* — 3.0HP (50Hz) with Motor Sheave and Fan Sheave (Stock
TWE156*DB
Belt used)
BAYHSMT122* — 5.0 HP (50Hz) with Motor Sheave, Fan Sheave and Belt TWE201*DB
Rubber Isolators(b) (c) (d)
BAYISLT004* (Floor — Blue) TWE051, TWE072, TWE076, TWE101
BAYISLT009* (Floor — Red)(e) TWE126, TWE156
BAYISLT010* (Floor — Green)(e)(b) TWE201, TWE251
BAYISLT012* (Suspended —Red/Green) TWE126, TWE156
BAYISLT013* (Suspended —Red/Green)(d) TWE051
BAYISLT014* (Suspended — Green)(d) TWE072, TWE076
BAYISLT015* (Suspended — Green/Black)(d) TWE101
BAYISLT016* (Suspended —Red/Green) TWE201
Steel Spring Isolators(c)
BAYISLT019* (Floor — Red)(e)(b) TWE051, TWE072, TWE076, TWE101
BAYISLT021* (Floor — Black)(e)(b) TWE126, TWE156
BAYISLT032* (Floor — Black/Yellow)(e)(b) TWE201, TWE251
BAYISLT028* (Suspended — Tan) TWE051
BAYISLT029* (Suspended — Red) TWE072, TWE076, TWE101
BAYISLT030* (Suspended — Black) TWE126, TWE156
BAYISLT031* (Suspended — Black/Yellow) TWE201, TWE251
Low Static Drive Kit(a)
BAYLSMT001* TWE201
Plenum(f)
BAYPLNM015* (Discharge Plenum & Grille)(f) TWE051
BAYPLNM016* (Discharge Plenum & Grille)(f) TWE072, TWE076
BAYPLNM017* (Discharge Plenum & Grille)(f) TWE101
BAYPLNM018* (Discharge Plenum/Hydronic Coil Plenum & Grille)(f) TWE126, TWE156
BAYPLNM019* (Discharge Plenum/Hydronic Coil Plenum & Grille)(f) TWE201, TWE251
BAYPLNM020* (Hydronic Coil Discharge Plenum & Grille)(f) TWE051

SSP-PRC024K-EN 13
Accessories

Table 4. TWE Accessories (continued)


Model Used With
BAYPLNM021* (Hydronic Coil Discharge Plenum & Grille)(f) TWE072, TWE076
BAYPLNM022* (Hydronic Coil Discharge Plenum & Grille)(f) TWE101
BAYPLNM030* (Electric Heat Discharge Plenum & Grille)(f) TWE051
BAYPLNM031* (Electric Heat Discharge Plenum & Grille)(f) TWE072, TWE076
BAYPLNM032* (Electric Heat Discharge Plenum & Grille)(f) TWE101
BAYPLNM033* (Electric Heat Discharge Plenum & Grille)(f) TWE126, TWE156
BAYPLNM034* (Electric Heat Discharge Plenum & Grille)(f) TWE201, TWE251
Return Air Grille
BAYGRLE001* TWE051
BAYGRLE002* TWE072, TWE076
BAYGRLE003* TWE101
BAYGRLE004* TWE126, TWE156
BAYGRLE005* TWE201, TWE251
Transformer
BAYTFMR013* -75VA transformer (380*415V/50hz) TWE076, TWE101, TWE072
Water Kits
BAYWATR022* (Steam Coil Enclosure)(f) TWE051
BAYWATR023* (Steam Coil Enclosure)(f) TWE072, TWE076
BAYWATR024* (Steam Coil Enclosure)(f) TWE101
BAYWATR025* (Steam Coil Enclosure)(f) TWE126, TWE156
BAYWATR026* (Steam Coil Enclosure)(f) TWE201, TWE251
BAYWATR027* (Hot Water Coil Enclosure)(f) TWE051
BAYWATR028* (Hot Water Coil Enclosure)(f) TWE072, TWE076
BAYWATR029* (Hot Water Coil Enclosure)(f) TWE101
BAYWATR030* (Hot Water Coil Enclosure)(f) TWE126, TWE156
BAYWATR031* (Hot Water Coil Enclosure)(f) TWE201, TWE251
Wire Kit — 180° Blower Discharge Reversal Kit(g)
BAYWRKT002* TWE051, TWE072, TWE076, TWE101
(a) Used on standard air handlers only.
(b) Requires use of subbase accessory.
(c) In units with steam or hot water coils applied vertically or horizontally, check IOM for proper Isolator Kit selection.
(d) Do not use if blower will operate less than 600 RPM.
(e) When the air handler is in the vertical position and close proximity trapping of condensate is required, use of subbase is required.
(f) When installed horizontally, plenum/water coil must be self-supported.
(g) Cannot be used on TWE126–201, due to motor mount location.

Electric Heaters
Table 5. Electric heaters
Model Used With
4.6–8.33 Ton Electric Heater Selection
BAYHTRL405* — 3.13/3.74 kW Heater 380/415 / 3 Phase TWE051, TWE072*D, TWE076, TWE101
BAYHTRL410* — 6.25/7.46 kW Heater 380/415 / 3 Phase TWE051, TWE072*D, TWE076, TWE101
BAYHTRL415* — 9.37/11.17 kW Heater 380/415 / 3 Phase TWE051, TWE072*D, TWE076, TWE101
BAYHTRL425* — 15.63/18.64 kW Heater 380/415 / 3 Phase TWE051, TWE072*D, TWE076, TWE101
BAYHTRL435* — 21.86/26.08 kW Heater 380/415 / 3 Phase TWE072*D, TWE076, TWE101
10.4–16.7 Ton Electric Heater Selection
BAYHTRM410* — 6.25/7.46 kW Heater 380/415 / 3 Phase TWE126, TWE156, TWE201
BAYHTRM420* — 12.50/14.92 kW Heater 380/415 / 3 Phase TWE126, TWE156, TWE201
BAYHTRM430* — 18.76/22.38 kW Heater 380/415 / 3 Phase TWE126, TWE156, TWE201
BAYHTRM450* — 31.26/37.29 kW Heater 380/415 / 3 Phase TWE126, TWE156, TWE201

14 SSP-PRC024K-EN
Application Considerations
Application of this product should be within the cataloged airflow and performance
considerations.

Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to assure
adequate serviceability, maximum capacity and peak operating efficiency. Actual clearances
which appear inadequate should be reviewed with the local representative.

180° Blower Rotation


The 4.6, 6.25, and 8.33 ton standard air handler blower section can be rotated 180° to change the
discharge pattern. This modification must be done in the field and requires an additional kit. See
unit installation guide.

Low Ambient Cooling


As manufactured, electromechanical units can operate to 50°F in the cooling mode of operation.
An accessory head pressure control will allow operation to 0°F outdoor ambient. When using
these units with control systems such as bypass changeover Variable Air Volume, make sure to
consider the requirement for a head pressure control to allow low ambient cooling.
Figure 5. Typical split system application

Air Handling
Unit

Split
Condensing
Unit

SSP-PRC024K-EN 15
Application Considerations

Figure 6. Typical horizontal air handler application

Isolator (4X)
(Spring or Rubber)

Support Rods and Attaching


Hardware (by others)

Electric Heater
Assembly

Air Handler

Heating Coil &


Enclosure Assembly
(Steam or Hot Water)

Figure 7. Typical vertical air handler application

Discharge Plenum &


Grille Assembly

Heating Coil &


Enclosure Assembly

Air Handler

Horizontal
Drain Return-Air Grille

Vertical
Drain

Subbase

Isolators
(Spring or Rubber)

16 SSP-PRC024K-EN
Selection Procedure
Cooling Capacity
1. Calculate the building’s total and sensible cooling loads at design conditions, using
standardized calculation methods.
2. Size the equipment using the gross cooling capacity tables. Match the cooling loads at design
conditions. For example, if the following specifies the building cooling requirements:
Electrical Characteristics: 415/50/3
Summer Design Conditions: Entering Evap Coil—80°F DB/67°F WB (27°C DB/19°C WB),
Outdoor Ambient—95°F (35°C)
Total Cooling Load: 75 MBh (22 kW)
Sensible Cooling Load: 56 MBh (16.4 kW)
Airflow: 2500 cfm (4248 m3/h)
External Static Pressure: .74 inches of water gauge
3. Use to determine that TWA076**A with TWE076**A has a gross cooling capacity of 77.2 MBh
(22.6 kW) and 62.8 MBh (18.4 kW) sensible capacity at 95°F DB (35°C) ambient and 2500 cfm
(4248 m3/h) with 80°F DB/67° F WB (27°C DB/19°C WB) air entering the evaporator.
4. To find the net cooling capacities, fan motor heat must be subtracted. Determine the total unit
static pressure:
External Static Duct System: 0.74 (191.8 Pa)
Standard Filter: 0.10 in. (25 Pa)
Supplementary Electric Heat: .16 in. (40.6 Pa)
Total Static Pressure: 1 in. (249.09 Pa)
Notes:
• The Evaporator Fan Performance Table has included the effect of a 1 in. (249 Pa)
filter already. Therefore, the actual Total Static Pressure is 1 - 0.1 = .9 in. (233.2 Pa).
With 2500 cfm (4248 m3/h) and .93 in. (231.6 Pa) , Table 62, p. 60 shows 1.51 Bhp
(ultra high static drive kit required).
• This formula can be used to calculate Fan Motor Heat:
3.15 X Bhp = MBh
3.15 X 1.51 = 4.75 MBh
Net Total Cooling Capacity = 77.2 MBh - 4.75 MBh = 72.45 MBh (21.2 kW)
Net Sensible Cooling Capacity = 62.8 MBh - 4.75 MBh = 58.05 MBh (17.0 kW)

Heating Capacity
1. Calculate the building heating load using the Trane calculation form or any other standard
accepted method.
2. Size the equipment using Table 77, p. 74 to match the heating loads at design conditions. For
example, if the following specifies the building heating requirements:
Total Heating Load: 90.0 MBh (26.34 kW)
Outdoor Ambient (Winter): 17°F DB (-8.3°C)
Indoor Return Temperature: 70°F DB (21.1°C)
Airflow: 2500 cfm (4248 m3/h)
3. Table 46, p. 51 indicates the mechanical heating portion of the heat pump will provide 40.4
MBh for the winter design conditions. Full heat load must be carried by the supplementary
heater in the unlikely event the heat pump malfunctions. From Table 78, p. 74, the 34.88 kW
heater at 460V has a capacity of 119,045. From , the 34.88 kW heater at 460V indicates the
heater model is BAYHTRL435.

SSP-PRC024K-EN 17
Selection Procedure

Air Delivery
1. The external static pressure drop through the air distribution system is .74 inches of water
gauge, use Table 77, p. 74 to determine that the static pressure drop through the electric
heater is 0.16 inches of water (.74 + .16 = .9 in.).
2. Enter Table 62, p. 60 for TWE0764DA at 2500 cfm (4248 m3/h) and 1.00 (249 Pa) static
pressure. The high static motor at 987 RPM gives the desired airflow.

18 SSP-PRC024K-EN
Model Number Description
Heat Pump Condenser
Digit 1–3 — Unit Function Digit 8 — Voltage Digit 15 — Controls

TWA = Split System Heat Pump D = 380–415VAC - 3 PH (50Hz) R = ReliaTel™

Digit 4–6 — Tonnage Digit 9 — Refrigeration Circuit/Stage Digit 16 — None

060 = 5 Tons (50Hz) A = 1 Compressor/1 Line/1 Stage (Single) 0 = None


076 = 6.25 Tons (50Hz) D = 2 Compressors/2 Line/2 Stage (Duals)
101 = 8.33 Tons (50Hz) Digit 17 — Coil Protection
156 = 13.0 Tons (50Hz) Digit 10 — Major Design Sequence
201 = 16.7 Tons (50Hz) 0 = Standard Coil
A = Rev A
1 = Standard Coil w/ Hail Guard
Digit 7 — Refrigerant
2 = Black Epoxy Pre-Coated Condenser Coil
Digit 11 — Minor Design Sequence (FIN/TUBE)
4 = R-410A 3 = Black Epoxy Pre-Coated Condenser Coil
B = Rev B with Hail Guard (FIN/TUBE)

Digit 18-20 — None


Digit 12–13 — Service Digits
0 = None
00 = 00

Digit 21 — Communications Options


Digit 14 — Efficiency Generation
0 = No Option
A = Generation A
2 = LonTalk® Communications Interface
(LCI)

Digit 22-40 — None

0 = None

SSP-PRC024K-EN 19
Model Number Description

Air Handler
Digit 1–3 — Unit Function Digit 8 — Voltage Digit 14 — Efficiency Generation

TWE = Air Handler D = 380–415VAC - 3 PH (50Hz) A = Generation A (2018 DOE)

Digit 4–6 — Tonnage Digit 9 — Refrigeration Circuit/Stage Digit 15 — Controls

051 = 4.6 Tons (50Hz) A = Single Circuit 0 = Constant Volume


072 = 6 Tons (50Hz) B = Dual Circuit A = 2 Stage Airflow (Electromechanical Cond
076 = 6.25 Tons (50Hz) Only)
101 = 8.33 Tons (50Hz) Digit 10 — Major Design Sequence B = Single Zone VAV (ReliaTel Cond Only)
126 = 10.4 Tons (50Hz)
A = Rev A Digit 16 — Indoor Fan Sizes
156 = 13.0 Tons (50Hz)
201 = 16.7 Tons (50Hz)
251 = 20.9 Tons (50Hz) Digit 11 — Minor Design Sequence 0 = Standard Motor
4 = High Static – (Oversized Motor for VFD
Digit 7 — Refrigerant A = Rev A Units)

Digit 17–40 — None


4 = R-410A Digit 12–13 — Service Digits
0 = None
00 = 00

20 SSP-PRC024K-EN
General Data
Table 6. General data for 5 - 6.25 ton (TWA0604DA* - TWA0764DD*) heat pump, 50 Hz
5 Tons 5 Tons 6.25 Tons 6.25 Tons
Single Compressor Dual Compressor Single Compressor Dual Compressor
TWA0604DA* TWA0604DD* TWA0764DA* TWA0764DD*
Cooling Performance - Gross Cooling
Capacity
Matched Air Handler TWE0764DA* TWE0724DB* TWE0764DA* TWE0764DB*
AHRI Rated Airflow - (m³/hr) 2,000 (3398) 2,000 (3398) 2,500 (4248) 2,500 (4248)
Matched Air Handler - Btu (kW) 69,000 (20.2) 65,000 (19.0) 75,000 (22) 80,000 (23.4)
Condensing Unit Only - Btu (kW) 63,500 (18.6) 57,500 (16.9) 70,000 (20.5) 72,000 (21.1)
AHRI Net Cooling Capacity - Btu (kW) 68,000 (19.9) 64,500 (18.9) 74,000 (21.7) 79,000 (23.2)
Efficiency
Matched Air Handler/Condensing Unit Only 11.8 / 13.2 11.8 / 12.9 11.8 / 12.7 11.8 / 13.1
System Power/Condensing Unit Power (kW) 5.3 / 4.8 4.9 / 4.5 6.2 / 5.5 6.1 / 5.5
Heating Performance - AHRI Htg/Matched
AH
High Temperature Capacity 62,000 (18.2) 52,000 (15.2) 66,000 (19.3) 65,000 (19)
System kW/COP 4.7 / 3.4 4 / 3.4 4.9 / 3.4 4.9 / 3.4
Low Temperature Capacity 38,500 (11.3) 29,800 (8.7) 41,000 (12) 38,000 (11.1)
System kW/COP 4.2 / 2.3 3.7 / 2.3 4.5 / 2.3 4.5 / 2.3
Compressor
Type Scroll Scroll Scroll Scroll
No. 1 2 1 2
System Data
No. Refrigerant Circuits(a) 1 2 1 2
Suction Line - in. (mm) OD(a) 1-3/8 (34.90) 7/8 (22.23) 1-3/8 (34.90) 1-1/8 (28.60)
Liquid Line - in. (mm) OD(a) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)
Outdoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size - in. (mm) OD 3/8 (9.50) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50)
Face Area, sq ft (m2) 19.24 (1.79) 19.24 (1.79) 19.24 (1.79) 23.96 (2.23)
Rows/FPI (Fins per inch) 2/18 2/18 2/18 2/18
Outdoor Fan
Type Propeller Propeller Propeller Propeller
No. Used/Diameter - in. (mm) 1/26 (660.40) 1/26 (660.40) 1/26 (660.40) 1/26 (660.40)
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM (m3/h) 5,525 (9,387) 5,525 (9,387) 5,525 (9,387) 5,525 (9,387)
No. Motor/HP (kW) 1/0.33 (0.25) 1/0.33 (0.25) 1/0.33 (0.25) 1/0.33 (0.25)
Motor RPM 925 925 925 925
Refrigerant Charge (Field Supplied)
lbs (kg) of R-410A 16.6 (7.5) 11.4/12.4 (5.2 / 5.6) 22.2 (10.1) 11.7/11.7 (5.3 / 5.3)
Shipping Dimensions
45” x 45” x 38” 45” x 55” x 42” 45” x 45” x 38” 45” x 55” x 42”
HxWxD - in. (mm)
(1143 x 1143 x 965) (1143 x 1397 x 1067) (1143 x 1143 x 965) (1143 x 1397 x 1067)
Note: Units are tested in accordance with AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°
F entering wet bulb with 25ft of interconnecting refrigerant piping with minimum external static pressure as determined by rating standard.
(a) Refer to refrigerant piping applications manual for line sizing and line length.

SSP-PRC024K-EN 21
General Data

Table 7. General data for 8.33 - 16.7 ton (TWA1014DA* - TWA2014DD*) heat pump, 50 Hz
8.33 Tons 8.33 Tons 13 Tons 16.7 Tons
Single Compressor Dual Compressor Dual Compressor Dual Compressor
TWA1014DA* TWA1014DD* TWA1564DD* TWA2014DD*
Cooling Performance - Gross Cooling
Capacity
Matched Air Handler TWE1014DA* TWE1014DB* TWE1564DB* TWE2014DB*
AHRI Rated Airflow - (m³/hr) 3,333 (5663) 3,333 (5663) 5,000 (8495) 6,667 (11327)
Matched Air Handler - Btu (kW) 106,000 (31.0) 102,000 (29.9) 158,000 (46.3) 220,000 (64.5)
Condensing Unit Only - Btu (kW) 96,000 (28.1) 93,000 (27.3) 154,000 (45.1) 230,000 (67.4)
AHRI Net Cooling Capacity - Btu (kW) 103,000 (30.2) 99,000 (29.0) 156,000 (45.7) 214,000 (62.7)
Efficiency
Matched Air Handler/Condensing Unit Only 11.8 / 12.9 11.8 / 13.0 11.6 / 12.8 10.7 / 13.2
System Power/Condensing Unit Power (kW) 8.3 / 7.4 7.9 / 7.1 13.5 / 12.2 19.2 / 17.4
Heating Performance - AHRI Htg/Matched
AH
High Temperature Capacity 90,000 (26.4) 88,000 (25.8) 158,000 (46.3) 194,000 (56.9)
System kW/COP 7 / 3.4 6.6 / 3.4 12.4 / 3.3 16.3 / 3.3
Low Temperature Capacity 59,000 (17.3) 54,500 (16) 91,000 (26.7) 118,000 (34.6)
System kW/COP 6.6 / 2.3 6.1 / 2.3 10.8 / 2.2 14.6 / 2.2
Compressor
Type Scroll Scroll Scroll Scroll
No. 1 2 2 2
System Data
No. Refrigerant Circuits(a) 1 2 2 2
Suction Line - in. (mm) OD(a) 1-3/8 (34.90) 1-1/8 (28.60) 1-1/8 (28.60) 1-3/8 (34.90)
Liquid Line - in. (mm) OD(a) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 5/8 (15.88)
Outdoor Coil
Type Lanced Lanced Lanced Lanced
Tube Size - in. (mm) OD 3/8 (9.50) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50)
Face Area, sq ft (m2) 29.02 (2.70) 29.02 (2.70) 52.6 (4.89) 52.6 (4.89)
Rows/FPI (Fins per inch) 2/18 2/18 2/18 2/18
Outdoor Fan
Type Propeller Propeller Propeller Propeller
No. Used/Diameter - in. (mm) 1/28 (711.20) 1/28 (711.20) 2/28 (711.20) 2/28 (711.20)
Drive Type/No. Speeds Direct/1 Direct/1 Direct/1 Direct/1
CFM (m3/h) 8,250 (14,017) 8,250 (14,017) 16,354 (27,786) 16,354 (27,786)
No. Motor/HP (kW) 1/.75 (0.56) 1/.75 (0.56) 1/.75 (0.56) 1/.75 (0.56)
Motor RPM 925 925 925 925
Refrigerant Charge (Field Supplied)
lbs (kg) of R-410A 34.7 (15.7) 14/14 (6.4 / 6.4) 19.2/19.9 (8.7 / 9.0) 18.6/18.4 (8.4 / 8.3)
Shipping Dimensions
52.1” x 55” x 42” 52.1” x 55” x 42” 51.1” x 96” x 48" 51.1” x 96” x 48"
HxWxD - in. (mm)
(1323 x 1397 x 1067) (1323 x 1397 x 1067) (1298 x 2438 x 1219) (1298 x 2438 x 1219)
Note: Units are tested in accordance with AHRI Standard 340-360 (I-P)-2007. Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°
F entering wet bulb with 25ft of interconnecting refrigerant piping with minimum external static pressure as determined by rating standard.
(a) Refer to refrigerant piping applications manual for line sizing and line length.

22 SSP-PRC024K-EN
General Data

Table 8. General data for 4.6 - 6.25 ton (TWE0514DA* - TWE0764DB*) air handler, 50 Hz
4.6 Tons 6 Tons 6.25 Tons 6.25 Tons
Single Circuit Dual Circuit Single Circuit Dual Circuit
TWE0514DA* TWE0724DB* TWE0764DA* TWE0764DB*
System Data
No. Refrigerant Circuits 1 2 1 2
Suction Line Connection, in. (mm) OD 1 1/8 (28.58) 1 1/8 (25.60) 1 3/8 (34.90) 1 1/8 (25.60)
Liquid Line Connection, in. (mm) OD 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70)
Indoor Coil
Type Lanced/Intertwined Lanced/Intertwined Lanced/Intertwined Lanced/Intertwined
Tube Size, in. (mm) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50)
Face Area, sq. ft. (m2) 5.0 (0.46) 8.1 (0.75) 8.1 (0.75) 8.1 (0.75)
Rows/FPI 4/14 4/14 4/14 4/14
Refrigerant Control Expansion Valve Expansion Valve Expansion Valve Expansion Valve
Drain Connection Size, in. (mm) 1.0 (25.40) PVC 1.0 (25.40) PVC 1.0 (25.40) PVC 1.0 (25.40) PVC
Indoor Fan
Type Centrifugal Centrifugal Centrifugal Centrifugal
1/12 x 12 1/15 x 15 1/15 x 15 1/15 x 15
No. Used/Diameter x Width, in. (mm)
(304.8 x 304.8) (381.0 x 381.0) (381.0 x 381.0) (381.0 x 381.0)
Drive Type/No. Speeds Belt/Adjustable Belt/Adjustable Belt/Adjustable Belt/Adjustable
CFM (m3/h) (Nominal) 2,000 (3,398) 2,000 (3,398) 2,500 (4,248) 2,500 (4,248)
No. Motors 1 1 1 1
0.75/1.0 1.5/2.0/3.0 1.5/2.0/3.0 1.5/2.0/3.0
Motor HP - Standard/Oversized (kw)
(0.56/0.75) (1.10/1.50/2.2) (1.10/1.50/2.2) (1.10/1.50/2.2)
Motor RPM 1450 1450 1450 1450
Motor Frame Size 56 56H 56H 56H
Filters
Type/Furnished Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes
(1) 16 x 20 x 1;
(No.)/Size Recommended (3) 16 X 25 X 1 (3) 16 X 25 X 1 (3) 16 X 25 X 1
(1) 20 x 20 x 1
Shipping Dimensions
55.1” x 27.5” x 43.5” 61.2” x 30.5” x 53” 61.2” x 30.5” x 53” 61.2” x 30.5” x 53”
HxWxD - in. (mm) (1399.5 x 698.5 x (1554.5 x 774.7 x (1554.5 x 774.7 x (1554.5 x 774.7 x
1104.9) 1346.2) 1346.2) 1346.2)

SSP-PRC024K-EN 23
24
Table 9. General data for 8.33 - 16.7 ton (TWE1014DA* - TWE2014DB*) air handler, 50 Hz
8.33 Tons 8.33 Tons 10.4 Tons 13 Tons 16.7 Tons
Single Circuit Dual Circuit Dual Circuit Dual Circuit Dual Circuit
TWE1014DA* TWE1014DB* TWE1264DB* TWE1564DB* TWE2014DB*
System Data
No. Refrigerant Circuits 1 2 2 2 2
General Data

Suction Line Connection, in. (mm) OD 1 3/8 (34.90) 1 1/8 (25.60) 1 3/8 (34.90) 1 3/8 (34.90) 1 3/8 (34.90)
Liquid Line Connection, in. (mm) OD 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 1/2 (12.70) 5/8 (15.88)
Indoor Coil
Type Lanced/Intertwined Lanced/Intertwined Lanced/Intertwined Lanced/Intertwined Lanced/Intertwined
Tube Size, in. (mm) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50) 3/8 (9.50)
Face Area, sq. ft. (m2) 11.2 (1.04) 11.2 (1.04) 16.3 (1.51) 16.3 (1.51) 21.7 (2.01)
Rows/FPI 4/14 4/14 4/14 4/14 3/14
Refrigerant Control Expansion Valve Expansion Valve Expansion Valve Expansion Valve Expansion Valve
Drain Connection Size, in. (mm) 1.0 (25.40) PVC 1.0 (25.40) PVC 1.0 (25.40) PVC 1.0 (25.40) PVC 1.0 (25.40) PVC
Indoor Fan
Type Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
1/15 x 15 1/15 x 15 2/15 x 15 2/15 x 15 2/15 x 15
No. Used/Diameter x Width, in. (mm)
(381.0 x 381.0) (381.0 x 381.0) (381.0 x 381.0) (381.0 x 381.0) (381.0 x 381.0)
Drive Type/No. Speeds Belt/Adjustable Belt/Adjustable Belt/Adjustable Belt/Adjustable Belt/Adjustable
CFM (m3/h) (Nominal) 3,350 (5,692) 3,350 (5,692) 4,200 (7,136) 5,000 (8,495) 6,675 (11,341)
No. Motors 1 1 1 1 1
2.0 2.0/3.0 2.0/3.0/5.0 3.0/5.0 3.0/5.0/7.5 (2.20/
Motor HP - Standard/Oversized (kw)
(1.50) (1.50/2.20) (1.50/2.20/3.70) (2.20/3.70) 3.70/5.60)
Motor RPM 1500 1500 1500 1,450/1,500 1,500/2,930
Motor Frame Size 56HZ 56HZ 145T 56HZ 184T
Filters
Type/Furnished Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes Throwaway/Yes
(4) 16 X 25 X 2;
(No.)/Size Recommended (4) 16 X 25 X 1 (4) 16 X 25 X 1 (8) 15 X 20 X 2 (8) 15 X 20 X 2
(4) 16 X 20 X 2
Shipping Dimensions
61.2” x 30.5” x 69” 61.2” x 30.5” x 69” 79.1” x 35.8” x 95”
76.3” x 33.8” x 85” 76.3” x 33.8” x 85”
HxWxD - in. (mm) (1554.5 x 774.7 x (1554.5 x 774.7 x (2009.1 x 909.3 x
(1938 x 850.9 x 2159) (1938 x 850.9 x 2159)
1752.6) 1752.6) 2413)

SSP-PRC024K-EN
Performance Data
Gross Cooling Capacities
Table 10. Gross cooling capacities (MBH) TWA0604*A condensing unit with TWE0764*A air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 64.6 53.9 72.1 42.1 80.2 29.7 61.5 52.4 68.7 40.7 76.5 28.3 58.2 50.9 65.1 39.2 72.5 26.9
80 64.7 63.6 71.9 51.9 80.3 39.7 61.6 61.6 68.5 50.5 76.6 38.3 58.3 58.3 65.2 49.1 72.6 36.9
1800
85 64.7 64.7 72.3 61.7 80.4 49.7 61.7 61.7 68.9 60.3 76.7 48.3 58.4 58.4 65.3 58.8 72.7 46.9
90 64.8 64.8 72.4 71.4 80.2 59.6 61.7 61.7 69.0 69.0 76.7 58.3 58.4 58.4 65.4 65.4 72.8 56.8
75 65.8 57.1 73.4 44.0 81.5 30.2 62.7 55.6 69.9 42.6 77.6 28.8 59.2 54.0 66.2 41.1 73.5 27.4
80 65.9 65.9 73.5 55.0 81.7 41.4 62.7 62.7 70.0 53.5 77.8 40.0 59.3 59.3 66.3 52.0 73.7 38.6
2000
85 66.0 66.0 73.6 65.7 81.8 52.5 62.8 62.8 70.1 64.3 77.9 51.1 59.4 59.4 66.4 62.8 73.4 49.6
90 66.0 66.0 73.7 73.7 81.8 63.4 62.8 62.8 70.2 70.2 78.0 62.0 59.4 59.4 66.5 66.5 73.9 60.5
75 66.9 60.2 74.5 45.9 82.6 30.7 63.6 58.7 70.9 44.5 78.6 29.3 60.1 57.1 67.0 43.0 74.4 27.9
80 66.9 66.9 74.6 57.8 82.7 43.0 63.7 63.7 71.0 56.4 78.8 41.6 60.2 60.2 67.2 54.8 74.6 40.2
2200
85 67.0 67.0 74.7 69.7 82.5 55.1 63.7 63.7 71.1 68.2 78.5 53.8 60.2 60.2 67.3 66.7 74.3 52.3
90 67.0 67.0 74.8 74.8 82.9 67.1 63.7 63.7 71.2 71.2 79.0 65.7 60.2 60.2 67.3 67.3 74.8 64.2
75 67.7 63.3 75.4 47.7 83.5 31.2 64.4 61.7 71.7 46.3 79.4 29.8 60.8 60.1 67.8 44.8 75.1 28.4
80 67.8 67.8 75.5 60.7 83.7 44.6 64.5 64.5 71.8 59.2 79.6 43.2 60.9 60.9 67.9 57.6 75.3 41.8
2400
85 67.9 67.9 75.6 73.6 83.4 57.9 64.5 64.5 71.9 71.9 79.7 56.4 60.9 60.9 68.0 68.0 75.4 54.9
90 67.9 67.9 75.7 75.7 83.9 70.8 64.5 64.5 72.0 72.0 79.8 69.4 60.9 60.9 68.1 68.1 75.6 67.9
Ambient Temperature (°F) Ambient Temperature (°F)
115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 54.7 49.2 61.2 37.7 68.2 25.4 50.8 47.5 57.1 36.0 63.6 23.8
80 54.8 54.8 61.3 47.5 68.4 35.4 50.9 50.9 57.2 45.8 63.8 33.8
1800
85 54.8 54.8 61.4 57.2 68.1 45.4 51.0 51.0 57.3 55.5 63.6 43.8
90 54.8 54.8 61.5 61.5 68.6 55.2 51.0 51.0 57.4 57.4 64.0 53.6
75 55.6 52.3 62.2 39.5 69.1 25.9 51.6 50.6 57.9 37.9 64.4 24.3
80 55.7 55.7 62.3 50.4 69.3 37.1 51.7 51.7 58.0 48.6 64.7 35.5
2000
85 55.7 55.7 62.4 61.1 69.1 48.1 51.8 51.8 58.2 58.2 64.8 46.5
90 55.7 55.7 62.5 62.5 69.6 58.9 51.8 51.8 58.2 58.2 64.9 57.3
75 56.3 55.4 63.0 41.4 69.9 26.4 52.3 52.3 58.6 39.7 65.1 24.8
80 56.4 56.4 63.1 53.2 70.1 38.7 52.4 52.4 58.7 51.5 65.4 37.1
2200
85 56.5 56.5 63.2 63.2 70.3 50.7 52.4 52.4 58.9 58.9 65.5 49.1
90 56.5 56.5 63.3 63.3 70.4 62.6 52.5 52.5 58.9 58.9 65.7 61.0
75 57.0 57.0 63.6 43.2 70.5 26.9 52.9 52.9 59.2 41.6 65.6 25.3
80 57.1 57.1 63.8 56.0 70.8 40.3 53.0 53.0 59.3 54.2 66.0 38.7
2400
85 57.1 57.1 63.9 63.9 71.0 53.3 53.0 53.0 59.4 59.4 66.1 51.6
90 57.1 57.1 63.9 63.9 71.1 66.3 53.0 53.0 59.5 59.5 66.3 64.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 25
Performance Data

Table 11. Gross cooling capacities (kW) TWA0604*A condensing unit with TWE0764*A air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)
30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 18.5 15.5 20.7 12.1 22.9 8.5 17.6 15.1 19.7 11.7 21.9 8.1 16.7 14.6 18.6 11.2 20.7 7.7
27 18.5 18.3 20.6 14.9 23.0 11.4 17.7 17.7 19.6 14.5 21.9 11.0 16.7 16.7 18.7 14.1 20.7 10.6
3058
30 18.6 18.6 20.7 17.7 22.9 14.2 17.7 17.7 19.7 17.3 21.9 13.9 16.7 16.7 18.7 16.9 20.8 13.5
33 18.6 18.6 20.7 20.5 22.9 17.1 17.7 17.7 19.8 19.8 21.9 16.7 16.7 16.7 18.7 18.7 20.8 16.3
24 18.9 16.4 21.0 12.6 23.3 8.6 18.0 16.0 20.0 12.2 22.2 8.2 17.0 15.5 18.9 11.8 21.0 7.8
27 18.9 18.9 21.0 15.8 23.3 11.8 18.0 18.0 20.0 15.4 22.2 11.5 17.0 17.0 19.0 14.9 21.0 11.0
3398
30 18.9 18.9 21.1 18.9 23.4 15.0 18.0 18.0 20.1 18.5 22.2 14.6 17.0 17.0 19.0 18.0 21.1 14.2
33 18.9 18.9 21.1 21.1 23.4 18.2 18.0 18.0 20.1 20.1 22.3 17.8 17.0 17.0 19.0 19.0 21.1 17.4
24 19.2 17.3 21.3 13.2 23.6 8.8 18.2 16.9 20.3 12.7 22.4 8.4 17.2 16.4 19.2 12.3 21.2 8.0
27 19.2 19.2 21.3 16.6 23.6 12.3 18.2 18.2 20.3 16.2 22.5 11.9 17.2 17.2 19.2 15.7 21.3 11.5
3738
30 19.2 19.2 21.4 20.0 23.7 15.8 18.3 18.3 20.3 19.6 22.5 15.4 17.2 17.2 19.2 19.1 21.3 15.0
33 19.2 19.2 21.4 21.4 23.7 19.3 18.3 18.3 20.4 20.4 22.5 18.8 17.2 17.2 19.3 19.3 21.4 18.4
24 19.4 18.2 21.6 13.7 23.8 8.9 18.4 17.7 20.5 13.3 22.7 8.5 17.4 17.3 19.4 12.8 21.4 8.1
27 19.4 19.4 21.6 17.4 23.9 12.8 18.5 18.5 20.5 17.0 22.7 12.4 17.4 17.4 19.4 16.5 21.5 12.0
4078
30 19.4 19.4 21.6 21.1 23.9 16.6 18.5 18.5 20.6 20.6 22.8 16.2 17.4 17.4 19.5 19.5 21.5 15.8
33 19.4 19.4 21.6 21.6 23.9 20.3 18.5 18.5 20.6 20.6 22.8 19.9 17.4 17.4 19.5 19.5 21.6 19.5
Ambient Temperature (°C) Ambient Temperature (°C)
45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22
Airflow DB
3
m /hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 15.7 14.1 17.5 10.8 19.5 7.2 14.5 13.6 16.3 10.3 18.2 6.8
27 15.7 15.7 17.5 13.6 19.5 10.1 14.6 14.6 16.3 13.1 18.2 9.7
3058
30 15.7 15.7 17.6 16.4 19.6 13.0 14.6 14.6 16.4 15.9 18.3 12.6
33 15.7 15.7 17.6 17.6 19.6 15.8 14.6 14.6 16.4 16.4 18.3 15.4
24 15.9 15.0 17.8 11.3 19.7 7.4 14.8 14.5 16.6 10.9 18.4 6.9
27 15.9 15.9 17.8 14.5 19.8 10.6 14.8 14.8 16.6 14.0 18.5 10.2
3398
30 16.0 16.0 17.9 17.6 19.8 13.8 14.8 14.8 16.6 16.6 18.5 13.4
33 16.0 16.0 17.9 17.9 19.9 16.9 14.8 14.8 16.6 16.6 18.5 16.4
24 16.1 15.9 18.0 11.9 20.0 7.5 15.0 15.0 16.7 11.4 18.6 7.1
27 16.2 16.2 18.0 15.3 20.0 11.1 15.0 15.0 16.8 14.8 18.7 10.6
3738
30 16.2 16.2 18.1 18.1 20.1 14.6 15.0 15.0 16.8 16.8 18.7 14.1
33 16.2 16.2 18.1 18.1 20.1 18.0 15.0 15.0 16.8 16.8 18.7 17.5
24 16.3 16.3 18.2 12.4 20.1 7.7 15.1 15.1 16.9 11.9 18.7 7.2
27 16.3 16.3 18.2 16.1 20.2 11.5 15.1 15.1 17.0 15.6 18.8 11.1
4078
30 16.3 16.3 18.3 18.3 20.2 15.3 15.2 15.2 17.0 17.0 18.9 14.8
33 16.3 16.3 18.3 18.3 20.3 19.0 15.2 15.2 17.0 17.0 18.9 18.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

26 SSP-PRC024K-EN
Performance Data

Table 12. Gross cooling capacities (MBH) TWA0604*D condensing unit with TWE0724*B air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)

85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent 61 67 73 61 67 73 61 67 73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
75 61.0 49.5 68.3 38.4 72.9 26.9 55.6 48.2 62.2 37.2 69.5 25.7 52.8 46.9 59.0 35.9 66.0 24.5
80 58.6 58.6 64.9 47.5 72.6 36.2 56.4 56.4 61.9 46.3 69.2 35.0 54.1 54.1 58.7 45.0 65.6 33.7
1800
85 64.9 64.9 64.9 56.6 72.3 45.4 59.7 59.7 61.9 55.4 68.8 44.1 57.2 57.2 58.8 54.1 65.3 42.9
90 65.4 65.4 65.5 65.5 72.0 54.6 62.9 62.9 63.0 63.0 71.9 55.9 60.4 60.4 60.5 60.5 65.1 52.1
75 59.5 52.4 66.4 40.1 74.1 27.5 56.7 51.1 63.3 38.9 70.6 26.2 53.8 49.8 60.0 37.6 66.9 24.9
80 60.8 60.8 66.1 50.2 73.8 37.7 58.4 58.4 63.0 49.0 70.3 36.4 55.9 55.9 59.7 47.7 66.6 35.2
2000
85 64.3 64.3 66.2 60.3 73.5 47.9 61.8 61.8 63.2 59.0 69.9 46.6 59.0 59.0 60.0 57.7 66.3 45.4
90 67.8 67.8 68.0 68.0 73.2 58.0 65.2 65.2 65.4 65.4 69.7 56.7 62.6 62.6 62.7 62.7 66.2 55.4
75 60.5 55.2 67.4 41.8 75.1 27.9 57.7 53.9 64.1 40.6 71.5 26.7 54.7 52.5 63.7 41.1 67.7 25.4
80 62.6 62.6 67.1 52.9 74.8 39.1 63.0 63.0 63.9 51.7 71.2 37.9 57.5 57.5 60.6 50.2 67.4 36.6
2200
85 66.3 66.3 67.4 63.9 74.5 50.3 63.7 63.7 64.4 62.6 70.8 49.0 61.0 61.0 61.3 60.3 67.1 47.8
90 70.0 70.0 70.1 70.1 74.4 61.3 67.3 67.3 70.6 70.6 70.8 60.0 64.5 64.5 64.6 64.6 67.1 58.7
75 61.2 58.6 68.2 43.5 76.0 28.4 58.6 56.7 64.9 42.2 72.3 27.2 55.5 55.5 61.5 40.9 68.4 25.9
80 64.3 64.3 68.0 55.4 75.7 40.6 61.7 61.7 64.8 54.1 71.8 39.3 58.9 58.9 64.3 55.2 68.1 38.0
2400
85 68.1 68.1 68.6 67.5 75.4 52.7 65.4 65.4 65.7 65.0 71.6 51.4 62.5 62.5 62.6 62.6 67.8 50.1
90 71.9 71.9 72.1 72.1 75.3 64.6 69.1 69.1 69.2 69.2 71.7 63.3 66.1 66.1 66.2 66.2 68.0 62.0
Ambient Temperature (°F) Ambient Temperature (°F)

115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent 61 67 73 61 67 73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
75 49.9 45.6 55.7 34.6 62.3 23.2 46.9 44.2 52.3 33.3 58.5 21.9
80 51.6 51.6 55.5 43.8 61.9 32.4 49.0 49.0 52.1 42.4 58.1 31.1
1800
85 54.7 54.7 55.6 52.8 61.6 41.6 52.0 52.0 52.5 50.7 57.7 40.3
90 57.7 57.7 57.8 57.8 61.4 50.7 54.9 54.9 55.0 55.0 57.7 49.4
75 53.2 50.7 56.6 36.3 63.1 23.7 47.9 46.3 53.1 34.9 59.2 22.3
80 53.3 53.3 56.4 46.4 62.8 33.9 50.6 50.6 52.9 44.9 58.9 32.6
2000
85 56.5 56.5 56.9 55.5 62.5 44.1 53.7 53.7 53.8 53.6 58.6 42.7
90 59.7 59.7 59.8 59.8 62.4 54.1 56.7 56.7 56.8 56.8 58.6 52.7
75 51.9 50.5 57.3 37.9 63.9 24.1 48.9 48.9 53.7 36.6 59.8 22.8
80 54.9 54.9 57.2 48.9 66.6 37.0 52.0 52.0 53.7 47.5 59.5 34.0
2200
85 58.1 58.1 58.2 58.2 63.2 46.4 55.2 55.2 55.2 55.2 59.3 45.0
90 61.5 61.5 61.6 61.6 63.3 57.4 58.3 58.3 58.4 58.4 59.3 56.0
75 52.8 52.8 57.9 39.5 64.4 24.5 50.0 50.0 54.2 38.1 60.3 23.2
80 56.2 56.2 57.9 51.4 64.2 36.7 53.2 53.2 54.1 50.4 60.1 35.4
2400
85 59.6 59.6 59.7 59.7 63.9 48.7 56.5 56.5 56.5 56.5 59.8 47.3
90 63.0 63.0 63.1 63.1 64.0 60.7 59.7 59.7 59.8 59.8 59.9 59.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 27
Performance Data

Table 13. Gross cooling capacities (kW) TWA0604*D condensing unit with TWE0724*B air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)

30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent 16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 17.9 14.5 20.0 11.3 21.4 7.9 16.3 14.1 18.2 10.9 20.4 7.5 15.5 13.7 17.3 10.5 19.3 7.2
27 17.2 17.2 19.0 13.9 21.3 10.6 16.5 16.5 18.1 13.6 20.3 10.2 15.8 15.8 17.2 13.2 19.2 9.9
3058
30 19.0 19.0 19.0 16.6 21.2 13.3 17.5 17.5 18.1 16.2 20.2 12.9 16.8 16.8 17.2 15.9 19.1 12.6
33 19.2 19.2 19.2 19.2 21.1 16.0 18.4 18.4 18.5 18.5 21.1 16.4 17.7 17.7 17.7 17.7 19.1 15.3
24 17.4 15.3 19.5 11.8 21.7 8.0 16.6 15.0 18.5 11.4 20.7 7.7 15.8 14.6 17.6 11.0 19.6 7.3
27 17.8 17.8 19.4 14.7 21.6 11.0 17.1 17.1 18.5 14.4 20.6 10.7 16.4 16.4 17.5 14.0 19.5 10.3
3398
30 18.8 18.8 19.4 17.7 21.5 14.0 18.1 18.1 18.5 17.3 20.5 13.7 17.3 17.3 17.6 16.9 19.4 13.3
33 19.9 19.9 19.9 19.9 21.5 17.0 19.1 19.1 19.2 19.2 20.4 16.6 18.3 18.3 18.4 18.4 19.4 16.2
24 17.7 16.2 19.8 12.3 22.0 8.2 16.9 15.8 18.8 11.9 21.0 7.8 16.0 15.4 18.7 12.1 19.9 7.4
27 18.3 18.3 19.7 15.5 21.9 11.5 18.5 18.5 18.7 15.1 20.9 11.1 16.9 16.9 17.8 14.7 19.8 10.7
3738
30 19.4 19.4 19.8 18.7 21.8 14.7 18.7 18.7 18.9 18.4 20.8 14.4 17.9 17.9 18.0 17.7 19.7 14.0
33 20.5 20.5 20.6 20.6 21.8 18.0 19.7 19.7 20.7 20.7 20.7 17.6 18.9 18.9 18.9 18.9 19.7 17.2
24 17.9 17.2 20.0 12.7 22.3 8.3 17.2 16.6 19.0 12.4 21.2 8.0 16.3 16.3 18.0 12.0 20.0 7.6
27 18.8 18.8 19.9 16.2 22.2 11.9 18.1 18.1 19.0 15.9 21.1 11.5 17.3 17.3 18.8 16.2 20.0 11.1
4078
30 20.0 20.0 20.1 19.8 22.1 15.4 19.2 19.2 19.2 19.1 21.0 15.1 18.3 18.3 18.4 18.4 19.9 14.7
33 21.1 21.1 21.1 21.1 22.1 18.9 20.2 20.2 20.3 20.3 21.0 18.6 19.4 19.4 19.4 19.4 19.9 18.2
Ambient Temperature (°C) Ambient Temperature (°C)

45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 14.6 13.4 16.3 10.1 18.3 6.8 13.7 13.0 15.3 9.7 17.1 6.4
27 15.1 15.1 16.3 12.8 18.2 9.5 14.4 14.4 15.3 12.4 17.0 9.1
3058
30 16.0 16.0 16.3 15.5 18.1 12.2 15.2 15.2 15.4 14.9 16.9 11.8
33 16.9 16.9 16.9 16.9 18.0 14.9 16.1 16.1 16.1 16.1 16.9 14.5
24 15.6 14.9 16.6 10.6 18.5 6.9 14.0 13.6 15.6 10.2 17.4 6.5
27 15.6 15.6 16.5 13.6 18.4 9.9 14.8 14.8 15.5 13.2 17.3 9.5
3398
30 16.6 16.6 16.7 16.3 18.3 12.9 15.7 15.7 15.8 15.7 17.2 12.5
33 17.5 17.5 17.5 17.5 18.3 15.9 16.6 16.6 16.7 16.7 17.2 15.5
24 15.2 14.8 16.8 11.1 18.7 7.1 14.3 14.3 15.7 10.7 17.5 6.7
27 16.1 16.1 16.8 14.3 19.5 10.8 15.2 15.2 15.7 13.9 17.4 10.0
3738
30 17.0 17.0 17.1 17.1 18.5 13.6 16.2 16.2 16.2 16.2 17.4 13.2
33 18.0 18.0 18.0 18.0 18.6 16.8 17.1 17.1 17.1 17.1 17.4 16.4
24 15.5 15.5 17.0 11.6 18.9 7.2 14.6 14.6 15.9 11.2 17.7 6.8
27 16.5 16.5 17.0 15.1 18.8 10.8 15.6 15.6 15.9 14.8 17.6 10.4
4078
30 17.5 17.5 17.5 17.5 18.7 14.3 16.5 16.5 16.6 16.6 17.5 13.9
33 18.5 18.5 18.5 18.5 18.8 17.8 17.5 17.5 17.5 17.5 17.6 17.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

28 SSP-PRC024K-EN
Performance Data

Table 14. Gross cooling capacities (MBH) TWA0764*A condensing unit with TWE0764*A air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 72.2 63.5 80.3 48.3 89.0 32.7 68.8 61.9 76.4 46.7 84.7 31.2 65.2 60.4 72.2 45.1 80.1 29.6
80 73.2 73.2 80.0 60.6 88.7 45.2 70.3 70.3 76.0 59.1 84.3 43.6 67.2 67.2 71.9 57.5 79.7 42.0
2250
85 77.2 77.2 80.0 73.0 88.4 57.6 74.2 74.2 76.2 71.5 84.0 56.0 70.9 70.9 72.2 69.9 79.4 54.4
90 81.3 81.3 81.4 81.4 88.1 69.9 78.1 78.1 78.2 78.2 83.8 68.4 74.7 74.7 74.8 74.8 79.2 66.9
75 73.6 67.6 81.5 50.6 90.3 33.3 70.0 66.0 77.5 49.1 85.8 31.8 66.2 64.3 73.2 47.4 81.1 30.2
80 75.6 75.6 81.2 64.3 90.0 47.2 72.5 72.5 77.2 62.8 85.5 45.6 69.2 69.2 73.0 61.2 80.7 44.0
2500
85 79.7 79.7 81.5 78.2 89.7 61.0 76.5 76.5 77.6 76.6 85.2 59.4 73.1 73.1 73.6 73.6 80.4 57.8
90 84.0 84.0 84.1 84.1 89.5 74.8 80.6 80.6 80.7 80.7 85.0 73.3 77.0 77.0 77.1 77.1 80.4 71.7
75 74.7 71.6 82.6 53.0 91.4 33.9 71.1 70.0 78.4 51.4 86.8 32.4 67.4 67.4 74.1 49.7 81.9 30.8
80 77.6 77.6 82.3 68.1 91.1 49.2 74.4 74.4 78.2 66.5 86.4 47.6 71.0 71.0 73.9 64.9 81.6 46.0
2750
85 82.0 82.0 82.9 82.9 90.7 64.4 78.6 78.6 79.0 79.0 86.1 62.8 75.0 75.0 75.0 75.0 81.3 61.2
90 86.4 86.4 86.5 86.5 90.7 79.6 82.8 82.8 82.9 82.9 86.1 78.1 79.0 79.0 79.2 79.2 81.4 76.5
75 75.8 75.6 83.5 55.2 92.3 34.5 72.2 72.2 79.2 53.7 87.6 33.0 68.4 68.4 74.8 52.0 82.6 31.3
80 79.4 79.4 83.3 71.8 92.0 51.2 76.1 76.1 79.1 70.2 87.2 49.6 72.5 72.5 74.7 68.6 82.3 48.0
3000
85 83.9 83.9 84.2 84.2 91.6 67.8 80.4 80.4 80.5 80.5 86.9 66.2 76.6 76.6 76.7 76.7 82.0 64.6
90 88.5 88.5 88.3 88.3 91.7 84.4 84.8 84.8 84.9 84.9 87.1 82.9 80.8 80.8 80.9 80.9 82.3 81.2
Ambient Temperature (°F) Ambient Temperature (°F)
115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 61.5 58.8 67.9 43.4 75.3 27.9 57.7 57.1 63.6 41.8 70.3 26.3
80 63.9 63.9 67.7 55.8 75.0 40.4 60.5 60.5 63.4 54.2 70.0 38.7
2250
85 67.5 67.5 68.1 68.1 74.6 52.8 63.8 63.8 63.9 63.9 69.7 51.2
90 71.1 71.1 71.2 71.2 74.5 65.3 67.3 67.3 67.4 67.4 69.7 63.6
75 62.6 62.6 68.8 45.8 76.2 28.5 58.8 58.8 64.4 44.1 71.1 26.9
80 65.7 65.7 68.6 59.5 75.9 42.4 62.2 62.2 64.3 57.9 70.8 40.7
2500
85 69.5 69.5 69.6 69.6 75.5 56.2 65.7 65.7 65.7 65.7 70.5 54.5
90 73.2 73.2 73.3 73.3 75.6 70.1 69.2 69.2 69.3 69.3 70.6 68.4
75 63.7 63.7 69.5 48.0 77.0 29.1 60.1 60.1 65.0 46.4 71.8 27.4
80 67.3 67.3 69.5 63.2 76.6 44.4 63.7 63.7 65.0 61.6 71.4 42.7
2750
85 71.2 71.2 71.3 71.3 76.3 59.6 67.2 67.2 67.3 67.3 71.1 57.9
90 75.1 75.1 75.2 75.2 76.5 74.8 70.9 70.9 71.0 71.0 71.6 71.6
75 64.9 64.9 70.2 50.3 77.6 29.7 61.3 61.3 65.6 48.6 72.3 28.0
80 68.8 68.8 70.2 66.9 77.2 46.4 64.9 64.9 65.6 65.1 71.9 44.7
3000
85 72.7 72.7 72.8 72.8 76.9 63.0 68.6 68.6 68.6 68.6 71.7 61.3
90 76.7 76.7 76.8 76.8 77.5 77.5 72.3 72.3 71.6 71.6 72.5 72.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 29
Performance Data

Table 15. Gross cooling capacities (kW) TWA0764*A condensing unit with TWE0764*A air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)
30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 21.0 18.5 23.3 14.1 25.7 9.5 20.0 18.1 22.1 13.6 24.4 9.0 18.9 17.6 20.9 13.1 23.1 8.5
27 21.3 21.3 23.2 17.7 25.6 13.1 20.4 20.4 22.0 17.2 24.3 12.7 19.5 19.5 20.8 16.7 23.0 12.2
3823
30 22.4 22.4 23.2 21.3 25.5 16.7 21.5 21.5 22.1 20.9 24.2 16.3 20.6 20.6 20.9 20.4 22.9 15.8
33 23.6 23.6 23.6 23.6 25.5 20.4 22.6 22.6 22.7 22.7 24.2 19.9 21.6 21.6 21.7 21.7 22.9 19.5
24 21.4 19.7 23.6 14.7 26.1 9.6 20.3 19.3 22.4 14.3 24.8 9.2 19.2 18.8 21.2 13.8 23.4 8.7
27 22.0 22.0 23.5 18.8 26.0 13.7 21.0 21.0 22.3 18.3 24.7 13.2 20.1 20.1 21.1 17.8 23.3 12.8
4248
30 23.2 23.2 23.6 22.8 25.9 17.7 22.2 22.2 22.5 22.4 24.6 17.3 21.2 21.2 21.3 21.3 23.2 16.8
33 24.4 24.4 24.4 24.4 25.9 21.8 23.4 23.4 23.3 23.3 24.5 21.3 22.3 22.3 22.3 22.3 23.2 20.9
24 21.7 20.9 23.9 15.4 26.4 9.8 20.6 20.4 22.7 14.9 25.0 9.4 19.5 19.5 21.4 14.5 23.6 8.9
27 22.5 22.5 23.8 19.8 26.3 14.3 21.6 21.6 22.6 19.4 24.9 13.8 20.6 20.6 21.4 18.9 23.5 13.4
4672
30 23.8 23.8 24.0 24.0 26.2 18.7 22.8 22.8 22.9 22.9 24.8 18.3 21.7 21.7 21.7 21.7 23.4 17.8
33 25.0 25.0 25.1 25.1 26.2 23.2 24.0 24.0 24.0 24.0 24.8 22.8 22.9 22.9 22.9 22.9 23.5 22.3
24 22.0 22.0 24.1 16.1 26.6 10.0 20.9 20.9 22.9 15.6 25.3 9.5 19.8 19.8 21.6 15.1 23.8 9.1
27 23.1 23.1 24.1 20.9 26.5 14.9 22.1 22.1 22.9 20.5 25.1 14.4 21.0 21.0 21.6 20.0 23.7 13.9
5097
30 24.3 24.3 24.4 24.4 26.4 19.7 23.3 23.3 23.3 23.3 25.0 19.3 22.2 22.2 22.2 22.2 23.6 18.8
33 25.6 25.6 25.7 25.7 26.5 24.6 24.5 24.5 24.6 24.6 25.1 24.2 23.4 23.4 23.4 23.4 23.7 23.7
Ambient Temperature (°C) Ambient Temperature (°C)
45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
16 19 22 16 19 22
Airflow
m3/hr kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
17.8 17.1 19.6 12.6 21.7 8.1 16.7 16.7 18.4 12.2 20.3 7.6
18.5 18.5 19.6 16.3 21.6 11.7 17.6 17.6 18.3 15.8 20.2 11.2
3823
19.6 19.6 19.7 19.7 21.5 15.4 18.5 18.5 18.5 18.5 20.1 14.9
20.6 20.6 20.6 20.6 21.5 19.0 19.5 19.5 19.5 19.5 20.1 18.5
18.1 18.1 19.9 13.3 22.0 8.2 17.1 17.1 18.6 12.8 20.5 7.8
19.1 19.1 19.8 17.3 21.9 12.3 18.0 18.0 18.5 16.9 20.4 11.8
4248
20.1 20.1 20.1 20.1 21.8 16.4 19.0 19.0 19.0 19.0 20.3 15.9
21.2 21.2 21.1 21.1 21.8 20.4 20.0 20.0 20.0 20.0 20.4 19.9
18.5 18.5 20.1 14.0 22.2 8.4 17.4 17.4 18.8 13.5 20.7 7.9
19.5 19.5 20.1 18.4 22.1 12.9 18.4 18.4 18.8 17.9 20.6 12.4
4672
20.6 20.6 20.6 20.6 22.0 17.3 19.4 19.4 19.5 19.5 20.5 16.9
21.7 21.7 21.7 21.7 22.1 21.8 20.5 20.5 20.5 20.5 20.6 20.6
18.8 18.8 20.3 14.6 22.3 8.6 17.8 17.8 18.9 14.1 20.8 8.1
19.9 19.9 20.3 19.5 22.2 13.5 18.8 18.8 19.0 19.0 20.7 13.0
5097
21.0 21.0 21.1 21.1 22.2 18.3 19.8 19.8 19.8 19.8 20.6 17.8
22.2 22.2 22.2 22.2 22.3 22.3 20.9 20.9 20.9 20.9 20.9 20.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

30 SSP-PRC024K-EN
Performance Data

Table 16. Gross cooling capacities (MBH) TWA0764*D condensing unit with TWE0764*B air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)

85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent 61 67 73 61 67 73 61 67 73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
75 74.9 61.3 83.7 47.5 89.5 33.0 69.3 60.0 77.3 46.1 86.0 31.8 66.3 58.7 73.9 44.8 82.0 30.4
80 72.6 72.6 80.0 58.7 89.0 44.5 70.2 70.2 76.7 57.4 85.3 43.1 67.7 67.7 73.3 56.0 81.4 41.7
2250
85 79.5 79.5 79.8 70.0 88.4 55.8 74.0 74.0 76.6 68.7 84.5 54.4 71.3 71.3 73.1 67.3 80.8 53.1
90 80.5 80.5 80.7 80.7 87.9 67.1 77.8 77.8 77.9 77.9 87.3 68.3 75.0 75.0 75.1 75.1 80.3 64.4
75 73.6 64.9 82.0 49.6 90.9 33.6 70.6 63.6 78.5 48.2 87.2 32.3 67.5 62.2 75.0 46.8 83.1 30.9
80 75.1 75.1 81.3 62.0 90.4 46.3 72.6 72.6 78.0 60.7 86.6 44.9 69.9 69.9 74.5 59.3 82.5 43.5
2500
85 79.2 79.2 81.3 74.6 89.8 58.8 76.5 76.5 78.0 73.2 85.8 57.4 73.7 73.7 74.6 71.8 81.9 56.0
90 83.4 83.4 83.5 83.5 89.3 71.3 80.4 80.4 80.6 80.6 85.4 70.0 77.5 77.5 77.6 77.6 81.5 68.6
75 74.8 68.4 83.1 51.6 92.1 34.2 71.5 67.8 79.6 50.2 88.2 32.9 68.5 65.7 78.9 50.7 84.1 31.5
80 77.3 77.3 82.5 65.2 91.5 48.0 77.5 77.5 79.1 63.8 87.6 46.6 71.8 71.8 75.4 62.4 83.4 45.2
2750
85 81.6 81.6 82.8 79.0 90.9 61.7 78.7 78.7 79.4 77.7 86.8 60.3 75.7 75.7 76.1 74.8 82.8 58.9
90 85.8 85.8 85.9 85.9 90.5 75.4 82.7 82.7 86.1 86.1 86.5 74.0 79.6 79.6 79.7 79.7 82.5 72.6
75 75.7 72.4 84.1 53.5 93.0 34.7 72.8 70.3 80.4 52.1 89.1 33.4 69.5 69.5 76.7 50.7 84.8 32.0
80 79.2 79.2 83.5 68.3 92.4 49.7 76.5 76.5 80.0 66.9 88.4 48.3 73.5 73.5 79.2 68.0 84.2 46.9
3000
85 83.6 83.6 84.1 83.3 91.8 64.5 80.7 80.7 80.9 80.3 87.6 63.1 77.5 77.5 77.6 77.6 83.5 61.8
90 88.0 88.0 88.1 88.1 91.6 79.4 84.8 84.8 84.9 84.9 87.5 78.0 81.5 81.5 81.6 81.6 83.0 77.5
Ambient Temperature (°F) Ambient Temperature (°F)

115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent 61 67 73 61 67 73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
75 63.1 57.2 70.3 43.3 77.9 28.9 59.8 55.8 66.5 41.9 73.8 27.5
80 65.0 65.0 69.7 54.6 77.3 40.3 62.1 62.1 66.0 53.1 73.1 38.9
2250
85 68.5 68.5 69.7 66.0 76.7 51.7 65.5 65.5 66.1 64.0 75.0 52.1
90 72.0 72.0 72.1 72.1 76.2 63.0 68.7 68.7 68.8 68.8 71.9 61.5
75 66.6 63.3 71.3 45.4 78.9 29.5 61.0 58.7 67.4 43.9 74.6 28.0
80 67.1 67.1 70.8 57.8 78.3 42.1 64.0 64.0 67.0 56.4 73.8 40.6
2500
85 70.7 70.7 71.2 69.3 77.6 54.6 67.5 67.5 67.6 67.6 73.2 53.1
90 74.3 74.3 74.4 74.4 77.3 67.2 70.8 70.8 70.9 70.9 72.5 66.5
75 65.1 65.1 72.2 47.3 79.7 30.0 62.1 62.1 68.2 45.8 75.1 28.5
80 68.8 68.8 71.7 61.0 82.1 45.5 65.7 65.7 67.8 59.5 74.5 42.2
2750
85 72.5 72.5 72.6 72.6 78.5 57.5 69.2 69.2 69.3 69.3 73.9 56.0
90 76.2 76.2 76.3 76.3 77.9 72.1 75.2 75.2 72.7 72.7 73.7 69.3
75 66.6 66.6 72.9 49.3 80.4 30.5 63.4 63.4 68.8 47.7 75.8 29.0
80 70.4 70.4 72.5 64.1 79.8 45.4 67.1 67.1 68.2 63.3 75.1 43.9
3000
85 74.2 74.2 74.2 74.2 79.1 60.3 70.7 70.7 70.8 70.8 74.5 58.8
90 77.9 77.9 78.0 78.0 79.0 74.8 74.1 74.1 74.2 74.2 74.3 74.3
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 31
Performance Data

Table 17. Gross cooling capacities (kW) TWA0764*D condensing unit with TWE0764*B air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)

30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent 16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 22.0 18.0 24.5 13.9 26.2 9.7 20.3 17.6 22.6 13.5 25.2 9.3 19.4 17.2 21.7 13.1 24.0 8.9
27 21.3 21.3 23.4 17.2 26.1 13.0 20.6 20.6 22.5 16.8 25.0 12.6 19.8 19.8 21.5 16.4 23.9 12.2
3823
30 23.3 23.3 23.4 20.5 25.9 16.4 21.7 21.7 22.4 20.1 24.8 15.9 20.9 20.9 21.4 19.7 23.7 15.6
33 23.6 23.6 23.6 23.6 25.8 19.7 22.8 22.8 22.8 22.8 25.6 20.0 22.0 22.0 22.0 22.0 23.5 18.9
24 21.6 19.0 24.0 14.5 26.6 9.9 20.7 18.6 23.0 14.1 25.6 9.5 19.8 18.2 22.0 13.7 24.4 9.1
27 22.0 22.0 23.8 18.2 26.5 13.6 21.3 21.3 22.9 17.8 25.4 13.2 20.5 20.5 21.8 17.4 24.2 12.8
4248
30 23.2 23.2 23.8 21.8 26.3 17.2 22.4 22.4 22.9 21.5 25.1 16.8 21.6 21.6 21.9 21.1 24.0 16.4
33 24.4 24.4 24.5 24.5 26.2 20.9 23.6 23.6 23.6 23.6 25.0 20.5 22.7 22.7 22.7 22.7 23.9 20.1
24 21.9 20.1 24.4 15.1 27.0 10.0 21.0 19.9 23.3 14.7 25.9 9.6 20.1 19.2 23.1 14.8 24.6 9.2
27 22.6 22.6 24.2 19.1 26.8 14.1 22.7 22.7 23.2 18.7 25.7 13.7 21.1 21.1 22.1 18.3 24.4 13.3
4672
30 23.9 23.9 24.3 23.1 26.6 18.1 23.1 23.1 23.3 22.8 25.4 17.7 22.2 22.2 22.3 21.9 24.3 17.3
33 25.1 25.1 25.2 25.2 26.5 22.1 24.3 24.3 25.2 25.2 25.4 21.7 23.3 23.3 23.4 23.4 24.2 21.3
24 22.2 21.2 24.6 15.7 27.3 10.2 21.3 20.6 23.6 15.3 26.1 9.8 20.4 20.4 22.5 14.9 24.9 9.4
27 23.2 23.2 24.5 20.0 27.1 14.6 22.4 22.4 23.5 19.6 25.9 14.2 21.5 21.5 23.2 19.9 24.7 13.7
5097
30 24.5 24.5 24.7 24.4 26.9 18.9 23.6 23.6 23.7 23.5 25.7 18.5 22.7 22.7 22.7 22.7 24.5 18.1
33 25.8 25.8 25.8 25.8 26.8 23.3 24.8 24.8 24.9 24.9 25.6 22.9 23.9 23.9 23.9 23.9 24.3 22.7
Ambient Temperature (°C) Ambient Temperature (°C)

45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 18.5 16.8 20.6 12.7 22.8 8.5 17.5 16.3 19.5 12.3 21.6 8.1
27 19.0 19.0 20.4 16.0 22.6 11.8 18.2 18.2 19.3 15.6 21.4 11.4
3823
30 20.1 20.1 20.4 19.3 22.5 15.1 19.2 19.2 19.4 18.8 22.0 15.3
33 21.1 21.1 21.1 21.1 22.3 18.5 20.1 20.1 20.2 20.2 21.1 18.0
24 19.5 18.5 20.9 13.3 23.1 8.6 17.9 17.2 19.8 12.9 21.9 8.2
27 19.7 19.7 20.8 17.0 22.9 12.3 18.8 18.8 19.6 16.5 21.6 11.9
4248
30 20.7 20.7 20.9 20.3 22.8 16.0 19.8 19.8 19.8 19.8 21.5 15.6
33 21.8 21.8 21.8 21.8 22.7 19.7 20.8 20.8 20.8 20.8 21.3 19.5
24 19.1 19.1 21.1 13.9 23.4 8.8 18.2 18.2 20.0 13.4 22.0 8.3
27 20.2 20.2 21.0 17.9 24.1 13.3 19.2 19.2 19.9 17.4 21.8 12.4
4672
30 21.2 21.2 21.3 21.3 23.0 16.8 20.3 20.3 20.3 20.3 21.7 16.4
33 22.3 22.3 22.4 22.4 22.8 21.1 22.1 22.1 21.3 21.3 21.6 20.3
24 19.5 19.5 21.4 14.4 23.6 8.9 18.6 18.6 20.2 14.0 22.2 8.5
27 20.6 20.6 21.3 18.8 23.4 13.3 19.7 19.7 20.0 18.5 22.0 12.9
5097
30 21.7 21.7 21.8 21.8 23.2 17.7 20.7 20.7 20.7 20.7 21.8 17.2
33 22.8 22.8 22.9 22.9 23.2 21.9 21.7 21.7 21.7 21.7 21.8 21.8
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

32 SSP-PRC024K-EN
Performance Data

Table 18. Gross cooling capacities (MBH) TWA1014*A condensing unit with TWE1014*A air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 98.6 84.4 109.4 64.9 121.1 44.7 94.5 82.5 104.7 63.0 115.7 42.8 90.1 80.4 99.7 61.0 110.0 40.8
80 99.7 99.7 109.1 80.7 120.7 60.7 96.2 96.2 104.4 78.8 115.3 58.8 92.5 92.5 99.4 76.8 109.7 56.8
3025
85 105.1 105.1 109.3 96.5 120.4 76.6 101.5 101.5 104.6 94.6 115.0 74.7 97.5 97.5 99.7 92.5 109.3 72.7
90 110.6 110.6 110.8 110.8 120.1 92.5 106.8 106.8 107.0 107.0 114.8 90.6 102.6 102.6 102.8 102.8 109.2 88.5
75 100.5 89.3 111.1 67.7 122.8 45.5 96.3 87.3 106.3 65.8 117.3 43.6 91.7 85.3 101.1 63.8 111.4 41.6
80 103.0 103.0 110.8 85.2 122.4 63.2 99.3 99.3 106.0 83.3 116.9 61.2 95.3 95.3 100.9 81.2 111.0 59.2
3350
85 108.7 108.7 111.3 102.7 122.1 80.8 104.8 104.8 106.6 100.8 116.5 78.8 100.6 100.6 101.6 98.7 110.7 76.8
90 114.4 114.4 114.6 114.6 122.0 98.3 110.3 110.3 110.5 110.5 116.5 96.3 105.9 105.9 106.0 106.0 110.7 94.3
75 102.1 94.1 112.6 70.5 124.2 46.3 97.8 92.2 107.6 68.6 118.5 44.3 93.2 90.1 102.3 66.6 112.6 42.3
80 105.9 105.9 112.4 89.6 123.8 65.6 102.0 102.0 107.4 87.7 118.2 63.6 97.8 97.8 102.2 85.6 112.2 61.6
3675
85 111.8 111.8 113.2 108.8 123.5 84.8 107.7 107.7 108.4 106.9 117.8 82.9 103.2 103.2 103.5 103.5 111.9 80.9
90 117.7 117.7 117.9 117.9 123.6 103.9 113.3 113.3 113.5 113.5 118.0 102.0 108.7 108.7 108.8 108.8 112.1 99.9
75 103.6 98.8 113.8 73.3 125.4 47.0 98.6 98.6 108.7 71.3 119.6 45.1 94.5 94.5 103.2 69.3 113.5 43.0
80 108.4 108.4 113.7 93.9 125.0 68.0 104.4 104.4 108.7 91.9 119.2 66.0 100.0 100.0 103.3 89.9 113.1 64.0
4000
85 114.5 114.5 115.0 114.9 124.7 88.8 110.2 110.2 110.3 110.3 118.9 86.9 105.6 105.6 105.7 105.7 112.9 84.8
90 120.6 120.6 120.7 120.7 125.0 109.5 116.0 116.0 116.2 116.2 119.3 107.5 111.1 111.1 111.2 111.2 113.3 105.4
Ambient Temperature (°F) Ambient Temperature (°F)
115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 85.4 78.3 94.3 58.8 104.0 38.7 80.2 76.0 88.4 56.6 97.4 36.5
80 88.3 88.3 94.0 74.6 103.6 54.7 83.7 83.7 88.2 72.3 97.1 52.4
3025
85 93.2 93.2 94.5 90.4 103.3 70.6 88.4 88.4 88.9 88.2 96.7 68.3
90 98.1 98.1 98.2 98.2 103.2 86.4 93.0 93.0 93.2 93.2 96.7 84.1
75 86.9 83.1 95.5 61.7 105.2 39.5 81.4 81.4 89.5 59.4 98.5 37.2
80 91.0 91.0 95.4 79.1 104.8 57.1 86.2 86.2 89.4 76.7 98.1 54.9
3350
85 96.0 96.0 96.4 96.4 104.5 74.7 90.9 90.9 91.1 91.1 97.8 72.5
90 101.1 101.1 101.2 101.2 104.6 92.1 95.7 95.7 95.8 95.8 98.1 89.8
75 88.1 88.1 96.6 64.4 106.2 40.2 83.3 83.3 90.4 62.1 99.4 37.9
80 93.3 93.3 96.6 83.4 105.8 59.5 88.2 88.2 90.5 81.0 99.0 57.2
3675
85 98.5 98.5 98.6 98.6 105.6 78.8 93.1 93.1 93.2 93.2 98.8 76.4
90 103.6 103.6 103.7 103.7 105.9 97.7 98.0 98.0 98.2 98.2 99.3 95.5
75 89.9 89.9 97.5 67.1 107.1 40.9 85.0 85.0 91.2 64.8 100.1 38.6
80 95.2 95.2 97.6 87.6 106.7 61.8 90.0 90.0 91.5 85.3 99.8 59.6
4000
85 100.6 100.6 100.7 100.7 106.5 82.6 95.0 95.0 95.1 95.1 99.6 80.2
90 105.8 105.8 106.0 106.0 107.1 103.3 100.1 100.1 100.2 100.2 100.6 100.6
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 33
Performance Data

Table 19. Gross cooling capacities (kW) TWA1014*A condensing unit with TWE1014*A air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)
30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 28.9 24.7 32.1 19.0 35.5 13.1 27.7 24.2 30.7 18.5 33.9 12.5 26.4 23.6 29.2 17.9 32.3 12.0
27 29.2 29.2 32.0 23.6 35.4 17.8 28.2 28.2 30.6 23.1 33.8 17.2 27.1 27.1 29.1 22.5 32.1 16.6
5148
30 30.8 30.8 32.0 28.3 35.3 22.4 29.7 29.7 30.7 27.7 33.7 21.9 28.6 28.6 29.2 27.1 32.0 21.3
33 32.4 32.4 32.5 32.5 35.2 27.1 31.3 31.3 31.3 31.3 33.6 26.5 30.1 30.1 30.1 30.1 32.0 25.9
24 29.5 26.2 32.6 19.9 36.0 13.3 28.2 25.6 31.1 19.3 34.4 12.8 26.9 25.0 29.6 18.7 32.7 12.2
27 30.2 30.2 32.5 25.0 35.9 18.5 29.1 29.1 31.1 24.4 34.3 17.9 27.9 27.9 29.6 23.8 32.5 17.4
5692
30 31.8 31.8 32.6 30.1 35.8 23.7 30.7 30.7 31.2 29.5 34.2 23.1 29.5 29.5 29.8 28.9 32.4 22.5
33 33.5 33.5 33.6 33.6 35.7 28.8 32.3 32.3 32.4 32.4 34.1 28.2 31.0 31.0 31.1 31.1 32.5 27.6
24 29.9 27.6 33.0 20.7 36.4 13.6 28.7 27.0 31.5 20.1 34.7 13.0 27.3 26.4 30.0 19.5 33.0 12.4
27 31.0 31.0 32.9 26.3 36.3 19.2 29.9 29.9 31.5 25.7 34.6 18.7 28.7 28.7 29.9 25.1 32.9 18.1
6252
30 32.8 32.8 33.2 31.9 36.2 24.9 31.6 31.6 31.8 31.3 34.5 24.3 30.3 30.3 30.3 30.3 32.8 23.7
33 34.5 34.5 34.5 34.5 36.2 30.5 33.2 33.2 33.3 33.3 34.6 29.9 31.8 31.8 31.9 31.9 32.9 29.3
24 30.4 29.0 33.3 21.5 36.8 13.8 28.9 28.9 31.8 20.9 35.0 13.2 27.7 27.7 30.3 20.3 33.3 12.6
27 31.8 31.8 33.3 27.5 36.6 19.9 30.6 30.6 31.8 26.9 34.9 19.3 29.3 29.3 30.3 26.3 33.2 18.7
6796
30 33.6 33.6 33.7 33.7 36.6 26.0 32.3 32.3 32.3 32.3 34.9 25.5 30.9 30.9 31.0 31.0 33.1 24.9
33 35.3 35.3 35.4 35.4 36.6 32.1 34.0 34.0 34.0 34.0 35.0 31.5 32.6 32.6 32.6 32.6 33.2 30.9
Ambient Temperature (°C) Ambient Temperature (°C)
45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22
Airflow DB
3
m /hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 25.0 22.9 27.6 17.2 30.5 11.4 23.5 22.3 25.9 16.6 28.6 10.7
27 25.9 25.9 27.6 21.9 30.4 16.0 24.5 24.5 25.8 21.2 28.4 15.4
5148
30 27.3 27.3 27.7 26.5 30.3 20.7 25.9 25.9 26.0 25.8 28.3 20.0
33 28.7 28.7 28.8 28.8 30.2 25.3 27.3 27.3 27.3 27.3 28.3 24.7
24 25.5 24.4 28.0 18.1 30.8 11.6 23.8 23.8 26.2 17.4 28.9 10.9
27 26.7 26.7 28.0 23.2 30.7 16.7 25.2 25.2 26.2 22.5 28.8 16.1
5692
30 28.1 28.1 28.2 28.2 30.6 21.9 26.7 26.7 26.7 26.7 28.7 21.2
33 29.6 29.6 29.7 29.7 30.7 27.0 28.0 28.0 28.1 28.1 28.7 26.3
24 25.8 25.8 28.3 18.9 31.1 11.8 24.4 24.4 26.5 18.2 29.1 11.1
27 27.3 27.3 28.3 24.4 31.0 17.4 25.9 25.9 26.5 23.7 29.0 16.8
6252
30 28.9 28.9 28.9 28.9 30.9 23.1 27.3 27.3 27.3 27.3 28.9 22.4
33 30.4 30.4 30.4 30.4 31.0 28.6 28.7 28.7 28.8 28.8 29.1 28.0
24 26.4 26.4 28.6 19.7 31.4 12.0 24.9 24.9 26.7 19.0 29.3 11.3
27 27.9 27.9 28.6 25.7 31.3 18.1 26.4 26.4 26.8 25.0 29.2 17.5
6796
30 29.5 29.5 29.5 29.5 31.2 24.2 27.8 27.8 27.9 27.9 29.2 23.5
33 31.0 31.0 31.1 31.1 31.4 30.3 29.3 29.3 29.4 29.4 29.5 29.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

34 SSP-PRC024K-EN
Performance Data

Table 20. Gross cooling capacities (MBH) TWA1014*D condensing unit with TWE1014*B air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)

85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent 61 67 73 61 67 73 61 67 73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
75 95.8 83.2 106.0 63.5 117.0 43.3 91.1 81.0 100.7 61.4 111.1 41.2 86.2 78.8 95.3 59.2 105.1 39.1
80 97.5 97.5 105.8 79.4 116.8 59.3 93.4 93.4 100.5 77.3 110.8 57.2 89.2 89.2 95.1 75.1 104.9 55.1
3025
85 102.8 102.8 106.2 95.3 116.5 75.3 98.6 98.6 100.9 93.2 110.6 73.2 94.3 94.3 95.7 91.1 104.7 71.1
90 108.2 108.2 108.4 108.4 116.5 91.3 103.8 103.8 104.0 104.0 110.6 89.2 99.3 99.3 99.5 99.5 104.7 87.1
75 97.6 88.1 107.6 66.4 118.6 44.0 92.7 85.9 102.1 64.2 112.5 41.9 87.6 83.8 96.5 62.1 106.4 39.8
80 100.6 100.6 107.5 83.9 118.3 61.8 96.3 96.3 102.0 81.8 112.2 59.6 91.9 91.9 96.5 79.6 106.2 57.6
3350
85 106.1 106.1 108.1 101.6 118.1 79.4 101.7 101.7 102.8 99.5 112.0 77.3 97.1 97.1 97.6 96.2 105.9 75.2
90 111.7 111.7 111.9 111.9 118.2 97.0 107.1 107.1 107.2 107.2 112.2 94.9 102.3 102.3 102.5 102.5 106.2 92.8
75 99.1 92.9 108.9 69.2 119.9 44.8 94.1 90.6 103.3 67.0 113.6 42.7 88.9 88.9 97.6 64.8 107.4 40.6
80 103.3 103.3 108.9 88.4 119.6 64.2 98.8 98.8 103.3 86.2 113.4 62.0 94.2 94.2 97.7 84.0 107.2 60.0
3675
85 109.0 109.0 109.9 107.7 119.4 83.5 104.3 104.3 104.8 103.7 113.1 81.4 99.6 99.6 99.7 99.7 107.0 79.3
90 114.8 114.8 115.0 115.0 119.7 102.7 109.9 109.9 110.1 110.1 113.5 100.6 105.0 105.0 105.1 105.1 107.5 98.5
75 100.5 97.4 110.0 71.9 120.9 45.5 95.4 95.4 104.3 69.7 114.6 43.4 90.8 90.8 98.5 67.5 108.3 41.3
80 105.7 105.7 110.1 92.7 120.7 66.5 101.0 101.0 104.4 90.5 114.3 64.4 96.3 96.3 98.8 88.3 108.0 62.3
4000
85 111.6 111.6 111.9 111.5 120.5 87.5 106.7 106.7 106.8 106.8 114.2 85.3 101.8 101.8 101.9 101.9 107.9 83.2
90 117.5 117.5 117.6 117.6 121.0 108.3 112.4 112.4 112.5 112.5 114.8 106.2 107.2 107.2 107.4 107.4 108.5 103.9
Ambient Temperature (°F) Ambient Temperature (°F)

115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent 61 67 73 61 67 73
DB
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
CFM (°F)
75 80.9 76.4 89.5 57.0 98.9 36.9 75.2 73.0 83.0 54.5 92.0 34.6
80 84.7 84.7 89.4 72.9 98.7 53.0 79.5 79.5 83.0 70.4 91.7 50.6
3025
85 89.6 89.6 90.2 88.6 98.5 69.0 84.3 84.3 84.5 84.5 91.5 66.7
90 94.5 94.5 94.7 94.7 98.6 84.9 89.1 89.1 89.2 89.2 91.8 82.6
75 82.1 82.1 90.6 59.8 100.0 37.7 76.9 76.9 84.1 57.3 92.9 35.3
80 87.2 87.2 90.7 77.3 99.8 55.4 81.8 81.8 84.2 74.8 92.7 53.1
3350
85 92.2 92.2 92.4 92.4 99.6 73.1 86.7 86.7 86.9 86.9 92.6 70.7
90 97.3 97.3 97.5 97.5 100.0 90.7 91.6 91.6 91.7 91.7 93.0 88.3
75 84.1 84.1 91.6 62.5 100.9 38.4 78.7 78.7 84.9 60.1 93.7 36.1
80 89.3 89.3 91.8 81.7 100.7 57.8 83.8 83.8 85.3 79.2 93.5 55.5
3675
85 94.5 94.5 94.7 94.7 100.6 77.1 88.8 88.8 88.9 88.9 93.5 74.7
90 99.7 99.7 99.8 99.8 101.0 96.3 93.8 93.8 93.9 93.9 94.0 94.0
75 85.8 85.8 92.4 65.2 101.7 39.1 80.3 80.3 85.6 62.7 94.4 36.7
80 91.2 91.2 92.8 86.0 101.5 60.1 85.5 85.5 86.2 83.0 94.2 57.8
4000
85 96.5 96.5 96.6 96.6 101.4 81.0 90.6 90.6 90.7 90.7 94.2 78.6
90 101.8 101.8 101.9 101.9 102.0 102.0 95.7 95.7 95.8 95.8 95.9 95.9
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 35
Performance Data

Table 21. Gross cooling capacities (kW) TWA1014*D condensing unit with TWE1014*B air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)

30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent 16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 28.1 24.4 31.1 18.6 34.3 12.7 26.7 23.7 29.5 18.0 32.5 12.1 25.3 23.1 27.9 17.4 30.8 11.5
27 28.6 28.6 31.0 23.3 34.2 17.4 27.4 27.4 29.5 22.7 32.5 16.8 26.1 26.1 27.9 22.0 30.7 16.2
5148
30 30.1 30.1 31.1 27.9 34.2 22.1 28.9 28.9 29.6 27.3 32.4 21.4 27.6 27.6 28.0 26.7 30.7 20.8
33 31.7 31.7 31.8 31.8 34.1 26.7 30.4 30.4 30.5 30.5 32.4 26.1 29.1 29.1 29.2 29.2 30.7 25.5
24 28.6 25.8 31.5 19.5 34.8 12.9 27.2 25.2 29.9 18.8 33.0 12.3 25.7 24.6 28.3 18.2 31.2 11.7
27 29.5 29.5 31.5 24.6 34.7 18.1 28.2 28.2 29.9 24.0 32.9 17.5 26.9 26.9 28.3 23.3 31.1 16.9
5692
30 31.1 31.1 31.7 29.8 34.6 23.3 29.8 29.8 30.1 29.1 32.8 22.7 28.5 28.5 28.6 28.2 31.1 22.1
33 32.7 32.7 32.8 32.8 34.6 28.4 31.4 31.4 31.4 31.4 32.9 27.8 30.0 30.0 30.0 30.0 31.1 27.2
24 29.1 27.2 31.9 20.3 35.1 13.1 27.6 26.6 30.3 19.6 33.3 12.5 26.1 26.1 28.6 19.0 31.5 11.9
27 30.3 30.3 31.9 25.9 35.1 18.8 29.0 29.0 30.3 25.3 33.2 18.2 27.6 27.6 28.6 24.6 31.4 17.6
6252
30 32.0 32.0 32.2 31.6 35.0 24.5 30.6 30.6 30.7 30.4 33.2 23.8 29.2 29.2 29.2 29.2 31.4 23.2
33 33.6 33.6 33.7 33.7 35.1 30.1 32.2 32.2 32.3 32.3 33.3 29.5 30.8 30.8 30.8 30.8 31.5 28.9
24 29.4 28.5 32.2 21.1 35.4 13.3 27.9 27.9 30.6 20.4 33.6 12.7 26.6 26.6 28.9 19.8 31.7 12.1
27 31.0 31.0 32.3 27.2 35.4 19.5 29.6 29.6 30.6 26.5 33.5 18.9 28.2 28.2 28.9 25.9 31.7 18.3
6796
30 32.7 32.7 32.8 32.7 35.3 25.6 31.3 31.3 31.3 31.3 33.5 25.0 29.8 29.8 29.9 29.9 31.6 24.4
33 34.4 34.4 34.5 34.5 35.5 31.7 32.9 32.9 33.0 33.0 33.6 31.1 31.4 31.4 31.5 31.5 31.8 30.4
Ambient Temperature (°C) Ambient Temperature (°C)

45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 23.7 22.4 26.2 16.7 29.0 10.8 22.0 21.4 24.3 16.0 27.0 10.1
27 24.8 24.8 26.2 21.4 28.9 15.5 23.3 23.3 24.3 20.6 26.9 14.8
5148
30 26.3 26.3 26.4 26.0 28.9 20.2 24.7 24.7 24.8 24.8 26.8 19.5
33 27.7 27.7 27.7 27.7 28.9 24.9 26.1 26.1 26.1 26.1 26.9 24.2
24 24.1 24.1 26.6 17.5 29.3 11.0 22.5 22.5 24.6 16.8 27.2 10.4
27 25.5 25.5 26.6 22.7 29.2 16.2 24.0 24.0 24.7 21.9 27.2 15.6
5692
30 27.0 27.0 27.1 27.1 29.2 21.4 25.4 25.4 25.5 25.5 27.1 20.7
33 28.5 28.5 28.6 28.6 29.3 26.6 26.9 26.9 26.9 26.9 27.2 25.9
24 24.6 24.6 26.8 18.3 29.6 11.3 23.1 23.1 24.9 17.6 27.5 10.6
27 26.2 26.2 26.9 23.9 29.5 16.9 24.6 24.6 25.0 23.2 27.4 16.3
6252
30 27.7 27.7 27.7 27.7 29.5 22.6 26.0 26.0 26.1 26.1 27.4 21.9
33 29.2 29.2 29.3 29.3 29.6 28.2 27.5 27.5 27.5 27.5 27.6 27.6
24 25.2 25.2 27.1 19.1 29.8 11.5 23.5 23.5 25.1 18.4 27.7 10.8
27 26.7 26.7 27.2 25.2 29.7 17.6 25.1 25.1 25.3 24.3 27.6 16.9
6796
30 28.3 28.3 28.3 28.3 29.7 23.7 26.6 26.6 26.6 26.6 27.6 23.0
33 29.8 29.8 29.9 29.9 29.9 29.9 28.0 28.0 28.1 28.1 28.1 28.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

36 SSP-PRC024K-EN
Performance Data

Table 22. Gross cooling capacities (MBH) TWA1564*D condensing unit with TWE1564*B air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 146.8 127.5 163.9 97.9 182.5 67.4 141.1 124.9 157.7 95.4 175.6 65.0 135.0 122.2 150.9 92.7 168.1 62.3
80 146.8 146.8 163.9 122.4 182.5 92.1 141.1 141.1 157.6 119.9 175.6 89.7 135.0 135.0 150.9 117.2 168.0 87.1
4500
85 146.8 146.8 163.9 146.8 182.4 116.8 141.1 141.1 157.7 144.2 175.5 114.3 135.0 135.0 150.9 141.5 168.0 111.7
90 146.8 146.8 164.0 164.0 182.4 141.3 141.1 141.1 157.7 157.7 175.5 138.9 135.0 135.0 150.9 150.9 168.0 136.2
75 149.2 135.2 166.4 102.4 185.1 68.7 143.4 132.6 160.0 99.9 178.0 66.2 137.0 129.8 153.0 97.2 170.3 63.6
80 149.2 149.2 166.4 129.6 185.1 96.1 143.4 143.4 160.0 127.0 178.0 93.6 137.0 137.0 153.0 124.3 170.2 90.9
5000
85 149.2 149.2 166.4 156.5 185.1 123.3 143.3 143.3 160.0 153.9 178.0 120.9 137.0 137.0 153.0 151.2 170.2 118.2
90 149.2 149.2 166.5 166.5 185.0 150.5 143.4 143.4 160.0 160.0 178.0 148.0 137.0 137.0 153.0 153.0 170.2 145.4
75 151.2 142.7 168.5 106.9 187.3 69.9 145.2 140.1 161.9 104.3 180.0 67.4 138.7 137.3 154.8 101.6 172.1 64.7
80 151.2 151.2 168.5 136.6 187.2 99.9 145.2 145.2 161.9 134.0 180.0 97.4 138.7 138.7 154.8 131.2 172.1 94.7
5500
85 151.2 151.2 168.5 166.0 187.2 129.8 145.2 145.2 161.9 161.9 179.9 127.3 138.7 138.7 154.8 154.8 172.1 124.7
90 151.2 151.2 168.5 168.5 187.2 159.5 145.2 145.2 161.9 161.9 180.0 157.0 138.7 138.7 154.8 154.8 172.1 154.4
75 152.9 150.1 170.3 111.2 189.1 71.0 146.7 146.5 163.5 108.6 181.7 68.6 140.1 140.1 156.3 105.9 173.7 65.9
80 152.9 152.9 170.3 143.4 189.0 103.7 146.7 146.7 163.5 140.9 181.6 101.2 140.1 140.1 156.3 138.1 173.6 98.5
6000
85 152.8 152.8 170.3 170.3 189.0 136.2 146.7 146.7 163.5 163.5 181.6 133.7 140.1 140.1 156.3 156.3 173.6 131.0
90 152.8 152.8 170.2 170.2 189.0 168.4 146.7 146.7 163.5 163.5 181.6 165.9 140.1 140.1 156.2 156.2 173.6 163.2
Ambient Temperature (°F) Ambient Temperature (°F)
115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 128.5 119.3 143.7 89.9 160.1 59.6 121.7 116.3 136.1 87.0 151.6 56.6
80 128.6 128.6 143.7 114.4 160.1 84.3 121.7 121.7 136.1 111.4 151.5 81.4
4500
85 128.5 128.5 143.7 138.7 160.1 108.9 121.7 121.7 136.1 134.8 151.5 106.0
90 128.5 128.5 143.8 143.8 160.1 133.5 121.7 121.7 136.1 136.1 151.5 130.5
75 130.4 126.9 145.6 94.4 162.1 60.8 123.4 122.6 137.8 91.4 153.4 57.8
80 130.4 130.4 145.7 121.5 162.1 88.2 123.4 123.4 137.8 118.4 153.3 85.2
5000
85 130.4 130.4 145.7 145.7 162.1 115.4 123.4 123.4 137.8 137.8 153.3 112.5
90 130.4 130.4 145.7 145.7 162.1 142.6 123.4 123.4 137.8 137.8 153.3 139.6
75 131.9 131.9 147.2 98.7 163.8 61.9 124.7 124.7 139.2 95.7 154.9 59.0
80 131.9 131.9 147.2 128.4 163.7 92.0 124.7 124.7 139.2 125.3 154.8 89.0
5500
85 131.9 131.9 147.3 147.3 163.7 121.9 124.7 124.7 139.2 139.2 154.8 118.9
90 131.9 131.9 147.2 147.2 163.7 151.5 124.7 124.7 139.2 139.2 154.8 148.6
75 133.2 133.2 148.6 103.0 165.2 63.1 125.9 125.9 140.4 100.0 156.1 60.1
80 133.2 133.2 148.6 135.2 165.1 95.7 125.9 125.9 140.4 132.2 156.0 92.7
6000
85 133.2 133.2 148.6 148.6 165.1 128.2 125.9 125.9 140.4 140.4 156.0 125.2
90 133.2 133.2 148.6 148.6 165.1 160.4 125.8 125.8 140.4 140.4 156.0 155.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 37
Performance Data

Table 23. Gross cooling capacities (kW) TWA1564*D heat pump with TWE1564*B air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)
30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 43.1 37.5 48.2 28.8 53.6 19.8 41.5 36.8 46.3 28.1 51.5 19.1 39.6 35.9 44.3 27.3 49.3 18.3
27 43.1 43.1 48.1 36.0 53.6 27.1 41.5 41.5 46.3 35.3 51.5 26.3 39.6 39.6 44.3 34.5 49.3 25.6
7646
30 43.1 43.1 48.2 43.2 53.6 34.3 41.5 41.5 46.3 42.4 51.5 33.6 39.6 39.6 44.3 41.6 49.3 32.8
33 43.1 43.1 48.2 48.2 53.5 41.6 41.5 41.5 46.3 46.3 51.5 40.8 39.6 39.6 44.3 44.3 49.3 40.1
24 43.8 39.8 48.9 30.1 54.3 20.2 42.1 39.0 47.0 29.4 52.2 19.4 40.2 38.2 44.9 28.6 49.9 18.6
27 43.8 43.8 48.9 38.1 54.3 28.2 42.1 42.1 47.0 37.4 52.2 27.5 40.2 40.2 44.9 36.6 49.9 26.7
8495
30 43.8 43.8 48.9 46.1 54.3 36.3 42.1 42.1 47.0 45.3 52.2 35.5 40.2 40.2 44.9 44.4 49.9 34.8
33 43.8 43.8 48.9 48.9 54.3 44.3 42.1 42.1 47.0 47.0 52.2 43.5 40.2 40.2 44.9 44.9 49.9 42.7
24 44.4 42.0 49.5 31.4 55.0 20.5 42.6 41.2 47.5 30.7 52.8 19.8 40.7 40.3 45.4 29.9 50.5 19.0
27 44.4 44.4 49.5 40.2 54.9 29.4 42.6 42.6 47.5 39.4 52.8 28.6 40.7 40.7 45.4 38.6 50.4 27.8
9345
30 44.4 44.4 49.5 48.9 54.9 38.2 42.6 42.6 47.5 47.5 52.8 37.4 40.7 40.7 45.4 45.4 50.4 36.6
33 44.4 44.4 49.5 49.5 54.9 46.9 42.6 42.6 47.5 47.5 52.8 46.2 40.7 40.7 45.4 45.4 50.4 45.4
24 44.9 44.2 50.0 32.7 55.5 20.9 43.1 43.1 48.0 31.9 53.3 20.1 41.1 41.1 45.8 31.1 50.9 19.3
27 44.9 44.9 50.0 42.2 55.5 30.5 43.1 43.1 48.0 41.4 53.3 29.7 41.1 41.1 45.8 40.6 50.9 28.9
10194
30 44.9 44.9 50.0 50.0 55.5 40.0 43.1 43.1 48.0 48.0 53.2 39.3 41.1 41.1 45.8 45.8 50.9 38.5
33 44.9 44.9 50.0 50.0 55.5 49.6 43.1 43.1 48.0 48.0 53.2 48.8 41.1 41.1 45.8 45.8 50.9 48.0
Ambient Temperature (°C) Ambient Temperature (°C)
45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22
Airflow DB
3
m /hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 37.7 35.1 42.2 26.4 46.9 17.5 35.7 34.2 39.9 25.6 44.4 16.6
27 37.7 37.7 42.2 33.7 46.9 24.8 35.7 35.7 39.9 32.8 44.4 23.9
7646
30 37.7 37.7 42.2 40.8 46.9 32.0 35.7 35.7 39.9 39.6 44.4 31.2
33 37.7 37.7 42.2 42.2 46.9 39.2 35.7 35.7 39.9 39.9 44.4 38.4
24 38.3 37.3 42.7 27.7 47.5 17.8 36.2 36.0 40.4 26.9 44.9 17.0
27 38.3 38.3 42.7 35.7 47.5 25.9 36.2 36.2 40.4 34.8 44.9 25.0
8495
30 38.3 38.3 42.7 42.7 47.5 33.9 36.2 36.2 40.4 40.4 44.9 33.1
33 38.3 38.3 42.7 42.7 47.5 41.9 36.2 36.2 40.4 40.4 44.9 41.1
24 38.7 38.7 43.2 29.0 48.0 18.2 36.6 36.6 40.8 28.1 45.4 17.3
27 38.7 38.7 43.2 37.8 48.0 27.0 36.6 36.6 40.8 36.9 45.3 26.1
9345
30 38.7 38.7 43.2 43.2 48.0 35.8 36.6 36.6 40.8 40.8 45.3 35.0
33 38.7 38.7 43.2 43.2 48.0 44.6 36.6 36.6 40.8 40.8 45.3 43.7
24 39.1 39.1 43.6 30.3 48.4 18.5 36.9 36.9 41.2 29.4 45.7 17.6
27 39.1 39.1 43.6 39.8 48.4 28.1 36.9 36.9 41.2 38.9 45.7 27.2
10194
30 39.1 39.1 43.6 43.6 48.4 37.7 36.9 36.9 41.2 41.2 45.7 36.8
33 39.1 39.1 43.6 43.6 48.4 47.2 36.9 36.9 41.2 41.2 45.7 45.5
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

38 SSP-PRC024K-EN
Performance Data

Table 24. Gross cooling capacities (MBH) TWA2014*D heat pump with TWE2014*B air handler (IP)
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb (°F) Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 201.8 168.5 224.9 131.1 250.0 92.3 195.2 165.3 217.5 128.1 241.7 89.3 187.5 161.8 208.9 124.6 232.2 85.8
80 202.0 198.8 224.9 162.2 249.9 123.5 195.3 195.0 217.5 159.1 241.6 120.5 187.7 187.7 209.0 155.5 232.1 117.1
6000
85 202.1 202.1 225.2 192.6 250.0 154.7 195.4 195.4 217.7 189.5 241.7 151.7 187.8 187.8 209.2 185.9 232.2 148.3
90 202.2 202.2 225.3 223.0 250.0 185.7 195.5 195.5 217.9 217.9 241.8 182.6 187.8 187.8 209.3 209.3 232.3 179.1
75 205.4 177.5 228.6 136.6 253.8 93.9 198.4 174.4 220.9 133.5 245.3 90.8 190.6 170.8 212.1 130.0 235.5 87.4
80 205.5 205.5 228.7 170.6 253.7 128.2 198.6 198.6 221.0 167.4 245.2 125.2 190.7 190.7 212.2 163.8 235.4 121.7
6680
85 205.6 205.6 228.9 204.0 253.8 162.5 198.7 198.7 221.2 200.9 245.2 159.4 190.8 190.8 212.4 197.3 235.5 156.0
90 205.7 205.7 229.0 229.0 253.9 196.4 198.7 198.7 221.3 221.3 245.3 193.3 190.9 190.9 212.5 212.5 235.6 189.8
75 208.3 186.3 231.7 141.8 257.0 95.4 201.2 183.1 223.8 138.7 248.2 92.3 193.1 179.5 214.7 135.1 238.2 88.8
80 208.4 208.4 231.8 178.7 256.9 132.8 201.3 201.3 223.9 175.5 248.1 129.7 193.3 193.3 214.9 171.9 238.1 126.2
7350
85 208.5 208.5 232.0 215.1 257.0 170.1 201.4 201.4 224.1 211.9 248.2 167.0 193.3 193.3 215.1 208.3 238.2 163.5
90 208.6 208.6 232.1 232.1 257.1 206.8 201.5 201.5 224.2 224.2 248.3 203.7 193.4 193.4 215.2 215.2 238.3 200.1
75 210.8 194.8 234.3 146.9 259.7 96.8 203.5 191.6 226.2 143.7 250.7 93.7 195.3 187.9 217.0 140.2 240.5 90.2
80 211.0 211.0 234.4 186.5 259.6 137.2 203.7 203.7 226.4 183.3 250.6 134.1 195.4 195.4 217.2 179.7 240.4 130.6
8030
85 211.0 211.0 234.6 225.9 259.7 177.5 203.8 203.8 226.6 222.7 250.7 174.4 195.5 195.5 217.3 217.3 240.5 170.9
90 211.1 211.1 234.7 234.7 259.9 217.0 203.8 203.8 226.6 226.6 250.9 213.8 195.5 195.5 217.4 217.4 240.7 210.2
Ambient Temperature (°F) Ambient Temperature (°F)
115 125
Entering Wet Bulb (°F) Entering Wet Bulb (°F)
Ent
61 67 73 61 67 73
DB
CFM (°F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 179.2 157.9 199.7 120.9 221.8 82.2 170.0 153.8 189.4 116.8 210.2 78.1
80 179.3 179.3 199.8 151.8 221.8 113.4 170.2 170.2 189.5 147.6 210.2 109.3
6000
85 179.4 179.4 200.0 182.1 221.8 144.6 170.3 170.3 189.7 178.0 210.3 140.5
90 179.5 179.5 200.1 200.1 221.9 175.3 170.3 170.3 189.8 189.8 210.4 171.2
75 181.9 166.9 202.6 126.2 224.8 83.6 172.5 162.6 192.0 122.1 212.9 79.5
80 182.1 182.1 202.7 160.0 224.7 118.0 172.7 172.7 192.2 155.8 212.8 113.9
6680
85 182.2 182.2 202.9 193.4 224.8 152.3 172.7 172.7 192.3 189.2 212.9 148.2
90 182.2 182.2 203.0 203.0 224.9 185.9 172.8 172.8 192.4 192.4 213.1 181.7
75 184.3 175.5 205.0 131.3 227.2 85.1 174.6 171.2 194.2 127.2 215.0 80.9
80 184.4 184.4 205.1 168.0 227.1 122.5 174.7 174.7 194.3 163.7 214.9 118.3
7350
85 184.5 184.5 205.3 204.4 227.3 159.8 174.8 174.8 194.5 194.5 215.1 155.7
90 184.5 184.5 205.4 205.4 227.4 196.3 174.8 174.8 194.6 194.6 215.3 192.0
75 186.2 183.9 207.0 136.3 229.3 86.4 176.4 176.4 196.0 132.2 216.9 82.3
80 186.4 186.4 207.2 175.8 229.2 126.8 176.5 176.5 196.2 171.5 216.8 122.6
8030
85 186.4 186.4 207.4 207.4 229.4 167.1 176.6 176.6 196.3 196.3 217.0 163.0
90 186.5 186.5 207.4 207.4 229.5 206.3 176.6 176.6 196.4 196.4 217.1 202.1
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. MBH = Total Gross Capacity, SHC = Sensible Heat Capacity

SSP-PRC024K-EN 39
Performance Data

Table 25. Gross cooling capacities (kW) TWA2014*D heat pump with TWE2014*B air handler (SI)
Ambient Temperature (°C) Ambient Temperature (°C) Ambient Temperature (°C)
30 35 40
Entering Wet Bulb (°C) Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22 16 19 22
Airflow DB
m3/hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 59.2 49.5 65.9 38.5 73.2 27.0 57.2 48.6 63.6 37.6 70.6 26.1 54.9 47.5 61.1 36.5 67.8 25.1
27 59.3 58.5 65.9 47.6 73.1 36.2 57.2 57.2 63.7 46.7 70.6 35.3 54.9 54.9 61.1 45.6 67.7 34.3
10194
30 59.3 59.3 66.0 56.6 73.2 45.4 57.3 57.3 63.7 55.7 70.6 44.5 54.9 54.9 61.2 54.6 67.8 43.4
33 59.3 59.3 66.0 65.6 73.2 54.5 57.3 57.3 63.8 63.8 70.7 53.6 55.0 55.0 61.2 61.2 67.8 52.5
24 60.2 52.2 67.0 40.1 74.3 27.5 58.1 51.2 64.6 39.1 71.6 26.5 55.7 50.1 62.0 38.1 68.7 25.5
27 60.3 60.3 67.0 50.1 74.2 37.6 58.2 58.2 64.7 49.1 71.6 36.7 55.8 55.8 62.0 48.1 68.7 35.6
11349
30 60.3 60.3 67.0 60.0 74.2 47.7 58.2 58.2 64.7 59.0 71.6 46.8 55.8 55.8 62.1 57.9 68.7 45.7
33 60.3 60.3 67.1 67.1 74.3 57.7 58.2 58.2 64.8 64.8 71.6 56.7 55.8 55.8 62.1 62.1 68.7 55.7
24 61.1 54.8 67.9 41.6 75.2 27.9 58.9 53.8 65.5 40.7 72.5 27.0 56.5 52.7 62.7 39.6 69.4 25.9
27 61.1 61.1 67.9 52.5 75.1 38.9 59.0 59.0 65.5 51.5 72.4 38.0 56.5 56.5 62.8 50.4 69.4 36.9
12488
30 61.1 61.1 67.9 63.2 75.2 49.9 59.0 59.0 65.5 62.2 72.5 49.0 56.5 56.5 62.8 61.2 69.5 47.9
33 61.2 61.2 68.0 68.0 75.2 60.7 59.0 59.0 65.6 65.6 72.5 59.8 56.5 56.5 62.9 62.9 69.5 58.7
24 61.8 57.3 68.6 43.1 75.9 28.3 59.6 56.3 66.2 42.2 73.2 27.4 57.1 55.2 63.4 41.1 70.1 26.3
27 61.8 61.8 68.7 54.8 75.9 40.2 59.6 59.6 66.2 53.8 73.1 39.3 57.1 57.1 63.4 52.7 70.1 38.2
13643
30 61.9 61.9 68.7 66.4 75.9 52.1 59.7 59.7 66.2 65.4 73.2 51.1 57.2 57.2 63.5 63.5 70.1 50.1
33 61.9 61.9 68.7 68.7 76.0 63.7 59.7 59.7 66.3 66.3 73.2 62.8 57.2 57.2 63.5 63.5 70.2 61.7
Ambient Temperature (°C) Ambient Temperature (°C)
45 52
Entering Wet Bulb (°C) Entering Wet Bulb (°C)
Ent
16 19 22 16 19 22
Airflow DB
3
m /hr (°C) kW SHC kW SHC kW SHC kW SHC kW SHC kW SHC
24 52.4 46.4 58.3 35.4 64.6 24.0 49.7 45.1 55.2 34.2 61.2 22.7
27 52.4 52.4 58.3 44.5 64.6 33.2 49.7 49.7 55.3 43.3 61.2 32.0
10194
30 52.5 52.5 58.4 53.5 64.6 42.3 49.8 49.8 55.3 52.2 61.2 41.1
33 52.5 52.5 58.4 58.4 64.7 51.4 49.8 49.8 55.4 55.4 61.2 50.2
24 53.2 49.0 59.1 37.0 65.5 24.4 50.4 47.7 56.0 35.7 61.9 23.2
27 53.2 53.2 59.2 46.9 65.4 34.5 50.4 50.4 56.0 45.7 61.9 33.3
11349
30 53.3 53.3 59.2 56.8 65.5 44.6 50.5 50.5 56.1 55.5 61.9 43.4
33 53.3 53.3 59.2 59.2 65.5 54.5 50.5 50.5 56.1 56.1 62.0 53.3
24 53.9 51.5 59.8 38.5 66.2 24.8 51.0 50.3 56.6 37.2 62.5 23.6
27 53.9 53.9 59.9 49.3 66.1 35.8 51.0 51.0 56.6 48.0 62.5 34.6
12488
30 53.9 53.9 59.9 59.9 66.2 46.8 51.0 51.0 56.7 56.7 62.5 45.6
33 53.9 53.9 59.9 59.9 66.2 57.6 51.1 51.1 56.7 56.7 62.6 56.3
24 54.4 54.0 60.4 39.9 66.7 25.2 51.5 51.5 57.1 38.7 63.0 23.9
27 54.5 54.5 60.4 51.6 66.7 37.1 51.5 51.5 57.2 50.3 63.0 35.8
13643
30 54.5 54.5 60.5 60.5 66.8 49.0 51.5 51.5 57.2 57.2 63.1 47.7
33 54.5 54.5 60.5 60.5 66.8 60.5 51.5 51.5 57.2 57.2 63.1 59.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling,
subtract indoor fan heat.
2. kW = Total Gross Capacity, SHC = Sensible Heat Capacity

40 SSP-PRC024K-EN
Performance Data

Table 26. Gross cooling capacities (MBH) TWA0604*A condensing unit only (IP)
Outdoor Suction Temperature (°F)
Temp (°F) 30 35 40 45 50 55
Head Press (psig) 246.0 251.5 257.4 263.6 270.3 277.2
65 Capacity (Btuh/1000) 56.9 62.7 68.9 75.5 82.6 90.0
Unit Power (kW) 3.4 3.5 3.5 3.6 3.7 3.8
Head Press (psig) 283.6 289.5 295.7 302.3 309.3 316.5
75 Capacity (Btuh/1000) 54.0 59.5 65.4 71.7 78.4 85.5
Unit Power (kW) 3.8 3.8 3.9 4.0 4.0 4.1
Head Press (psig) 324.9 331.1 337.7 344.6 351.8 359.4
85 Capacity (Btuh/1000) 50.8 56.1 61.7 67.7 74.1 80.8
Unit Power (kW) 4.2 4.2 4.3 4.4 4.4 4.5
Head Press (psig) 369.8 376.4 383.3 390.5 398.0 405.9
95 Capacity (Btuh/1000) 47.4 52.4 57.8 63.5 69.6 75.9
Unit Power (kW) 4.6 4.7 4.7 4.8 4.9 5.0
Head Press (psig) 418.6 425.5 432.7 440.3 448.1 456.2
105 Capacity (Btuh/1000) 43.7 48.5 53.6 59.1 64.8 70.9
Unit Power (kW) 5.1 5.2 5.2 5.3 5.4 5.5
Head Press (psig) 471.6 478.8 486.3 494.0 502.0 510.2
115 Capacity (Btuh/1000) 39.8 44.4 49.3 54.5 59.9 65.6
Unit Power (kW) 5.7 5.7 5.8 5.9 6.0 6.1
Head Press (psig) 529.0 536.3 543.8 551.5 559.4 567.4
125 Capacity (Btuh/1000) 35.7 40.1 44.7 49.6 54.8 60.2
Unit Power (kW) 6.3 6.3 6.4 6.5 6.6 6.7
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 27. Gross cooling capacities (kW) TWA0604*A condensing unit only (SI)
Outdoor Suction Temperature (°C)
Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1695.8 1734.1 1774.7 1817.8 1863.5 1911.3
18.3 Capacity (kW) 16.7 18.4 20.2 22.1 24.2 26.4
Unit Power (kW) 3.4 3.5 3.5 3.6 3.7 3.8
Head Press (kPa) 1955.5 1996.1 2039.1 2084.5 2132.2 2182.3
23.9 Capacity (kW) 15.8 17.4 19.2 21.0 23.0 25.0
Unit Power (kW) 3.8 3.8 3.9 4.0 4.0 4.1
Head Press (kPa) 2239.8 2282.8 2328.2 2375.6 2425.5 2478.0
29.4 Capacity (kW) 14.9 16.4 18.1 19.8 21.7 23.7
Unit Power (kW) 4.2 4.2 4.3 4.4 4.4 4.5
Head Press (kPa) 2549.8 2595.0 2642.6 2692.3 2744.2 2798.6
35 Capacity (kW) 13.9 15.4 16.9 18.6 20.4 22.3
Unit Power (kW) 4.6 4.7 4.7 4.8 4.9 5.0
Head Press (kPa) 2886.5 2933.8 2983.6 3035.5 3089.3 3145.4
40.6 Capacity (kW) 12.8 14.2 15.7 17.3 19.0 20.8
Unit Power (kW) 5.1 5.2 5.2 5.3 5.4 5.5
Head Press (kPa) 3251.7 3301.3 3352.8 3406.1 3461.3 3517.8
46.1 Capacity (kW) 11.7 13.0 14.4 16.0 17.6 19.2
Unit Power (kW) 5.7 5.7 5.8 5.9 6.0 6.1
Head Press (kPa) 3647.1 3697.4 3749.1 3802.6 3857.1 3912.2
51.7 Capacity (kW) 10.5 11.8 13.1 14.5 16.0 17.6
Unit Power (kW) 6.3 6.3 6.4 6.5 6.6 6.7
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

SSP-PRC024K-EN 41
Performance Data

Table 28. Gross cooling capacities (kW) TWA0604*D condensing unit only (IP)

Outdoor Suction Temperature (°F)


Temp (°F) 30 35 40 45 50 55
Head Press (psig) 243.4 248.8 254.6 260.8 267.4 274.3
65 Capacity (Btuh/1000) 52.2 57.8 63.8 70.2 77.1 84.4
Unit Power (kW) 3.1 3.2 3.2 3.2 3.2 3.2
Head Press (psig) 280.2 285.9 292.0 298.4 305.2 312.4
75 Capacity (Btuh/1000) 49.3 54.6 60.3 66.4 72.9 79.8
Unit Power (kW) 3.5 3.5 3.6 3.6 3.6 3.7
Head Press (psig) 320.4 326.4 332.7 339.4 346.5 353.9
85 Capacity (Btuh/1000) 46.1 51.2 56.6 62.3 68.4 74.8
Unit Power (kW) 3.9 4.0 4.0 4.0 4.1 4.1
Head Press (psig) 364.1 370.4 377.0 383.9 391.1 398.7
95 Capacity (Btuh/1000) 42.7 47.5 52.6 58.0 63.7 69.8
Unit Power (kW) 4.4 4.5 4.5 4.5 4.6 4.6
Head Press (psig) 411.5 418.1 424.9 432.1 439.5 447.2
105 Capacity (Btuh/1000) 39.0 43.6 48.4 53.6 59.0 64.6
Unit Power (kW) 5.0 5.0 5.0 5.1 5.1 5.2
Head Press (psig) 463.1 469.9 476.9 484.2 491.7 499.4
115 Capacity (Btuh/1000) 35.3 39.6 44.2 49.0 54.1 59.4
Unit Power (kW) 5.6 5.6 5.7 5.7 5.7 5.8
Head Press (psig) 518.9 525.7 532.8 540.0 547.4 554.9
125 Capacity (Btuh/1000) 31.5 35.6 39.9 44.4 49.1 54.0
Unit Power (kW) 6.2 6.3 6.3 6.4 6.4 6.5
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 29. Gross cooling capacities (kW) TWA0604*D condensing unit only (SI)

Outdoor Suction Temperature (°C)


Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1678.2 1715.5 1755.4 1798.0 1843.4 1891.5
18.3 Capacity (kW) 15.3 16.9 18.7 20.6 22.6 24.7
Unit Power (kW) 3.1 3.2 3.2 3.2 3.2 3.2
Head Press (kPa) 1932.0 1971.4 2013.2 2057.5 2104.5 2154.2
23.9 Capacity (kW) 14.5 16.0 17.7 19.5 21.4 23.4
Unit Power (kW) 3.5 3.5 3.6 3.6 3.6 3.7
Head Press (kPa) 2208.9 2250.4 2294.1 2340.2 2388.8 2439.8
29.4 Capacity (kW) 13.5 15.0 16.6 18.3 20.0 21.9
Unit Power (kW) 3.9 4.0 4.0 4.0 4.1 4.1
Head Press (kPa) 2510.3 2553.8 2599.3 2646.9 2696.9 2749.0
35 Capacity (kW) 12.5 13.9 15.4 17.0 18.7 20.5
Unit Power (kW) 4.4 4.5 4.5 4.5 4.6 4.6
Head Press (kPa) 2837.5 2882.8 2929.8 2979.0 3030.2 3083.4
40.6 Capacity (kW) 11.4 12.8 14.2 15.7 17.3 18.9
Unit Power (kW) 5.0 5.0 5.0 5.1 5.1 5.2
Head Press (kPa) 3193.0 3239.7 3288.1 3338.2 3389.9 3443.2
46.1 Capacity (kW) 10.3 11.6 13.0 14.4 15.9 17.4
Unit Power (kW) 5.6 5.6 5.7 5.7 5.7 5.8
Head Press (kPa) 3577.7 3624.8 3673.3 3723.0 3774.0 3825.9
51.7 Capacity (kW) 9.2 10.4 11.7 13.0 14.4 15.8
Unit Power (kW) 6.2 6.3 6.3 6.4 6.4 6.5
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

42 SSP-PRC024K-EN
Performance Data

Table 30. Gross cooling capacities (MBH) TWA0764*A condensing unit only (IP)
Outdoor Suction Temperature (°F)
Temp (°F) 30 35 40 45 50 55
Head Press (psig) 249.7 255.6 262.0 268.8 276.2 284.0
65 Capacity (Btuh/1000) 63.0 69.3 76.0 83.2 90.9 99.0
Unit Power (kW) 4.0 4.0 4.1 4.2 4.3 4.4
Head Press (psig) 287.9 294.1 300.8 307.9 315.5 323.6
75 Capacity (Btuh/1000) 60.3 66.2 72.6 79.4 86.6 94.2
Unit Power (kW) 4.4 4.4 4.5 4.6 4.7 4.8
Head Press (psig) 329.1 335.7 342.6 350.0 357.9 366.3
85 Capacity (Btuh/1000) 56.9 62.5 68.5 74.9 81.7 88.8
Unit Power (kW) 4.8 4.9 4.9 5.0 5.1 5.2
Head Press (psig) 373.8 380.6 387.8 395.5 403.6 412.3
95 Capacity (Btuh/1000) 53.0 58.4 64.0 70.0 76.3 83.0
Unit Power (kW) 5.3 5.3 5.4 5.5 5.6 5.7
Head Press (psig) 422.2 429.3 436.8 444.7 453.1 461.9
105 Capacity (Btuh/1000) 49.0 54.0 59.3 64.9 70.9 77.1
Unit Power (kW) 5.8 5.9 6.0 6.1 6.2 6.3
Head Press (psig) 475.0 482.2 489.9 497.9 506.4 515.3
115 Capacity (Btuh/1000) 44.9 49.6 54.6 59.8 65.3 71.1
Unit Power (kW) 6.4 6.5 6.6 6.7 6.8 6.9
Head Press (psig) 532.2 539.4 547.1 555.1 563.5 572.3
125 Capacity (Btuh/1000) 40.9 45.2 49.8 54.6 59.7 65.0
Unit Power (kW) 7.1 7.2 7.3 7.4 7.5 7.6
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 31. Gross cooling capacities (kW) TWA0764*A condensing unit only (SI)
Outdoor Suction Temperature (°C)
Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1721.6 1762.4 1806.3 1853.5 1904.0 1958.2
18.3 Capacity (kW) 18.5 20.3 22.3 24.4 26.6 29.0
Unit Power (kW) 4.0 4.0 4.1 4.2 4.3 4.4
Head Press (kPa) 1984.9 2027.9 2073.9 2123.0 2175.5 2231.5
23.9 Capacity (kW) 17.7 19.4 21.3 23.3 25.4 27.6
Unit Power (kW) 4.4 4.4 4.5 4.6 4.7 4.8
Head Press (kPa) 2269.3 2314.4 2362.4 2413.5 2467.9 2525.7
29.4 Capacity (kW) 16.7 18.3 20.1 22.0 23.9 26.0
Unit Power (kW) 4.8 4.9 4.9 5.0 5.1 5.2
Head Press (kPa) 2577.3 2624.2 2674.1 2726.9 2783.0 2842.4
35 Capacity (kW) 15.5 17.1 18.8 20.5 22.4 24.3
Unit Power (kW) 5.3 5.3 5.4 5.5 5.6 5.7
Head Press (kPa) 2911.1 2959.8 3011.5 3066.1 3123.8 3184.7
40.6 Capacity (kW) 14.4 15.8 17.4 19.0 20.8 22.6
Unit Power (kW) 5.8 5.9 6.0 6.1 6.2 6.3
Head Press (kPa) 3274.7 3324.7 3377.6 3433.2 3491.6 3553.1
46.1 Capacity (kW) 13.2 14.5 16.0 17.5 19.1 20.8
Unit Power (kW) 6.4 6.5 6.6 6.7 6.8 6.9
Head Press (kPa) 3669.1 3719.4 3772.1 3827.4 3885.4 3945.8
51.7 Capacity (kW) 12.0 13.2 14.6 16.0 17.5 19.1
Unit Power (kW) 7.1 7.2 7.3 7.4 7.5 7.6
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

SSP-PRC024K-EN 43
Performance Data

Table 32. Gross cooling capacities (MBH) TWA0764*D condensing unit only (IP)

Outdoor Suction Temperature (°F)


Temp (°F) 30 35 40 45 50 55
Head Press (psig) 250.9 257.3 264.0 271.0 278.3 286.0
65 Capacity (Btuh/1000) 64.7 71.9 79.5 87.5 95.9 104.5
Unit Power (kW) 3.8 3.8 3.9 3.9 4.0 4.0
Head Press (psig) 287.9 294.6 301.6 308.8 316.3 324.5
75 Capacity (Btuh/1000) 61.0 67.8 75.0 82.5 90.4 98.5
Unit Power (kW) 4.2 4.3 4.3 4.4 4.4 4.5
Head Press (psig) 328.2 335.2 342.4 349.9 357.6 366.2
85 Capacity (Btuh/1000) 57.0 63.4 70.2 77.4 84.7 92.3
Unit Power (kW) 4.8 4.8 4.9 4.9 4.9 5.0
Head Press (psig) 372.0 379.2 386.7 394.4 402.2 411.2
95 Capacity (Btuh/1000) 52.8 58.9 65.3 72.0 78.9 86.0
Unit Power (kW) 5.4 5.4 5.5 5.5 5.5 5.6
Head Press (psig) 419.4 426.8 434.5 442.3 450.3 459.4
105 Capacity (Btuh/1000) 48.4 54.1 60.2 66.5 73.0 79.7
Unit Power (kW) 6.1 6.1 6.1 6.2 6.2 6.3
Head Press (psig) 470.7 478.3 486.0 493.9 501.9 510.7
115 Capacity (Btuh/1000) 43.8 49.3 55.0 60.9 67.0 73.2
Unit Power (kW) 6.9 6.9 6.9 7.0 7.0 7.0
Head Press (psig) 525.8 533.3 540.9 548.6 556.3 564.1
125 Capacity (Btuh/1000) 39.2 44.3 49.6 55.2 60.8 66.5
Unit Power (kW) 7.8 7.8 7.9 7.9 7.9 7.9
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 33. Gross cooling capacities (kW) TWA0764*D condensing unit only (SI)

Outdoor Suction Temperature (°C)


Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1729.6 1773.8 1820.3 1868.6 1918.6 1972.0
18.3 Capacity (kW) 19.0 21.1 23.3 25.6 28.1 30.6
Unit Power (kW) 3.8 3.8 3.9 3.9 4.0 4.0
Head Press (kPa) 1984.8 2031.0 2079.2 2129.2 2180.8 2237.4
23.9 Capacity (kW) 17.9 19.9 22.0 24.2 26.5 28.9
Unit Power (kW) 4.2 4.3 4.3 4.4 4.4 4.5
Head Press (kPa) 2262.7 2310.9 2360.9 2412.6 2465.5 2524.7
29.4 Capacity (kW) 16.7 18.6 20.6 22.7 24.8 27.1
Unit Power (kW) 4.8 4.8 4.9 4.9 4.9 5.0
Head Press (kPa) 2564.7 2614.6 2666.1 2719.0 2773.0 2834.8
35 Capacity (kW) 15.5 17.3 19.1 21.1 23.1 25.2
Unit Power (kW) 5.4 5.4 5.5 5.5 5.5 5.6
Head Press (kPa) 2891.6 2942.8 2995.7 3049.9 3104.8 3167.5
40.6 Capacity (kW) 14.2 15.9 17.6 19.5 21.4 23.3
Unit Power (kW) 6.1 6.1 6.1 6.2 6.2 6.3
Head Press (kPa) 3245.2 3297.4 3351.1 3405.5 3460.2 3521.0
46.1 Capacity (kW) 12.8 14.4 16.1 17.9 19.6 21.4
Unit Power (kW) 6.9 6.9 6.9 7.0 7.0 7.0
Head Press (kPa) 3625.4 3677.1 3729.7 3782.7 3835.6 3889.1
51.7 Capacity (kW) 11.5 13.0 14.5 16.2 17.8 19.5
Unit Power (kW) 7.8 7.8 7.9 7.9 7.9 7.9
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

44 SSP-PRC024K-EN
Performance Data

Table 34. Gross cooling capacities (MBH) TWA1014*A condensing unit only (IP)
Outdoor Suction Temperature (°F)
Temp (°F) 30 35 40 45 50 55
Head Press (psig) 260.5 266.2 271.8 277.6 283.3 288.9
65 Capacity (Btuh/1000) 86.3 95.0 104.4 114.4 124.9 135.9
Unit Power (kW) 5.4 5.5 5.5 5.6 5.7 5.7
Head Press (psig) 298.8 304.6 310.4 316.3 322.0 327.6
75 Capacity (Btuh/1000) 81.8 90.1 99.0 108.5 118.4 128.7
Unit Power (kW) 5.9 6.0 6.1 6.2 6.2 6.3
Head Press (psig) 340.8 346.8 352.7 358.7 364.4 369.9
85 Capacity (Btuh/1000) 77.2 85.1 93.5 102.4 111.7 121.4
Unit Power (kW) 6.6 6.6 6.7 6.8 6.8 6.9
Head Press (psig) 386.6 392.7 398.8 404.7 410.4 415.9
95 Capacity (Btuh/1000) 72.2 79.7 87.6 96.0 104.8 113.9
Unit Power (kW) 7.2 7.3 7.4 7.4 7.5 7.6
Head Press (psig) 436.5 442.7 448.8 454.7 460.3 465.5
105 Capacity (Btuh/1000) 66.9 74.0 81.5 89.4 97.6 106.1
Unit Power (kW) 8.0 8.0 8.1 8.2 8.3 8.3
Head Press (psig) 490.6 496.8 502.8 508.6 513.9 518.8
115 Capacity (Btuh/1000) 61.3 68.0 75.0 82.4 90.1 98.0
Unit Power (kW) 8.8 8.9 9.0 9.0 9.1 9.1
Head Press (psig) 549.0 555.0 560.7 566.0 570.9 575.1
125 Capacity (Btuh/1000) 55.3 61.5 68.1 75.0 82.2 89.5
Unit Power (kW) 9.7 9.8 9.9 9.9 10.0 10.0
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 35. Gross cooling capacities (kW) TWA1014*A condensing unit only (SI)
Outdoor Suction Temperature (°C)
Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1796.2 1835.1 1874.3 1913.9 1953.2 1991.6
18.3 Capacity (kW) 25.3 27.9 30.6 33.5 36.6 39.8
Unit Power (kW) 5.4 5.5 5.5 5.6 5.7 5.7
Head Press (kPa) 2060.3 2100.2 2140.4 2180.6 2220.3 2258.8
23.9 Capacity (kW) 24.0 26.4 29.0 31.8 34.7 37.7
Unit Power (kW) 5.9 6.0 6.1 6.2 6.2 6.3
Head Press (kPa) 2349.9 2390.9 2432.0 2472.8 2512.7 2550.7
29.4 Capacity (kW) 22.6 24.9 27.4 30.0 32.7 35.6
Unit Power (kW) 6.6 6.6 6.7 6.8 6.8 6.9
Head Press (kPa) 2665.8 2707.7 2749.5 2790.4 2829.9 2867.3
35 Capacity (kW) 21.2 23.4 25.7 28.1 30.7 33.4
Unit Power (kW) 7.2 7.3 7.4 7.4 7.5 7.6
Head Press (kPa) 3009.4 3052.2 3094.2 3135.0 3173.9 3209.8
40.6 Capacity (kW) 19.6 21.7 23.9 26.2 28.6 31.1
Unit Power (kW) 8.0 8.0 8.1 8.2 8.3 8.3
Head Press (kPa) 3382.9 3425.6 3467.0 3506.5 3543.4 3576.9
46.1 Capacity (kW) 18.0 19.9 22.0 24.2 26.4 28.7
Unit Power (kW) 8.8 8.9 9.0 9.0 9.1 9.1
Head Press (kPa) 3785.4 3826.7 3866.0 3902.7 3936.0 3965.1
51.7 Capacity (kW) 16.2 18.0 20.0 22.0 24.1 26.2
Unit Power (kW) 9.7 9.8 9.9 9.9 10.0 10.0
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

SSP-PRC024K-EN 45
Performance Data

Table 36. Gross cooling capacities (MBH) TWA1014*D condensing unit only (IP)

Outdoor Suction Temperature (°F)


Temp (°F) 30 35 40 45 50 55
Head Press (psig) 249.0 254.7 260.7 266.9 273.4 280.2
65 Capacity (Btuh/1000) 86.6 95.3 104.5 114.2 124.4 135.0
Unit Power (kW) 4.9 5.0 5.0 5.1 5.2 5.2
Head Press (psig) 285.4 291.2 297.3 303.8 310.5 317.4
75 Capacity (Btuh/1000) 80.7 88.8 97.4 106.5 116.0 126.0
Unit Power (kW) 5.5 5.5 5.6 5.7 5.7 5.8
Head Press (psig) 325.9 331.9 338.3 344.9 351.8 358.9
85 Capacity (Btuh/1000) 75.3 83.0 91.0 99.6 108.6 118.0
Unit Power (kW) 6.2 6.2 6.3 6.4 6.4 6.5
Head Press (psig) 370.2 376.5 383.2 390.1 397.2 404.6
95 Capacity (Btuh/1000) 70.0 77.2 84.9 93.0 101.5 110.3
Unit Power (kW) 7.0 7.0 7.1 7.2 7.2 7.3
Head Press (psig) 418.1 424.8 431.8 439.0 446.5 454.1
105 Capacity (Btuh/1000) 64.2 71.2 78.5 86.3 94.4 102.8
Unit Power (kW) 7.8 7.9 8.0 8.0 8.1 8.1
Head Press (psig) 469.3 476.4 483.8 491.4 499.2 507.0
115 Capacity (Btuh/1000) 57.7 64.5 71.6 79.1 86.8 94.8
Unit Power (kW) 8.7 8.8 8.9 8.9 9.0 9.0
Head Press (psig) 523.4 530.9 538.7 546.6 554.6 562.6
125 Capacity (Btuh/1000) 50.3 56.9 63.9 71.1 78.5 86.2
Unit Power (kW) 9.6 9.7 9.8 9.9 9.9 10.0
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 37. Gross cooling capacities (kW) TWA1014*D condensing unit only (SI)

Outdoor Suction Temperature (°C)


Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1716.9 1756.1 1797.2 1840.2 1885.3 1932.2
18.3 Capacity (kW) 25.4 27.9 30.6 33.5 36.5 39.6
Unit Power (kW) 4.9 5.0 5.0 5.1 5.2 5.2
Head Press (kPa) 1967.7 2007.8 2050.1 2094.4 2140.6 2188.6
23.9 Capacity (kW) 23.6 26.0 28.5 31.2 34.0 36.9
Unit Power (kW) 5.5 5.5 5.6 5.7 5.7 5.8
Head Press (kPa) 2246.7 2288.4 2332.2 2378.0 2425.6 2474.9
29.4 Capacity (kW) 22.1 24.3 26.7 29.2 31.8 34.6
Unit Power (kW) 6.2 6.2 6.3 6.4 6.4 6.5
Head Press (kPa) 2552.4 2596.2 2641.9 2689.4 2738.7 2789.3
35 Capacity (kW) 20.5 22.6 24.9 27.3 29.7 32.3
Unit Power (kW) 7.0 7.0 7.1 7.2 7.2 7.3
Head Press (kPa) 2882.4 2928.8 2976.9 3027.0 3078.3 3130.8
40.6 Capacity (kW) 18.8 20.9 23.0 25.3 27.7 30.1
Unit Power (kW) 7.8 7.9 8.0 8.0 8.1 8.1
Head Press (kPa) 3235.4 3284.8 3335.9 3388.3 3441.8 3495.9
46.1 Capacity (kW) 16.9 18.9 21.0 23.2 25.4 27.8
Unit Power (kW) 8.7 8.8 8.9 8.9 9.0 9.0
Head Press (kPa) 3608.4 3660.7 3714.2 3768.7 3823.8 3878.9
51.7 Capacity (kW) 14.8 16.7 18.7 20.8 23.0 25.3
Unit Power (kW) 9.6 9.7 9.8 9.9 9.9 10.0
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

46 SSP-PRC024K-EN
Performance Data

Table 38. Gross cooling capacities (MBH) TWA1564*D condensing unit only (IP)
Outdoor Suction Temperature (°F)
Temp (°F) 30 35 40 45 50 55
Head Press (psig) 230.1 234.1 238.4 243.1 248.1 253.5
65 Capacity (Btuh/1000) 137.9 151.4 166.0 181.6 198.4 216.3
Unit Power (kW) 8.7 8.9 9.1 9.3 9.5 9.8
Head Press (psig) 266.3 270.7 275.4 280.5 285.8 291.5
75 Capacity (Btuh/1000) 130.8 144.0 158.1 173.2 189.5 206.9
Unit Power (kW) 9.5 9.7 9.9 10.1 10.3 10.6
Head Press (psig) 306.2 310.9 315.9 321.2 326.9 333.0
85 Capacity (Btuh/1000) 123.1 135.8 149.4 164.0 179.6 196.4
Unit Power (kW) 10.5 10.6 10.8 11.0 11.2 11.5
Head Press (psig) 349.8 354.8 360.0 365.6 371.6 378.0
95 Capacity (Btuh/1000) 114.9 127.0 140.0 154.0 169.0 185.1
Unit Power (kW) 11.5 11.7 11.8 12.0 12.2 12.5
Head Press (psig) 397.4 402.6 408.1 413.9 420.1 426.6
105 Capacity (Btuh/1000) 106.3 117.8 130.2 143.5 157.8 173.1
Unit Power (kW) 12.7 12.8 13.0 13.2 13.4 13.6
Head Press (psig) 449.3 454.6 460.3 466.2 472.6 479.3
115 Capacity (Btuh/1000) 97.6 108.4 120.1 132.7 146.2 160.6
Unit Power (kW) 14.0 14.2 14.4 14.5 14.7 15.0
Head Press (psig) 505.8 511.1 516.7 522.7 529.0 535.7
125 Capacity (Btuh/1000) 88.7 98.9 109.8 121.5 134.2 147.7
Unit Power (kW) 15.6 15.7 15.9 16.1 16.2 16.5
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 39. Gross cooling capacities (kW) TWA1564*D condensing unit only (SI)
Outdoor Suction Temperature (°C)
Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1586.2 1614.0 1644.1 1676.3 1710.8 1747.8
18.3 Capacity (kW) 40.4 44.4 48.6 53.2 58.1 63.4
Unit Power (kW) 8.7 8.9 9.1 9.3 9.5 9.8
Head Press (kPa) 1836.4 1866.7 1899.1 1933.7 1970.7 2010.2
23.9 Capacity (kW) 38.3 42.2 46.3 50.8 55.5 60.6
Unit Power (kW) 9.5 9.7 9.9 10.1 10.3 10.6
Head Press (kPa) 2111.2 2143.5 2178.0 2214.8 2254.0 2295.9
29.4 Capacity (kW) 36.1 39.8 43.8 48.1 52.6 57.6
Unit Power (kW) 10.5 10.6 10.8 11.0 11.2 11.5
Head Press (kPa) 2411.8 2445.9 2482.3 2521.0 2562.3 2606.0
35 Capacity (kW) 33.7 37.2 41.0 45.1 49.5 54.2
Unit Power (kW) 11.5 11.7 11.8 12.0 12.2 12.5
Head Press (kPa) 2740.0 2775.6 2813.4 2853.6 2896.4 2941.6
40.6 Capacity (kW) 31.2 34.5 38.2 42.1 46.2 50.7
Unit Power (kW) 12.7 12.8 13.0 13.2 13.4 13.6
Head Press (kPa) 3098.0 3134.5 3173.4 3214.6 3258.4 3304.9
46.1 Capacity (kW) 28.6 31.8 35.2 38.9 42.8 47.1
Unit Power (kW) 14.0 14.2 14.4 14.5 14.7 15.0
Head Press (kPa) 3487.4 3523.8 3562.5 3603.8 3647.4 3693.5
51.7 Capacity (kW) 26.0 29.0 32.2 35.6 39.3 43.3
Unit Power (kW) 15.6 15.7 15.9 16.1 16.2 16.5
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

SSP-PRC024K-EN 47
Performance Data

Table 40. Gross cooling capacities (MBH) TWA2014*D condensing unit only (IP)
Outdoor Suction Temperature (°F)
Temp (°F) 30 35 40 45 50 55
Head Press (psig) 252.9 259.0 265.6 272.5 279.9 287.8
65 Capacity (Btuh/1000) 208.6 228.8 250.3 273.1 297.2 322.7
Unit Power (kW) 12.6 12.8 13.1 13.4 13.7 14.1
Head Press (psig) 289.6 296.0 302.8 310.1 317.8 326.0
75 Capacity (Btuh/1000) 197.9 217.5 238.3 260.3 283.5 307.9
Unit Power (kW) 13.8 14.0 14.3 14.6 14.9 15.3
Head Press (psig) 329.5 336.2 343.3 350.8 358.8 367.3
85 Capacity (Btuh/1000) 186.0 204.8 224.8 245.8 268.0 291.3
Unit Power (kW) 15.1 15.4 15.6 15.9 16.2 16.6
Head Press (psig) 372.8 379.8 387.1 394.9 403.0 411.7
95 Capacity (Btuh/1000) 173.0 190.9 210.0 230.0 251.1 273.1
Unit Power (kW) 16.7 16.9 17.2 17.4 17.7 18.1
Head Press (psig) 419.7 426.8 434.3 442.2 450.6 459.3
105 Capacity (Btuh/1000) 159.2 176.2 194.1 213.1 233.0 253.8
Unit Power (kW) 18.5 18.7 18.9 19.2 19.4 19.8
Head Press (psig) 470.4 477.6 485.2 493.1 501.4 510.2
115 Capacity (Btuh/1000) 144.7 160.7 177.6 195.4 214.0 233.4
Unit Power (kW) 20.5 20.7 20.9 21.1 21.4 21.7
Head Press (psig) 524.9 531.9 539.3 547.1 555.1 563.6
125 Capacity (Btuh/1000) 129.8 144.6 160.3 176.7 193.9 211.8
Unit Power (kW) 22.7 22.9 23.1 23.3 23.6 23.8
Note: Performance data calculated at 15°F subcooling and 15°F superheat and does not include capacity loss due to refrigerant lines.

Table 41. Gross cooling capacities (kW) TWA2014*D condensing unit only (SI)
Outdoor Suction Temperature (°C)
Temp (°C) -1.1 1.7 4.4 7.2 10 12.8
Head Press (kPa) 1744.0 1786.0 1830.9 1878.8 1929.9 1984.5
18.3 Capacity (kW) 61.1 67.1 73.4 80.0 87.1 94.6
Unit Power (kW) 12.6 12.8 13.1 13.4 13.7 14.1
Head Press (kPa) 1996.5 2040.8 2087.9 2137.9 2191.1 2247.6
23.9 Capacity (kW) 58.0 63.7 69.8 76.3 83.1 90.2
Unit Power (kW) 13.8 14.0 14.3 14.6 14.9 15.3
Head Press (kPa) 2271.6 2317.9 2367.0 2419.0 2474.0 2532.2
29.4 Capacity (kW) 54.5 60.0 65.9 72.0 78.5 85.4
Unit Power (kW) 15.1 15.4 15.6 15.9 16.2 16.6
Head Press (kPa) 2570.4 2618.3 2668.9 2722.4 2778.8 2838.3
35 Capacity (kW) 50.7 56.0 61.5 67.4 73.6 80.0
Unit Power (kW) 16.7 16.9 17.2 17.4 17.7 18.1
Head Press (kPa) 2893.7 2942.7 2994.5 3049.1 3106.6 3167.1
40.6 Capacity (kW) 46.6 51.6 56.9 62.5 68.3 74.4
Unit Power (kW) 18.5 18.7 18.9 19.2 19.4 19.8
Head Press (kPa) 3243.4 3292.8 3345.0 3399.8 3457.3 3517.4
46.1 Capacity (kW) 42.4 47.1 52.0 57.3 62.7 68.4
Unit Power (kW) 20.5 20.7 20.9 21.1 21.4 21.7
Head Press (kPa) 3618.7 3667.3 3718.3 3771.8 3827.6 3885.7
51.7 Capacity (kW) 38.0 42.4 47.0 51.8 56.8 62.1
Unit Power (kW) 22.7 22.9 23.1 23.3 23.6 23.8
Note: Performance data calculated at 8.3°C subcooling and 8.3°C superheat and does not include capacity loss due to refrigerant lines.

48 SSP-PRC024K-EN
Performance Data

Gross Heating Capacities


Table 42. Gross heating capacities (MBH) - TWA0604*A heat pump with TWE0764*A air handler at 2000 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Temp (°F) 60 70 75 80 60 70 75 80
-18 20.1 18.4 17.6 16.7 3.9 4.3 4.5 4.7
-13 22.0 20.5 19.7 18.8 4.0 4.4 4.5 4.7
-8 24.3 22.8 22.0 21.1 4.1 4.4 4.6 4.8
-3 26.8 25.3 24.5 23.6 4.1 4.5 4.7 4.9
2 29.5 28.0 27.2 26.4 4.2 4.6 4.8 5.0
7 32.4 31.0 30.1 29.3 4.3 4.6 4.9 5.1
12 35.6 34.1 33.3 32.4 4.3 4.7 4.9 5.2
17 38.9 37.4 36.5 35.7 4.4 4.8 5.0 5.2
22 42.4 40.8 39.9 39.0 4.5 4.9 5.1 5.3
27 46.2 44.5 43.6 42.6 4.6 5.0 5.2 5.4
32 50.3 48.4 47.4 46.4 4.7 5.1 5.3 5.5
37 54.3 52.3 51.3 50.3 4.7 5.2 5.4 5.6
42 58.6 56.4 55.3 54.3 4.8 5.3 5.5 5.7
47 63.0 60.8 59.6 58.5 4.9 5.4 5.6 5.8
52 67.7 65.3 64.1 62.8 5.0 5.5 5.7 5.9
57 72.6 70.0 68.6 67.3 5.1 5.6 5.8 6.1
62 77.6 74.7 73.3 71.9 5.3 5.7 5.9 6.2
67 82.7 79.6 78.1 76.6 5.4 5.8 6.1 6.3
72 87.8 84.6 83.0 81.4 5.5 6.0 6.2 6.5
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 43. Gross heating capacities (kW) TWA0604*A heat pump with TWE0764*A air handler at 2000 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Temp (°C) 15 21 24 27 15 21 24 27
-28 5.8 5.4 5.1 4.8 3.7 4.1 4.3 4.5
-25 6.4 5.9 5.7 5.4 3.8 4.2 4.4 4.6
-22 7.0 6.6 6.4 6.1 3.9 4.3 4.5 4.7
-19 7.7 7.3 7.1 6.8 3.9 4.3 4.5 4.8
-17 8.5 8.1 7.8 7.6 4.0 4.4 4.6 4.8
-14 9.3 8.9 8.7 8.4 4.1 4.5 4.7 4.9
-11 10.2 9.8 9.5 9.3 4.2 4.6 4.8 5.0
-8 11.2 10.7 10.5 10.2 4.2 4.7 4.9 5.1
-6 12.2 11.7 11.5 11.2 4.3 4.7 5.0 5.2
-3 13.3 12.8 12.5 12.2 4.4 4.8 5.1 5.3
0 14.5 13.9 13.6 13.4 4.5 4.9 5.2 5.4
3 15.6 15.0 14.8 14.5 4.6 5.0 5.3 5.5
6 16.8 16.2 15.9 15.6 4.7 5.1 5.4 5.6
8 18.1 17.5 17.2 16.8 4.8 5.2 5.5 5.7
11 19.5 18.8 18.5 18.1 4.9 5.4 5.6 5.9
14 20.9 20.2 19.8 19.4 5.0 5.5 5.7 6.0
17 22.4 21.6 21.2 20.8 5.1 5.6 5.9 6.1
19 23.8 23.0 22.6 22.2 5.3 5.8 6.0 6.3
22 25.4 24.5 24.0 23.6 5.4 5.9 6.1 6.4
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

SSP-PRC024K-EN 49
Performance Data

Table 44. Gross heating capacities (MBH) - TWA0604*D heat pump with TWE0724*B standard air handler at 2000
CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Outdoor
Temp (°F) 60 70 75 80 60 70 75 80
-18 11.3 9.5 9.8 9.7 3.4 3.6 3.8 4.0
-13 13.7 12.1 11.1 10.1 3.4 3.7 3.9 4.1
-8 16.5 14.9 13.9 12.9 3.5 3.8 4.0 4.2
-3 19.2 17.5 16.5 15.7 3.6 3.9 4.1 4.3
2 21.8 20.2 19.5 18.7 3.7 4.0 4.2 4.4
7 25.2 23.4 22.6 21.9 3.8 4.1 4.3 4.5
12 27.7 26.4 25.7 25.0 3.8 4.2 4.4 4.6
17 31.0 29.7 29.0 28.2 3.9 4.3 4.5 4.7
22 34.5 33.1 32.4 31.6 3.9 4.3 4.5 4.8
27 38.1 36.7 35.9 35.1 4.0 4.4 4.6 4.8
32 41.9 40.3 39.5 38.6 4.0 4.4 4.7 4.9
37 45.7 44.0 43.1 42.2 4.1 4.5 4.7 5.0
42 49.5 47.7 46.8 45.8 4.1 4.5 4.8 5.0
47 53.6 51.7 50.7 49.7 4.2 4.6 4.8 5.1
52 58.0 56.0 54.9 53.8 4.2 4.6 4.9 5.1
57 62.7 60.4 59.3 58.1 4.3 4.7 5.0 5.2
62 67.5 65.0 63.8 62.5 4.3 4.8 5.0 5.3
67 72.5 69.7 68.4 67.1 4.4 4.9 5.1 5.4
72 77.7 74.8 73.3 71.9 4.5 5.0 5.2 5.5
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 45. Gross heating capacities (kW) TWA0604*D heat pump with TWE0724*B air handler at 2000 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Outdoor
Temp (°C) 15 21 24 27 15 21 24 27
-28 3.3 2.8 2.9 2.8 3.4 3.6 3.8 4.0
-25 4.0 3.5 3.3 2.9 3.4 3.7 3.9 4.1
-22 4.8 4.4 4.1 3.8 3.5 3.8 4.0 4.2
-19 5.6 5.1 4.8 4.6 3.6 3.9 4.1 4.3
-17 6.4 5.9 5.7 5.5 3.7 4.0 4.2 4.4
-14 7.4 6.8 6.6 6.4 3.8 4.1 4.3 4.5
-11 8.1 7.7 7.5 7.3 3.8 4.2 4.4 4.6
-8 9.1 8.7 8.5 8.3 3.9 4.3 4.5 4.7
-6 10.1 9.7 9.5 9.3 3.9 4.3 4.5 4.8
-3 11.2 10.7 10.5 10.3 4.0 4.4 4.6 4.8
0 12.3 11.8 11.6 11.3 4.0 4.4 4.7 4.9
3 13.4 12.9 12.6 12.4 4.1 4.5 4.7 5.0
6 14.5 14.0 13.7 13.4 4.1 4.5 4.8 5.0
8 15.7 15.1 14.9 14.6 4.2 4.6 4.8 5.1
11 17.0 16.4 16.1 15.8 4.2 4.6 4.9 5.1
14 18.4 17.7 17.4 17.0 4.3 4.7 5.0 5.2
17 19.8 19.1 18.7 18.3 4.3 4.8 5.0 5.3
19 21.2 20.4 20.0 19.7 4.4 4.9 5.1 5.4
22 22.8 21.9 21.5 21.1 4.5 5.0 5.2 5.5
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

50 SSP-PRC024K-EN
Performance Data

Table 46. Gross heating capacities (MBH) TWA0764*A heat pump with TWE0764*A air handler at 2500 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Temp (°F) 60 70 75 80 60 70 75 80
-18 17.5 17.2 16.9 16.4 3.7 4.1 4.2 4.4
-13 21.5 20.6 20.1 19.6 3.8 4.2 4.3 4.5
-8 24.0 23.7 23.3 22.9 3.9 4.2 4.4 4.6
-3 27.3 27.0 26.4 26.0 4.0 4.3 4.5 4.7
2 30.8 29.9 29.6 29.1 4.0 4.4 4.6 4.8
7 34.3 33.8 33.4 32.9 4.1 4.5 4.7 4.9
12 37.3 36.7 36.3 35.8 4.2 4.5 4.7 4.9
17 41.0 40.4 39.9 39.3 4.2 4.6 4.8 5.0
22 44.9 44.2 43.6 43.0 4.3 4.7 4.9 5.1
27 49.0 48.1 47.2 46.6 4.3 4.7 4.9 5.2
32 53.2 52.1 51.4 50.7 4.4 4.8 5.0 5.2
37 57.4 56.2 55.4 54.6 4.5 4.9 5.1 5.3
42 61.7 60.3 59.4 58.5 4.5 4.9 5.2 5.4
47 66.3 64.6 63.7 62.7 4.6 5.0 5.2 5.5
52 71.2 69.3 68.3 67.2 4.7 5.1 5.3 5.6
57 76.5 74.3 73.1 71.9 4.8 5.2 5.4 5.7
62 82.1 79.6 78.3 77.0 4.9 5.3 5.5 5.8
67 88.0 85.2 83.7 82.2 5.0 5.5 5.7 5.9
72 94.1 91.0 89.3 87.6 5.2 5.6 5.8 6.0
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 47. Gross heating capacities (kW) TWA0764*A heat pump with TWE0764*A air handler at 2500 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Temp (°C) 15 21 24 27 15 21 24 27
-28 5.0 5.0 4.9 4.7 4.1 4.5 4.7 4.9
-25 6.3 6.0 5.8 5.7 4.2 4.6 4.8 5.0
-22 6.9 6.8 6.7 6.6 4.3 4.7 4.9 5.1
-19 7.7 7.6 7.7 7.5 4.4 4.8 5.0 5.3
-17 8.8 8.7 8.6 8.5 4.4 4.9 5.1 5.4
-14 9.7 9.6 9.4 9.3 4.5 5.0 5.2 5.5
-11 10.7 10.6 10.5 10.3 4.6 5.1 5.3 5.6
-8 11.8 11.6 11.5 11.3 4.7 5.2 5.4 5.6
-6 12.9 12.7 12.6 12.4 4.8 5.2 5.5 5.7
-3 14.1 13.9 13.7 13.5 4.8 5.3 5.6 5.8
0 15.3 15.0 14.9 14.7 4.9 5.4 5.7 5.9
3 16.6 16.2 16.0 15.8 5.0 5.5 5.7 6.0
6 17.8 17.4 17.2 16.9 5.1 5.6 5.8 6.1
8 19.1 18.7 18.4 18.1 5.2 5.7 5.9 6.2
11 20.5 20.0 19.7 19.4 5.3 5.8 6.0 6.3
14 22.0 21.4 21.1 20.8 5.4 5.9 6.2 6.5
17 23.6 23.0 22.6 22.2 5.5 6.0 6.3 6.6
19 25.4 24.6 24.2 23.8 5.7 6.2 6.5 6.7
22 27.1 26.3 25.8 25.3 5.8 6.4 6.6 6.9
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

SSP-PRC024K-EN 51
Performance Data

Table 48. Gross heating capacities (MBH) TWA0764*D heat pump with TWE0764*B air handler at 2500 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Outdoor
Temp (°F) 60 70 75 80 60 70 75 80
-18 13.5 12.8 12.3 11.8 4.5 5.1 5.5 5.8
-13 16.5 16.0 15.6 15.2 4.6 5.2 5.5 5.8
-8 19.8 19.3 18.9 18.5 4.6 5.2 5.5 5.8
-3 23.3 22.7 22.4 21.9 4.6 5.2 5.5 5.9
2 26.9 26.4 26.0 25.5 4.7 5.2 5.6 5.9
7 30.7 30.0 29.6 29.1 4.7 5.3 5.6 5.9
12 34.6 33.8 33.3 32.8 4.8 5.3 5.6 6.0
17 38.8 37.8 37.2 36.7 4.8 5.4 5.7 6.0
22 43.2 42.0 41.4 40.8 4.9 5.4 5.7 6.1
27 47.7 46.3 45.6 44.9 4.9 5.5 5.8 6.1
32 52.5 50.9 50.0 49.2 5.0 5.6 5.9 6.2
37 57.2 55.4 54.5 53.5 5.1 5.6 5.9 6.2
42 62.0 59.9 58.9 57.9 5.1 5.7 6.0 6.3
47 67.0 64.6 63.5 62.4 5.2 5.8 6.1 6.4
52 72.2 69.7 68.5 67.3 5.3 5.8 6.1 6.5
57 77.7 74.9 73.5 72.2 5.4 5.9 6.2 6.5
62 83.4 80.4 78.9 77.5 5.4 6.0 6.3 6.6
67 89.4 86.1 84.5 82.9 5.5 6.1 6.4 6.7
72 95.4 91.7 89.8 85.5 5.6 6.2 6.5 7.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 49. Gross heating capacities (kW) TWA0764*D heat pump with TWE0764*B air handler at 2500 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Outdoor
Temp (°C) 15 21 24 27 15 21 24 27
-28 3.9 3.7 3.6 3.4 4.5 5.1 5.5 5.8
-25 4.8 4.7 4.6 4.4 4.6 5.2 5.5 5.8
-22 5.8 5.7 5.5 5.4 4.6 5.2 5.5 5.8
-19 6.8 6.7 6.6 6.4 4.6 5.2 5.5 5.9
-17 7.9 7.7 7.6 7.5 4.7 5.2 5.6 5.9
-14 9.0 8.8 8.7 8.5 4.7 5.3 5.6 5.9
-11 10.1 9.9 9.8 9.6 4.8 5.3 5.6 6.0
-8 11.4 11.1 10.9 10.8 4.8 5.4 5.7 6.0
-6 12.7 12.3 12.1 11.9 4.9 5.4 5.7 6.1
-3 14.0 13.6 13.4 13.2 4.9 5.5 5.8 6.1
0 15.4 14.9 14.7 14.4 5.0 5.6 5.9 6.2
3 16.8 16.2 16.0 15.7 5.1 5.6 5.9 6.2
6 18.2 17.6 17.3 17.0 5.1 5.7 6.0 6.3
8 19.6 18.9 18.6 18.3 5.2 5.8 6.1 6.4
11 21.1 20.4 20.1 19.7 5.3 5.8 6.1 6.5
14 22.8 22.0 21.6 21.2 5.4 5.9 6.2 6.5
17 24.4 23.6 23.1 22.7 5.4 6.0 6.3 6.6
19 26.2 25.2 24.8 24.3 5.5 6.1 6.4 6.7
22 28.0 26.9 26.3 25.1 5.6 6.2 6.5 7.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

52 SSP-PRC024K-EN
Performance Data

Table 50. Gross heating capacities (MBH) TWA1014*A heat pump with TWE1014*A air handler at 3350 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Temp (°F) 60 70 75 80 60 70 75 80
-18 25.4 25.3 25.3 25.2 6.4 7.0 7.3 7.7
-13 29.8 29.6 29.5 29.3 6.5 7.1 7.5 7.8
-8 34.4 34.1 34.0 33.8 6.6 7.3 7.6 8.0
-3 39.2 38.8 38.6 38.3 6.8 7.4 7.8 8.1
2 44.1 43.6 43.3 43.0 6.9 7.5 7.9 8.3
7 49.2 48.6 48.2 48.0 7.0 7.7 8.0 8.4
12 54.3 53.6 53.2 52.8 7.1 7.8 8.1 8.5
17 59.9 59.1 58.5 58.0 7.2 7.9 8.3 8.6
22 65.8 64.7 64.1 63.5 7.3 8.0 8.4 8.7
27 71.9 70.6 70.0 69.3 7.4 8.1 8.5 8.8
32 78.5 77.0 76.3 75.4 7.5 8.2 8.6 8.9
37 84.9 83.1 82.2 81.3 7.6 8.3 8.6 9.0
42 91.5 89.5 88.5 87.5 7.7 8.4 8.7 9.1
47 98.5 96.1 95.0 93.8 7.8 8.4 8.8 9.2
52 105.6 103.0 101.7 100.3 7.8 8.5 8.9 9.3
57 112.7 109.8 108.3 106.7 7.9 8.6 8.9 9.3
62 119.6 116.2 114.5 112.8 8.0 8.6 9.0 9.4
67 126.9 123.2 121.4 119.5 8.1 8.7 9.1 9.5
72 134.9 130.8 128.8 126.8 8.2 8.9 9.3 9.6
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 51. Gross heating capacities (kW) TWA1014*A heat pump with TWE1014*A air handler at 3350 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Temp (°C) 15 21 24 27 15 21 24 27
-28 7.4 7.4 7.4 7.4 6.4 7.0 7.3 7.7
-25 8.7 8.7 8.6 8.6 6.5 7.1 7.5 7.8
-22 10.1 10.0 10.0 9.9 6.6 7.3 7.6 8.0
-19 11.5 11.4 11.3 11.2 6.8 7.4 7.8 8.1
-17 12.9 12.8 12.7 12.6 6.9 7.5 7.9 8.3
-14 14.4 14.3 14.1 14.1 7.0 7.7 8.0 8.4
-11 15.9 15.7 15.6 15.5 7.1 7.8 8.1 8.5
-8 17.6 17.3 17.2 17.0 7.2 7.9 8.3 8.6
-6 19.3 19.0 18.8 18.6 7.3 8.0 8.4 8.7
-3 21.1 20.7 20.5 20.3 7.4 8.1 8.5 8.8
0 23.0 22.6 22.4 22.1 7.5 8.2 8.6 8.9
3 24.9 24.4 24.1 23.8 7.6 8.3 8.6 9.0
6 26.8 26.2 25.9 25.6 7.7 8.4 8.7 9.1
8 28.9 28.2 27.8 27.5 7.8 8.4 8.8 9.2
11 31.0 30.2 29.8 29.4 7.8 8.5 8.9 9.3
14 33.0 32.2 31.7 31.3 7.9 8.6 8.9 9.3
17 35.1 34.1 33.6 33.1 8.0 8.6 9.0 9.4
19 37.2 36.1 35.6 35.0 8.1 8.7 9.1 9.5
22 39.5 38.3 37.7 37.1 8.2 8.9 9.3 9.6
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

SSP-PRC024K-EN 53
Performance Data

Table 52. Gross heating capacities (MBH) TWA1014*D heat pump with TWE1014*B air handler at 3350 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Outdoor
Temp (°F) 60 70 75 80 60 70 75 80
-18 23.1 22.5 22.2 21.6 5.9 6.4 6.7 7.1
-13 26.7 26.4 26.1 25.5 5.9 6.6 6.9 7.2
-8 31.0 30.6 30.2 29.6 6.1 6.7 7.0 7.4
-3 35.5 34.9 34.4 33.8 6.2 6.8 7.2 7.5
2 40.3 39.4 38.9 38.3 6.3 6.9 7.3 7.7
7 45.3 44.2 43.6 42.8 6.3 7.0 7.4 7.8
12 50.2 48.9 48.4 47.6 6.4 7.1 7.5 7.9
17 55.6 54.0 53.2 52.4 6.5 7.2 7.6 8.0
22 61.2 59.4 58.5 57.6 6.6 7.3 7.7 8.2
27 67.1 65.1 64.1 63.1 6.7 7.4 7.8 8.3
32 73.3 70.9 69.9 68.8 6.8 7.5 7.9 8.4
37 79.5 77.0 75.8 74.6 6.9 7.6 8.0 8.5
42 85.9 83.1 81.8 80.6 7.0 7.7 8.1 8.6
47 92.6 89.5 88.1 86.7 7.1 7.8 8.2 8.7
52 99.7 96.2 94.7 93.2 7.2 7.9 8.3 8.8
57 106.8 103.0 101.3 99.7 7.3 8.0 8.4 8.9
62 114.0 109.9 108.0 106.2 7.4 8.1 8.5 9.0
67 121.0 116.6 114.5 112.6 7.5 8.2 8.6 9.1
72 127.8 122.9 120.7 118.6 7.6 8.3 8.7 9.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 53. Gross heating capacities (kW) TWA1014*D heat pump with TWE1014*B air handler at 3350 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Outdoor
Temp (°C) 15 21 24 27 15 21 24 27
-28 6.8 6.6 6.5 6.3 5.9 6.4 6.7 7.1
-25 7.8 7.7 7.7 7.5 5.9 6.6 6.9 7.2
-22 9.1 9.0 8.8 8.7 6.1 6.7 7.0 7.4
-19 10.4 10.2 10.1 9.9 6.2 6.8 7.2 7.5
-17 11.8 11.6 11.4 11.2 6.3 6.9 7.3 7.7
-14 13.3 12.9 12.8 12.6 6.3 7.0 7.4 7.8
-11 14.7 14.3 14.2 14.0 6.4 7.1 7.5 7.9
-8 16.3 15.8 15.6 15.4 6.5 7.2 7.6 8.0
-6 17.9 17.4 17.2 16.9 6.6 7.3 7.7 8.2
-3 19.7 19.1 18.8 18.5 6.7 7.4 7.8 8.3
0 21.5 20.8 20.5 20.2 6.8 7.5 7.9 8.4
3 23.3 22.6 22.2 21.9 6.9 7.6 8.0 8.5
6 25.2 24.4 24.0 23.6 7.0 7.7 8.1 8.6
8 27.1 26.2 25.8 25.4 7.1 7.8 8.2 8.7
11 29.2 28.2 27.7 27.3 7.2 7.9 8.3 8.8
14 31.3 30.2 29.7 29.2 7.3 8.0 8.4 8.9
17 33.4 32.2 31.7 31.1 7.4 8.1 8.5 9.0
19 35.5 34.2 33.6 33.0 7.5 8.2 8.6 9.1
22 37.5 36.0 35.4 34.8 7.6 8.3 8.7 9.1
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

54 SSP-PRC024K-EN
Performance Data

Table 54. Gross heating capacities (MBH) TWA1564*D heat pump with TWE1564*B air handler at 5000 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Temp (°F) 60 70 75 80 60 70 75 80
-18 37.6 35.4 34.6 32.2 11.5 12.1 12.5 13.0
-13 44.0 40.8 39.3 38.2 11.2 12.2 12.7 13.3
-8 50.6 47.0 45.9 45.4 11.4 12.4 13.0 13.7
-3 57.2 54.3 53.6 53.0 11.6 12.7 13.4 14.0
2 64.3 62.3 61.5 60.7 11.8 13.0 13.7 14.3
7 73.3 70.8 69.8 69.0 12.2 13.3 14.0 14.7
12 82.1 79.7 78.6 77.6 12.4 13.6 14.3 15.0
17 92.3 89.1 87.8 86.7 12.7 13.9 14.6 15.3
22 101.9 99.1 97.5 96.3 13.0 14.2 14.9 15.6
27 112.6 109.5 107.8 106.3 13.3 14.5 15.2 15.9
32 124.2 120.4 118.6 116.9 13.6 14.8 15.5 16.2
37 135.3 131.4 129.5 127.6 13.9 15.1 15.8 16.5
42 147.5 143.1 141.0 139.0 14.2 15.4 16.1 16.8
47 160.3 155.7 153.5 151.3 14.5 15.8 16.5 17.2
52 174.0 169.0 166.6 164.2 14.9 16.1 16.8 17.6
57 188.1 182.8 180.2 177.6 15.2 16.5 17.2 17.9
62 202.8 197.1 194.3 191.6 15.6 16.9 17.6 18.3
67 217.3 211.9 208.9 206.0 16.1 17.3 18.0 18.8
72 231.9 227.1 223.9 220.9 16.6 17.8 18.5 19.3
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 55. Gross heating capacities (kW) TWA1564*D heat pump with TWE1564*B air handler at 5000 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Temp (°C) 15 21 24 27 15 21 24 27
-28 10.6 10.3 9.7 9.3 9.7 10.2 10.7 11.3
-25 12.8 11.9 11.4 11.1 9.5 10.4 11.0 11.6
-22 14.6 13.6 13.2 13.0 9.7 10.7 11.2 11.9
-19 16.5 15.6 15.4 15.2 9.9 11.0 11.6 12.2
-17 18.5 17.9 17.7 17.4 10.1 11.3 11.9 12.5
-14 21.0 20.4 20.1 19.8 10.4 11.6 12.2 12.8
-11 23.6 23.0 22.6 22.3 10.7 11.9 12.5 13.1
-8 26.4 25.6 25.2 24.9 11.0 12.2 12.8 13.5
-6 29.3 28.4 28.0 27.7 11.3 12.5 13.1 13.8
-3 32.5 31.5 31.0 30.6 11.6 12.8 13.4 14.1
0 35.7 34.6 34.1 33.6 11.9 13.1 13.7 14.4
3 39.0 37.8 37.3 36.7 12.2 13.3 14.0 14.7
6 42.4 41.2 40.6 40.0 12.5 13.7 14.3 15.0
8 46.2 44.8 44.2 43.6 12.8 14.0 14.7 15.3
11 50.1 48.7 48.0 47.3 13.1 14.4 15.0 15.7
14 54.2 52.7 51.9 51.2 13.5 14.7 15.4 16.1
17 58.5 56.9 56.0 55.3 13.9 15.1 15.8 16.5
19 62.8 61.2 60.3 59.5 14.2 15.5 16.2 16.9
22 67.1 65.6 64.7 63.8 14.6 15.9 16.6 17.4
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

SSP-PRC024K-EN 55
Performance Data

Table 56. Gross heating capacities (MBH) TWA2014*D heat pump with TWE2014*B air handler at 6675 CFM (IP)
Integrated Heating Capacity (MBH) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°F) at Indicated Indoor Dry Bulb Temp (°F)
Temp (°F) 60 70 75 80 60 70 75 80
-18 52.8 47.6 44.0 40.8 13.2 14.3 14.7 15.5
-13 61.0 55.5 52.9 50.4 13.4 14.6 15.3 15.9
-8 70.1 64.4 61.6 59.0 13.6 15.0 15.6 16.4
-3 79.5 73.9 71.3 69.0 14.0 15.3 16.1 16.8
2 89.7 84.6 82.2 79.6 14.4 15.7 16.5 17.2
7 100.9 95.9 93.4 90.9 14.7 16.1 16.9 17.7
12 113.1 107.8 105.2 102.6 15.1 16.5 17.3 18.1
17 125.9 120.4 117.6 114.8 15.4 16.9 17.6 18.5
22 139.4 133.6 130.8 127.8 15.8 17.2 18.0 18.9
27 153.6 147.5 144.5 141.4 16.1 17.6 18.4 19.2
32 168.4 162.1 158.8 155.6 16.5 18.0 18.8 19.6
37 183.3 176.6 173.2 169.7 16.8 18.3 19.2 20.0
42 198.8 191.7 188.1 184.5 17.2 18.7 19.5 20.4
47 215.2 207.7 203.9 200.0 17.6 19.1 20.0 20.9
52 232.5 224.5 220.5 216.5 18.0 19.6 20.4 21.3
57 250.4 242.0 237.7 233.5 18.4 20.0 20.9 21.8
62 268.8 260.0 255.5 251.1 18.9 20.5 21.4 22.3
67 287.4 278.1 273.5 268.9 19.3 21.0 21.9 22.8
72 306.4 296.7 291.9 287.1 19.8 21.5 22.4 23.3
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

Table 57. Gross heating capacities (kW) TWA2014*D heat pump with TWE2014*B air handler at 6675 CFM (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor at Indicated Indoor Dry Bulb Temp (°C) at Indicated Indoor Dry Bulb Temp (°C)
Temp (°C) 15 21 24 27 15 21 24 27
-28 15.3 13.8 13.2 12.3 12.1 13.3 13.8 14.6
-25 17.6 16.0 15.1 14.5 12.4 13.6 14.1 14.9
-22 20.0 18.4 17.6 16.8 12.6 13.8 14.5 15.2
-19 22.6 21.0 20.1 19.5 12.9 14.1 14.8 15.6
-17 25.3 23.7 23.0 22.3 13.1 14.4 15.2 15.9
-14 28.2 26.7 26.0 25.3 13.4 14.8 15.5 16.3
-11 31.3 29.8 29.1 28.3 13.7 15.1 15.8 16.6
-8 34.6 33.1 32.3 31.5 13.9 15.3 16.1 16.9
-6 38.1 36.4 35.6 34.7 14.2 15.6 16.4 17.2
-3 41.7 39.9 39.0 38.1 14.5 15.9 16.7 17.5
0 45.4 43.5 42.6 41.6 14.8 16.2 17.0 17.8
3 49.1 47.1 46.1 45.1 15.1 16.5 17.3 18.1
6 52.9 50.8 49.7 48.6 15.4 16.9 17.6 18.4
8 57.2 55.0 53.8 52.7 15.8 17.2 18.0 18.8
11 61.1 58.7 57.5 56.4 16.1 17.6 18.3 19.2
14 65.5 63.0 61.7 60.5 16.5 18.0 18.7 19.6
17 70.0 67.4 66.0 64.7 16.9 18.4 19.2 20.0
19 74.6 71.8 70.4 69.0 17.4 18.8 19.6 20.4
22 79.2 76.3 74.8 73.4 17.8 19.3 20.1 20.9
Notes:
1. Net heating capacity and power include indoor fan heat at AHRI ESP. To obtain net heating at other conditions, subtract fan heat at this condition
and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70% outdoor
relative humidity and demand defrost cycle.

56 SSP-PRC024K-EN
Performance Data

Fan Performance
Table 58. Evaporator fan performance — TWE051 — air handler (IP)
External Static Pressure (Inches of Water Gauge)
0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
0.5 HP Standard Motor 1 HP High Static Motor
1400 612 0.20 674 0.24 731 0.29 786 0.34 840 0.39 891 0.45 941 0.51 989 0.58 1034 0.65 1077 0.72 1117 0.78
1500 647 0.24 705 0.29 760 0.34 812 0.39 863 0.44 912 0.50 960 0.56 1006 0.63 1051 0.70 1094 0.77 — —
1600 683 0.28 738 0.33 790 0.38 840 0.44 888 0.50 936 0.56 980 0.62 1025 0.69 1070 0.76 1111 0.83 — —
1700 719 0.33 771 0.38 821 0.44 869 0.50 914 0.56 959 0.62 1003 0.68 1047 0.75 1089 0.82 — — — —
1800 756 0.39 804 0.44 853 0.50 898 0.56 942 0.62 985 0.69 1028 0.75 1068 0.82 1109 0.89 — — — —
1900 792 0.45 838 0.51 884 0.57 928 0.63 971 0.69 1012 0.76 1052 0.83 1092 0.90 — — — — — —
2000 829 0.52 873 0.58 917 0.64 959 0.71 1000 0.77 1040 0.84 1079 0.91 1117 0.98 — — — — — —
2100 866 0.60 908 0.66 950 0.72 991 0.79 1030 0.86 1069 0.93 1106 1.00 1144 1.08 — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full rsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

Table 59. Evaporator fan performance — TWE051 — air handler (SI)


External Static Pressure (Pascals)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
0.38 kW Standard Motor .75 kW High Static Motor
2379 612 0.15 674 0.18 731 0.22 786 0.25 840 0.29 891 0.34 941 0.38 989 0.43 1034 0.48 1077 0.53 1117 0.58
2549 647 0.18 705 0.21 760 0.25 812 0.29 863 0.33 912 0.37 960 0.42 1006 0.47 1051 0.52 1094 0.58 — —
2719 683 0.21 738 0.25 790 0.29 840 0.33 888 0.37 936 0.42 980 0.46 1025 0.51 1070 0.57 1111 0.62 — —
2889 719 0.25 771 0.29 821 0.33 869 0.37 914 0.41 959 0.46 1003 0.51 1047 0.56 1089 0.61 — — — —
3059 756 0.29 804 0.33 853 0.37 898 0.42 942 0.46 985 0.51 1028 0.56 1068 0.61 1109 0.66 — — — —
3228 792 0.34 838 0.38 884 0.42 928 0.47 971 0.52 1012 0.57 1052 0.62 1092 0.67 — — — — — —
3398 829 0.39 873 0.43 917 0.48 959 0.53 1000 0.58 1040 0.63 1079 0.68 1117 0.73 — — — — — —
3568 866 0.45 908 0.49 950 0.54 991 0.59 1030 0.64 1069 0.69 1106 0.75 1144 0.80 — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

SSP-PRC024K-EN 57
Performance Data

Table 60. Evaporator fan performance — TWE072 — air handler (IP)


External Static Pressure (Inches of Water Gauge)

0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

1 HP Standard Motor 1.5 HP High Static Motor


1600 — — — — 550 0.33 629 0.39 695 0.46 747 0.52 807 0.72 854 0.77 887 0.80 906 0.81 912 0.82
1700 — — — — 559 0.35 634 0.43 697 0.48 751 0.61 809 0.75 857 0.81 894 0.84 920 0.87 985 1.07
1800 — — — — 569 0.38 640 0.46 701 0.53 756 0.64 813 0.77 861 0.85 901 0.90 952 1.07 991 1.14
1900 — — — — 578 0.41 647 0.50 707 0.58 761 0.68 817 0.81 866 0.90 912 1.01 957 1.13 996 1.21
2000 — — 522 0.34 590 0.45 654 0.52 711 1 768 0.73 821 0.84 870 0.95 917 1.06 962 1.20 1002 1.27
2100 — — 534 0.38 599 0.48 662 0.59 719 0.67 774 0.77 826 0.88 875 1.00 921 1.11 968 1.27 1007 1.35
2200 474 0.30 547 0.43 610 0.52 671 0.64 727 0.72 781 0.82 832 0.93 881 1.06 926 1.17 973 1.33 1013 1.42
2300 489 0.35 560 0.47 621 0.56 680 0.69 736 0.77 788 0.87 838 0.98 886 1.12 932 1.23 979 1.40 1018 1.50
2400 505 0.41 573 0.52 632 0.61 690 0.74 745 0.83 796 0.93 844 1.04 893 1.18 937 1.30 969 1.47 1023 1.57
External Static Pressure (Inches of Water Gauge)

1.20" 1.30" 1.40" 1.50" 1.60" 1.70"


CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Ultra High Static Motor
1600 1018 1.09 1060 1.21 1094 1.29 — — — — — —
1700 1024 1.16 1065 1.28 1099 1.37 — — — — — —
1800 1029 1.24 1070 1.35 1105 1.45 — — — — — —
1900 1035 1.31 1075 1.42 1110 1.53 — — — — — —
2000 1040 1.38 1080 1.50 1116 1.61 — — — — — —
2100 1046 1.46 1085 1.58 1122 1.69 — — — — — —
2200 1052 1.54 1090 1.66 — — — — — — — —
2300 1057 1.62 1095 1.74 — — — — — — — —
2400 1063 1.70 1101 1.82 — — — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

58 SSP-PRC024K-EN
Performance Data

Table 61. Evaporator fan performance — TWE072 — air handler (SI)


External Static Pressure (Pascals)

25 50 75 100 125 150 174 199 224 249 274


m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW

.75 kW Standard Motor 1.12 kW High Static Motor 1.5 kW Ultra High Static Motor
2718 — — — — 550 0.25 629 0.29 695 0.34 747 0.39 807 0.54 854 0.58 887 0.60 906 0.61 912 0.61
2888 — — — — 559 0.26 634 0.32 697 0.36 751 0.45 809 0.56 857 0.61 894 0.62 920 0.65 985 0.80
3058 — — — — 569 0.29 640 0.34 701 0.39 756 0.48 813 0.58 861 0.64 901 0.67 952 0.80 991 0.85
3228 — — — — 578 0.31 647 0.37 707 0.43 761 0.51 817 0.60 866 0.67 912 0.75 957 0.84 996 0.90
3398 — — 522 0.26 590 0.34 654 0.39 711 0.46 768 0.54 821 0.63 870 0.71 917 0.79 962 0.89 1002 0.95
3568 — — 534 0.29 599 0.36 662 0.44 719 0.50 774 0.57 826 0.66 875 0.75 921 0.83 968 0.94 1007 1.01
3738 474 0.22 547 0.32 610 0.39 671 0.47 727 0.54 781 0.61 832 0.69 881 0.79 926 0.87 973 1.00 1013 1.06
3908 489 0.26 560 0.35 621 0.42 680 0.51 736 0.58 788 0.65 838 0.73 886 0.83 932 0.92 979 1.05 1018 1.12
4078 505 0.30 573 0.39 632 0.46 690 0.55 745 0.62 796 0.69 844 0.78 893 0.88 937 0.97 969 1.10 1023 1.17
External Static Pressure (Pascals)

299 324 349


m3/hr RPM kW RPM kW RPM kW
1.5 kW Ultra High Static Motor
2718 1018 0.81 1060 0.90 1094 0.96
2888 1024 0.87 1065 0.95 1099 1.02
3058 1029 0.92 1070 1.00 1105 1.08
3228 1035 0.98 1075 1.06 1110 1.14
3398 1040 1.03 1080 1.12 1116 1.20
3568 1046 1.09 1085 1.18 1122 1.26
3738 1052 1.15 1090 1.24 — —
3908 1057 1.21 1095 1.30 — —
4078 1063 1.27 1101 1.36 — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

SSP-PRC024K-EN 59
Performance Data

Table 62. Evaporator fan performance — TWE076 — air handler (IP)


External Static Pressure (Inches of Water Gauge)
0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor 1.5 HP High Static Motor 2 HP Ultra High Static Motor
2000 — — 522 0.34 590 0.44 654 0.52 711 0.62 768 0.73 821 0.84 870 0.95 916 1.06 959 1.16 1001 1.27
2125 — — 537 0.39 604 0.48 664 0.58 721 0.68 775 0.78 828 0.90 877 1.01 923 1.13 966 1.25 1009 1.36
2250 481 0.33 553 0.44 617 0.53 675 0.64 731 0.74 784 0.84 834 0.96 884 1.09 929 1.21 973 1.33 1016 1.46
2375 501 0.39 569 0.49 631 0.59 688 0.70 742 0.81 794 0.91 842 1.03 891 1.16 937 1.29 981 1.42 1022 1.55
2500 521 0.47 585 0.55 646 0.65 701 0.77 754 0.89 804 0.99 852 1.11 898 1.23 944 1.37 987 1.51 1028 1.64
2625 540 0.53 602 0.61 661 0.72 715 0.84 767 0.97 816 1.08 862 1.19 908 1.32 950 1.45 994 1.60 1036 1.74
2750 559 0.60 619 0.66 677 0.80 729 0.91 780 1.05 827 1.17 872 1.29 916 1.41 960 1.55 1001 1.69 1043 1.84
2875 579 0.67 636 0.72 692 0.88 744 1.00 793 1.13 840 1.27 885 1.40 928 1.52 969 1.65 1009 1.79 1049 1.94
3000 599 0.74 654 0.79 709 0.96 760 1.09 807 1.22 852 1.36 896 1.51 939 1.63 980 1.76 1019 1.90 1057 2.05
External Static Pressure (Inches of Water Gauge)
1.20" 1.30" 1.40" 1.50" 1.60" 1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Ultra High Static Motor
2000 1040 1.38 1080 1.50 1116 1.61 — — — — — —
2125 1048 1.48 1085 1.59 1123 1.71 — — — — — —
2250 1054 1.58 1093 1.70 — — — — — — — —
2375 1062 1.68 1099 1.80 — — — — — — — —
2500 1068 1.78 1107 1.92 — — — — — — — —
2625 1075 1.88 1113 2.02 — — — — — — — —
2750 1083 1.99 — — — — — — — — — —
2875 1090 2.10 — — — — — — — — — —
3000 1097 2.21 — — — — — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

60 SSP-PRC024K-EN
Performance Data

Table 63. Evaporator fan performance — TWE076 — air handler (SI)


External Static Pressure (Pascals)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
.75 kW Standard Motor 1.12 kW High Static Motor 1.5 kW Ultra High Static Motor
3398 — 0.18 522 0.25 590 0.33 654 0.39 711 0.46 768 0.54 821 0.62 870 0.71 916 0.79 959 0.87 1001 0.95
3611 — 0.21 537 0.29 604 0.36 664 0.43 721 0.50 775 0.58 828 0.67 877 0.76 923 0.84 966 0.93 1009 1.02
3823 481 0.24 553 0.32 617 0.40 675 0.48 731 0.55 784 0.63 834 0.72 884 0.81 929 0.90 973 0.99 1016 1.09
4036 501 0.29 569 0.36 631 0.44 688 0.53 742 0.60 794 0.68 842 0.77 891 0.87 937 0.96 981 1.06 1022 1.15
4248 521 0.35 585 0.41 646 0.49 701 0.57 754 0.66 804 0.74 852 0.83 898 0.92 944 1.02 987 1.12 1028 1.22
4460 540 0.40 602 0.46 661 0.54 715 0.62 767 0.72 816 0.81 862 0.89 908 0.99 950 1.08 994 1.19 1036 1.30
4673 559 0.45 619 0.50 677 0.59 729 0.68 780 0.78 827 0.88 872 0.96 916 1.05 960 1.15 1001 1.26 1043 1.37
4885 579 0.50 636 0.54 692 0.65 744 0.74 793 0.84 840 0.95 885 1.04 928 1.13 969 1.23 1009 1.33 1049 1.45
5098 599 0.55 654 0.59 709 0.72 760 0.81 807 0.91 852 1.02 896 1.12 939 1.22 980 1.32 1019 1.42 1057 1.53
External Static Pressure (Pascals)
299 324 349
m3/hr RPM kW RPM kW RPM kW
1.5 kW Ultra High Static Motor
3398 1040 1.03 1080 1.12 1116 1.20
3611 1048 1.10 1085 1.19 1123 1.28
3823 1054 1.18 1093 1.27 — —
4036 1062 1.25 1099 1.35 — —
4248 1068 1.33 1107 1.43 — —
4460 1075 1.40 1113 1.51 — —
4673 1083 1.49 — — — —
4885 1090 1.57 — — — —
5098 1097 1.65 — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

SSP-PRC024K-EN 61
Performance Data

Table 64. Evaporator fan performance — TWE101 — air handler (IP)


External Static Pressure (Inches of Water Gauge)
0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor 2 HP High Static Motor
2600 — — — — 523 0.53 563 0.61 601 0.69 638 0.75 673 0.83 707 0.91 739 0.99 772 1.08 802 1.17
2775 — — 499 0.55 541 0.62 580 0.69 617 0.78 653 0.86 687 0.93 719 1.01 750 1.09 782 1.18 812 1.27
2950 — — 519 0.63 560 0.71 598 0.79 634 0.87 668 0.96 701 1.05 732 1.12 763 1.21 793 1.30 822 1.39
3125 499 0.70 540 0.71 579 0.82 616 0.90 651 0.98 684 1.08 716 1.17 747 1.26 777 1.34 805 1.42 834 1.52
3300 522 0.81 561 0.81 600 0.94 635 1.02 669 1.10 701 1.20 731 1.30 762 1.40 791 1.49 819 1.57 847 1.66
3475 545 0.93 582 0.93 620 1.07 654 1.15 687 1.24 718 1.33 748 1.43 777 1.54 806 1.65 834 1.74 860 1.83
3650 568 1.05 604 1.09 640 1.18 674 1.30 706 1.39 736 1.48 766 1.58 794 1.69 821 1.81 848 1.91 874 2.01
3825 592 1.19 628 1.27 661 1.30 694 1.46 725 1.55 754 1.65 783 1.75 810 1.85 838 1.98 864 2.09 890 2.20
4000 615 1.34 652 1.47 682 1.45 714 1.63 745 1.73 774 1.83 801 1.93 829 2.04 855 2.16 880 2.28 — —
External Static Pressure (Inches of Water Gauge)
1.20" 1.30" 1.40" 1.50" 1.60" 1.70" 1.80" 1.90"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static Motor w/ Field Supplied Sheave & Belt
2600 832 1.25 860 1.34 887 1.43 914 1.52 939 1.6 964 1.69 988 1.77 1011 1.86
2775 841 1.37 870 1.46 897 1.56 923 1.65 949 1.74 973 1.83 997 1.93 1020 2.02
2950 851 1.49 879 1.59 906 1.69 932 1.79 958 1.89 983 1.99 1006 2.08 1030 2.18
3125 861 1.61 889 1.72 916 1.82 943 1.93 967 2.04 992 2.14 1016 2.25 1040 2.36
3300 873 1.76 900 1.86 926 1.97 951 2.08 977 2.19 1002 2.31 — — — —
3475 886 1.92 912 2.02 938 2.13 962 2.24 — — — — — — — —
3650 900 2.10 926 2.20 950 2.31 — — — — — — — — — —
3825 — — — — — — — — — — — — — — — —
4000 — — — — — — — — — — — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

62 SSP-PRC024K-EN
Performance Data

Table 65. Evaporator fan performance — TWE101 — air handler (SI)


External Static Pressure (Pascals)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW Standard Motor 1.12 kW High Static Motor
4418 — — — — 523 0.40 563 0.45 601 0.51 638 0.56 673 0.62 707 0.68 739 0.74 772 0.80 802 0.87
4715 — — 499 0.41 541 0.46 580 0.52 617 0.58 653 0.64 687 0.69 719 0.75 750 0.81 782 0.88 812 0.95
5013 — — 519 0.47 560 0.53 598 0.59 634 0.65 668 0.72 701 0.78 732 0.84 763 0.90 793 0.97 822 1.03
5310 499 0.52 540 0.53 579 0.61 616 0.67 651 0.73 684 0.80 716 0.88 747 0.94 777 1.00 805 1.06 834 1.13
5607 522 0.60 561 0.60 600 0.70 635 0.76 669 0.82 701 0.89 731 0.97 762 1.04 791 1.11 819 1.17 847 1.24
5905 545 0.69 582 0.70 620 0.80 654 0.86 687 0.92 718 0.99 748 1.07 777 1.15 806 1.23 834 1.30 860 1.36
6202 568 0.79 604 0.81 640 0.88 674 0.97 706 1.03 736 1.10 766 1.18 794 1.26 821 1.35 848 1.43 874 1.50
6499 592 0.89 628 0.95 661 0.97 694 1.09 725 1.16 754 1.23 783 1.30 810 1.38 838 1.47 864 1.56 890 1.64
6797 615 1.00 652 1.10 682 1.08 714 1.22 745 1.29 774 1.36 801 1.44 829 1.52 855 1.61 880 1.70 905 1.79
External Static Pressure (Pascals)
299 324 349 374 398 423 448 473
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW High Static Motor w/ Field Supplied Sheave & Belt
4418 832 0.93 860 1.00 887 1.06 914 1.13 939 1.19 964 1.26 988 1.32 1011 1.39
4715 841 1.02 870 1.09 897 1.16 923 1.23 949 1.30 973 1.37 997 1.44 1020 1.50
5013 851 1.11 879 1.18 906 1.26 932 1.33 958 1.41 983 1.48 1006 1.55 1030 1.63
5310 861 1.20 889 1.28 916 1.36 943 1.44 967 1.52 992 1.60 1016 1.68 1040 1.76
5607 873 1.31 900 1.39 926 1.47 951 1.55 977 1.63 1002 1.72 — — — —
5905 886 1.43 912 1.51 938 1.59 962 1.67 986 1.75 — — — — — —
6202 900 1.57 926 1.64 950 1.72 975 1.81 998 1.89 — — — — — —
6499 915 1.72 939 1.79 963 1.87 987 1.95 1010 2.04 — — — — — —
6797 929 1.88 953 1.96 977 2.03 1000 2.11 1023 2.20 — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

SSP-PRC024K-EN 63
Performance Data

Table 66. Evaporator fan performance —TWE126 — air handler (IP)


External Static Pressure (Inches of Water Gauge)
0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP Standard Motor w/ 2 HP High Static
1.5 HP Standard Motor Field Supplied Sheave & Belt Motor
3200 — — — — 515 0.51 565 0.63 601 0.71 638 0.81 678 0.93 718 1.06 759 1.21 794 1.35 826 1.49
3400 — — 472 0.46 528 0.57 578 0.69 617 0.80 650 0.89 686 1.00 724 1.13 762 1.27 800 1.42 834 1.57
3600 — — 486 0.51 541 0.63 590 0.76 633 0.89 666 0.98 697 1.08 732 1.20 767 1.34 804 1.49 840 1.65
3800 — — 500 0.57 554 0.70 601 0.82 646 0.97 682 1.09 712 1.19 742 1.29 776 1.43 810 1.57 843 1.72
4000 — — 515 0.64 567 0.78 614 0.91 658 1.05 698 1.20 728 1.31 756 1.41 786 1.53 817 1.66 849 1.82
4200 477 0.58 531 0.71 581 0.85 627 1.00 669 1.13 710 1.29 744 1.43 772 1.55 799 1.65 827 1.78 858 1.93
4400 494 0.65 546 0.79 595 0.94 640 1.09 682 1.23 722 1.39 758 1.55 789 1.69 814 1.80 840 1.92 867 2.05
4600 513 0.73 563 0.87 609 1.03 653 1.19 695 1.34 732 1.48 771 1.66 804 1.83 831 1.96 856 2.08 880 2.20
4800 531 0.82 579 0.96 624 1.13 667 1.29 707 1.45 745 1.60 783 1.77 817 1.96 847 2.12 872 2.25 896 2.37
External Static Pressure (Inches of Water Gauge)
1.20" 1.30" 1.40" 1.50" 1.60" 1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static
Motor 3 HP Ultra High Static Motor
3200 857 1.63 887 1.78 916 1.93 943 2.08 970 2.23 996 2.39
3400 865 1.72 895 1.88 924 2.03 952 2.19 978 2.35 1003 2.50
3600 873 1.81 903 1.97 931 2.13 959 2.29 986 2.46 1012 2.62
3800 877 1.89 912 2.08 940 2.24 967 2.41 994 2.58 — —
4000 882 1.98 915 2.16 947 2.34 976 2.53 1002 2.70 — —
4200 888 2.08 919 2.25 950 2.44 980 2.63 1010 2.82 — —
4400 896 2.20 925 2.37 955 2.55 985 2.73 1013 2.92 — —
4600 906 2.34 934 2.50 961 2.67 989 2.85 — — — —
4800 918 2.50 944 2.65 970 2.81 996 2.98 — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will
not be affected.

64 SSP-PRC024K-EN
Performance Data

Table 67. Evaporator fan performance — TWE126 — air handler (SI)


External Static Pressure (Pascals)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.12 kW Standard Motor w/ 1.49 kW High Static
1.12 kW Standard Motor
Field Supplied Sheave & Belt Motor
5437 — — — — 515 0.38 565 0.47 601 0.53 638 0.60 678 0.69 718 0.79 759 0.90 794 1.01 826 1.11
5777 — — 472 0.34 528 0.42 578 0.52 617 0.60 650 0.66 686 0.74 724 0.84 762 0.94 800 1.06 834 1.17
6117 — — 486 0.38 541 0.47 590 0.56 633 0.66 666 0.73 697 0.81 732 0.90 767 1.00 804 1.11 840 1.23
6457 — — 500 0.43 554 0.52 601 0.61 646 0.72 682 0.81 712 0.89 742 0.97 776 1.06 810 1.17 843 1.29
6797 — — 515 0.48 567 0.58 614 0.68 658 0.78 698 0.89 728 0.98 756 1.05 786 1.14 817 1.24 849 1.35
7137 477 0.43 531 0.53 581 0.64 627 0.74 669 0.84 710 0.96 744 1.07 772 1.15 799 1.23 827 1.33 858 1.44
7476 494 0.48 546 0.59 595 0.70 640 0.81 682 0.92 722 1.03 758 1.16 789 1.26 814 1.34 840 1.43 867 1.53
7816 513 0.54 563 0.65 609 0.77 653 0.88 695 1.00 732 1.10 771 1.24 804 1.36 831 1.46 856 1.55 880 1.64
8156 531 0.61 579 0.72 624 0.84 667 0.96 707 1.08 745 1.19 783 1.32 817 1.46 847 1.58 872 1.68 896 1.77
External Static Pressure (Pascals)
299 324 349 374 398 423
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.49 kW High Static
2.24 kW Ultra High Static Motor
Motor
5437 857 1.22 887 1.33 916 1.44 943 1.55 970 1.66 996 1.78
5777 865 1.29 895 1.40 924 1.51 952 1.63 978 1.75 1003 1.87
6117 873 1.35 903 1.47 931 1.59 959 1.71 986 1.83 1012 1.96
6457 877 1.41 912 1.55 940 1.67 967 1.80 994 1.92 — —
6797 882 1.48 915 1.61 947 1.75 976 1.88 1002 2.01 — —
7137 888 1.55 919 1.68 950 1.82 980 1.96 1010 2.11 — —
7476 896 1.64 925 1.76 955 1.90 985 2.04 1013 2.18 — —
7816 906 1.74 934 1.86 961 1.99 989 2.12 — — — —
8156 918 1.86 944 1.97 970 2.10 996 2.22 — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will not be
affected.

SSP-PRC024K-EN 65
Performance Data

Table 68. Evaporator fan performance —TWE156 — air handler (IP)


External Static Pressure (Inches of Water Gauge)
0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor w/ Field Supplied 1.5 HP Standard Motor w/ 2 HP High Static
Sheave & Belt Field Supplied Sheave & Belt Motor
4000 428 0.5 482 0.62 531 0.72 576 0.84 621 0.98 663 1.11 701 1.25 737 1.38 771 1.51 803 1.64 833 1.77
4250 448 0.58 499 0.71 546 0.82 590 0.94 633 1.08 674 1.22 712 1.37 748 1.51 782 1.65 814 1.79 845 1.93
4500 468 0.68 517 0.81 563 0.93 605 1.05 646 1.19 686 1.34 724 1.50 760 1.65 793 1.80 825 1.95 855 2.09
4750 488 0.78 535 0.91 579 1.06 621 1.18 660 1.32 698 1.46 735 1.63 772 1.79 805 1.95 837 2.11 867 2.27
5000 509 0.90 554 1.03 596 1.19 637 1.32 675 1.46 712 1.61 748 1.77 783 1.94 817 2.11 848 2.28 878 2.44
5250 530 1.02 573 1.16 614 1.32 653 1.47 691 1.61 726 1.76 760 1.92 795 2.10 828 2.28 859 2.45 890 2.64
5500 551 1.16 593 1.31 632 1.47 670 1.64 706 1.78 741 1.93 774 2.09 807 2.26 840 2.46 871 2.64 902 2.83
5750 572 1.32 612 1.47 651 1.63 687 1.81 722 1.97 757 2.12 789 2.28 821 2.45 852 2.64 883 2.84 912 3.03
6000 593 1.48 632 1.64 670 1.81 705 1.99 739 2.17 772 2.32 804 2.48 835 2.66 865 2.84 895 3.04 924 3.24
External Static Pressure (Inches of Water Gauge)
1.20" 1.30" 1.40" 1.50" 1.60" 1.70"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP High Static
Motor 3 HP Ultra High Static Motor
4000 863 1.9 891 2.03 919 2.15 944 2.28 970 2.40 994 2.53
4250 874 2.07 902 2.20 928 2.33 955 2.47 981 2.61 1004 2.74
4500 884 2.24 913 2.38 939 2.53 966 2.68 991 2.82 1015 2.96
4750 895 2.42 924 2.58 951 2.74 977 2.88 1002 3.04 — —
5000 907 2.61 934 2.77 962 2.94 — — — — — —
5250 918 2.81 946 2.98 973 3.16 — — — — — —
5500 931 3.02 958 3.20 — — — — — — — —
5750 941 3.23 — — — — — — — — — —
6000 — — — — — — — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to
operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan motors as
shown in our tabular data will not result in nuisance tripping or premature motor failure. Our product's warranty will
not be affected.

66 SSP-PRC024K-EN
Performance Data

Table 69. Evaporator fan performance — TWE156 — air handler (SI)


External Static Pressure (Pascals)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1.49 kW Standard Motor w/
1.49 kW Standard Motor 2.24 kW High Static Motor
Field Supplied Sheave & Belt
6797 428 0.37 482 0.46 531 0.54 576 0.63 621 0.73 663 0.83 701 0.93 737 1.03 771 1.13 803 1.22 833 1.32
7222 448 0.43 499 0.53 546 0.61 590 0.70 633 0.80 674 0.91 712 1.02 748 1.13 782 1.23 814 1.33 845 1.44
7646 468 0.50 517 0.60 563 0.70 605 0.79 646 0.89 686 1.00 724 1.12 760 1.23 793 1.34 825 1.45 855 1.56
8071 488 0.58 535 0.68 579 0.79 621 0.88 660 0.98 698 1.09 735 1.21 772 1.34 805 1.46 837 1.57 867 1.69
8496 509 0.67 554 0.77 596 0.88 637 0.99 675 1.09 712 1.20 748 1.32 783 1.45 817 1.58 848 1.70 878 1.82
8921 530 0.76 573 0.87 614 0.99 653 1.10 691 1.20 726 1.31 760 1.43 795 1.57 828 1.70 859 1.83 890 1.97
9346 551 0.87 593 0.97 632 1.10 670 1.22 706 1.33 741 1.44 774 1.56 807 1.69 840 1.83 871 1.97 902 2.11
9770 572 0.98 612 1.09 651 1.22 687 1.35 722 1.47 757 1.58 789 1.70 821 1.83 852 1.97 883 2.11 912 2.26
10195 593 1.11 632 1.22 670 1.35 705 1.49 739 1.61 772 1.73 804 1.85 835 1.98 865 2.12 895 2.27 924 2.42
External Static Pressure (Pascals)
299 324 349 374 398 423
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 kW High Static Motor w/ Field Supplied Sheave & Belt
6797 863 1.42 891 1.51 919 1.61 944 1.70 970 1.79 994 1.88
7222 874 1.54 902 1.64 928 1.74 955 1.84 981 1.95 1004 2.04
7646 884 1.67 913 1.78 939 1.88 966 2.00 991 2.10 1015 2.21
8071 895 1.80 924 1.92 951 2.04 977 2.15 1002 2.26 — —
8496 907 1.95 934 2.07 962 2.19 — — — — — —
8921 918 2.09 946 2.22 973 2.35 — — — — — —
9346 931 2.25 958 2.39 — — — — — — — —
9770 941 2.41 — — — — — — — — — —
10195 — — — — — — — — — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

SSP-PRC024K-EN 67
Performance Data

Table 70. Evaporator fan performance —TWE201 — air handler (IP)


External Static Pressure (Inches of Water Gauge)
0.10" 0.20" 0.30" 0.40" 0.50" 0.60" 0.70" 0.80" 0.90" 1.00" 1.10"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard
Motor w/ Field
Supplied
2 HP Low Static Motor 3 HP Standard Motor Sheave & Belt
5200 — — 531 0.83 580 0.96 627 1.09 666 1.21 707 1.37 748 1.54 787 1.71 825 1.88 864 2.06 902 2.24
5525 — — 551 0.96 599 1.10 644 1.23 684 1.37 722 1.51 760 1.68 799 1.87 834 2.04 872 2.23 909 2.42
5850 — — 572 1.10 619 1.25 662 1.39 703 1.54 738 1.68 774 1.84 810 2.02 846 2.22 880 2.40 916 2.60
6175 543 1.11 593 1.26 638 1.42 680 1.57 720 1.72 757 1.87 790 2.02 824 2.20 859 2.40 893 2.61 926 2.81
6500 566 1.28 614 1.43 659 1.61 699 1.77 737 1.92 775 2.08 807 2.24 839 2.40 871 2.59 904 2.80 936 3.02
6825 590 1.47 636 1.62 679 1.80 718 1.98 755 2.14 792 2.31 826 2.48 857 2.64 886 2.81 918 3.02 950 3.25
7150 614 1.67 658 1.83 700 2.02 738 2.21 774 2.38 809 2.55 844 2.73 875 2.90 903 3.07 932 3.26 962 3.47
7475 638 1.89 680 2.06 720 2.25 758 2.45 794 2.63 827 2.81 861 2.99 893 3.18 921 3.36 949 3.54 976 3.73
7800 662 2.13 702 2.31 742 2.50 779 2.71 814 2.91 846 3.09 879 3.28 910 3.48 940 3.67 967 3.86 993 4.04
External Static Pressure (Inches of Water Gauge)
1.20" 1.30" 1.40" 1.50" 1.60" 1.70" 1.80" 1.90"
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard
Motor w/ Field 5 HP Ultra High Static Motor
Supplied w/ Field Supplied Sheave &
Sheave & Belt 5 HP Ultra High Static Motor Belt
5200 937 2.42 972 2.59 1004 2.77 1036 2.95 1066 3.12 1095 3.29 1125 3.46 1152 3.63
5525 943 2.60 978 2.80 1012 2.99 1042 3.17 1072 3.35 1102 3.54 1132 3.73 1159 3.91
5850 951 2.80 984 3.00 1018 3.21 1050 3.41 1080 3.60 1109 3.80 1138 4.00 1166 4.19
6175 958 3.00 992 3.22 1024 3.43 1056 3.64 1086 3.86 1115 4.06 1143 4.27 — —
6500 967 3.22 998 3.44 1030 3.65 1063 3.89 1093 4.11 1122 4.33 1151 4.56 — —
6825 980 3.47 1010 3.69 1039 3.90 1069 4.13 1098 4.36 1129 4.61 1158 4.85 — —
7150 991 3.70 1021 3.94 1051 4.18 1078 4.41 1107 4.65 1135 4.88 1165 5.14 — —
7475 1005 3.97 1034 4.21 1062 4.46 1090 4.71 1117 4.94 1144 5.19 — — — —
7800 1019 4.24 1047 4.49 1074 4.74 1102 5.01 1128 5.25 1154 5.51 — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (MBh) = 3.15 x BHP.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

68 SSP-PRC024K-EN
Performance Data

Table 71. Evaporator fan performance — TWE201 — air handler (SI)


External Static Pressure (Pascals)
25 50 75 100 125 150 174 199 224 249 274
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
2.24 kW Standard
Motor w/ Field
1.49 kW Low Static Motor 2.24 kW Standard Motor
Supplied Sheave &
Belt
8836 — — 531 0.62 580 0.71 627 0.81 666 0.90 707 1.02 748 1.15 787 1.27 825 1.40 864 1.54 902 1.67
9388 — — 551 0.72 599 0.82 644 0.92 684 1.02 722 1.12 760 1.25 799 1.39 834 1.52 872 1.66 909 1.80
9940 — — 572 0.82 619 0.94 662 1.04 703 1.15 738 1.25 774 1.37 810 1.51 846 1.65 880 1.79 916 1.94
10493 543 0.83 593 0.94 638 1.06 680 1.17 720 1.29 757 1.40 790 1.51 824 1.64 859 1.79 893 1.94 926 2.09
11045 566 0.95 614 1.07 659 1.20 699 1.32 737 1.43 775 1.55 807 1.67 839 1.79 871 1.93 904 2.09 936 2.25
11597 590 1.09 636 1.21 679 1.34 718 1.48 755 1.59 792 1.72 826 1.85 857 1.97 886 2.09 918 2.25 950 2.42
12149 614 1.25 658 1.37 700 1.50 738 1.65 774 1.77 809 1.90 844 2.03 875 2.16 903 2.29 932 2.43 962 2.59
12702 638 1.41 680 1.54 720 1.68 758 1.83 794 1.96 827 2.09 861 2.23 893 2.37 921 2.51 949 2.64 976 2.79
13254 662 1.59 702 1.72 742 1.86 779 2.02 814 2.17 846 2.31 879 2.45 910 2.59 940 2.74 967 2.88 993 3.02
External Static Pressure (Pascals)
299 324 349 374 398 423 448
m3/hr RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
3.73 kW Ultra High 3.73 kW Ultra High Static Motor w/ Field Supplied
Static Motor Sheave & Belt
8836 937 1.80 972 1.94 1004 2.07 1036 2.20 1066 2.33 1095 2.45 1125 2.58
9388 943 1.94 978 2.09 1012 2.23 1042 2.36 1072 2.50 1102 2.64 1132 2.78
9940 951 2.09 984 2.24 1018 2.39 1050 2.54 1080 2.69 1109 2.83 — —
10493 958 2.24 992 2.40 1024 2.56 1056 2.72 1086 2.88 1115 3.03 — —
11045 967 2.40 998 2.56 1030 2.73 1063 2.90 1093 3.07 1122 3.23 — —
11597 980 2.59 1010 2.75 1039 2.91 1069 3.08 1098 3.26 1129 3.44 — —
12149 991 2.76 1021 2.94 1051 3.12 1078 3.29 1107 3.47 — — — —
12702 1005 2.96 1034 3.14 1062 3.32 1090 3.51 1117 3.69 — — — —
13254 1019 3.17 1047 3.35 1074 3.54 1102 3.74 1128 3.92 — — — —
Notes:
1. Data includes pressure drop due to wet coil and 1" filter.
2. Fan motor heat (kW) = 1.238 x kW.
3. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our product's warranty will not be affected.

SSP-PRC024K-EN 69
Performance Data

Table 72. Low static fan motors - standard air handlers


Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 541
1 511 Variable Pitch (2.4 - 3.4 Fixed Pitch (9.5 Inch
Standard Motor
Inch Pitch Diameter), Pitch Diameter),
with Field Supplied 2 464
TWE156 0.875 Inch Bore, Single 1.4375 Inch Bore, Browning AX59
Components 3 417
Groove, Browning Single Groove,
2 HP (1.5 kW) 4 370 1VL40 Browning BK105
5 391
0 712
1 677
Low Static Motor 2 641
TWE201 N/A N/A N/A
2 HP (1.5 kW) 3 605
4 569
5 533

Table 73. Standard fan motors - standard air handlers


Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 892
1 833
Standard Motor 2 773
TWE051 N/A N/A N/A
.5 HP (.38 kW) 3 714
4 654
5 595
0 706
1 659
Standard Motor 2 612
TWE072 N/A N/A N/A
1 HP (.75 kW) 3 565
4 518
5 471
0 706
1 659
Standard Motor 2 612
TWE076 N/A N/A N/A
1 HP (.75 kW) 3 565
4 518
5 471
0 682
1 644
Standard Motor 2 606
TWE101 N/A N/A N/A
1.5 HP (1.13 kW) 3 568
4 530
5 492
0 640
1 604
Standard Motor 2 569
TWE126 N/A N/A N/A
1.5 HP (1.13 kW) 3 533
4 498
5 462
0 704
1 676
2 648
Standard Motor
TWE156 3 620 N/A N/A N/A
2 HP (1.5 kW)
4 592
5 565
6 537

70 SSP-PRC024K-EN
Performance Data

Table 73. Standard fan motors - standard air handlers (continued)


Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 805
1 777
2 749
Standard Motor
TWE201 3 721 N/A N/A N/A
3 HP (2.25 kW)
4 693
5 665
6 637

Table 74. High static fan motors - standard air handlers


Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 1122
1 1066
High Static Motor 2 1010
TWE051 N/A N/A N/A
1 HP (.75kW) 3 954
4 898
5 842
0 912
1 866
High Static Motor 2 820
TWE072 N/A N/A N/A
1.5 HP (1.13 kW) 3 775
4 729
5 683
0 912
1 866
High Static Motor 2 820
TWE076 N/A N/A N/A
1.5 HP (1.13 kW) 3 775
4 729
5 683
0 810
1 769
High Static Motor 2 729
TWE101 N/A N/A N/A
2 HP (1.5 kW) 3 688
4 648
5 607
0 941
1 894 Variable Pitch (2.8 - 3.8 Fixed Pitch (6.0 Inch
High Static Motor
Inch Pitch Diameter), Pitch Diameter),
with Field Supplied 2 847
TWE101 0.875 Inch Bore, 1.0 Inch Bore, Browning A50
Components 3 800 Single Groove, Single Groove,
2 HP (1.5 kW) 4 753 Browning 1VP44 Browning AK64
5 706
0 761
1 718 Variable Pitch (2.4 - 3.4 Fixed Pitch (6.7 Inch
Standard Motor
Inch Pitch Diameter), Pitch Diameter),
with Field Supplied 2 671
TWE126 0.875 Inch Bore, 1.4375 Inch Bore, Browning A55
Components 3 624 Single Groove, Single Groove,
1.5 HP (1.13 kW) 4 577 Browning 1VL40 Browning AK71
5 549
0 912
1 866
High Static Motor 2 825
TWE126 N/A N/A N/A
2 HP (1.5 kW) 3 785
4 744
5 683

SSP-PRC024K-EN 71
Performance Data

Table 74. High static fan motors - standard air handlers (continued)
Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 853
1 824
2 794
High Static Motor
TWE156 3 765 N/A N/A N/A
3.5 HP (2.6 kW)
4 735
5 705
6 676
0 1014
1 979 Variable Pitch (3.4 - 4.4 Fixed Pitch (6.6 Inch
High Static Motor 2 932 Inch Pitch Diameter), Pitch Diameter),
with Field Supplied
TWE156 3 885 1.125 Inch Bore, 1.4375 Inch Bore, Browning BX58
Components
4 838 Single Groove, Single Groove,
3.5 HP (2.6 kW)
5 803 Browning 1VP50 Browning BK72
6 803
0 909
1 878 Variable Pitch (2.8 - 3.8 Fixed Pitch (10.4 Inch
Standard Motor 2 846 Inch Pitch Diameter), Pitch Diameter),
with Field Supplied
TWE201 3 815 1.125 Inch Bore, 1.4375 Inch Bore, Browning BX62
Components
4 783 Single Groove, Single Groove,
3 HP (2.25 kW)
5 751 Browning 1VP50 Browning BK80
6 720

Table 75. Ultra high static fan motors - standard air handlers
Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 1122
1 1034
2 946
Ultra High Static Motor
TWE072 3 859 N/A N/A N/A
2 HP (1.5 kW)
4 771
5 683
— —
0 1122
1 1034
2 946
Ultra High Static Motor
TWE076 3 859 N/A N/A N/A
2 HP (1.5 kW)
4 771
5 683
— —
0 1014
1 979
2 944
Ultra High Static Motor
TWE126 3 909 N/A N/A N/A
3.5 HP (2.6 kW)
4 874
5 838
6 803
0 1078
1 1036
2 993
Ultra High Static Motor
TWE201 3 950 N/A N/A N/A
5 HP (3.75 kW)
4 907
5 864
6 822

72 SSP-PRC024K-EN
Performance Data

Table 75. Ultra high static fan motors - standard air handlers (continued)
Motor Required Field Supplied Components
Sheave Nominal
Model Motor
Turns RPM Motor Sheave Blower Sheave Belt
Open
0 1096
1 1067 Variable Pitch (2.8 - 3.8 Fixed Pitch (10.4 Inch
Ultra High Static Motor 2 1036 Inch Pitch Diameter), Pitch Diameter),
with Field Supplied
TWE201 3 1004 1.125 Inch Bore, Single 1.4375 Inch Bore, Browning BX62
Components
4 973 Groove, Browning Single Groove,
5 HP (3.75 kW)
1VP44 Browning BK110
5 941
6 926

Table 76. Discharge plenum and grille assembly throw distance — air handler — ft (m)
Unit Model Louver angle Deflection Position (ft) Louver angle Deflection Position (m)
CFM m3/h
No. Straight 20° 40° 55° Straight 20° 40° 55°
1800 3060 46 37 29 22 14.0 11.3 8.8 6.7
2000 3395 48 43 33 24 14.6 13.1 10.1 7.3
TWE051
2200 3737 51 50 36 25 15.5 15.2 11.0 7.6
2400 4074 44 58 41 28 13.4 17.7 12.5 8.5
1800 3061 47 34 28 24 14.0 10.3 8.3 8.0
2000 3400 49 37 30 26 14.7 11.2 9.0 8.3
TWE072
2200 3739 50 40 32 28 15.3 12.2 9.8 8.5
2400 4078 52 43 35 29 15.9 13.1 10.6 8.8
2250 3823 51 41 33 28 15.4 12.4 10.0 8.6
2500 4249 53 45 36 30 16.2 13.6 10.9 9.0
TWE076
2750 4671 56 49 39 31 16.9 14.9 11.9 9.4
3000 5098 58 53 42 32 17.7 16.2 12.8 9.9
3025 5139 57 44 36 32 17.4 13.4 10.8 9.6
3350 5692 60 48 39 32 18.3 14.7 12.0 9.7
TWE101
3675 6245 63 52 43 33 19.3 16.0 13.2 10.0
4000 6795 67 57 47 35 20.3 17.3 14.4 10.5
3750 6370 44 27 25 38 13.4 8.1 7.5 11.7
4200 7137 45 31 28 48 13.7 9.5 8.5 14.5
TWE126
4650 7902 47 36 31 57 14.3 10.9 9.5 17.4
5100 8666 50 40 34 67 15.2 12.3 10.5 20.5
4500 7644 46 34 30 22 14.1 10.5 9.2 6.6
5000 8497 49 39 34 25 14.9 12.0 10.3 7.6
TWE156
5500 9346 53 45 37 28 16.2 13.6 11.4 8.5
6000 10195 58 50 41 31 17.7 15.1 12.5 9.3
6000 10195 53 43 36 28 16.0 13.1 10.9 8.6
6680 11348 57 48 40 31 17.5 14.5 12.1 9.4
TWE201
7350 12488 62 52 44 33 18.8 16.0 13.3 10.0
8030 13645 65 57 47 35 19.8 17.4 14.5 10.5
Note: Throw distance values are based on a terminal velocity of 75 fpm (0.38 m/s). Throw distance values at other terminal velocities may be established
by multiplying throw distances in table above by throw factor as follows: for 50 FPM (0.25 m/s) terminal velocity, multiply by 1.50 throw factor; for
100 FPM (0.51 m/s) terminal velocity, multiply by 0.75 throw factor; for 150 FPM (0.76 m/s) terminal velocity, multiply by 0.50 throw factor.

SSP-PRC024K-EN 73
Performance Data

Table 77. Static pressure drop through accessories (inches if water column) — air handler
Discharge
Return Grille Plenum & Electric Heaters (kW)
Unit
Model CFM m3/h Grille
No. 5–10 15–20 25–30 35–50
in. wc Pascal in. wc Pascal
in. wc Pascal in. wc Pascal in. wc Pascal in. wc Pascal
1400 2379 0.09 23.60 0.16 41.10 0.06 16.20 0.05 13.70 0.09 23.60 — —
TWE051 1700 2889 0.14 34.90 0.24 60.60 0.09 23.90 0.08 20.20 0.14 34.90 — —
2000 3398 0.18 45.70 0.33 83.80 0.13 33.00 0.13 33.00 0.19 48.30 — —
1600 2718 0.03 9.51 0.11 28.91 0.03 7.47 0.03 7.47 0.06 14.94 0.06 14.94
TWE072 2000 3398 0.04 14.70 0.18 45.20 0.03 7.47 0.05 12.45 0.08 19.93 0.10 24.91
2400 4078 0.06 21.11 0.26 65.07 0.04 9.96 0.07 17.44 0.11 27.40 0.15 37.36
2000 3398 0.06 14.70 0.18 45.20 0.03 6.80 0.05 13.50 0.08 19.20 0.10 26.00
TWE076 2500 4248 0.09 22.90 0.28 70.60 0.04 10.60 0.08 21.20 0.12 30.00 0.16 40.60
3000 5098 0.13 33.00 0.40 101.60 0.06 15.20 0.12 30.50 0.17 43.20 0.23 58.40
2600 4418 0.05 11.70 0.28 72.10 0.04 10.10 0.09 21.80 0.13 31.90 0.17 43.60
TWE101 3300 5607 0.07 18.90 0.46 116.20 0.06 16.20 0.14 35.10 0.20 51.30 0.28 70.20
4000 6797 0.11 27.80 0.67 170.70 0.09 23.80 0.20 51.60 0.30 75.40 0.41 103.20
3200 5436 0.04 10.20 0.10 25.60 0.01 2.50 0.02 5.00 0.03 7.50 0.04 10.00
TWE126 4000 6797 0.06 15.90 0.16 39.90 0.02 5.00 0.03 7.50 0.04 10.00 0.06 15.00
4800 8156 0.09 22.90 0.23 57.50 0.03 7.50 0.03 7.50 0.06 15.00 0.08 20.00
4000 6797 0.07 16.90 0.15 38.40 0.02 3.80 0.03 6.80 0.05 13.50 0.08 19.20
TWE156 5000 8496 0.10 26.50 0.24 60.00 0.04 10.60 0.04 10.60 0.08 21.20 0.12 30.00
6000 10195 0.15 38.10 0.34 86.40 0.06 15.20 0.06 15.20 0.12 30.50 0.17 43.20
5200 8836 0.07 18.40 0.30 73.80 0.04 10.60 0.04 10.60 0.08 21.10 0.13 31.70
TWE201 6650 11300 0.12 30.20 0.46 114.90 0.07 17.30 0.07 17.30 0.14 34.50 0.21 51.80
7800 13254 0.16 41.50 0.63 156.10 0.10 23.80 0.10 23.80 0.19 47.50 0.29 71.30
Notes:
1. Return air filter ESP included in Fan Performance Table data.
2. On discharge plenum and grille - at louver opening angle of 42 degrees. For ESP at other angle openings, see accessory installation
instruction.

Table 78. Auxiliary electric heat capacity — air handler


Stage 1 Stage 2 Total
No. of
Unit Model No. Total kW Btu Btu Btu
Stages kW Input kW Input kW Input
Output Output Output
5.00 1 5.00 17,065 — — 5.00 17,065
TWE0514DA, 0724DB, 9.96 1 9.96 33,993 — — 9.96 33,993
0764DA/B, 1014DA/B 14.96 1 14.96 51,058 — — 14.96 51,058
24.92 2 14.96 51,058 9.96 33993 24.92 85,051
TWE0724DB, 0764DA/
34.88 2 19.92 67,987 14.96 51058 34.88 119,045
B, 1014DA/B
10.00 1 10.00 34,130 — — 10.00 34,130
TWE1264DB, 1564DB, 19.92 1 19.92 67,987 — — 19.92 67,987
2014DB 29.92 2 19.92 67,987 10.00 34130 29.92 102,117
49.84 2 29.92 102,117 19.92 67987 49.84 170,104

Note: Heaters are rated at 240V, 480V and 600V. For other than rated voltage, capacity = (Voltage/Related Voltage)2 x Rated Capacity

74 SSP-PRC024K-EN
Controls
ReliaTel
Zone Sensors are the building occupant’s comfort control devices. Zone sensors are required for
SZVAV applications. The following zone sensor options are available for units with ReliaTel
control.
Manual Changeover Manual/Automatic Manual/Automatic
(BAYSENS106*) Changeover (BAYSENS108*) Changeover (BAYSENS110*)

Heat, Cool or Off System Switch. Auto, Heat, Cool or Off System Auto, Heat, Cool or Off System
Fan Auto or Off Switch. One Switch. Fan Auto or Off Switch. Switch. Fan Auto or Off Switch.
temperature setpoint lever. Two temperature setpoint levers. Two temperature setpoint levers.
Status Indication LED lights,
System On, Heat, Cool, or
Service.

Integrated Comfort™ System Remote Sensor Wireless Zone Sensor Programmable Night Setback
(BAYSENS074*) (BAYSENS077*) (BAYSENS050*) (BAYSENS119*)

Sensor(s) available with optional Sensor(s) available for all zone LCD display that provides heat, Auto or manual changeover with
temperature adjustment and sensors to provide remote cool, auto or off. Includes two seven-day programming.
override buttons to provide sensing capabilities. temperature setpoints and a Keyboard selection of Heat, Cool,
central control through a Trane lockable setting with °F or °C Fan, Auto, EM Heat or On. All
Integrated Comfort™ system. indicators. sensors have System On, Heat,
Cool, Service LED/ indicators as
standard. Night Setback Sensors
have one (1) Occupied, one (1)
Un-occupied, and one (1)
Override program per day.

SSP-PRC024K-EN 75
Controls

Electromechanical
Non-Programmable Thermostats
TCONT200*** (1H/1C) TCONT401*** (2H/1C) TCONT402*** (3H/2C)

$ $
$
Filter/O D Fan Mode Filter/O D Fan Mode

FILTER FA N M O DE

Auto-changeover Backlit Display & Auto-changeover Backlit Display & Auto-changeover Backlit Display &
Keys Filter Reminder Keypad Lock Keys Filter Reminder Keypad Lock Keys Filter Reminder Keypad Lock
Outdoor Temp Sensor Available Outdoor Temp Sensor Included

Programmable Thermostats
TCONT600***(1H/1C) TCONT602***(2H/2C)

5/2 or 5/1/1 Programming Actual 5/2 or 5/1/1 Programming Actual


and Setpoint temps displayed and Setpoint temps displayed
simultaneously simultaneously

TCONT800*** (1H/1C) TCONT802*** (3H/2C) TCONT803*** (3H/2C)

MON TUE WED THU FRI SAT SUN MON TUE WED THU FRI SAT SUN MON TUE WED THU FRI SAT SUN

FAN FAN FAN


ON ON ON
HEAT HEAT HEAT
AUTO AUTO AUTO
CIRC CIRC CIRC

SYSTEM RESET CANCEL SYSTEM RESET CANCEL SYSTEM RESET CANCEL


EM HEAT PERIOD DEHUMIDIFIER EM HEAT PERIOD DEHUMIDIFIER EM HEAT PERIOD DEHUMIDIFIER
HEAT HEAT HEAT
OFF OFF OFF
COOL COOL COOL
COOL PM COOL PM COOL PM
AUTO AUTO AUTO

DONE EDIT WAKE LEAVE RETURN SLEEP CANCEL DONE EDIT WAKE LEAVE RETURN SLEEP CANCEL DONE EDIT WAKE LEAVE RETURN SLEEP CANCEL

Interactive touchscreen Large Interactive touchscreen Large Interactive touchscreen Large


display Real time clock display Real time clock display Real time clock Built-in
humidity sensor

Notes:
• All thermostats may be used with ReliaTel units.
• Thermostats may be used with ReliaTel-equipped Cooling units, but only when
matched with Standard Air Handlers (SZVAV Air Handlers excluded).

76 SSP-PRC024K-EN
Electrical Data
Heat Pump Condenser
Table 79. Electrical Characteristics — Motors — Heat Pumps — 50Hz
Compressor Motors Condenser Fan Motor
Unit Model Compressor 1 Compressor 2 Amps
Tons
Number Volts Phase RLA LRA RLA LRA No. Volts Phase FLA LRA
(Amps) (Amps) (Amps) (Amps) (Ea.) (Ea.)
TWA0604DA 380/415 3 10.6 74.0 N/A N/A 1 380/415 1 1.6 3.8
5
TWA0604DD 380/415 3 5.4 38.0 5.4 38.0 1 380/415 1 1.6 3.8
TWA0764DA 380/415 3 12.2 100.0 N/A N/A 1 380/415 1 1.6 3.8
6.25
TWA0764DD 380/415 3 6.0 43.0 6.0 43.0 1 380/415 1 1.6 3.8
TWA1014DA 380/415 3 17.8 145.0 N/A N/A 1 380/415 1 1.9 5.8
8.33
TWA1014DD 380/415 3 7.8 51.5 7.8 51.5 1 380/415 1 1.9 5.8
13 TWA1564DD 380/415 3 12.2 101.0 12.2 101.0 2 380/415 1 1.9 5.8
16.7 TWA2014DD 380/415 3 18.5 118.0 18.5 118.0 2 380/415 1 1.9 5.8

Table 80. Unit wiring — heat pumps — 50 Hz


Max Max Fuse Size or
Unit Model Unit Operating
Tons Circuit Max Circuit
Number Voltage Range
Ampacity Breaker
5 TWA0604DA 380/415 14.9 25
5 TWA0604DD 380/415 13.8 15
6.25 TWA0764DA 380/415 17.0 25
6.25 TWA0764DD 380/415 15.1 20
8.33 TWA1014DA 380/415 24.2 40
8.33 TWA1014DD 380/415 19.5 25
13 TWA1564DD 380/415 31.2 40
16.7 TWA2014DD 380/415 45.4 60

Note: HACR type circuit breaker per NEC.

Air Handler (Standard)


Table 81. Electrical characteristics — standard motor — 50 Hz air handler
Standard Evaporator Fan Motor
Unit Model
Tons Amps
Number No. Volts Phase HP MCA MFS
FLA LRA
4.6 TWE0514DA 1 380-415 3 0.75 1.45 8.00 1.81 15.00
6 TWE0724DB 1 380-415 3 1.00 2.50 17.00 3.13 15.00
6.25 TWE0764DA, B 1 380-415 3 1.00 2.50 17.00 3.13 15.00
8.33 TWE1014DA, B 1 380-415 3 1.50 3.30 19.00 4.13 15.00
10.4 TWE1264DB 1 380-415 3 2.00 3.20 35.00 4.00 15.00
13 TWE1564DB 1 380-415 3 2.00 4.60 39.00 5.75 15.00
16.7 TWE2014DB 1 380-415 3 3.50 8.00 43.00 10.00 15.00

SSP-PRC024K-EN 77
Electrical Data

Table 82. Unit wiring with electric heat (single point connection) — air handlers

Min Max
Heater Heater Unit Power Control
Ton Used With Circuit Fuse
Model No. kW Rating Supply Stages
Ampacity Breaker Size

BAYHTRL405* 5 380/3/50 1 8 15

BAYHTRL410* 9.96 380/3/50 1 14 15

BAYHTRL415* 14.96 380/3/50 1 20 20

BAYHTRL425* 24.92 380/3/50 2 31 35


4.6 TWE0514DA
BAYHTRL405* 5 415/3/50 1 8 15

BAYHTRL410* 9.96 415/3/50 1 15 15

BAYHTRL415* 14.96 415/3/50 1 21 25

BAYHTRL425* 24.92 415/3/50 2 34 35

BAYHTRL405* 5 380/3/50 1 9 15

BAYHTRL410* 9.96 380/3/50 1 15 15

BAYHTRL415* 14.96 380/3/50 1 21 25

BAYHTRL425* 24.92 380/3/50 2 33 35

BAYHTRL435* 34.88 380/3/50 2 45 45


6 TWE0724DB
BAYHTRL405* 5 415/3/50 1 10 15

BAYHTRL410* 9.96 415/3/50 1 16 20

BAYHTRL415* 14.96 415/3/50 1 23 25

BAYHTRL425* 24.92 415/3/50 2 36 40

BAYHTRL435* 34.88 415/3/50 2 48 50

BAYHTRL405* 5 380/3/50 1 9 15

BAYHTRL410* 9.96 380/3/50 1 15 15

BAYHTRL415* 14.96 380/3/50 1 21 25

BAYHTRL425* 24.92 380/3/50 2 33 35

BAYHTRL435* 34.88 380/3/50 2 45 45


6.25 TWE0764DA, B
BAYHTRL405* 5 415/3/50 1 10 15

BAYHTRL410* 9.96 415/3/50 1 16 20

BAYHTRL415* 14.96 415/3/50 1 23 25

BAYHTRL425* 24.92 415/3/50 2 36 40

BAYHTRL435* 34.88 415/3/50 2 48 50

BAYHTRL405* 5 380/3/50 1 10 15

BAYHTRL410* 9.96 380/3/50 1 16 20

BAYHTRL415* 14.96 380/3/50 1 22 25

BAYHTRL425* 24.92 380/3/50 2 34 35

BAYHTRL435* 34.88 380/3/50 2 46 50


8.33 TWE1014DA, B
BAYHTRL405* 5 415/3/50 1 11 15

BAYHTRL410* 9.96 415/3/50 1 17 20

BAYHTRL415* 14.96 415/3/50 1 24 25

BAYHTRL425* 24.92 415/3/50 2 37 40

BAYHTRL435* 34.88 415/3/50 2 49 50

78 SSP-PRC024K-EN
Electrical Data

Table 82. Unit wiring with electric heat (single point connection) — air handlers (continued)

Min Max
Heater Heater Unit Power Control
Ton Used With Circuit Fuse
Model No. kW Rating Supply Stages
Ampacity Breaker Size

BAYHTRM410* 10 380/3/50 1 16 20

BAYHTRM420* 19.92 380/3/50 1 28 30

BAYHTRM430* 29.92 380/3/50 2 40 40

BAYHTRM450* 49.84 380/3/50 2 63 70


10.4 TWE1264DB
BAYHTRM410* 10 415/3/50 1 17 20

BAYHTRM420* 19.92 415/3/50 1 30 30

BAYHTRM430* 29.92 415/3/50 2 43 45

BAYHTRM450* 49.84 415/3/50 2 69 70

BAYHTRM410* 10 380/3/50 1 18 20

BAYHTRM420* 19.92 380/3/50 1 29 30

BAYHTRM430* 29.92 380/3/50 2 41 45

BAYHTRM450* 49.84 380/3/50 2 65 70


13 TWE1564DB
BAYHTRM410* 10 415/3/50 1 19 20

BAYHTRM420* 19.92 415/3/50 1 32 35

BAYHTRM430* 29.92 415/3/50 2 45 45

BAYHTRM450* 49.84 415/3/50 2 71 80

BAYHTRM410* 10 380/3/50 1 22 25

BAYHTRM420* 19.92 380/3/50 1 34 35

BAYHTRM430* 29.92 380/3/50 2 46 50

BAYHTRM450* 49.84 380/3/50 2 69 70


16.7 TWE2014DB
BAYHTRM410* 10 415/3/50 1 23 25

BAYHTRM420* 19.92 415/3/50 1 36 40

BAYHTRM430* 29.92 415/3/50 2 49 50

BAYHTRM450* 49.84 415/3/50 2 75 80

SSP-PRC024K-EN 79
Jobsite Connections
ReliaTel Controls
Wiring shown with dashed lines is to be furnished and installed by the customer. All customer
supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes
may require line of sight between disconnect switch and unit.
Notes:
1. When electric heater accessory is used, single point power entry or dual point power
entry is field optional. Single point power entry option is through electric heater only.
2. ***Choose only one of the following; Thermostat, Zone Sensor, or NSB Panel.
I m p o r t a n t : For the EDC switch to be functional and thereby facilitate reliable unit operation,
make the EDC connections from the indoor to the outdoor control boxes.
Figure 8. ReliaTel jobsite connections
Disconnect Switch
(By Others)
Note 2

B Air Handler

Electric
Heat Accessory

B
D Disconnect Switch
(By Others) Note 2

A Disconnect Switch
(By Others)
C E F

T’stat Zone NSB Panel


Sensor

A. 3 power wires, line voltage for 3 phase, (2 power wires for single phase)

B. 3 power wires, line voltage for 3 phase, (2 power wires for single phase)

C. Heat Pump thermostat: 5 to 8 wires depending on stages of electric heat

D. 3 to 7 wires depending on type of outdoor unit(s)

E. Zone Sensor: 4 to 10 wires depending on zone sensor model(a)

F. Night Setback Panel: 7 wires

(a) For SZVAV air handlers: 4 additional wires are required (2 of which require twisted pair or shielded wire) in order to make
connections between ReliaTel boards in the condenser and air handler.

80 SSP-PRC024K-EN
Dimensional Data
Heat Pump Condenser
Figure 9. 5-6.25 ton heat pump, single compressor
SEE NOTE 3

NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" ( 914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
SERVICE PANEL
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

HAIL GUARD
(OPTIONAL)
SEE NOTE 4

SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE)
35 15/16"
HAIL GUARD (912.8)
WITH HAIL GUARD SEE NOTE 1
(OPTIONAL) LINE VOLTAGE
33 15/16"
(862) REFRIGERANT ACCESS
CONTROL WIRING

36 3/8" 39 3/16"
(923.9) SERVICE PANEL (995.4)
29 13/16" 26 15/16"
(757.2) (684.2)
14 3/8"
8 5/16" (365.1)
5 5/8"
(211.1)
(143)
1/16"
(1.6) 6" 3 1/16" (77.8)
6" (152.4)
LIQUID LINE (152.4)
2" (50.8)
21 11/16"
SUCTION LINE (550.9) 41 1/16"
(1043)
33 13/16"
(858.8) 42 1/8"
(1070)
WITH HAIL GUARD
SERVICE PANEL SIDE

3" (76.2) 7/16" (11.1) DIA. ISOLATOR MOUNTING


HOLES (OUTSIDE HOLES - 4 PLACES)

34 3/4" BOTTOM
40 3/4" (882.7) OF UNIT
(1035)

4 3/16"
(106.4)
1 13/16" 27 11/16" 2 5/16"
(46) (703.3) (58.7)

SSP-PRC024K-EN 81
Dimensional Data

Figure 10. 5-6.25 ton heat pump, dual compressor

82 SSP-PRC024K-EN
Dimensional Data

Figure 11. 8.33 ton heat pump, single compressor


SEE NOTE 3
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
SERVICE PANEL CLEARANCE 48" (1219.2)
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)

SEE NOTE 4 HAIL GUARD


(OPTIONAL)

SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE

4 1/4" (108) 39 15/16"


(1014.4) SEE NOTE 1
HAIL GUARD 1 1/4" (31.7) WITH HAIL GUARD
(OPTIONAL) LINE VOLTAGE
37 15/16" REFRIGERANT ACCESS
CONTROL WIRING (963.6)

42 5/16" 44 3/4"
SERVICE PANEL
35 3/4" (1074.7) (1136.6)
5 9/16" (908) 32 7/8"
(141.3) (835)
14 5/16"
8 1/4" (363.5)
(209.5)
1/16" (1.6)
LIQUID LINE 6" (152.4) 25 11/16" 6" (152.4) 1 13/16" (46)
(652.5)
4" (101.6)
SUCTION LINE 37 11/16" 2 7/8" (73)
4 3/8" (111.1) (957.3)
50 15/16"
(1293.8)

SERVICE PANEL SIDE 51 15/16"


(1319.2)
WITH HAIL GUARD
3" (76.2)

7/16" (11.1) DIA. ISOLATOR MOUNTING


HOLES (OUTSIDE HOLES - 4 PLACES)

44 3/4" BOTTOM
50 3/4" (1136.6) OF UNIT
(1289)

3 13/16"
(96.8)
2 3/16" 31 11/16" 1 11/16"
(55.6) (805) (42.9)

SSP-PRC024K-EN 83
Dimensional Data

Figure 12. 8.33 ton heat pump, dual compressor

84 SSP-PRC024K-EN
Dimensional Data

Figure 13. 13-16.7 ton heat pump, dual compressor

SEE NOTE 2 NOTES:


1. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1829). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
2. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
3. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING).

HAIL GUARD
(OPTIONAL)
SEE NOTE 3

SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 1
FOR CLEARANCE)

46"
DETAIL A (1168.4)
SERVICE PANEL WITH HAIL GUARD

95 7/16" 44 3/16"
(2424.112) (1122.4)
WITH HAIL GUARD

HAIL GUARD
(OPTIONAL) HAIL GUARD
(OPTIONAL)

45 1/8"
(1146.2)

1/16"
SERVICE (1.6)
41 3/8"
PANEL
(1051)
9" 25 11/16" 9"
93 5/16"
(228.6) (652.5) (228.6)
(2370.1)

9 1/4" (235)

6 13/16" (173)
7/16" (11.1) ( DIA. ISOLATOR MOUNTING
HOLES (OUTSIDE HOLES - 4 PLACES) CONTROL WIRING 1 3/16" (30.2)

SERVICE PANEL SIDE LINE VOLTAGE

REFRIGERANT ACCESS
41 5/8"
39 7/8" (1057.3)
(1012.8)

BOTTOM OF UNIT 36 7/8" 14 1/2" 14 5/8" 12 5/8"


(936.6) 41 1/2" (368.3) (371.5) (320.7)
(1054.1)

LIQUID LINES
5 5/8" 4 1/4" 15/16" (23.8)
(143) (108)
SUCTION LINES 3 11/16" (94)
3" (76.2) 2 3/16" 6 13/16"
87" (55.6) (173) 6 5/16" (160.3)
(2210)
93"
(2362.2)
FRONT DETAIL A
DIMENSIONAL DETAIL

SSP-PRC024K-EN 85
Dimensional Data

Air Handler
Figure 14. 4.6 ton air handler, single circuit
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
.50" (12.7) 22 5/8"
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
(574.7)
DUCT FLANGE .77" OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
1" (25.4) (19.6) ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
HEIGHT 16 1/4" SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
(412.8) SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
6 15/16" (176.2) DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

24 1/16" SUPPLY 37 15/16"


(611.2) OPEN (963.6)

12 7/16" BOTTOM RETURN 13 5/16"


7 9/16" SIDE RETURN
(315.9) (338.14)
(192.1)
HEATER CONTROL
AND SINGLE POWER
ENTRY WIRES 2 5/16" 1 3/4"
6 7/8" (58.7) 3 9/16" (44.45)
HEATER (174.6) (90.5)
VENTILATION 2 3/4" 32 1/2" 32 1/2" 2 3/4"
22 5/8" (69.9) (825.5) (825.5) (69.9)
(574.7)
CONTROL WIRING 3 7/16" (87.3)

COPPER LIQUID LINE


5 15/16" FIELD CONNECTION
LINE VOLTAGE (150.8)
13 3/16" (335)
CONTROL BOX
ACCESS PANEL
COPPER SUCTION LINE
1 11/16"
(42.9) FIELD CONNECTION
REMOTE BULB TXV
DRAIN CONNECTION
FOR HORIZONTAL 1 3/8" (34.9) O.D. SUCTION LINE
(SEE NOTE 2,3,5)

20 1/16" 13 9/16" 12"


(509.6) (344.5) (304.8)
12" 13 9/16" (344.5)
(304.8)
.99" (25.15)
FILTER ACCESS PANEL .99" (25.15) SEE NOTES 2,3,4
32" (813) MIN. DISTANCE 1 3/8"
1 3/8" (34.9)
BOTH SIDE (34.9)

LIQUID LINES 3 3/16" (81)


SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL
SUSPENSION
1 1/8"
35 5/8"
(28.6)
(904.9)
SUPPLY OPENING
3" (76.2) (4) - HOLE FOR HORIZONTAL
SUSPENSION

BOTTOM RETURN

34 9/16"
48 1/16" (877.9) SIDE RETURN
(1220.8)

FILTER
10 7/16"
(265.1)
BOTTOM RETURN
SIDE RETURN
SUPPLY HORIZONTAL -
SUPPLY VERTICAL - RETURN VERTICAL /
RETURN HORIZONTAL / RETURN HORIZONTAL
RETURN VERTICAL

86 SSP-PRC024K-EN
Dimensional Data

Figure 15. 6, 6.25 ton air handler, single circuit


25 1/2" NOTES:
(647.7) 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
DUCT FLANGE 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
16 1/4" .70"
1" (25.4) OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
(412.8) (17.8)
HEIGHT ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PL ATE MUST BE RE-INSTALLED AFTER
SLIDING DRAIN PAN BACK INTO UNIT.
11 11/16" 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
(296.8) DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

24 1/16" SUPPLY 47 1/2"


(611.2) OPEN (1206.5)

12 5/16"
HEATER CONTROL 8 5/16"
(312.7) 16 7/8"
AND SINGLE POWER (211.1) 16 1/16" BOTTOM RETURN
SIDE RETURN (428.6)
ENTRY WIRES (408)

HEATER 2 1/4" (57.15)


VENTILATION 6 13/16" 1 9/16" 1 13/16"
(173) (39.7) (46)
2 3/4" 42" 2 3/4" 42"
25 1/2" (69.85) (1066.8) (1066.8)
(69.85)
CONTROL WIRING (647.7)
3 1/2" (88.9)
LINE VOLTAGE

COPPER LIQUID LINE


8 13/16" (223.8) FIELD CONNECTION
CONTROL BOX 16"
ACCESS PANEL (406.4)

1 3/16" (30.2)
COPPER SUCTION LINE
DRAIN CONNECTION REMOTE BULB TXV FIELD CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5) SUCTION LINE

22 7/8"
(581) 20"
16 11/16" 17 7/16" 17 3/8" 16 11/16"
(508)
(423.9) (442.9) (441.3) (423.9)

FILTER ACCESS PANEL 3 5/8" (92.1) 1 9/16" (39.7) SEE NOTES 2,3,4
22" (558.8) MIN. DISTANCE
BOTH SIDE 1 11/16" (42.9) 3 1/2" (88.9)

LIQUID LINES

SEE NOTES 2,3,4

1 3/16" (30.16) 45 1/8" (4) - HOLE FOR


(1146.2) HORIZONTAL SUSPENSION
(4) HOLE FOR
SUPPLY OPENING HORIZONTAL
6 3/4"
(171.45) SUSPENSION

BOTTOM RETURN

54 1/16" 36 7/8"
SIDE RETURN
(1373.2) (936.6)

FILTER

10 7/16"
(265.1) BOTTOM RETURN SIDE RETURN

SUPPLY VERTICAL - SUPPLY HORIZONTAL -


RETURN HORIZONTAL / RETURN VERTICAL /
RETURN VERTICAL RETURN HORIZONTAL

SSP-PRC024K-EN 87
Dimensional Data

Figure 16. 6–6.25 ton air handler, dual circuit


NOTES:
25 1/2"
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
(647.7)
DUCT FLANGE 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
1" (25.4) 16 1/4" OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
HEIGHT (412.8) ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
.70" SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
(17.78)
SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
11 11/16"
(296.9) DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.

47 1/2"
24 1/16" SUPPLY (1206.5)
(611.2) OPEN

12 5/16"
HEATER CONTROL 8 5/16" 16 1/16" 16 7/8" BOTTOM RETURN
(312.7) SIDE RETURN
AND SINGLE POWER (211.1) (408) (406.4)
ENTRY WIRES

HEATER 2 1/4" (57.15)


1 9/16" 1 13/16"
VENTILATION 6 13/16" (173) (46)
(39.7)
2 3/4" 42" 2 3/4" 42"
25 1/2" (69.9) (1066.8) (69.9) (1066.8)
CONTROL WIRING (647.7)
3 1/2" (88.9)

LINE VOLTAGE COPPER LIQUID LINE


8 13/16" (223.8) FIELD CONNECTION
CONTROL BOX 16"
ACCESS PANEL (406.4)

1 3/16" (30.2)
COPPER SUCTION LINE
DRAIN CONNECTION (2) REMOTE BULB TXV FIELD CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5) SUCTION LINE

22 7/8" 20 1/16" 20 1/16"


(581) 16 1/4" 16 3/4" 19 1/16"
(509.6) (509.6) 16 3/4" 16 1/4" 13 3/4"
11 1/16" 13 3/4" (412.8) (425.5) (484.2)
(425.5) (412.8) (349.3)
(281) (349.2)

1 5/16" (33.3)
FILTER ACCESS PANEL 1 5/16" (33.3) SEE NOTES 2,3,4
22" (559) MIN. DISTANCE 1 5/8" (41.3)
BOTH SIDE 1 5/8" (41.3)
3 5/8" (92.1) 3 5/8" (92.1)
LIQUID LINES

SEE NOTES 2,3,4


(4) - HOLE FOR HORIZONTAL
SUSPENSION
1 3/16" (30.2) 45 1/8"
(1146.2)
SUPPLY OPENING
(4) HOLE FOR
6 3/4"
HORIZONTAL
(171.5)
SUSPENSION

BOTTOM RETURN

36 7/8" SIDE RETURN


54 1/16"
(1373.2) (936.6)

FILTER

10 7/16"
BOTTOM RETURN
(265.1) SIDE RETURN
SUPPLY VERTICAL -
SUPPLY HORIZONTAL -
RETURN HORIZONTAL /
RETURN VERTICAL /
RETURN VERTICAL
RETURN HORIZONTAL

88 SSP-PRC024K-EN
Dimensional Data

Figure 17. 8.33 ton air handler, single circuit


NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
25 1/2" OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
(647.7) ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
16 1/4" .70" (17.8) SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
DUCT FLANGE (412.8) SLIDING DRAIN PAN BACK INTO UNIT.
1" (25.4) 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
HEIGHT DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
19 11/16"
(500.1)

63 1/2"
24 1/16" SUPPLY (1612.9)
(611.2) OPEN
15 15/16" 16 7/8"
SIDE RETURN BOTTOM RETURN
(404.8) (428.6)

HEATER CONTROL 20 5/16"


AND SINGLE POWER 16 5/16" (515.9) 1 11/16" 1 13/16"
ENTRY WIRES (414.3) (42.9) (46)
2 3/4" 58" 2 3/4" 58"
(69.8) (1473.2) (69.8) (1473.2)
HEATER
2 1/4" (57.2)
VENTILATION
6 13/16" (173)

CONTROL WIRING 25 1/2"


(647.7)
LINE VOLTAGE 3 1/2" (89)

8 7/8"
CONTROL BOX (225.4) 16 1/16"
COPPER LIQUID LINE
(408)
ACCESS PANEL FIELD CONNECTION

DRAIN CONNECTION REMOTE BULB TXV


FOR HORIZONTAL
COPPER SUCTION LINE
(SEE NOTE 2,3,5) SUCTION LINE
FIELD CONNECTION

1 3/16"
22 7/8" (30.2) 20"
(581) 16 11/16" 17 3/8" 17 3/8" 16 11/16"
(508)
(423.9) (441.4) (441.3) (423.9)

FILTER ACCESS PANEL SEE NOTES


1 11/16" (42.9) 3 5/8" (92.1)
22" (559) MIN. DISTANCE 2,3,4
BOTH SIDE 3 5/8" (92.1) 1 11/16" (42.9)

LIQUID LINES

SEE NOTES 2,3,4

(4) - HOLE FOR


63 1/2" (4) HOLE FOR
HORIZONTAL
(1613) HORIZONTAL
SUSPENSION
SUSPENSION
1 3/16" (30.2) 61 1/8" SUPPLY OPENING
(1552.6)

6 3/4" BOTTOM RETURN


(171.45)
SIDE RETURN

36 7/8"
54 1/16" (936.63)
(1373.2)
FILTER

SIDE RETURN
BOTTOM RETURN
SUPPLY HORIZONTAL -
10 7/16" (265.1) SUPPLY VERTICAL -
RETURN VERTICAL /
RETURN HORIZONTAL /
RETURN HORIZONTAL
RETURN VERTICAL

SSP-PRC024K-EN 89
Dimensional Data

Figure 18. 8.33 ton air handler, dual circuit


NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
25 1/2" 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
(647.7) OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
16 1/4" .70" (17.8) SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
DUCT FLANGE
(412.7) SLIDING DRAIN PAN BACK INTO UNIT.
1" (25.4)
HEIGHT 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
19 11/16" 5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
(500.1)

63 1/2"
24 1/16" SUPPLY (1613)
(611.2) OPEN
15 15/16" 16 7/8"
SIDE RETURN (428.6) BOTTOM RETURN
(404.8)

HEATER CONTROL 20 5/16"


AND SINGLE POWER 16 5/16" (515.9)
(414.3) 1 11/16" 1 13/16"
ENTRY WIRES (42.9) (46)
2 3/4" 58" 2 3/4" 58"
HEATER (69.8) (1473.2) (69.8) (1473.2)
2 1/4" (57.15)
VENTILATION
6 13/16" (173)

25 1/2"
CONTROL WIRING (647.7)

LINE VOLTAGE 3 1/2" (89)

8 7/8"
CONTROL BOX (225.4) 16 1/16"
(408) COPPER LIQUID LINE
ACCESS PANEL FIELD CONNECTION
DRAIN CONNECTION (2) REMOTE BULB TXV
FOR HORIZONTAL
COPPER SUCTION LINE
(SEE NOTE 2,3,5) SUCTION LINE
FIELD CONNECTION

1 3/16"
22 7/8" (30.2)
19" 20" 20 1/16"
(581)
13 11/16" 16 1/4" 16 11/16" 16 3/4" 16 1/4" 13 3/4"
(423.9) (482.6) (508) (509.6)
11" (279.4) (347.7) (412.8) (425.5) (412.8) (349.3)

FILTER ACCESS PANEL 1 5/16" (33.4) 1 5/16" (33.3) SEE NOTES


22" (558.8) MIN. DISTANCE 2,3,4
BOTH SIDE 1 5/8" (41.3) 1 5/8" (41.3)
3 5/8" (92.1) 3 5/8" (92.1)
LIQUID LINES

SEE NOTES 2,3,4

(4) - HOLE FOR HORIZONTAL


SUSPENSION (4) HOLE FOR
HORIZONTAL
1 3/16" 61 1/8" SUPPLY OPENING SUSPENSION
(30.2) (1552.6)

6 3/4"
(171.45) BOTTOM RETURN

SIDE RETURN

54 1/16" 36 7/8"
(1373.2) (936.6)

FILTER

BOTTOM RETURN SIDE RETURN

10 7/16" (265.1) SUPPLY VERTICAL - SUPPLY HORIZONTAL -


RETURN HORIZONTAL / RETURN VERTICAL /
RETURN VERTICAL RETURN HORIZONTAL

90 SSP-PRC024K-EN
Dimensional Data

Figure 19. 10.4, 13 ton air handler, dual circuit


NOTES:
29 1/16"
DUCT FLANGE 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
(738.2)
1" (25.4) 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
16 5/16"
HEIGHT OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
(414.3)
2 7/8" (73) ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING
DRAIN PAN BACK INTO UNIT.
12 3/8" (314.3) 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
SUPPLY 5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
OPEN

79 9/16"
54 15/16" (2020.9)
(1395.4)
19 1/2"
17 7/8" (495.3) BOTTOM RETURN
SIDE RETURN SIDE RETURN BOTTOM RETURN
SUPPLY (454)
OPEN

12 1/8" 3 5/16" (84.1) 3 7/16" (87.3)


(308)
2 3/4" 74 1/8" 2 3/4" 74 1/8"
HEATER CONTROL (69.8) (1882.8) (69.8) (1882.8)
AND SINGLE POWER
ENTRY WIRES 4 5/16" (109.5)

29 1/16"
(738.2)
CONTROL WIRING
4 1/4" (108)
LINE VOLTAGE 12 13/16" (325.4)

20"
(508)
CONTROL BOX COPPER LIQUID LINE
ACCESS PANEL FIELD CONNECTION
DRAIN CONNECTION (2) REMOTE BULB TXV
FOR HORIZONTAL
COPPER SUCTION LINE
(SEE NOTE 2,3,5) SUCTION LINE
FIELD CONNECTION

1 1/4"
25 1/8" (31.8) 22"
21 1/2" 21 1/2"
(638.2) 15 13/16" 18 5/16" 18 11/16" (546.1) (558.8) (546.1)
18 11/16" 18 3/8" 15 13/16"
12" (304.8) (401.6) (465.1) (474.7) (474.6) (466.7) (401.64)

2" (50.8) SEE NOTES


FILTER ACCESS PANEL 1 5/16" (33.3)
2,3,4
32" (813) MIN. 2 1/8" (54) 2 5/16" (58.7)
DISTANCE
BOTH SIDE 2 7/16" (62) 4 1/8" (104.8)
4 1/4" (108)
LIQUID LINES
(4) - HOLE FOR HORIZONTAL
SEE NOTES 2,3,4
SUSPENSION

79 5/8" (4) HOLE FOR


(2022.5) HORIZONTAL
SUPPLY OPENING
1 3/16" 77 3/16" SUSPENSION
(30.2) (1960.6)
BOTTOM RETURN
9 5/8"
(244.5)

SIDE RETURN

69 1/16" 48"
(1754.2) (1219.2) FILTER

BOTTOM RETURN SIDE RETURN


SUPPLY VERTICAL - SUPPLY HORIZONTAL -
RETURN HORIZONTAL / RETURN VERTICAL /
11 7/16" (290.5) RETURN VERTICAL RETURN HORIZONTAL

SSP-PRC024K-EN 91
Dimensional Data

Figure 20. 16.7 ton air handler, dual circuit


31 1/8"
(790.6)
DUCT FLANGE 16 5/16" NOTES:
1" (25.4) 1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
(414.3)
HEIGHT 4 15/16" (125.4) 2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END
OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN
ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO
SLIDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER
18 7/8" SLIDING DRAIN PAN BACK INTO UNIT.
(479.4) 3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF
DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
SUPPLY 5. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
OPEN
92 9/16"
(2351.1)
54 15/16"
(1395.4)

20 15/16" 20 15/16"
BOTTOM RETURN BOTTOM RETURN
(531.8) SIDE RETURN SIDE RETURN (531.8)

18 5/8"
HEATER CONTROL (473.1)
2 15/16"
AND SINGLE POWER 3"
(74.6)
ENTRY WIRES (76.2)
4 3/4" 83 1/8" 4 3/4" 83 1/8"
6 7/16" (163.5)
(120.6) (2111.4) (120.6) (2111.4)
31 1/8"
CONTROL WIRING
(790.6)
4 1/4" (108)
LINE VOLTAGE

CONTROL BOX 20" (508)


ACCESS PANEL

DRAIN CONNECTION 12 13/16" COPPER LIQUID LINE


FOR HORIZONTAL (325.4) FIELD CONNECTION
(SEE NOTE 2,3,5) REMOTE BULB TXV
COPPER SUCTION LINE
SUCTION LINE FIELD CONNECTION

1 3/16"
28 1/2" (30.2) 25 1/2"
(724) 18 3/8" 19 1/8" 21 3/8" 21 13/16" (647.7) 25 1/2" 21 13/16"
12 7/8" 15 7/8" (466.7) (485.8) (542.9) (554) (647.7) 19 1/8" 18 3/8" 15 7/8"
(327) (403.2) (554)
(485.8) (466.7) (403.2)

FILTER ACCESS PANEL SEE NOTES


32" (813) MIN. DISTANCE 1 11/16" (42.9)
2,3,4
BOTH SIDE
1 15/16" (49.2) 1 9/16" (39.7)
LIQUID LINES
3 3/8" (85.7)
1 7/8" (47.6)
SEE NOTES 2,3,4 4" (101.6)
(4) - HOLE FOR HORIZONTAL 3 1/4" (82.5)
SUSPENSION
92 9/16" 3 7/8" (98.4)
(2351.1)
1 11/16"
(42.9) 89 3/16" (4) HOLE FOR
SUPPLY OPENING HORIZONTAL
(2265.4)
SUSPENSION
9 5/8"
(244.5) SIDE RETURN

SIDE RETURN
71 7/8" 50 13/16"
(1825.6) (1290.6) FILTER

BOTTOM RETURN BOTTOM RETURN


SUPPLY VERTICAL - SUPPLY HORIZONTAL -
RETURN HORIZONTAL / RETURN VERTICAL /
11 7/16"
RETURN VERTICAL RETURN HORIZONTAL
(290.5)

92 SSP-PRC024K-EN
Dimensional Data

Accessories
Figure 21. Rubber isolator accessory dimensions

Table 83. Rubber isolator accessory dimensions


Model No. L W H A B C D E

BAYISLT004 3-1/8 (79.375) 1-3/4 (44.45) 1-1/4 (31.75) 1-1/4 (31.75) 3/8 (9.525) 2-3/8 (60.325) 3/8 (9.525) 1/4 (6.35)

BAYISLT005 3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45) 1-3/4 (44.45) 3/8 (9.525) 3 (76.2) 3/8 (9.525) 1/4 (6.35)

BAYISLT009 3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45) 1-3/4 (44.45) 3/8 (9.525) 3 (76.2) 3/8 (9.525) 1/4 (6.35)

BAYISLT010 3-7/8 (98.425) 2-3/8 (60.325) 1-3/4 (44.45) 1-3/4 (44.45) 3/8 (9.525) 3 (76.2) 3/8 (9.525) 1/4 (6.35)

BAYISLT013 2-1/4 (57.15) 2 (50.8) 3 (76.2) 1-3/8 (34.925) 3/4 (19.05) 3/8 (9.525) 1/2 (12.7) —

BAYISLT014 2-1/4 (57.15) 2 (50.8) 3 (76.2) 1-3/8 (34.925) 3/4 (19.05) 3/8 (9.525) 1/2 (12.7) —

BAYISLT015 2-1/4 (57.15) 2 (50.8) 3 (76.2) 1-3/8 (34.925) 3/4 (19.05) 3/8 (9.525) 1/2 (12.7) —

BAYISLT012 3 (76.2) 2-1/4 (57.15) 4-1/2 (114.3) 1-7/8 (47.625) 1/4 (6.35) 5/8 (15.875) 3/4 (19.05) —

BAYISLT015(a) 3 (76.2) 2-1/4 (57.15) 4-1/2 (114.3) 1-7/8 (47.625) 1/4 (6.35) 5/8 (15.875) 3/4 (19.05) —

BAYISLT016 3 (76.2) 2-1/4 (57.15) 4-1/2 (114.3) 1-7/8 (47.625) 1/4 (6.35) 5/8 (15.875) 3/4 (19.05) —

Note: BAYISLT015 contains a quantity 2 of the 2-1/4 x 2 x 3 isolators and quantity of 3 of the 3 x 2-1/4 x 4-1/2 isolators.

SSP-PRC024K-EN 93
Dimensional Data

Figure 22. Spring isolator accessory dimensions – inches (millimeters)

Figure 23. Electric heater accessory for 4.6-8.3 ton air handlers – inches (millimeters)

94 SSP-PRC024K-EN
Dimensional Data

Figure 24. Electric heater accessory for 10.4-16.7 ton air handlers – inches (millimeters)

SSP-PRC024K-EN 95
Dimensional Data

Figure 25. Hot water coil accessory – inches (millimeters)

J
H DUCT OPENING
DUCT OPENING
1"
(25.4)
N

DUCT FLANGE

16" (406.4)

P
M

1"
(25.4)
C
L

"D" # HOLES EQUALLY


F
SPACED AT "E" APART 1/4" (6.3) DIA.
3" (76.2) DIA. B
HOLE FOR "Q" A "G" HOLES
(RETURN) 2 1/8"
(54)
3 7/8"
(98.4)

3" (76.2) DIA. HOLE AIR HANDLER


FOR "Q" (SUPPLY) MATING SURFACE

Table 84. Hot water coil accessory – inches (millimeters)


Model No. A B C D E F G H
BAYWATR027 38.14 (969) 22.74 (576) 13.74 (349) 5 (127) 9 (229) 13.65 (347) 16 (406) 26 (660)

BAYWATR028 47.74 (1213) 25.74 (654) 15.95 (405) 5 (127) 10.84 (275) 17.17 (436) 16 (406) 30 (762)

BAYWATR029 63.84 (1621) 25.74 (654) 15.95 (405) 6 (152) 11.84 (301) 17.16 (436) 18 (457) 36 (914)

BAYWATR030 79.74 (2025) 29.18 (741) 14.36 (365) 8 (203) 10.85 (276) 19.67 (500) 22 (559) 51 (1295)

BAYWATR031 92.74 (2356) 31.24 (793) 16.48 (419) 8 (203) 10.85 (276) 19.67 (500) 22 (559) 64 (1626)

Model No. J K L M N P Q

BAYWATR027 12 (305) 6 (152) 4.94 (125) 7.79 (198) 2.88 (73) 10.24 (260) 2 NPT (51) NPTI
2.5 NPTI (64)
BAYWATR028 18 (457) 8.88 (225) 8.45 (215) 10.27 (261) 2.88 (73) 7.77 (197)
NPTI
2.5 NPTI (64)
BAYWATR029 18 (457) 13.88 (352) 8.45 (215) 10.03 (255) 2.88 (73) 7.58 (192)
NPTI
2.5 NPTI (64)
BAYWATR030 18 (457) 14.25 (362) 6.86 (174) 9.91 (252) 1.88 (48) 7.41 (188)
NPTI
2.5 NPTI (64)
BAYWATR031 18 (457) 14.25 (362) 8.98 (228) 9.88 (251) 3.75 (95) 7.38 (187)
NPTI
Note: Hot Water Coil Dimensions - inches (millimeters)

96 SSP-PRC024K-EN
Dimensional Data

Figure 26. Steam coil accessory – inches (millimeters)

Table 85. Steam coil accessory – inches (millimeters)


Model No. A B C D E F G H J K

BAYWATR022 38.14 (969) 22.74 (577) 14.32 (364) 5 (127) 9 (229) 13.67 (347) 16 (406) 10.88 (276) 11.17 (284) 2 (51)
47.74
BAYWATR023 25.74 (654) 20.14 (511) 5 (127) 10.84 (275) 17.17 (436) 16 (406) 10.88 (276) 11.17 (284) 2 (51)
(1212)
63.84
BAYWATR024 25.74 (654) 20.14 (511) 6 (152) 11.87 (301) 17.16 (436) 18 (457) 13.70 (348) 10.57 (268) 2.5 (64)
(1621)
79.74
BAYWATR025 29.18 (741) 18.55 (471) 8 (203) 10.85 (275) 19.67 (500) 22 (559) 12.11 (308) 10.05 (255) 2.5 (64)
(2025)
92.74
BAYWATR026 31.24 (793) 20.67 (525) 8 (203) 10.85 (275) 19.67 (500) 22 (559) 14.23 (361) 10.01 (254) 2.5 (64)
(2355)
Model No. L M N P Q R

BAYWATR022 1.5 (38) 26 (660) 12 (305) 6 (152) 2.87 (73) 9.95 (253)

BAYWATR023 2 (51) 30 (762) 18 (457) 8.87 (225) 2.87 (73) 9.95 (253)

BAYWATR024 2 (51) 36 (914) 18 (457) 13.87 (352) 2.87 (73) 9.13 (232)

BAYWATR025 2 (51) 51 (1295) 18 (457) 14.12 (359) 1.87 (48) 8.61 (219)

BAYWATR026 2 (51) 64 (1626) 18 (457) 14.12 (359) 3.75 (95) 8.58 (218)

SSP-PRC024K-EN 97
Dimensional Data

Figure 27. Discharge plenum and grille accessory

A
B

Table 86. Discharge plenum and grille dimensions – no heat – inches (millimeters)
Unit Model No.(a) A B C
TWE051 BAYPLNM015 37.94 (963.6) 21.94 (557.2) 28 (711.2)
TWE072, TWE076 BAYPLNM016 47.5 (1206.5) 24.99 (634.7) 28 (711.2)
TWE101 BAYPLNM017 63.5 (1612.9) 24.99 (634.7) 28 (711.2)
TWE126, TWE156 BAYPLNM018(b) 79.5 (2019.3) 27.63 (701.8) 22 (558.8)
TWE201 BAYPLNM019(b) 92.5 (2349.5) 30.43 (772.9) 24 (609.6)
(a) When installed horizontally, plenum/water coil must be self-supported.
(b) For use with hydronic heat or no heat.

Figure 28. Discharge plenum and grille accessory

Table 87. Discharge plenum and grille dimensions – inches (millimeters) – (for use with electric heat)
Tons Model No. A B C
TWE051 BAYPLNM030 38.07 (967) 22.69 (576.3) 29.05 (738)
TWE072,
BAYPLNM031 47.86 (1216) 25.69 (652.5) 29.05 (738)
TWE076
TWE101 BAYPLNM032 63.86 (1622) 25.69 (652.5) 29.05 (738)

98 SSP-PRC024K-EN
Dimensional Data

Table 87. Discharge plenum and grille dimensions – inches (millimeters) – (for use with electric heat) (continued)
Tons Model No. A B C
TWE126,
BAYPLNM033 80.14 (2036) 29.10 (739.1) 35.11 (892)
TWE156
TWE201 BAYPLNM034 92.96 (2361) 31.10 (789.9) 35.05 (890)

Figure 29. Subbase accessory – inches (millimeters)

Table 88. Subbase dimensions – inches (millimeters)


Tons Model No. A B
TWE051 BAYBASE009 38 (965.2) 22.63 (574.8)
TWE072,
BAYBASE010 47.5 (1206.5) 25.51 (648.0)
TWE076
TWE101 BAYBASE011 63.5 (1612.9) 25.52 (648.2)
TWE126,
BAYBASE012 79.5 (2019.3) 29.04 (737.6)
TWE156
TWE201 BAYBASE013 92.5 (2349.5) 31.14 (791.0)

SSP-PRC024K-EN 99
Weights
Heat Pump Condenser
Table 89. TWA unit and corner weights — kg (50 Hz)
Shipping Net Max Corner Weights
Tons Model No.
Max (kg) (kg) 1 2 3 4
TWA0604DA 163 148 50 38 25 34
5
TWA0604DD 185 159 54 38 41 26
TWA0764DA 173 150 37 53 27 33
6.25
TWA0764DD 209 183 63 44 47 30
TWA1014DA 224 211 74 49 53 34
8.33
TWA1014DD 215 195 67 46 50 32
13 TWA1564DD 395 344 106 75 89 74
16.7 TWA2014DD 453 382 114 120 67 82

Figure 30. TWA060, 076, 101 Figure 31. TWA156, 201

#3 #4

#4 #1

#1
#3
#2

SER
ACC VICE
ESS #2

SER
SER ACC VICE
ACC VICE ESS
ESS

LIFTING HOLES
LIFTING HOLES (BOTH SIDES)
(BOTH SIDES)

100 SSP-PRC024K-EN
Weights

Air Handler
Table 90. Standard air handler (TWE) — unit and corner weights - (50 Hz)
1 2 3 4 1 2 3 4
4.6 TWE0514DA 285 232 55 71 51 55 54 67 50 61
6 TWE0724DB 385 323 67 99 75 82 56 92 87 88
6.25 TWE0764DA/B 385 323 67 99 75 82 56 92 87 88
8.33 TWE1014DA/B 441 393 77 121 110 85 79 118 77 119
10.4 TWE1264DB 753 676 168 192 181 135 196 164 145 171
13 TWE1564DB 752 675 167 192 181 135 196 163 145 171
16.7 TWE2014DB 912 818 258 168 161 231 256 181 146 235

Figure 32. Vertical — TWE051, 072, 076, 101


Control Box Access

Top View

Figure 33. Vertical — TWE126, 156, 201


Control Box Access

Top View

Figure 34. Horizontal — TWE051, 072, 076, 101

Top View

Control Box
Access

SSP-PRC024K-EN 101
Weights

Figure 35. Horizontal — TWE126, 156, 201

Top View

Control Box
Access

102 SSP-PRC024K-EN
Weights

Accessories
Table 91. Accessory weights (net lbs.)

Discharge Discharge
Plenum Discharge Plenum
Unit and Grille Plenum and Grille RIS
Used with and Grille with Electric Isolator
w/ Hot Water Hydronic without Electric Return Air Heat Min/ Oversized Floor
Tons Coil Steam Coil Heat Heat Heat Grille Max Subbase Motor Mount
5 86 94 63 58 115 3 32/43 14.4 31 2

6.25 116 131 78 73 160 5 27/45 19.4 48 2

8.33 165 148 97 92 195 7 27/45 23.5 50 2

10.4 211 234 — 230 235 10 79/100 28.4 80 2

13 211 234 — 230 235 10 79/100 28.4 80 2

16.7 242 261 — 145 265 12 79/100 31.7 88 2

Steel Steel
Unit RIS Spring Spring Service
Used Isolator Isolator Isolator Control Modulat- On/Off Valve
w/ Suspend- Floor Suspend- Hail Trans- ing Low Low
Tons ed Mount Mount ed Mount Guard former Sensors Ambient Ambient
5 9 12 6 21 — — — — 5

6.25 6 12 6 21 — — — — 5

8.33 7 12 6 28 — — — — 5

10.4 7 12 6 33 — — — — 5

13 7 12 6 55 — — — — 5

16.7 9 12 6 55 — — — — 5

SSP-PRC024K-EN 103
Mechanical Specifications
Condensing Units
Standard Options
General
• Weatherproofed steel mounting/lifting rails
• Hermetic scroll compressors
• Plate fin condenser coils
• Fans and motors
• Standard operating range 50-125°F (min. 0°F with low ambient accessory)
• Nitrogen holding charge

Casing
• Zinc coated, heavy gauge, galvanized steel
• Weather resistant baked enamel finish
• Meets ASTM B117, 672 hour salt spray test
• Removable single side maintenance access panels
• Lifting handles in maintenance access panels
• Unit base provisions for forklift and/or crane lifting

Refrigeration System - Single Compressor (TWA060**A, TWA076**A,


TWA101**A)
• Single refrigeration circuit with integral subcooling circuit
• Single direct drive hermetic scroll compressor
• Suction gas-cooled motor w/ ± 10% voltage utilization range of unit nameplate voltage
• Reversing valve
• Crankcase heater
• Internal temperature and current sensitive motor overloads
• No compressor suction and/or discharge valves (reduced vibration/sound)
• Factory installed liquid line filter drier
• Phase loss/reverse rotation monitor
• Liquid line service valve (with gauge port)
• Suction line service valve (with gauge port)
• External high pressure cutout device
• External low pressure cutout device
• Evaporator defrost control
• Loss of charge protection (discharge temperature limit)

Refrigeration System - Dual Compressor (TWA060**D, TWA076**D,


TWA101**D, TWA156**D, TWA201**D)
• Two (2) separate and independent refrigerant circuits
• Each refrigeration circuit equipped with integral subcooling circuit
• Two (2) direct drive hermetic scroll compressor
• Suction gas-cooled motors w/ ± 10% voltage utilization range of unit nameplate voltage
• Reversing valves
• Crankcase Heaters
• Internal temperature and current sensitive motor overloads
• Factory installed liquid line filter driers
• Phase loss/reverse rotation monitor
• No compressor suction and/or discharge valves (reduced vibration/sound)
• External high pressure cutout devices
• External low pressure cutout devices

104 SSP-PRC024K-EN
Mechanical Specifications

• Evaporator defrost control


• Loss of charge protection (discharge temperature limit)

Condenser Coil (Fin and Tube)


• 3/8” internally enhanced copper tube
• Mechanically bonded to lanced aluminum plate fins
• Factory pressure and leak tested to 660 psig
• Perforated steel hail guards available (factory installed option or field installed accessory)

Condenser Fan
• 26" or 28" propeller fan(s)
• Direct drive
• Statically and dynamically balanced

Condenser Motor(s)
• Permanently lubricated totally enclosed or open construction
• Built-in current and thermal overloads
• Ball or sleeve bearing type

Controls
• Centralized microprocessor
• Indoor and outdoor temperature sensors drive algorithms, making decisions for all heating,
cooling, and ventilation
• Integrated anti-short cycle timer
• Integrated time delay between compressors
• Completely internally wired
• Numbered and colored wires
• Contactor pressure lugs or terminal block
• Unit external mounting location for disconnect device
• Single point power entry

Factory Installed Options


Hail Guards
• Condenser coil protection from hail, vandals, etc.
• Perforated, painted galvanized steel
• Factory or field installed

Black Epoxy Coated Condenser Coil (Fin and Tube)


• Thermoset vinyl coating
• Bonded to aluminum fin stock (prior to fin-stamping process)
• Economical protectant in mildly corrosive environments

LonTalk Communication Interface


• Factory or field installed
• Communications board
• Allows unit communication as a Tracer™ LCI-R device
• Allows unit communication with generic LonTalk® Network building automation controls

Controls: Microprocessor
• Centralized processor
• Indoor and outdoor temperature sensors drive algorithms, making decisions for all heating,
cooling, and ventilation
• Integrated anti-short cycle timer
• Integrated time delay between compressors

SSP-PRC024K-EN 105
Mechanical Specifications

Field Installed Options


Low Ambient (Fan ON/OFF)
• Provides unit cooling operation to outdoor ambient of 0°F
• Low cost solution
• Liquid line temperature controls condenser fan operation
• 1 kit per condenser fan required

Low Ambient (Modulating)


• Provides unit cooling operation to outdoor ambient of 0°F
• “Wave-chopper”
• Discharge line pressure controls condenser fan operation
• 1 kit per condenser fan required

Vibration Isolators
• Neoprene-in-shear or spring flex choice
• Reduce vibration transmission to building structures, equipment, and adjacent spaces
• Reduce noise transmission to building structures, equipment, and adjacent spaces

Zone Sensor
• Interfaces with microprocessor units
• Manual or automatic programmable
• System malfunction lights
• Remote sensor options
• Wireless option

Thermostat
• 1H/1C available
• 2H/1C available
• Manual or automatic changeover available
• Programmable and non-programmable solutions available

LonTalk Communication Interface


• Factory or field installed
• Communications board
• Allows unit communication as a Tracer™ LCI-R device
• Allows unit communication with generic LonTalk® Network building automation controls

BACnet Communication Interface


• Communicates directly with a generic open protocol BACnet MS/TP Network building
automation system control

Air Handlers
Standard Options
General
• Completely factory assembled
• Convertible for horizontal or vertical configuration
• Convertible for cooling only or heat pump application
• Convertible for left or right external connections (refrigerant and/or electrical)
• Convertible for front or bottom air return
• Nitrogen holding charge

Casing
• Zinc coated, heavy gauge, galvanized steel
• Weather resistant baked enamel finish

106 SSP-PRC024K-EN
Mechanical Specifications

• Access panels with captive screws


• Completely insulated with foil faced, cleanable, fire retardant, permanent, odorless glass fiber
material
• Captured or sealed insulation edges
• Electrical connection bushings or plugs
• Refrigerant connection bushings or plugs
• Withstand elevated internal static pressure

Refrigeration System
• Single or dual circuit
• Distributor(s)
• Thermal expansion valves (TXVs)

Evaporator Coil
• 3/8” internally enhanced copper tube mechanically bonded to lanced aluminum plate fins
• Factory pressure and leak tested to 449 psig.
• Draw-through airflow
• Dual circuits are interlaced/intertwined
• Double sloped, removable, cleanable, composite drain pan
• Four drain pan positions

Indoor Fan
• Double inlet, double width, forward curved, centrifugal type fan
• Dual fans on 10.4 – 16.7 ton air handlers
• Adjustable belt drive
• Permanently lubricated bearings

Indoor Motor
• Adjustable motor sheaves (standard units)
• Thermal overload protection
• Permanently lubricated bearings
• Meet energy policy of 1992 (EPACT)
• Optional oversized motors for high static applications

Controls
• Completely internally wired
• Numbered and colored wires
• Magnetic indoor fan contactor
• Low voltage terminal strip
• Single point power entry
• Evaporator defrost control

Filters
• Access from side coil panels
• Filters slide on rack
• One inch (1"), throwaway filters on 4.6 - 8.33 ton units
• Filter rack convertible to two inch (2") capability on 4.6 - 8.33 ton units
• Two inch (2"), throwaway filters on 10.4 - 20.9 ton units

Field Installed Options


Electric Heaters
• Heavy duty nickel chromium elements
• Installs directly on fan discharge
• One or two stage control (dependent upon capacity)
• Single point power entry

SSP-PRC024K-EN 107
Mechanical Specifications

• Terminal strip connections


• 460V Heaters
– Internally wye connected
– Automatic line break high limit controls
• 230V Heaters
– Internally delta connected
– Automatic reset of high limit controls through pilot duty with secondary backup fuse links

Hydronic Heat Coils


• One row steam
• Two row hot water
• Installs directly on fan discharge
• Heavy gauge sheet metal casing matches air handler
• Convertible for horizontal or vertical configurations

Discharge Plenums and Grilles


• Vertical, free discharge applications
• Heavy gauge sheet metal casing matches air handler
• Satin-finished, 4-way adjustable louver grilles

Return Air Grilles


• Vertical, free discharge applications
• Satin-finished, non-adjustable louver grilles
• Replaces front lower access panel

Mounting Sub-Base
• Vertical floor mount configuration requirement
• Heavy gauge sheet metal casing matches air handler
• Provides additional clearance for condensate drain trapping
• Required when isolators are used

Vibration Isolators
• Neoprene-in-shear or spring flex choice
• Floor or suspended applications
• Reduce vibration transmission to building structures, equipment, and adjacent spaces
• Reduce noise transmission to building structures, equipment, and adjacent spaces

Oversize Motors
• High static applications
• Motor, sheaves, belt included

108 SSP-PRC024K-EN
Notes

SSP-PRC024K-EN 109
Notes

110 SSP-PRC024K-EN
Notes

SSP-PRC024K-EN 111
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and
Trane® — work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.

ingersollrand.com

Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.

SSP-PRC024K-EN 10 Jul 2018


Supersedes SSP-PRC024J-EN (March 2018) ©2018 Ingersoll Rand

You might also like