150 KV Circuit Breaker: Kupang Gas Engine Power Plant (Peaker) 40 MW 150 KV Switchard Site Test Report

1) This document is a site test report for a 150 kV circuit breaker at a 40 MW gas engine power plant in Kupang. 2) The report details the visual checks, power supply tests, local operation tests, minimum DC voltage tests, contact resistance measurements, closing and opening time tests, insulation resistance tests, individual interlock checks, and indicator checks that were performed on the circuit breaker. 3) The test results are documented along with ambient temperature and humidity conditions and the test equipment used. Signatures are included to verify those who tested, witnessed, and approved the circuit breaker site tests.

Uploaded by

rio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views6 pages

150 KV Circuit Breaker: Kupang Gas Engine Power Plant (Peaker) 40 MW 150 KV Switchard Site Test Report

1) This document is a site test report for a 150 kV circuit breaker at a 40 MW gas engine power plant in Kupang. 2) The report details the visual checks, power supply tests, local operation tests, minimum DC voltage tests, contact resistance measurements, closing and opening time tests, insulation resistance tests, individual interlock checks, and indicator checks that were performed on the circuit breaker. 3) The test results are documented along with ambient temperature and humidity conditions and the test equipment used. Signatures are included to verify those who tested, witnessed, and approved the circuit breaker site tests.

Uploaded by

rio
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

KUPANG GAS ENGINE POWER PLANT (PEAKER) 40 MW

150 kV SWITCHARD
SITE TEST REPORT
PT.ENERGI DIAN RAYA page: 1/2 JACOBSEN ELECTRO
Rev-0: 11 Nov 19 150 KV CIRCUIT BREAKER Form No.: 18 EDR/MOF/KP-01

I EQUIPMENT DATA
1) Manufacturer : 5) Rating :
2) Type : 6) S/N :
3) Installed at :
4) Supply voltage :
II VISUAL CHECK
NO CHECK ITEMS METHOD/ACCEPTANCE LEVEL RESULT/COMMENT

1 Poles Installation Chek Orientation and alignment, no loseness

2 Grounding Installation Proper path, no loseness

3 SF6 Leakage Density meter indication within normal range

4 Operating Mechanism Spring charge Indicator, CB Post. indicator

5 SF6 Pressure Switch Tested during SF6 Gas Filling

III POWER SUPPLY & AUXILIARY


NO CHECK ITEMS METHOD/ACCEPTANCE LEVEL RESULT/COMMENT

1 AC Supply Measure at Outlet or dedicated AC terminals

2 Space Heater & Lamp Function Simulate from Thermostat, Open/Close Door

3 DC Supply Measure at dedicated DC terminals

IV LOCAL MODE OPERATION


NO CHECK ITEMS METHOD/ACCEPTANCE LEVEL RESULT/COMMENT

1 Close & Open Selector Switch at Local mode

2 CB Position Indicator Should be fully close or open

V MINIMUM DC VOLTAGE T ambient : …………..°C Humidity : ………..%

ACCEPTANCE VOLTAGE MINIMUM COIL [VDC]


NO COIL
CRITERIA POLE A POLE B POLE C

1 Close DC DC DC
2 Trip 1 80 % x Vn DC DC DC
3 Trip 2 DC DC DC

VI CONTACT RESISTANT T ambient : …………..°C Humidity : ………..%

INJECTED MAESURED CONTACT RESISTANCE MEASUREMENT Acceptance


NO POLE CURRENT VOLTAGE Criteria
POLE A POLE B POLE C

1 POLE A mV

2 POLE B 100 A mV μΩ μΩ μΩ 50 μΩ

3 POLE C mV
KUPANG GAS ENGINE POWER PLANT (PEAKER) 40 MW
150 kV SWITCHARD
SITE TEST REPORT
PT.ENERGI DIAN RAYA page: 2/3 JACOBSEN ELECTRO
Rev-0: 11 Nov 19 150 KV CIRCUIT BREAKER Form No.: 18 EDR/MOF/KP-01

VII CLOSING & OPENING TIME AT NOMINAL DC VOLTAGE

OPERATING TIME (ms) BETWEEN Acceptance


NO POSITION CB POLES Criteria
Pole-A Pole-B Pole-C

1 Closing ms ≤ 5 ms
2 Trip-1 ms
≤ 3 ms
3 Trip-2 ms

VIII MEASUREMENT OF INSULATION RESISTANT T ambient : …………..°C Humidity : ………..%

NO POLE TEST TEST REMARKS


VOLTAGE RESULT

1 POLE A
2 5KV DC CB Open Position
POLE B (Upper - Lower)
3 POLE C
4 POLE A
CB Close
5 POLE B 5KV DC Position
(Phase - Ground)
6 POLE C
* Standart VDE 1MΩ/1kV
IX INDIVIDUAL INTERLOCK
NO CHECK ITEMS METHOD/ACCEPTANCE LEVEL RESULT/COMMENT

1 Close & Open Position Remote Remote position to block local operation

2 SF Block Operation SF6 very low to block closing or opening order

X INDICATION RESULT/COMMENT
NO CHECK ITEMS Ok Not Ok
1 Circuit Breaker close position
2 Circuit Breaker open position
3 SF6 fault indication - 1st threshold
4 SF6 fault indication - 2nd threshold
5 Motor MCB trips
6 Pole Discrepancy
7 Excessive motor running
8 Remote closing
9 Remote opening
10 Local closing mechanical/electrical
11 Local opening mechanical/electrical
KUPANG GAS ENGINE POWER PLANT (PEAKER) 40 MW
150 kV SWITCHARD
SITE TEST REPORT
PT.ENERGI DIAN RAYA page: 3/3 JACOBSEN ELECTRO
Rev-0: 11 Nov 19 150 KV CIRCUIT BREAKER Form No.: 18 EDR/MOF/KP-01

XI LIST OF TEST EQUIPMENT USED


Test corresponding to paragr
NO Designation
III IV V VI VII VIII
1
2
3
4
5

XII NOTE

TESTED BY Witnessed by : Witnessed by : Approved by :


ENDIRA JACOBSEN ELECTRO RECONSUL PUSERTIF