Circular Column Design Based On ACI 318-14: Project: Client: Design By: Job No.: Date: Review by

This document summarizes the design of a circular reinforced concrete column according to ACI 318-14. The column has a diameter of 20 inches, with #6 vertical bars and #4 spiral ties spaced at 12 inches. It is designed to support an axial load of 300 kips and a maximum bending moment of 140 foot-kips. The analysis shows the column has adequate strength for both axial and flexural demands, with safety factors exceeding code minimums for shear and development lengths.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
139 views1 page

Circular Column Design Based On ACI 318-14: Project: Client: Design By: Job No.: Date: Review by

This document summarizes the design of a circular reinforced concrete column according to ACI 318-14. The column has a diameter of 20 inches, with #6 vertical bars and #4 spiral ties spaced at 12 inches. It is designed to support an axial load of 300 kips and a maximum bending moment of 140 foot-kips. The analysis shows the column has adequate strength for both axial and flexural demands, with safety factors exceeding code minimums for shear and development lengths.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Circular Column Design Based on ACI 318-14

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH fc ' = 5 ksi, (34 MPa)
e
REBAR YIELD STRESS fy = 60 ksi, (414 MPa)
SECTION SIZE D = 20 in, (508 mm)
FACTORED AXIAL LOAD Pu = 300 kips, (1334 kN) e

FACTORED MAGNIFIED MOMENT Mu = 140 ft-kips, (190 kN-m)


FACTORED SHEAR LOAD Vu = 20 kips, (89 kN)
COLUMN VERT. REINFORCEMENT 8 # 6
LATERAL REINF. OPTION (0=Spirals, 1=Ties) 1 Ties
LATERAL REINFORCEMENT # 4 @ 12 in. (305 mm), o.c. THE COLUMN DESIGN IS ADEQUATE.

ANALYSIS
(
2 0.85 f C' )
e o = e max or , E c = 57 f C , E s = 29000ksi
'
900
Ec
800    e   e 2

 0.85 f
'

C 2
c −
 
c  ,
 for 0  e c  e o
700
fC=   e o   e o  
600 
0.85 f C , for e c  e o

'
f Pn (k)
500
e s E s , for e s  e t

fS=
400
 f , for e s  e t
 y
300
f Pn (k) f Mn (ft-k)
200
AT AXIAL LOAD ONLY 796 0
100 AT MAXIMUM LOAD 796 57
AT 0 % TENSION 584 122
0 AT 25 % TENSION 481 143
0 50 100 150 200 250
AT 50 % TENSION 395 153
AT e t = 0.002 272 156
f Mn (ft-k) AT BALANCED CONDITION 267 157
AT e t = 0.005 38 203
AT FLEXURE ONLY 0 189
CHECK FLEXURAL & AXIAL CAPACITY
f Pmax =F f [ 0.85 fc' (Ag - Ast) + fy Ast] = 796.34 kips., (at max axial load, ACI 318-14 22.4)
where f = 0.65 (ACI 318-14 21.2) > Pu [Satisfactory]
2 2
F = 0.8 Ag = 314 in Ast = 3.52 in

0.75 + ( et - 0.002 ) (50), for Spiral


f= = 0.656 (ACI 318-14 21.2)
0.65 + ( et - 0.002 ) (250 / 3), for Ties

where Cb = d ec / (ec + es) = 10.4 in et = 0.0021 ec = 0.003


d = 17.6 in, (ACI 20.6) D = 20.0 in Cover = 1.5 in, (ACI 318 20.6.1)
f Mn = 155 ft-kips @ Pu = 300 kips > Mu = 140 ft-kips [Satisfactory]
rmax = 0.08 (ACI 318-14 10.6) rprovd = 0.011
rmin = 0.01 (ACI 318-14 10.6) [Satisfactory]

CHECK SHEAR CAPACITY (ACI 318-14 10 & 22.5)


f Vn = f (Vs + Vc) (ACI 318-11 22.5)
> Vu [Satisfactory]
where f = 0.75 (ACI 318-11 21.2) fy = 60 ksi
d A0 Av Vc = 2 (fc') A00.5
Vs = MIN (d fy Av / s , 4Vc) f Vn
x 17.6 182.7 0.40 25.8 35.3 46

smax = 12 (ACI 318-14 25.7) sprovd = 12 in


smin = 1 [Satisfactory]