Project: 220Kv Switchyard - I & Ii For Balco Title: Technical Specification For Lighting Transformer

The document provides the technical specifications for a 250 kVA lighting transformer that will be used for a 220kV switchyard project. The dry type transformer has a voltage ratio of 415/415, is naturally air cooled with copper windings, and has a standard loss figure. It provides ±5% taps in 2.5% steps and has an IP 42 enclosure for protection. Temperature indicators and alarms are included to monitor winding temperature.

Uploaded by

Sureshraja9977
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views2 pages

Project: 220Kv Switchyard - I & Ii For Balco Title: Technical Specification For Lighting Transformer

The document provides the technical specifications for a 250 kVA lighting transformer that will be used for a 220kV switchyard project. The dry type transformer has a voltage ratio of 415/415, is naturally air cooled with copper windings, and has a standard loss figure. It provides ±5% taps in 2.5% steps and has an IP 42 enclosure for protection. Temperature indicators and alarms are included to monitor winding temperature.

Uploaded by

Sureshraja9977
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT : 220KV SWITCHYARD – I & II FOR BALCO

TITLE : TECHNICAL SPECIFICATION FOR LIGHTING TRANSFORMER

LIGHTING TRANSFORMER

The lighting transformer shall be of dry type, natural air cooled. Winding shall
be of electrolytic grade copper and transformer shall have standard loss figure. + 5%
@ 2.5% tapping links shall be provided.

The transformer shall be housed in naturally ventilated floor mounted cubicle


with louvers backed by fine brass wire mech. Degree of protection for enclosure shall
be at least IP 42.

The HV/LV connections shall be through cables.

The dry type transformers shall be provided with winding temperature


indicators, winding temperature high alarms and trip contacts.

The insulation class of transformer shall be class B.


DATA SHEET:

S.No Description Unit


1 Service Lighting transformer
2 Type Dry type, Natural Air Cooled
3 Rating kVA 250 kVA
4 Voltage ratio V/V 415/415
5 Rated Frequency HZ 50 HZ
6 No. of Phases 3
7 System type 3 phase , 4 wire
8 Vector Group Dyn11
9 Class of Insulation Class -B
10 Impedance 4 % ± 10%
11 Terminal arrangement Suitable for cable termination
12 No. of taps & Steps 5, ± 5% in steps of 2.5 %
13 Enclosure IP 42
14 Painting Epoxy Powder coating ,
Pebble grey, RAL 7032