XNC Modbus Master

The document provides instructions for installing and configuring an IQ3/XNC Modbus Master driver. It discusses downloading the necessary .xnc and .xnp files using SET and the Trend Controller interface. Configuration involves setting up communication protocols and mappings between Modbus slave registers and IQ strategy inputs/outputs. Supported protocols are TCP/IP, RS232, and RS485, and functions 1-6, 15, and 16 can be used.

Uploaded by

jgr77
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
328 views12 pages

XNC Modbus Master

The document provides instructions for installing and configuring an IQ3/XNC Modbus Master driver. It discusses downloading the necessary .xnc and .xnp files using SET and the Trend Controller interface. Configuration involves setting up communication protocols and mappings between Modbus slave registers and IQ strategy inputs/outputs. Supported protocols are TCP/IP, RS232, and RS485, and functions 1-6, 15, and 16 can be used.

Uploaded by

jgr77
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

IQ3/XNC Modbus Master v. 2.

8
Installation, configuration and error handling

ElectroCom ApS
Torvet 5, 1.
DK-5700 Svendborg
Denmark

t: +45 88 80 75 80
e:[email protected]
1. Installation
The Modbus Master XNC driver consists of two files:

● .xnc file – Application file


● .xnp file – Configuration file

Quick list for the installation:

1. Download the strategy with the .xnp file


2. Download the .xnc file
1.1. Download the strategy with the .xnp file

Start up SET (System Engineering Tool) and open your strategy. Right-click on the strategy with
the mouse and you will get a menu popping up. In the menu choose “Device”->”XNC Interface
Module”.

XNC Interface module is opened then press the “...” button which can be seen in the next screenshot
marked by a red ring. There will be an open dialog and you can choose the .xnp file.

Now download the strategy to the Trend Controller.


1.2. Download the .xnc file

Switch to “System View” and find the Trend Controller. Right-click on it and choose “Download
IQ3/XNC Application”. This will open a new dialog where you press the “Open File” button and an
open dialog will appear which is used to find the .xnc file.

Now press the download button and the Modbus Master XNC driver will be installed on the Trend
Controller but still needs configuration.
2. Configuration

The Modbus master can be configured according to the Modbus standard. The available
communication protocols are TCP/IP, RS232 and RS485. Both ASCII and RTU package formats
are supported. Function 1 – 6, 15 and 16 are supported at the moment. The module continuously
synchronises registers in Modbus slaves attached to the Modbus master with inputs or outputs in the
IQ strategy.

To configure the module use the following steps:


1. Configuration of communication
2. Configuration of slave register to IQ strategy mappings

The Modbus master is configured in the XNC Interface Module. String values in the Store area
defines the configuration. The screen shot below is an example of a configuration of the Modbus
master. Predefined configurations (XNP-files) can be selected by clicking “...” next to “XNC App.”.

The String Value for communication specifies how to communicate with the slaves. The String
Values for Mapping specifies how to map the slaves onto the IQ strategy.

The Modbus master can be used in conjunction with the ElectroCom XNC Tool. Configurations for
the Modbus master can be made within and debug information from the Modbus master can be
viewed from the tool.
In order to use the ElectroCom XNC Tool the Modbus master must know the IP address of the PC
that is running the tool. The connection will be made to port 3532. It is recommended that the
debug IP address is deleted when no debug is needed since the Trend IQ3/XNC Modbus master
otherwise continuously would try to make a connection to that IP address.
• Use the String Value for debug_IP to specify the IP Address.

The amount of debug information posted to the ElectroCom XNC Tool (debug level) can be
selected. Posts with a level lower or equal to the debug level are send.
• Use the String Value for debug_level to specify the debug level
∙ 0 – No debug
∙ 1 – Alarms
∙ 2 – Warnings
∙ 3 – Debug

Input and output labels can be a given arbitrary name in order to make the IQ strategy more
readable.
2.1. Configuration of communication

Use the string value of communication to configure the protocol and package format. The string
contains a number of tokens separated by a “;”. The tokens are interpreted according to the desired
protocol.

RS232
In order to use this protocol the baud rate, the number of data bits, the number of stop bits, the
parity, the package format and the delay in seconds between updates must be specified according to
the following list.

• Baud rate: 2400, 4800, 9600, 19200, 38400, 57600 ...


• Data bits: 7 or 8
• Stop bits: 1 or 2
• Parity: 0 (NONE), 1 (ODD) or 2 (EVEN)
• Package format: ASCII or RTU
• Delay: Time in seconds

The configuration string must comply with the format below.

RS232 ; Baud rate ; Data bits ; Stop bits ; Parity ; Package format ; Delay ;

Example of a configuration for RS232 using 9600 baud, 8 data bits, 1 stop bit, no parity, ASCII
package format and 1 second delay between updates:

RS232;9600;8;1;0;ASCII;1;

RS485
In order to use this protocol the type, the baud rate, the number of data bits, the number of stop bits,
the parity, the package format and the delay in seconds between updates must be specified
according to the following list.

• Type: RS485 2 wire or RS485 4 wire


• Baud rate: 2400, 4800, 9600, 19200, 38400, 57600 ...
• Data bits: 7 or 8
• Stop bits: 1 or 2
• Parity: 0 (NONE), 1 (ODD) or 2 (EVEN)
• Package format: ASCII or RTU
• Delay: Time in seconds

The configuration string must comply with the format below.

Type ; Baud rate ; Data bits ; Stop bits ; Parity ; Package format ; Delay ;
Example of a configuration for RS485 2 wire using 9600 baud, 8 data bits, 1 stop bit, no parity,
RTU package format and 1 second delay between updates:

RS485 2 wire;9600;8;1;0;RTU;1;

TCP/IP
In order to use this protocol only the delay in seconds between updates must be specified.

The configuration string must comply with the format below.

TCP/IP ; Delay ;

Example of a configuration for TCP/IP and a 2 second delay between updates:

TCP/IP;2;
2.2. Configuration of slave register to IQ strategy mappings

A mapping specifies how registers at a Modbus slave are mapped onto the IQ strategy. A mapping
is defined by the IP address (only when using TCP/IP), the address of the slave, the function to use,
the starting register address in the slave, the starting number of IQ strategy input/output and the
number of registers. A mapping configuration string must comply with the format below.

IP address ; Slave address ; Function ; Slave ; Starting IQ ; Number of ;


(only number register strategy registers
TCP/IP) address input/output

Example of a mapping (not TCP/IP) from slave with address 1, using function 2, from register
starting at 0, to output starting at 1 and a total of 2 registers are mapped:

1;2;0;1;2;

Example of a mapping (TCP/IP) from slave with address 1, using function 2, from register starting
at 0, to output starting at 1 and a total of 2 registers are mapped:

192.168.10.98;1;2;0;1;2;

Mapping strings are specified using the string values for Mapping.

The maximum number of allowed slaves are determined by the version of the master. Versions for
1, 5 and 32 slaves are available.

Whether or not the registers are mapped to input or output is dependent on the function. Some
functions read from the slave and are therefore mapped to output, and some functions write to the
slave and are therefore mapped to input. See the table below or other Modbus documentation
(www.modbus.org) for description of the functions:

Function Function name Read/Write Input/Outp 1 bit/16bit


number ut at slave at slave
1 Read Coil Status Read Output 1 bit
2 Read Input Status Read Input 1 bit
3 Read Holding Registers Read Output 16 bit
4 Read Input Registers Read Input 16 bit
5 Force Single Coil Write Output 1 bit
6 Preset Single Register Write Output 16 bit
15 Force Multiple Coils Write Output 1 bit
16 Force Multiple Registers Write Output 16 bit
2.3. Configuration of the Slave registers data format

Modbus Slave units can have values in the Modbus registers presented in a lot of different data
formats. This situation only occurs when using Modbus functions 3, 4, 6 and 16.

The affected Modbus registers are Holding and Input Registers. They can contain a value from 0 to
65535. When using different data formats you can have negative, bigger and decimal values.

Data format Possible values Size Description


Unsigned16 0 to 65535 1 This is a normal Modbus register
Unsigned32 0 to 4294967295 2 Adding 2 registers gives a higher value
Signed16 -32767 to 32767 1 Can contain negative values
Signed32 -2147483647 to 2147483647 2 Adding 2 register gives higher negative values
Float32 Decimal values 2 Float can contain decimal and negative values

It is optional to extend a IQ strategy mapping with data format. Example showing Modbus registers
read in data format Float32.

1;3;0;1;2;F32L;

There has been added “F32L” to the IQ strategy mapping. The first character tells if the data format
is signed, unsigned or float. In this example it is a float, “F”. This table will show all the
combinations.

Data format Format Size Order Mapping


Unsigned16 “U” “16” “” * “U16”
Unsigned32 “U” “32” “L” or “B” “U32L” or “U32B”
Signed16 “S” “16” “” * “S16”
Signed32 “S” “32” “L” or “B” “S32L” or “S32B”
Float32 “F” “32” “L” or “B” “F32L” or “F32B”

* For Unsigned16 and Signed16 Order do not have any importance and is ignored.

Order is used for those data formats which are bigger than 1 Modbus Register. The order tells
which Modbus Register is the least significant part or most significant part. “L” for little part first
(least significant part) and “B” for big part first (most significant part).
3. Error handling
When an error occurs a LED will be flashed at the Trend controller. There are defined three
different errors:
• No response from slave – Green LED flashes (number 2)
• Error in response from slave – Red LED flashes (number 3)
• LRC/CRC error in package – Yellow LED flashes (number 4)

During each pause a yellow LED (number 1) and a green LED (number 2) flashes.

Only on serial versions of the XNC have LEDs.


4. FAQ
FAQ is short for Frequently Asked Questions. This is a short compilation of questions and answer
which can have the solution for a problem with the XNC Modbus Master.

Q: How to split a value from a Modbus Register to bits in SET strategy?

Q: How to combine several bits to a value for a Modbus Register in SET strategy?