Building Design 2 Final Examination: Load Schedule

This document provides a load schedule detailing 10 electrical circuits in a building. It includes information such as the number and type of loads on each circuit, the voltage and amperage draw. The total connected load is 10,440 VA, with a demand factor of 76.67% and total demand load of 8,004 VA. The maximum current draw is calculated to be 45.39 amps. Based on these calculations, a 75 amp, 3-phase, 240 volt circuit breaker with a 100 amp frame is recommended along with 2/22 mm2 copper wire and an 8 mm2 grounding conductor.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
123 views1 page

Building Design 2 Final Examination: Load Schedule

This document provides a load schedule detailing 10 electrical circuits in a building. It includes information such as the number and type of loads on each circuit, the voltage and amperage draw. The total connected load is 10,440 VA, with a demand factor of 76.67% and total demand load of 8,004 VA. The maximum current draw is calculated to be 45.39 amps. Based on these calculations, a 75 amp, 3-phase, 240 volt circuit breaker with a 100 amp frame is recommended along with 2/22 mm2 copper wire and an 8 mm2 grounding conductor.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD SCHEDULE

DF AMPERES CKT. BREAKER DIAMETER OF


CKT # DESCRIPTION OF LOADS VA VOLTS GROUNDINGS SIZE OF WIRE
(%) CONDUIT
1ɸ AT AF POLE

+2.0 mm2 THHN Copper 2 x 2.0 mm2 THHN 20mm Diameter


1 9 LIGHTING OUTLET @100 VA 900 100 230 3.91 15 50 2 Copper wire
wire uPVC PIPE

+3.5 mm2 THHN Copper 2 x 3.5 mm2 THHN 20mm Diameter


2 7 CONVENIENCE OUTLET @180 VA 1260 100 230 5.48 20 50 2 wire Copper wire uPVC PIPE

+2.0 mm2 THHN Copper 2 x 2.0 mm2 THHN 20mm Diameter


3 9 LIGHTING OUTLET @100 VA 900 100 230 3.91 15 50 2 Copper wire
wire uPVC PIPE

2
+3.5 mm THHN Copper 2 x 3.5 mm2 THHN 20mm Diameter
4 7 CONVENIENCE OUTLET @180 VA 1260 50 230 5.48 20 50 2 wire Copper wire uPVC PIPE

+2.0 mm2 THHN Copper 2 x 2.0 mm2 THHN 20mm Diameter


5 8 LIGHTING OUTLET @100 VA 800 50 230 3.48 15 50 2 Copper wire
wire uPVC PIPE

+2.0 mm2 THHN Copper 2 x 2.0 mm2 THHN 20mm Diameter


6 10 LIGHTING OUTLET @100 VA 1000 50 230 4.35 15 50 2 Copper wire
wire uPVC PIPE

+3.5 mm2 THHN Copper 2 x 3.5 mm2 THHN 20mm Diameter


7 6 CONVENIENCE OUTLET @180 VA 1080 80 230 4.70 20 50 2 wire Copper wire uPVC PIPE

+2.0 mm2 THHN Copper 2 x 5.5 mm2 THHN 20mm Diameter


8 9 LIGHTING OUTLET @100 VA 900 80 230 3.91 15 50 2 Copper wire
wire uPVC PIPE

+3.5 mm2 THHN Copper 2 x 3.5 mm2 THHN 20mm Diameter


9 8 CONVENIENCE OUTLET @180 VA 1440 80 230 6.26 20 50 2 Copper wire
wire uPVC PIPE

+2.0 mm2 THHN Copper 2 x 2.0 mm2 THHN 20mm Diameter


10 9 LIGHTING OUTLET @100 VA 900 80 230 3.9100 15 50 2 Copper wire
wire uPVC PIPE

45.39

TOTAL CONNECTED LOAD (VA) 10440 DEMAND FACTOR ( DF ), % 76.67 FEEDER PROTECTION

USE : 75AT, 3P, 240V, 100 AF


TOTAL DEMAND LOAD (VA) 8004 CURRENT (AMPS) 45.39 51 AMPS
MOLDED CASE CKT. BREAKER

TOTAL LINE CURRENT ( IL ), AMPS 36.30 MOTOR LOAD CONTRIBUTION (AMPS) 6.00 FEEDER CONDUCTOR

2 x 22 mm2 THHN Copper wire


51 AMPS
+ 8.0 mm2 Grounding Conductor

\Users\neilmadelo\Desktop\E1.png
\Users\neilmadelo\Desktop\E2.png
\Users\neilmadelo\Desktop\E4.png

TABULATED LOAD COMPUTATIONS AND LEGENDS


SCALE 1:100m

SUBMITTED BY ACTIVITY: SUBMITTED TO PAGE NO. RATING

3
MANGALINO, KENT ALDWIN ENGR. FELIX C. ALINDADA
BACHELOR OF SCIENCE IN CIVIL ENGINEERING BUILDING DESIGN 2 FINAL EXAMINATION PROFESSOR