Western Metal Industries LTD Yavat - Harmonics Case Study
Western Metal Industries LTD Yavat - Harmonics Case Study
OF
Date 29.05.17
The scenario as regards Electrical loads, Utility Tariff structures and Electrical Power Quality
issues is rapidly changing. A fresh approach is needed to protect the Electrical installation from
adverse impact of these changes. Electrical Loads today are increasingly Non Linear in nature
and lead to poor Power Quality. Electrical circuits carry currents of undesirable frequencies
besides fundamental current of 50Hz or 60Hz. Fundamental current performs the intended work
of catering to power needs of the loads whereas currents of frequencies which are multiples of
fundamental frequency create various undesirable effects in the Electrical network.
The term “Harmonic Currents” is a popular buzz word in the power quality industry and the
layman needs some information to understand the term and realize they can be a serious problem
if not treated properly. The treatment and the details of harmonics is better left to the expert with
the proper tools and training.
Western Group of Companies was established in 1960, by a group having rich experience of 30 years
in manufacturing of aluminium products. Today WESTERN stands tall among all Indian manufacturers
of Aluminium Circles, Strips, Sheets and in particular, Aluminium Slugs.
• Solution:
1. After installation, Commissioning of 650KVAr, 525V Tuned RTPFC panel and 100Amp Active
Harmonic Filter, significant reduction of harmonic has been achieved at Unity Power Factor:
• Voltage Harmonics are reduced from 16.5% to 2.5%.
• Current Harmonics are reduced from 77.1% to 7.1% at secondary side of 630KVA Transformer.
2. The Power Factor is maintained to 0.998 lag after installation of panels.
• Customer Benefits: