Comnavsurflantinst 3541.1a PDF
Comnavsurflantinst 3541.1a PDF
COMNAVSURFORINST 3541.1A
1. Purpose. To issue the Surface Force Repair Party Manual (RPM) for
Commander Naval Surface Forces Atlantic/Commander Naval Surface Force
Pacific ships.
P. A. GUMATAOTAO
Chief of Staff
Distribution:
Electronic only via COMNAVSURFOR Directives Website,
https://www.surfor.navy.mil/cl/directives/default.aspx
2
COMNAVSURFORINST 3541.1A
9 Jun 08
3
COMNAVSURFORINST 3541.1A
9 Jun 08
SURFACE FORCES
STANDARD REPAIR PARTY MANUAL
Enclosure (1)
COMNAVSURFORINST 3541.1A
9 Jun 08
RECORD OF CHANGES
SIGNATURE OF
CHANGE DATE DATE PERSON
NUMBER OF CHANGE ENTERED MAKING CHANGE
ii
COMNAVSURFORINST 3541.1A
9 Jun 08
TABLE OF CONTENTS
iii
COMNAVSURFORINST 3541.1A
9 Jun 08
Tab A - DCRS and Damage Control Unit Locker/ 2-6
Damage Control Unit Patrol Station Areas of
Responsibility
CHAPTER 4 - FIREFIGHTING
iv
COMNAVSURFORINST 3541.1A
9 Jun 08
Tab G - Electrical Isolation 4-29
v
COMNAVSURFORINST 3541.1A
9 Jun 08
Section 3 - Casualty Power System 6-5
APPENDICES
vi
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 1
DAMAGE CONTROL ORGANIZATION AND RESPONSIBILITIES
SECTION 1
FUNDAMENTAL PRECEPTS
1-1
COMNAVSURFORINST 3541.1A
9 Jun 08
e. The CO is responsible for adherence to, and the
effective application of, the principles and standards
established in this and all damage control publications. These
standards are the minimum; they should not restrict the CO’s
decision to take additional action to control damage. Listed
below are some basic tenets of damage control.
(4) Know your way around your ship even in the dark.
1-2
COMNAVSURFORINST 3541.1A
9 Jun 08
1-3
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
REQUIRED INFORMATION
1-4
COMNAVSURFORINST 3541.1A
9 Jun 08
1-5
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 3
GENERAL REQUIREMENTS
1-6
COMNAVSURFORINST 3541.1A
9 Jun 08
(7) Charts, nomograms, and other required materials to
calculate various radiological factors.
1-7
COMNAVSURFORINST 3541.1A
9 Jun 08
1304. DCRS INVENTORIES
1-8
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 4
DAMAGE CONTROL ORGANIZATION
1400. DC ORGANIZATION
(2) Electrician1
NOTE:
1
Rapid Response Team - Shall report directly to the scene.
2
Shall be PQS qualified up to DC 308.
3
Back up Team - Shall report to the designated DCRS.
() Denotes the number of personnel required.
Plotter and talker/messenger functions listed in reference (b)
may be performed by Non-Flying Squad personnel on watch in
control stations.
1-9
COMNAVSURFORINST 3541.1A
9 Jun 08
if required (see Figure 1). Primary boundaries, such as fire,
smoke and/or flooding shall be set as required.
1-10
COMNAVSURFORINST 3541.1A
9 Jun 08
FIGURE 1 – DC ORGANIZATION 1 FLOW CHART
Damage Reported
No
Flying Squad
Is the Flying
Set Condition II DC Squad
containing No additional personnel required
CO’s Discretion the damage?
(CO/OOD)
Condition I (GQ)
No
Set Condition II DC
Man 1 or 2 DCRSs as
needed
No
Man additional DCRSs
as needed
Is Condition
II DC Yes No additional personnel required
containing
the damage?
No
GQ
1-11
COMNAVSURFORINST 3541.1A
9 Jun 08
1401. CONCEPT
1-12
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 5
DAMAGE CONTROL TRAINING
1-13
COMNAVSURFORINST 3541.1A
9 Jun 08
e. All Hands General DC PQS Training. The DCA will monitor
and ensure that all ship-wide general DC PQS meet the
requirements set forth in reference (a).
1-14
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
COMMAND POLICES
1-15
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
CONDITION I DAMAGE CONTROL STATION ORDER OF SUCCESSION
1-16
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB C
FLYING SQUAD ORGANIZATION
1-17
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB D
DC COMMUNICATION PLAN
1-18
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB E
DAMAGE CONTROL REPAIR STATION ORGANIZATION CHART
1-19
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB F
ALTERNATE REPAIR PARTY MUSTERING LOCATIONS
1-20
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB G
DCRS INVENTORY/SHORTAGES
1-21
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB H
DAMAGE CONTROL COMMAND AND CONTROL ORGANIZATIONAL CHART
1-22
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB I
IET MANNING CHART
NOTES:
1. If the Fire Marshal is also the Engineering Duty Officer
(EDO), a separate Scene Leader is required.
8. Stationed in CCS/DCC.
9. Any electrical rating (EM, ET, IC, GSE, DS, ST, FC, CTM, GM,
EW) can PQS qualify and serve as the duty electrician.
1-23
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB J
RESCUE AND ASSISTANCE DETAIL MANNING (INPORT/UNDERWAY)
1-24
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 2
INVESTIGATING DAMAGE
SECTION 1
REQUIRED INFORMATION
2-1
COMNAVSURFORINST 3541.1A
9 Jun 08
2-2
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
INVESTIGATING DAMAGE
2-3
COMNAVSURFORINST 3541.1A
9 Jun 08
d. Ship system damage reports must pinpoint the system
affected and damage location by frame. This will ensure that
the required sections of the system are isolated with a minimal
impact on the rest of the ship. The investigator shall be
knowledgeable of all ship’s systems that are in or traverse
their areas of responsibility.
2-4
COMNAVSURFORINST 3541.1A
9 Jun 08
(2) Locating the source or seat of the fire.
2-5
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
DCRS AND DAMAGE CONTROL UNIT LOCKER (DCUL)/DAMAGE CONTROL UNIT
PATROL STATION (DCUPS) AREAS OF RESPONSIBILITY
2-6
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
TANKS AND VOIDS
DCRS 5 (Sample)
2-7
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 3
COMPARTMENT ISOLATION
SECTION 1
REQUIRED INFORMATION
(2) Mechanical
(3) Ventilation
3-1
COMNAVSURFORINST 3541.1A
9 Jun 08
b. List individual items logically while considering its
relative importance. A sample is provided in Chapter 3, TAB A.
3-2
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
COMPARTMENT ISOLATION
3-3
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
COMPARTMENT ISOLATION LISTS/KILL CARDS
ELECTRICAL ISOLATION:
MECHANICAL ISOLATION:
VENTILATION:
3-4
COMNAVSURFORINST 3541.1A
9 Jun 08
HAZARDOUS MATERIALS:
3-5
COMNAVSURFORINST 3541.1A
9 Jun 08
3-6
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 4
FIREFIGHTING
SECTION 1
REQUIRED INFORMATION
4-1
COMNAVSURFORINST 3541.1A
9 Jun 08
4-2
COMNAVSURFORINST 3541.1A
9 Jun 08
o. TAB O, Fixed CO2 Flooding System Actuation Stations.
Per references (d) and (h), list by location all fixed CO2
actuation stations, if applicable.
4-3
COMNAVSURFORINST 3541.1A
9 Jun 08
4-4
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
FIREFIGHTING
4-5
COMNAVSURFORINST 3541.1A
9 Jun 08
(g) If the space is inaccessible, isolate the space,
break out fire fighting equipment, and stand by in the area to
brief the Scene Leader.
(5) Extinguishing the fire. Put the fire out using the
preferred agents listed in Section 2, TAB A. The Damage Control
organization (DCA, RPL, and OSL) should consider the need to use
indirect cooling (fire fighting) prior to using a direct attack,
based on space accessibility. Procedures for indirect fire
fighting are addressed in reference (d).
4-6
COMNAVSURFORINST 3541.1A
9 Jun 08
c. Obstructions (e.g. machinery, thermal, or acoustic
insulation) can shield burning GRP from seawater hose streams or
other extinguishing media. The MHC unmanned machinery spaces
are limited in maneuvering area making it more vital to ensure
complete and reliable fire protection system operation.
4-7
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
FIREFIGHTING METHODS
Electrical/Electronic C 1. CO2
2. HALON 1301
3. Freshwater FF
4. Firemain (not solid stream)
5. AFFF
6. PKP
4-8
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
REPAIR PARTY LEADER'S (RPL) FIREFIGHTING CHECKLIST
4-9
COMNAVSURFORINST 3541.1A
9 Jun 08
___ Investigators report at least every 15 Min. Time _____
4-10
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB C
COMPARTMENT HAZARD
4-11
COMNAVSURFORINST 3541.1A
9 Jun 08
DAMAGE CONTROL REPAIR STATION 5
GALLEY DEEP FAT FRYER PRI - RANGE GUARD
1-260-0-Q SEC - PKP/PORT. AFFF
ELECT ISO ________
4-12
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB D
MAGAZINE SPRINKLER CONTROL VALVES
4-13
COMNAVSURFORINST 3541.1A
9 Jun 08
4-14
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 3
MACHINERY SPACE FIREFIGHTING
4-15
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
CLASS B FIRE- HALON
PROTECTED MACHINERY CASUALTY CHECK-LIST
SPACE
SIZE IT UP FIGHT IT
Casualty initial reports, assessment, Casualty Engagement
evaluation and information. What am I doing to make progress?
What do I have?
ORDERED
EXECUTED
ORDERED
EXECUTED
ORDERED
EXECUTED
B
B Time
B
Time Time Engaged = (Fight It)
Reported = (Size it up) Engage Casualty Steps
7. If smoke is being pulled into adjacent
Report Casualty Steps 1. Verify primary Halon 1301 activated.
machinery spaces from the weather,
1. Verify foam-proportioning station request the ship maneuver, secure 555-10.10.4
manned. ventilation, or have watchstanders use 2. Don’t operate AFFF bilge sprinkling
555-10.9.3 breathing apparatus. longer than 4 minutes. Bilge sprinkling
2. Verify that the oil source is secured. 555-10.9.6c.2 secured at time ____________.
555-10.9.5 8. Verify that the affected space is 555-10.10.8
3. Verify AFFF bilge sprinkling isolated except for firefighting 3. Verify all doors and accesses to space
activated and time (____) activated. equipment, lighting and ventilation. are secured.
Leave bilge sprinkling activated until 555-10.9.6d. 555-10.10.6.1
Fire Out is reported or space is 9. Verify that smoke boundaries are set 4. DC response organization briefed on
evacuated. around the affected space. location of the fire and plant status.
555-10.9.6a. 555-10.9.6e. 555-10.10.10e.
4. Verify plant and operating machinery 10. Investigate for fire spread to 5. Verify mechanical isolation is set.
secured in affected space. adjoining compartments. 555-10.12.2
555-10.9.6b. 555-10.9.6e. 6. Verify electrical isolation is in
5. Verify negative ventilation set in the 11. Fire contained or space evacuation progress.
affected space, or if not possible, report received. 555-10.12.3
ventilation left in operation. 555-10.10 7. Verify that fire boundaries are
555-10.9.6c.1 established around the affected space.
-- -- Note: If fire is contained, go to
6. Verify positive ventilation set in 555-10.12.4
MONITOR IT, Step 1. If space is
unaffected spaces, or if not possible, evacuated, go to FIGHT IT, Step 1.
ventilation left in operation.
555-10.9.6c.2
4-16
COMNAVSURFORINST 3541.1A
ORDERED 9 Jun 08
EXECUTED
B CASUALTY CHECK- LIST
Time
ORDERED
EXECUTED
ORDERED
EXECUTED
8. Establish smoke control. B B
a. Set inner and outer smoke Time Time
boundaries around accesses to the
affected space to establish a -- -- Note: If Halon is Good (effective),
-- -- Note: Steps 17-25 apply for Halon Bad
smoke control zone. follow steps 10 to 16. If Halon is Bad
(ineffective).
555-10.11.2 (ineffective), go to step 17.
17. Secure ventilation within space, if
b. For CPS equipped ships, operate 10. Report that Halon is Good (effective)
operating, and initiate indirect attack
CPS to maintain positive pressure and the fire is contained.
using water high within the space.
on the DC deck. If CPS is 555-10.14.1, 555-10.14.3b.
555-10.16.1a., 555-7.6
ineffective in preventing smoke -- -- Note: Steps 11-13 can be performed
18. Stage attack team with 1-1/2” AFFF
spread to the DC deck, conduct concurrently.
hose during indirect attack. Re-entry via
active desmoking. 11. Following 15-minute Halon soak
escape trunk preferred. Seawater hoses
555-10.11.2.2 period, operate exhaust ventilation, if may be used to cool access doors,
c. For non-CPS ships, use positive available, for at least 15 minutes before hatches, and scuttles intended for use
pressure ventilation in the smoke re-entry.
during re-entry.
control zone. 555-10.14.3b. 555-10.16.1.b. 555-16.1.c
555-10.11.2.3.1 12. Activate AFFF bilge sprinkling a 19. Before the attack team enters the
d. For SES equipped ships, activate second time for at least two minutes. space, a second backup attack AFFF hose
SES in the smoke control zone. 555-10.14.3c.
shall be manned to render assistance.
555-10.11.2.2 13. Have standby AFFF hose manned 555-10.16.1.c
e. For non-SES ships, active and charged, with agent checked. 20. When attack team is manned and
desmoking of smoke control zone 555-10.14.3d indirect attack has been applied for at
may be conducted at the scene 14. Assessment team re-enter with least 5 minutes, secure indirect attack.
leader’s discretion. minimum of two fully protected (FFE and 555-10.16.1.d
555-10.11.2.3 SCBA) fire party members with NFTI 21. Set exhaust ventilation in the space
9. Determine effectiveness of Halon and AFFF extinguishers.
on high, if operable.
1301. 555-10.14.3d. 555-10.16.1.d
a. If 1st shot was ineffective, rapidly 15. Assessment team locate and
assess reason and correct or 22. Operate AFFF bilge sprinkling for at
extinguish any remaining fire, extinguish least 2 minutes.
actuate 2nd shot, as appropriate. minor residual fires. Directs use of AFFF
555-10.14.2, 555-10.14.3a. 555-10.16.1.d
hose, if required.
23. If Halon had been discharged into the
555-10.14.3e.
space, test for HF gas.
-- -- 16. Go to MONITOR IT, Step 1. 555-10.16.1.d
4-17
COMNAVSURFORINST 3541.1A
9 Jun 08
CASUALTY CHECK-LIST
ORDERED
EXECUTED
B MONITOR IT
ORDERED
D
EXECUTE
Time The fight is complete, B
No further spread, Clean it up
24. If HF concentration is acceptable, Time
<90ppm, attack team re-enters with
7. Assess damage before attempting
AFFF, determines if a direct attack is
ORDERED
EXECUTED
restart of any equipment in space. Get
feasible, and extinguishes any remaining B photos and prepare report, as required.
fire.
Time Restore from casualty and debrief team.
555-10.16.1.d
555-10.15.7 and 555-7.10.5
-- -- 25. Go to MONITOR IT, Step 1. No = (Monitor It)
No Casualty Steps
1. Assessment or attack team reports fire
is out and reflash watch is set.
555-10.14.3e.
2. Report when fire overhauled.
555-10.14.3e.
3. As time permits, verify electrical
integrity of ventilation fans for continued
use and operate on high speed for a
minimum of 15 minutes. Otherwise,
exhaust smoke using portable blowers or
overpressure from adjacent spaces
through open accesses to the affected
space.
555-10.15.2.1, 555-10.15.3, 555-10.15.4
4. When space is cleared of smoke, test
for oxygen, combustible and toxic gases.
555-10.15.5
-- -- Note: Steps 5-6 can be performed
concurrently.
5. Dewater space with commanding
officer’s permission.
555-10.15.6
6. Clear space of hazards and certify
space as safe. Reman space.
555-10.15.7
4-18
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
CLASS B FIRE- WATER MIST
CASUALTY CHECK-LIST
PROTECTED MACHINERY
SPACE
SIZE IT UP FIGHT IT
Casualty initial reports, assessment, Casualty Engagement
evaluation and information. What am I doing to make progress?
What do I have?
ORDERED
EXECUTED
ORDERED
EXECUTED
ORDERED
EXECUTED
B B Time
Time Time Engaged = (Fight It)
Reported = (Size it up) 7. If smoke is being pulled into adjacent Engage Casualty Steps
Report Casualty Steps machinery spaces from the weather, 1. Verify Water Mist activated.
1. Verify foam-proportioning and Water request the ship maneuver, secure Verify Water Mist tanks being refilled
Mist stations manned. Verify Water ventilation, or have watchstanders use from potable water tanks.
Mist tanks aligned for refilling. breathing apparatus. 555-10.10. 4
555-10.9.3 555-10.9.6c.2 2. Don’t operate AFFF bilge
2. Verify that the oil source is secured. 8. Verify that the affected space is sprinkling longer than 4 minutes.
555-10.9.5 isolated except for firefighting Bilge sprinkling secured at time
3. Verify AFFF bilge sprinkling equipment, lighting and ventilation. ____________.
activated and time (____) activated. 555-10.9.6d. 555-10.10.8
Leave bilge sprinkling activated until 9. Verify that smoke boundaries are set 3. Verify all doors and accesses to
Fire Out is reported or space is around the affected space. space are secured.
evacuated. 555-10.9.6e. 555-10.10.6.1
555-10.9.6a. 10. Investigate for fire spread to 4. DC response organization briefed
4. Verify plant and operating machinery adjoining compartments. on location of the fire and plant status.
secured in affected space. 555-10.9.6e. 555-10.10.10e.
555-10.9.6b. 11. Fire contained or space evacuation 5. Verify mechanical isolation is set.
5. Verify negative ventilation set in the report received. 555-10.12.2
affected space, or if not possible, 555-10.10 6. Verify electrical isolation is in
ventilation left in operation. -- -- Note: If fire is contained, go to progress.
555-10.9.6c.1 MONITOR IT, Step 1. If space is 555-10.12.3
6. Verify positive ventilation set in evacuated, go to FIGHT IT, Step 1. 7. Verify that fire boundaries are
unaffected spaces, or if not possible, established around the affected space.
ventilation left in operation. 555-10.12.4
555-10.9.6c.2
4-19
COMNAVSURFORINST 3541.1A
9 Jun 08
CASUALTY CHECK-LIST
ORDERED
EXECUTED
ORDERED
EXECUTED
B
B
ORDERED
EXECUTED
B Time
Time
Time
-- - Note: Steps 17-22 apply for Water
8. Establish smoke control. Mist Bad (ineffective).
a. Set inner and outer smoke -- -- Note: If Water Mist is Good -
boundaries around accesses to the (effective), follow steps 10 to 16. If 17. Secure ventilation within space, if
affected space to establish a Water Mist is Bad (ineffective), go to operating, and initiate indirect attack
smoke control zone. step 17. using water high within the space.
555-10.11.2 10. Report that Water Mist is Good 555-10.16.1a., 555-7.6
b. For CPS equipped ships, operate (effective) and the fire is contained. 18. Stage attack team with 1-1/2” AFFF
CPS to maintain positive pressure 555-10.14.2 hose during indirect attack. Re-entry via
on the DC deck. If CPS is -- -- Note: Steps 11-15 can be performed escape trunk preferred. Seawater hoses
ineffective in preventing smoke concurrently. may be used to cool access doors,
spread to the DC deck, conduct 11. Activate AFFF bilge sprinkling a hatches, and scuttles intended for use
active desmoking. second time for at least two minutes. during re-entry.
555-10.11.2.2 555-10.14.4d. 555-10.16.1.b. 555-16.1.c
c. For non-CPS ships, use positive 12. Re-establish or maintain desmoking 19. Before the attack team enters the
pressure ventilation in the smoke with installed ventilation. space, a second backup attack AFFF hose
control zone. 555-10.14.4e. shall be manned to render assistance.
555-10.11.2.3.1 13. Have standby AFFF hose manned 555-10.16.1.c
d. For SES equipped ships, activate and charged, with agent checked. 20. When attack team is manned and
SES in the smoke control zone. 555-10.14.4f indirect attack has been applied for at
555-10.11.2.2 14. Assessment team re-enter with least 5 minutes, secure indirect attack.
e. For non-SES ships, active minimum of two protected (SCBA) fire 555-10.16.1.d
desmoking of smoke control zone party members with AFFF extinguishers. 21. Set exhaust ventilation in the space
may be conducted at the scene 555-10.14.4f., 555-10.14.4g. on high, if operable.
leader’s discretion. 15. Assessment team locate and 555-10.16.1.d
555-10.11.2.3 extinguish any remaining fire, extinguish 22. Attack team re-enters with AFFF,
9. Determine effectiveness of Water minor residual fires. Directs use of AFFF determines if a direct attack is feasible,
Mist. hose, if required. and extinguishes any remaining fire.
a. If Water Mist did not operate, 555-10.14.4f. 555-10.16.1.e
review and reconfigure system -- -- 16. Go to MONITOR IT, Step 1. -- - 23. Go to MONITOR IT, Step 1.
and operate again, as appropriate. -
555-10.14.2, 555-10.14..4b.
4-20
COMNAVSURFORINST 3541.1A
9 Jun 08
CASUALTY CHECK-LIST
MONITOR IT
The fight is complete,
No further spread, Clean it up
ORDERED
EXECUTED
ORDERED
D
EXECUTE
B
Time Time
No = (Monitor It) 6. Clear space of hazards and certify
No Casualty Steps space as safe. Reman space.
1. Assessment team or attack team 555-10.15.7
reports fire is out and reflash watch is set. 7. Assess damage before attempting
555-10.14.4h. restart of any equipment in space. Get
2. Report when fire overhauled. photos and prepare report, as required.
555-10.14.4h. Restore from casualty and debrief team.
3. As time permits, verify electrical 555-10.15.7, 555-7.10.5
integrity of ventilation fans for continued
use and operate on high speed for a
minimum of 15 minutes. Otherwise,
exhaust smoke using portable blowers or
overpressure from adjacent spaces
through open accesses to the affected
space.
555-10.15.2.1, 555-10.15.3, 555-10.15.4
4. When space is cleared of smoke, test
for oxygen, combustible and toxic gases.
555-10.15.5
-- -- Note: Steps 5 and 6 can be performed
concurrently.
5. Dewater space with commanding
officer’s permission.
555-10.15.6
4-21
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB C
ORDERED
EXECUTED
B
ORDERED
EXECUTED
ORDERED
EXECUTED
Time
B Engaged = (Fight It)
Time B Engage Casualty Steps
Reported = (Size it up) Time 1. Verify HFP activated.
Report Casualty Steps 7. If smoke is being pulled into adjacent 555-10.10.4
1. Verify foam-proportioning station machinery spaces from the weather, 2. Don’t operate AFFF bilge sprinkling
manned. request the ship maneuver, secure longer than 4 minutes. Bilge sprinkling
555-10.9.3 ventilation, or have watchstanders use secured at time ____________.
2. Verify that the oil source is secured. breathing apparatus. 555-10.10.8
555-10.9.5 555-10.9.6c.2 3. Verify all doors and accesses to space
3. Verify AFFF bilge sprinkling 8. Verify that the affected space is are secured.
activated and time (____) activated. isolated except for firefighting 555-10.10.6.1
Leave bilge sprinkling activated until equipment, lighting and ventilation. 4. DC response organization briefed on
Fire Out is reported or space is 555-10.9.6d. location of the fire and plant status.
evacuated. 9. Verify that smoke boundaries are set 555-10.10.10e.
555-10.9.6a. around the affected space. 5. Verify mechanical isolation is set.
4. Verify plant and operating machinery 555-10.9.6e. 555-10.12.2
secured in affected space. 10. Investigate for fire spread to 6. Verify electrical isolation is in
555-10.9.6b. adjoining compartments. progress.
5. Verify negative ventilation set in the 555-10.9.6e. 555-10.12.3
affected space, or if not possible, 11. Fire contained or space evacuation 7. Verify that fire boundaries are
ventilation left in operation. report received. established around the affected space.
555-10.9.6c.1 555-10.10 55-10.12.4
6. Verify positive ventilation set in -- -- Note: If fire is contained, go to
unaffected spaces, or if not possible, MONITOR IT, Step 1. If space is
ventilation left in operation. evacuated, go to FIGHT IT, Step 1.
555-10.9.6c.2
4-22
COMNAVSURFORINST 3541.1A
9 Jun 08
CASUALTY CHECK-LIST
ORDERED
D
EXECUTE
B
ORDERED
D
EXECUTE
ORDERED
D
EXECUTE
B B Time
Time Time -- -- Note: Steps 18-25 apply for HFP Bad
(ineffective).
8. Establish smoke control. 10. Report that HFP is Good (effective)
18. Secure ventilation within space, if
f. Set inner and outer smoke and the fire is contained.
operating, and initiate indirect attack
boundaries around accesses to the 555-10.14.5c.1
using water high within the space.
affected space to establish a -- -- Note: Steps 11-13 can be performed
555-10.16.1a., 555-7.6
smoke control zone. concurrently.
19. Stage attack team with 1-1/2” AFFF
555-10.11.2 11. Following 15-minute HFP soak
hose during indirect attack. Seawater
g. For CPS equipped ships, operate period, operate exhaust ventilation, if
hoses may be used to cool access doors,
CPS to maintain positive pressure available, for at least 15 minutes before
hatches, and scuttles intended for use
on the DC deck. If CPS is re-entry. Maintain negative ventilation
during re-entry.
ineffective in preventing smoke during re-entry and overhaul.
555-10.16.1.b. 555-16.1.c
spread to the DC deck, conduct 555-10.14.5c.1., 555-10.14.5c.3.
20. Before the attack team enters the
active desmoking. 12. Activate AFFF bilge sprinkling a
space, a second backup attack AFFF hose
555-10.11.2.2 second time for at least two minutes.
shall be manned to render assistance.
h. For non-CPS ships, use positive 555-10.14.5b
555-10.16.1.c
pressure ventilation in the smoke 13. Have standby AFFF hose manned
control zone. 21. When attack team is manned and
and charged, with agent checked.
555-10.11.2.3.1 indirect attack has been applied for at
555-10.14.5c.3
i. For SES equipped ships, activate least 5 minutes, secure indirect attack.
14. Determine HF level in the space.
SES in the smoke control zone. 555-10.16.1.d
555-10.14.5c.3.
555-10.11.2.2 22. Set exhaust ventilation in the space
15. Assessment team re-enter with
j. For non-SES ships, active on high, if operable.
minimum of two fully protected (FFE and
desmoking of smoke control zone 555-10.16.1.d
SCBA) fire party members with NFTI
may be conducted at the scene 23. If HFP had been discharged into the
and AFFF extinguishers.
leader’s discretion. space, test for HF gas.
555-10.14.5c.3., 555-10.14.5d.
555-10.11.2.3 555-10.16.1.d
16. Assessment team locate and
9. Determine effectiveness of HFP. 24. If HF concentration is acceptable,
extinguish any remaining fire, extinguish
555-10.14.2 <90ppm, attack team re-enters with
minor residual fires. Directs use of AFFF
Note: If HFP is Good (effective), follow AFFF, determines if a direct attack is
-- -- hose, if required.
feasible, and extinguishes any remaining
steps 10 to 17. If HFP is Bad 555-10.14.5e.
(ineffective), go to step 18. fire.
-- -- 17. Go to MONITOR IT, Step 1.
555-10.16.1.d, 555-10.16.1.d
-- -- 25. Go to MONITOR IT, Step 1.
4-23
COMNAVSURFORINST 3541.1A
9 Jun 08
CASUALTY CHECK-LIST
MONITOR IT
The fight is complete,
No further spread, Clean it up
ORDERED
EXECUTED
ORDERED
D
EXECUTE
B B
Time Time
No = (Monitor It) 7. Assess damage before attempting
No Casualty Steps restart of any equipment in space. Get
1. Assessment or attack team reports fire photos and prepare report, as required.
is out and reflash watch is set. Restore from casualty and debrief team.
555-10.14.5e. 555-10.15.7, 555-7.10.5
2. Report when fire overhauled.
555-10.14.5e.
3. As time permits, verify electrical
integrity of ventilation fans for continued
use and operate on high speed for a
minimum of 15 minutes. Otherwise,
exhaust smoke using portable blowers or
overpressure from adjacent spaces
through open accesses to the affected
space.
555-10.15.2.1, 555-10.15.3, 555-10.15.4
4. When space is cleared of smoke, test
for oxygen, combustible and toxic gases.
555-10.15.5
-- -- Note: Steps 5 and 6 can be performed
concurrently.
5. Dewater space with commanding
officer’s permission.
555-10.15.6
6. Clear space of hazards and certify
space as safe. Reman space.
555-10.15.7
4-24
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB D
CLASS B FIRE IN MACHINERY
SPACE- AGENT NOT AVAILABLE CASUALTY CHECK-LIST FIGHT IT
Casualty Engagement
SIZE IT UP What am I doing to make progress?
Casualty initial reports, assessment,
evaluation and information.
ORDERED
EXECUTED
What do I have?
B
ORDERED
EXECUTED
ORDERED
EXECUTED
B Time
Time Engaged = (Fight It)
Reported = (Size it up) B Engage Casualty Steps
Report Casualty Steps Time 1. Don’t operate AFFF bilge sprinkling
1. Verify foam-proportioning station 8. Verify that the affected space is longer than 4 minutes. Bilge sprinkling is
manned. 555-10.9.3 isolated except for firefighting secured at time ____________.
2. Verify that the oil source is secured. equipment, lighting and ventilation. 555-10.10.8
555-10.9.5 555-10.9.6d. 2. Verify all doors and accesses to space
3. Verify AFFF bilge sprinkling 9. Verify that smoke boundaries are set are secured.
activated and time (____) activated. around the affected space. 555-10.10.6.1
Leave bilge sprinkling activated until 555-10.9.6e. 3. Verify space ventilation secured.
Fire Out is reported or space is 10. Investigate for fire spread to 555-10.10.6.1
evacuated. adjoining compartments. 4. DC response organization briefed on
555-10.9.6a. 555-10.9.6e. location of the fire and plant status.
4. Verify plant and operating machinery 11. Fire contained or space evacuation 555-10.10.10e.
secured in affected space. report received. 5. Verify mechanical isolation is set.
555-10.9.6b. 555-10.10 555-10.12.2
5. Verify negative ventilation set in the -- -- Note: If fire is contained, go to 6. Verify electrical isolation is in
affected space, or if not possible, MONITOR IT, Step 1. If space is progress.
ventilation left in operation. evacuated, go to FIGHT IT, Step 1. 555-10.12.3
555-10.9.6c.1 7. Verify fire boundaries are established
6. Verify positive ventilation set in around the affected space.
unaffected spaces, or if not possible, 555-10.12.4
ventilation left in operation.
555-10.9.6c.2
7. If smoke is being pulled into adjacent
machinery spaces from the weather,
request the ship maneuver, secure
ventilation, or have watchstanders use
breathing apparatus.
555-10.9.6c.2
4-25
COMNAVSURFORINST 3541.1A
9 Jun 08
CASUALTY CHECK-LIST
MONITOR IT
The fight is complete,
No further spread, Clean it up
ORDERED
EXECUTED
ORDERED
EXECUTED
ORDERED
EXECUTED
B B B
Time Time Time
8. Establish smoke control. 10. Stage attack team with 1-1/2” AFFF No = (Monitor It)
k. Set inner and outer smoke hose during indirect attack. Re-entry via No Casualty Steps
boundaries around accesses to the escape trunk preferred. Seawater hoses 1. Attack team reports fire is out and
affected space to establish a may be used to cool access doors, reflash watch is set. 555-10.16.1.f
smoke control zone. hatches, and scuttles intended for use 2. Report when fire overhauled.
555-10.11.2 during re-entry. 555-10.16.1.f
l. For CPS equipped ships, operate 555-10.16.1.b. 555-16.1.c 3. As time permits, verify electrical
CPS to maintain positive pressure 11. Before the attack team enters the integrity of ventilation fans for continued
on the DC deck. If CPS is space, a second backup attack AFFF hose use and operate on high speed for a
ineffective in preventing smoke shall be manned to render assistance. minimum of 15 minutes. Otherwise,
spread to the DC deck, conduct 555-10.16.1.c exhaust smoke using portable blowers or
active desmoking. 12. When attack team is manned and overpressure from adjacent spaces
555-10.11.2.2 indirect attack has been applied for at through open accesses to the affected
m. For non-CPS ships, use positive least 5 minutes, secure indirect attack. space.
pressure ventilation in the smoke 555-10.16.1.d 555-10.15.2.1, 555-10.15.3, 555-10.15.4
control zone. 13. Set exhaust ventilation in the space 4. When space is cleared of smoke, test
555-10.11.2.3.1 on high, if operable. for oxygen, combustible and toxic gases.
n. For SES equipped ships, activate 555-10.15.5
555-10.16.1.d
SES in the smoke control zone. 14. Operate AFFF bilge sprinkling for at -- -- Note: Steps 5 and 6 can be performed
555-10.11.2.2 least 2 minutes. concurrently.
o. For non-SES ships, active 555-10.16.1.d 5. Dewater space with commanding
desmoking of smoke control zone 15. Attack team re-enters with AFFF, officer’s permission. 555-10.15.6
may be conducted at the scene determines if a direct attack is feasible, 6. Clear space of hazards and certify
leader’s discretion. and extinguishes any remaining fire. space as safe. Reman space. 555-10.15.7
555-10.11.2.3 555-10.16.1.e 7. Assess damage before attempting
9. Secure ventilation within space, if 16. Go to MONITOR IT, Step 1. restart of any equipment in space. Get
-- -- photos and prepare report, as required.
operating, and initiate indirect attack
using water high within the space. Restore from casualty and debrief team.
555-10.16.1a., 555-7.6.1.j 555-10.15.7 and 555-7.10.5
4-26
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB E
FIRE BOUNDARIES
BOUNDARY or GROUP #
COMPARTMENT NAME/NUMBER
BULKHEAD/DECK
FIRE STATION/# Hose Lengths
RESPONSIBLE PARTY (INPT/UW)
OBA/SCBA REQUIRED? (Y/N)
BOUNDARY or GROUP #
COMPARTMENT NAME/NUMBER
BULKHEAD/DECK
FIRE STATION/# Hose Lengths
RESPONSIBLE PARTY (INPT/UW)
OBA/SCBA REQUIRED? (Y/N)
4-27
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB F
SMOKE BOUNDARIES
PRIMARY:
(INCLUDING BUFFER ZONE)
FITTING NUMBER
CLASSIFICATION
CURTAIN/BLANKET
RESPONSIBLE PARTY
INPT/UW
OBA/SCBA REQUIRED? (Y/N)
SECONDARY:
(OUTSIDE BUFFER ZONE)
FITTING NUMBER
CLASSIFICATION
CURTAIN/BLANKET
RESPONSIBLE PARTY
INPT/UW
OBA/SCBA REQUIRED? (Y/N)
ISOLATION LIST
4-28
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB G
ELECTRICAL ISOLATION
ELECTRICAL SYSTEMS
SYSTEM TYPE
NOUN NAME
CKT NUMBER
LOCATION
RESPONSIBLE PARTY (INPT/UW)
FUSE/CKT BKR
PRIMARY/ALTERNATE
4-29
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB H
MECHANICAL ISOLATION
MECHANICAL SYSTEMS
TYPE
NOUN NAME
VALVE NUMBER
REMOTE OPERATOR
RESPONSIBLE PARTY (INPT/UW)
PRIORITY
4-30
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB I
VENTILATION SYSTEMS
NATURAL/FAN
CONTROLLER
LOCATION
REMOTE CONTROLLER LOCATION
CLSR TYPE
DESIGNATION
AREA SERVED
WTRDECK
INTAKE
WTRDECK
EXHAUST
RESPONSIBLE PARTY (INPT/UW)
4-31
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB J
DE-WATERING FROM OUTSIDE THE SPACE
SPACE TO DEWATER
EDUCTOR NUMBER USED
OPEN THE FOLLOWING VALVES (LOC. OF OPERATORS)
PRIMARY/ALTERNATE
4-32
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB K
OBA CANISTER/SCBA CHANGE-OUT AREA/SCBA CHARGING STATION
FIRE LOCATION
DCRS RESPONSIBILITY
ALTERNATE LOCATION
DCRS RESPONSIBILITY
AUX 1
MER 1
GEN ROOM
4-33
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB L
PRIMARY/SECONDARY SPACE REENTRY PLAN
SPACE: _______________
HOSE NUMBER
FIREPLUG NUMBER
LENGTHS OF HOSE
IN-LINE EDUCTOR? YES/NO
AFFF HOSE REELS? YES/NO
#1 HOSE
#2 HOSE
HOSE NUMBER
FIREPLUG NUMBER
LENGTHS OF HOSE
IN-LINE EDUCTOR? YES/NO
AFFF HOSE REELS? YES/NO
#1 HOSE
#2 HOSE
4-34
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB M
DE-SMOKING
SPACE
LOCATION
PRIMARY
LOCATION
ALTERNATE
DCRS RESPONSIBLE
PRIMARY
DCRS RESPONSIBLE
ALTERNATE
DE-SMOKING PLAN
STANDARD METHODS
FROM VIA TO
FROM VIA TO
4-35
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB N
ATMOSPHERIC TESTING
Note: Ship must list the atmospheric tests that may be required
during post-fire gas free testing for each machinery space.
Different spaces may require different gas free tests based on
the potential hazards in that particular space. (e.g., if HALON
1301 has been discharged, a test of Hydrogen Fluoride shall be
done.) References (a) and (c) apply.
4-36
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB O
FIXED CO2 FLOODING SYSTEM ACTUATION STATIONS
4-37
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB P
HALON/HFP FLOODING SYSTEM ACTUATION STATIONS
4-38
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB Q
AFFF STATIONS
4-39
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB R
SMOKE EJECTION SYSTEM (SES)
Spaces Protected
By TYPE I
By TYPE II
By TYPE III
4-40
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB S
TOXIC GAS BILL
4-41
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB T
FIRE/SMOKE DETECTION SYSTEMS
Detection Zones
Frame XX to XXX
Zone X at X-XXX-X-X
Power Source (PRI/ALT)
UPS (YES/NO)
4-42
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB U
WATER MIST FIRE EXTINGUISHING SYSTEM (WMFES)
Pump Locations:
Activation Stations:
4-43
COMNAVSURFORINST 3541.1A
9 Jun 08
Primary and Secondary Alignment Procedures: Use the following
sequence to actuate Water Mist utilizing the Primary or
Secondary Pump.
WARNING: Do not use two pumps simultaneously for the same space
when the primary pump is functioning correctly.
4-44
COMNAVSURFORINST 3541.1A
9 Jun 08
4-45
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 5
SHIP STABILITY AND FLOODING CONTROL
SECTION 1
REQUIRED INFORMATION
5-1
COMNAVSURFORINST 3541.1A
9 Jun 08
5-2
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
REQUIRED AND AVAILABLE STABILITY
5200. STABILITY
5-3
COMNAVSURFORINST 3541.1A
9 Jun 08
(b) Electrically isolate affected space(s)
5-4
COMNAVSURFORINST 3541.1A
9 Jun 08
(d) Heavy winds and seas combined with flooding
damage.
5-5
COMNAVSURFORINST 3541.1A
9 Jun 08
Table 1
Flooding Exceeds
Floodable Length FLB, De-Water, Shore Holes and Bulkheads
List to the Danger FLB, Determine Cause of List, Correct for GM,
Angle Correct for Off-Center Weight
5-6
COMNAVSURFORINST 3541.1A
9 Jun 08
(b) List caused by negative metacentric height only:
5203. PREVENTION
5-7
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
STRIP SHIP BILL
5-8
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
JETTISON BILL
5-9
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB C
MODIFIED ZEBRA BILL
5-10
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 6
REPAIRING DAMAGE IN ACTION
SECTION 1
Required Information
6-1
COMNAVSURFORINST 3541.1A
9 Jun 08
6-2
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
SHORING
6-3
COMNAVSURFORINST 3541.1A
9 Jun 08
c. Carefully inspect equipment located near damage.
Weakened supports under guns and machinery may not be readily
noticed. These must be shored so further operation will not
make the problem worse.
6-4
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 3
CASUALTY POWER SYSTEMS
6-5
COMNAVSURFORINST 3541.1A
9 Jun 08
6302. PROCEDURE FOR RIGGING CASUALTY POWER
6-6
COMNAVSURFORINST 3541.1A
9 Jun 08
l. The DCA will request that the Bridge pass the word,
"Stand clear of casualty power cables rigged between frames
____ and ____" (every 5 minutes)
(1) Test the bulkhead terminal and rig that end ONLY.
6-7
COMNAVSURFORINST 3541.1A
9 Jun 08
(3) Disconnect the casualty power cable from the riser
(or bulkhead terminal) leading from the switchboard compartment.
g. The DCA will inform the Engineer Officer who will then
direct the energizing of appropriate power supply circuits. The
Engineer Officer will notify the OOD when the casualty has been
repaired and the normal power source has been restored.
6-8
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
CASUALTY POWER BILL
The following pages lay out the various routes to be used when
rigging casualty power from designated vital equipment to an
available power source. The responsible DCRS and the terminals
and cables to be used are listed. Other routes may be used, but
those listed below are the "best case scenario" (the shortest
available). In case of damage or other obstruction, the DCA
will order an alternate route. The DCRS responsible for rigging
casualty power is identified in the column on the right.
Note: Casualty power can only provide power from one source to
one load, regardless of ABT or MBT at the power panel or
controller. On some ships certain important equipment (e.g.
HPAC, FOTP) may be on a non-vital circuit where there is no
casualty power terminal at the power panel. If this equipment
is required, then casualty power must be rigged directly into
the motor controller. This is a special case requiring
additional precautions.
TO 1E SWBD:
TO 1SA/1SB SWBD:
6-9
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
CASUALTY POWER CHECKLIST
___ Open power panel breakers to load and tag them out (OOC).
___ DCA order Main Control to open and tag-out load circuit
breakers on Norm/Alt/Emergency power supplies.
6-10
COMNAVSURFORINST 3541.1A
9 Jun 08
CHAPTER 7
CHEMICAL, BIOLOGICAL, AND RADIOLOGICAL DEFENSE
SECTION 1
REQUIRED INFORMATION
7-1
COMNAVSURFORINST 3541.1A
9 Jun 08
7-2
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 2
CHEMICAL WARFARE
7-3
COMNAVSURFORINST 3541.1A
9 Jun 08
agent types nor detect chemical agent vapors. Extremely high
temperatures, scuffs, or certain types of organic liquids and
decontaminating solution number 2 (DS2) cause the M9 paper to
falsely react positive. (DS 2 is not authorized for use on
Naval vessels.) M9 paper is much more sensitive than M-8 paper.
7-4
COMNAVSURFORINST 3541.1A
9 Jun 08
• Flush (irrigate) your eye or eyes immediately with copious
amounts of water. To irrigate the eyes with water (from a
canteen or other container of uncontaminated water) tilt
your head to one side, open the eyelids as wide as
possible, and slowly pour water into the eye so that it
will run off the side of your face to avoid spreading the
contamination. DO NOT use your fingers or gloved hand to
hold the eyelids apart. You must irrigate your eyes
despite the presence of toxic vapors in the atmosphere.
Hold your breath and keep your mouth closed to prevent
contamination and absorption through the mucous membranes.
Neutralize chemical agent residue along the flush path on
the face.
• Reseal, clear, and check your mask. Then resume breathing.
7-5
COMNAVSURFORINST 3541.1A
9 Jun 08
7204. DIAGNOSIS OF NERVE AGENT POISONING
7-6
COMNAVSURFORINST 3541.1A
9 Jun 08
(e) Vomiting.
(h) Convulsions.
(i) Unconsciousness.
7-7
COMNAVSURFORINST 3541.1A
9 Jun 08
b. In a single exposure, the eyes are more susceptible than
either the respiratory tract or the skin to mustard. Symptoms
are swelling of eye and/or corneal damage.
b. Hydrogen cyanide
c. Cyanogen chloride
(1) Coughing
(2) Choking
7-8
COMNAVSURFORINST 3541.1A
9 Jun 08
(3) Feeling of tightness in the chest
(4) Nausea
(5) Vomiting
(6) Headache
(7) Lacrimation
7-9
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB A
SELF AID FOR NERVE POISONING
____ Stop breathing, put on your mask, clear and seal the mask,
resume breathing. Secure the mask hood. The mask and
protective clothing are worn until the "all clear" signal
is given.
Note: All liquid nerve agents must be removed from the skin
and/or clothing as described in section 7202 before donning the
over garment.
____ Wait 10-15 minutes. During this time the mild nerve agent
poisoning symptoms should diminish, or the signs of
atropinization will appear (rapid pulse, dry mouth, dry
skin).
____ If vapor hazard still exists make sure the casualty’s mask
is properly adjusted and sealed to the extent practical.
7-10
COMNAVSURFORINST 3541.1A
9 Jun 08
____ Inject the casualty with all 6 injections (or the
remainder).
7-11
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB B
SELF AID FOR BLISTERING AGENT
7-12
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB C
SELF AID FOR BLOOD AGENT
7-13
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB D
SELF AID FOR CHOKING AGENT
7-14
COMNAVSURFORINST 3541.1A
9 Jun 08
7-15
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 3
BIOLOGICAL WARFARE
7-16
COMNAVSURFORINST 3541.1A
9 Jun 08
d. Biological survey is another method of detection. If a
biological attack is suspected because of a large number of
breakouts or other indications, biomedical and environmental
samples can be collected and sent to laboratories. The Bio
Response Kit, maintained in Repair 3 contains the necessary gear
to collect surface samples. Repair Party Monitoring Teams
perform environmental samplings per steps below.
7-17
COMNAVSURFORINST 3541.1A
9 Jun 08
(1) Dress out two personnel in full MOPP gear (JSLST
with MCU-2P).
(8) Remove two swabs from the package and conical tube
from DFU Kit.
Note: If swab dries, break it off into buffer solution and use
another other swab, never rewet and reuse it.
7-18
COMNAVSURFORINST 3541.1A
9 Jun 08
(b) Cover at least a 4 in x 4 in area.
7-19
COMNAVSURFORINST 3541.1A
9 Jun 08
(j) Start timer, set at 15 minutes, after placing
sample fluid into last sample well, if using a watch, write
finish time (15 minutes after last well filled) onto margin of
HHA panel with a marker. Ensure that you do not become
distracted.)
7-20
COMNAVSURFORINST 3541.1A
9 Jun 08
f. Concerning samples, it is important to take sufficient
amounts to allow testing using both onboard systems and off ship
laboratories. When transferring samples off the ship, it is
important to utilize appropriate chain of custody procedures
7-21
COMNAVSURFORINST 3541.1A
9 Jun 08
contact with the sick individual(s) must be quarantined for the
disease’s incubation period. Preventing transmission of the
disease to healthy individuals is the focus of the effort as
well as providing medical care.
7-22
COMNAVSURFORINST 3541.1A
9 Jun 08
7-23
COMNAVSURFORINST 3541.1A
9 Jun 08
SECTION 4
RADIOLOGICAL WARFARE
7401. DETECTION
7-24
COMNAVSURFORINST 3541.1A
9 Jun 08
(2) All personnel inside the skin of the ship will wear
full body coverage and respiratory protection regardless of
7-25
COMNAVSURFORINST 3541.1A
9 Jun 08
status of ventilation (even with Circle William set). When beta
radiation is confirmed absent, full body coverage can be relaxed
but the mask shall still be worn.
7-26
COMNAVSURFORINST 3541.1A
9 Jun 08
TAB E
CBR BILL
7-27
COMNAVSURFORINST 3541.1A
9 Jun 08
APPENDIX A
DCRS FUNCTIONAL REQUIREMENTS
# of Functional
Personnel When Required at Three or more DCRS
Function Required at Condition I ships
Condition I
1 Officer in Charge
2 Fire Marshall
3 Repair Party Leader 1 All 1
4 Scene Leader 1 All 1
5 Plotter 1 All 1
6 Talker 1 All 1(*5)
7 Messenger 1 All 1
8 Investigator 2 All 2
9 Electrician 1 All 1
10 Team Leader 1 Fire 1
11 Nozzleman 2 Fire 2
12 Hoseman 4 Fire 4
13 Smoke Control / Removal 2 Fire 2(*11 & 12)
14 Boundaryman 4 Fire / Flooding 4(*23)
15 Accessman / Overhaulman 1 Fire / Flooding 1(*12)
16 Dewatering 2 Damage / Flooding 2(*18)
17 Shoring 3 Damage / Flooding 3(*19)
18 Pipe Patching 2 Damage / Flooding 2(*16)
19 Hull Patching / Plugging 2 Damage / Flooding 2(*17)
20 Sounding As Required Damage / Flooding 1(*17)
Stretcher Bearer / First 4 per BDS Personnel Casualty PROVIDE BY BDS NOT
21 Aid DCRS
AFFF Station Operator As Required Bravo Fire VARIES BY SHIP CLASS
22 (1/station)
Closure Detail / Zebra As Required by When COND II DC or
23 Setter Area GQ is set VARIES BY SHIP CLASS
Magazine Sprinkler Operator 1 Fire PROVIDED BY
24 WEPS/COMBAT NOT DCRS
25 P-100 Operator As Required As Required AS REQUIRED (*12)
26 P-100 Assistant As Required As Required AS REQUIRED (*12)
DCRS 5 Space Isolation As Required When Ordered
27 Detail AS REQUIRED (*23)
28 Radiological Plotter^ 1 Radiological Defense 1(*3)
29 Radiological Recorder^ 1 Radiological Defense 1(*7)
Radiological CP-95 1 Radiological Defense
30 Operator^ 1(*35)
31 Internal Monitor ^ 1 All CBR Warfare 1(*16)
32 External Monitor^ 1 All CBR Warfare 1(*17)
33 CBR Hoseman^ 2 All CBR Warfare 2(*12)
34 CBR Scrubber^ 1 All CBR Warfare 1(*11)
35 CBR Decon Station Leader^ 1 All CBR Warfare 1(*30)
36 CBR Decon Station Cutter^ 2 All CBR Warfare 2
37 CBR Traffic Control^ 1 All CBR Warfare 1
38 CMWD System Operator^ As Required All CBR Warfare AS REQUIRED (*22)
1(*30) 1 is the minimum number of personnel required to perform the
function
*30 is the line item that can be combined with this function
^ Function of whole ship
A-1
COMNAVSURFORINST 3541.1A
9 Jun 08
APPENDIX B
MCM FUNCTIONAL REQUIREMENTS
# of Functional
Personnel When Required at
Function Required at Condition I
MCM
Condition I
1 Officer in Charge
2 Fire Marshall
3 Repair Party Leader 1 All 1
4 Scene Leader 1 All 1
5 Plotter 1 All 1
6 Talker 1 All 1(*7)
7 Messenger 1 All 1(*6)
8 Investigator 2 All 2
9 Electrician 1 All 1
10 Team Leader 1 Fire 1
11 Nozzleman 2 Fire 2
12 Hoseman 4 Fire 4
13 Smoke Control / Removal 2 Fire 3(*15)
14 Boundaryman 4 Fire / Flooding 3(*14)
15 Accessman / Overhaulman 1 Fire / Flooding 1
16 Dewatering 2 Damage / Flooding 1(*11)
17 Shoring 3 Damage / Flooding 1(*12)
18 Pipe Patching 2 Damage / Flooding 1(*12)
19 Hull Patching / Plugging 2 Damage / Flooding 1(*12)
20 Sounding As Required Damage / Flooding As required
Stretcher Bearer / First 4 per BDS Personnel Casualty
21 Aid 2(provide from BDS)
22 AFFF Station Operator As Required Bravo Fire 2 (total/ship)
Closure Detail / Zebra As Required by When COND II DC or 6(total/ship)(*14
23 Setter Area GQ is set &15)
24 Magazine Sprinkler Operator 1 Fire
1(*30)
1 is the min number of personnel required to perform the function
*30 is the line item that can be combined with this function
^ Function of whole ship
B-1
COMNAVSURFORINST 3541.1A
9 Jun 08
APPENDIX C
MHC-51 FUNCTIONAL REQUIRMENTS
# of Functional
Personnel When Required at
Function Required at Condition I
MHC 51
Condition I
1 Officer in Charge
2 Fire Marshall
3 Repair Party Leader 1 All 1
4 Scene Leader 1 All 1
5 Plotter 1 All 1
6 Talker 1 All 1(*7)
7 Messenger 1 All 1(*6)
8 Investigator 2 All 2
9 Electrician 1 All 1
10 Team Leader 1 Fire 1
11 Nozzleman 2 Fire 1
12 Hoseman 4 Fire 2
13 Smoke Control / Removal 2 Fire 3(*15)
14 Boundaryman 4 Fire / Flooding 2(*8)
15 Accessman / Overhaulman 1 Fire / Flooding 1(*12)
16 Dewatering 2 Damage / Flooding 3
17 Shoring 3 Damage / Flooding 2
18 Pipe Patching 2 Damage / Flooding 4
19 Hull Patching / Plugging 2 Damage / Flooding 4(*18)
20 Sounding As Required Damage / Flooding As required
Stretcher Bearer / First 4 per BDS Personnel Casualty
21 Aid 4(provide from BDS)
22 AFFF Station Operator As Required Bravo Fire 1
Closure Detail / Zebra As Required by When COND II DC or
23 Setter Area GQ is set repair party
Magazine Sprinkler 1 Fire
24 Operator
25 P-100 Operator As Required As Required 1(*16)
26 P-100 Assistant As Required As Required 2(*16)
DCRS 5 Space Isolation As Required When Ordered
27 Detail
28 Radiological Plotter^ 1 Radiological Defense 0
29 Radiological Recorder^ 1 Radiological Defense 0
Radiological CP-95 1 Radiological Defense
30 Operator^ 0
31 Internal Monitor ^ 1 All CBR Warfare 0
32 External Monitor^ 1 All CBR Warfare 0
33 CBR Hoseman^ 2 All CBR Warfare 0
34 CBR Scrubber^ 1 All CBR Warfare 0
35 CBR Decon Station Leader^ 1 All CBR Warfare 0
36 CBR Decon Station Cutter^ 2 All CBR Warfare 0
37 CBR Traffic Control^ 1 All CBR Warfare 0
38 CMWD System Operator^ As Required All CBR Warfare 0
1(*30)
1 is the minimum number of personnel required to perform the function
*30 is the line item that can be combined with this function
^ Function of whole ship
C-1
COMNAVSURFORINST 3541.1A
9 Jun 08
APPENDIX D
PC FUNCTIONAL REQUIREMTENTS
# of Functional
Function Personnel Required When Required at Condition I PC
at Condition I
1 Officer in Charge
2 Fire Marshall
3 Repair Party Leader 1 All 1(*5,6)
4 Scene Leader 1 All 1
5 Plotter 1 All 1(*3,6)
6 Talker 1 All 1(*3,5)
7 Messenger 1 All 1(*8)
8 Investigator 2 All 2(*7)
9 Electrician 1 All 1(*13)
10 Team Leader 1 Fire 0
11 Nozzleman 2 Fire 2(*27)
12 Hoseman 4 Fire 4(*15, 23)
13 Smoke Control / Removal 2 Fire 1(*9)
14 Boundaryman 4 Fire / Flooding 2
15 Accessman / Overhaulman 1 Fire / Flooding 1(*12, 23)
Dewatering 2 Damage / Flooding 2(*17,18,19,
16 25,26)
Shoring 3 Damage / Flooding 2(*16,18,19, 25,
17 26)
Pipe Patching 2 Damage / Flooding 2(*16,17,19, 25,
18 26)
Hull Patching / Plugging 2 Damage / Flooding 2(*16,17,18,
19 25,26)
20 Sounding As Required Damage / Flooding 0
21 Stretcher Bearer / First Aid 4 per BDS Personnel Casualty BDS
22 AFFF Station Operator As Required Bravo Fire 0
23 Closure Detail / Zebra Setter As Required by Area When COND II DC or GQ is set 2(*12, 15)
24 Magazine Sprinkler Operator 1 Fire WEP
P-100 Operator As Required As Required 1(*16,17,18,19,
25 26)
P-100 Assistant As Required As Required 1(*16,17,18,19,
26 25)
27 DCRS 5 Space Isolation Detail As Required When Ordered 1(*11)
28 Radiological Plotter^ 1 Radiological Defense 0
29 Radiological Recorder^ 1 Radiological Defense 0
30 Radiological CP-95 Operator^ 1 Radiological Defense 0
31 Internal Monitor^ 1 All CBR Warfare 0
32 External Monitor^ 1 All CBR Warfare 0
33 CBR Hoseman^ 2 All CBR Warfare 0
34 CBR Scrubber^ 1 All CBR Warfare 0
35 CBR Decon Station Leader^ 1 All CBR Warfare 0
36 CBR Decon Station Cutter^ 2 All CBR Warfare 0
37 CBR Traffic Control^ 1 All CBR Warfare 0
38 CMWD System Operator^ As Required All CBR Warfare 0
1(*30)
1 is the minimum number of personnel required to perform the function
*30 is the line item that can be combined with this function
^ Function of whole ship
D-1