0% found this document useful (0 votes)
111 views20 pages

High Speed Fuses: Section Contents

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
111 views20 pages

High Speed Fuses: Section Contents

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

High Speed Fuses

Section Contents
Page
General Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . 88-89
North American fuses & accessories . . . . . . . . . . . . 90-106
Square Body fuses & accessories . . . . . . . . . . . . . 107-180
BS 88 fuses & accessories . . . . . . . . . . . . . . . . . . . .181-190
Ferrule fuses & accessories. . . . . . . . . . . . . . . . . . . .191-212

High Speed
Fuses
www.DataSheet.co.kr

87
Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

General applications

Rated Voltage For other power factor X

The ac voltage rating of Cooper Bussmann® fuses is given in values, the total clearing
1.0
volts rms. Fuses tested to IEC are tested at 10% above their integral can be calculat-
rated voltage. British Style BS 88 fuses are tested at 5% ed as a multiple of the
above its rated voltage. UL recognition tests are performed at clearing integrals, the
the rated voltage. correction factor K and 0.9
the correction factor X.
Rated Current
Rated current is given in amperes rms. Cooper Bussmann 0.8
fuses can continuously carry the rated current.

Melting Characteristic
The melting char- Arc Voltage 0.7
104 0.1 0.2 0.3 0.4 0.5
acteristic shows
6
COS ␸
4 This curve gives the
the virtual melting 2 1.4
peak arc voltage, U L ,
103 1.2 UL
time in seconds as 6 which may appear
4 103
a function of the across the fuse during its
2 9
prospective current 8
102
operation as a function
in amperes rms. 6
4
7
of the applied working
The fuses are spe- 2 6
voltage, E g , (rms) at a
Virtual Pre-Arcing Time In Seconds

cially constructed 101


6 5
for short-circuit pro- 4 power factor of 15%.
2 4
tection against high
100 Power Losses Eg
level fault currents. 6 3
4
Loading and opera- 2
Watts loss at rated cur- 200 300 400 500 600 660
tion of the fuse in 10–1 rent is given in the electri-
6
www.DataSheet.co.kr 1.0
the non-continu- cal characteristics. The Kp
4 0.8
ous/dashed section 2
curve allows the calcula- 0.6
10–2
of the melt curve 6 tion of the power losses 0.5
must be avoided. 4
at load currents lower 0.4
2
The curve can also 0.3
10 –3
than the rated current .
be read as the real 6
4
The correction factor, K p , 0.2
melting time as a 2

function of the 10–4


is given as a function of
1 2 3
10 2 4 6 8 10 2 4 6 8 10

RMS value of the Prospective Current In Amperes RMS the RMS load current, Ib ,
Ib
in % of the rated current . 0.1
pre-arc current. 30 40 50 60 70 80 90 100%

Clearing Integrals Cut-Off Current


1.5
The total clearing I t at
2 A fuse operation relating to short-circuits only. When a fuse
K
rated voltage and at operates in its current-limiting range, it will clear a short-cir-
1.0
power factor of 15% are cuit in less than 1⁄2 cycle. Also, it will limit the instantaneous
given in the electrical peak let-through current to a value substantially less than
characteristics. For that obtainable in the same circuit if that fuse were replaced
0.5 with a solid conductor of equal impedance.
other voltages, the
0.4
clearing I2t is found by 105

multiplying by correction 0.3


factor, K, given as a
function of applied work- 0.2
Peak Let-Through Current

104

Eg
ing voltage, Eg, (rms).
100 200 300 400 500 600 660
103 A
B

2≈ 10 2
102 103 104 105 106
Prospective Current in Amperes RMS

A asymmetrical current
B symmetrical current

88 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

General applications

Parallel Connection Frequency of Occurrence Overloads (> 1 sec) Impulse Loads (< 1 sec)
Less than once per month Imax < 80% x It Imax < 70% x It
When fuses are connected in parallel it is recommended that Less than twice per week Imax < 70% x It Imax < 60% x It
the applied voltage does not exceed 0.9 UN (the rated volt- Several times per day Imax < 60% x It —
age of the fuse). This is due to the fact that the energy
When impulse loads are an intrinsic/normal parameter of the
released within the fuses may be unevenly shared between
load current either as single pulse or in trains of pulses or
the parallel connected barrels.
when their level is higher than the melting current at 0.01
When fuses are connected in parallel, one must take into seconds (per time-current curve), contact Cooper Bussmann
account that the current sharing is not necessarily equal. for application assistance.
And it must be checked, that the maximum load current is
In addition to the parameters set forth in the preceding table,
not exceeded.
the RMS value of the load current as calculated for any
Series Connection period of 10 minutes or more should not exceed the maxi-
mum permissible load current.
Fuses in series may not equally divide the applied voltage. It
is recommended that series connected fuses should only be Furthermore, it is important that a fuse should not be applied
operated at fault currents that yield melting times less than in the non-continuous/dashed portion of the associated

High Speed
Fuses
10 ms and a recovery voltage per fuse of less than or equal time-current curve.
to 0.9 UN (the rated voltage of the fuse). Any time-current combination point which falls in the
Mounting Guidance non-continuous/dashed portion of the time-current curve is
beyond the capability of the fuse to operate properly.
The recommendations below have to be followed when
mounting a Cooper Bussmann fuse with end plate threaded DC Operation
holes. Depending upon the short-circuit time constant and the mag-
1. Screw in studs: 5 N•m Max, 3 N•m Min nitude of the prospective short-circuit current, the dc voltage
2. Attachment of the fuse to buss-bar by means of nut and at which a fuse can be applied may be less than its ac rating.
washer: Long time constants require a lower dc voltage. Conversely,
Thread Torque (N•m)*
Configuration Max Min
www.DataSheet.co.kr

however, higher available prospective short-circuit currents


5
⁄16” – 18, M8 25 20 result in faster fuse openings and thus permit a fuse to be
3
⁄8” – 16, M10 45 40
3
⁄8” – 24 45 40
operated at a higher dc voltage.
1
⁄2” – 13, M12 65 50 Consult Cooper Bussmann for additional information and
1
⁄2” – 20 65 50
*1 N•m = 0.7375 lb-ft application assistance when fuses have to operate under dc
conditions.
Overloads
Load Current Versus
The design of Cooper Bussmann® fuses is such that they Reduction Factor
can be operated under rather severe operating conditions Conductor Cross
imposed by overloads (any load current in excess of the Section
1.0
maximum permissible load current). Reduction of permissible
In applications, there will be a maximum overload current, load current when the 0.9
Imax, which can be imposed on the fuse with a conductor cross section is
corresponding duration and frequency of occurrence. less than that given in IEC 0 . 8
Publication 269-1 & 4
Time durations fall into two categories:
valid for Cooper
1. Overloads longer than one second 0 . 5 0 . 6 0 . 7 0.8 0.9 1.0
Bussmann semiconductor
2. Overloads less than one second termed “impulse” loads. ≈ (IEC cross section)
fuses.
The following table gives general application guidelines
which, in the expression Imax < (% factor) x It. It is the melt- Application Assistance
ing current corresponding to the time “t” of the overload dura- If you have application problems or need a fuse outside our
tion as read from the time-current curve of the fuse. The standard program, please contact the nearest Cooper
guidelines in the table below determine the acceptability of Bussmann representative. Phone numbers are shown on the
the selected fuses for a given Imax. back cover.

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 89


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American fuses

Introduction General Information


Cooper Bussmann offers a complete range of North
North American Contents
Catalog Amp American blade and flush-end style fuses and accessories.
Number Volts Range Page Their design and construction were optimized to provide:
www.DataSheet.co.kr

FWA 130 1000-4000 91-92 • Low energy let-through (I2t)


FWA 150 70-1000 93-94 • Low watts loss
FWX 250 35-2500 95-96 • Superior cycling capability
FWH 500 35-1600 97-98
KAC 600 1-1000 99
• Low arc voltage
KBC 600 35-800 100 • Excellent dc performance
FWP 700 5-1200 101-103 North American style fuses provide an excellent solution for
FWJ 1000 35-2000 104-105
medium power applications. While there are currently no
published standards for these fuses, the industry has
Accessories
standardized on mounting centers that accept
Fuse Bases 106
Cooper Bussmann fuses.
North American Fuse Ranges
Amps Volts AC DC Voltage Rating
1000-4000 130 X X
70-1000 150 X X All Cooper Bussmann® North American style fuses are tested
35-2500 250 X X at their rated voltage. Cooper Bussmann should be consulted
35-1600 500 X X for applications exceeding those values.
1-1000 600 X —
5-1200 700 X X
40-600 800 — X
Accessories
35-2000 1000 X — External and internal open fuse indication is available for
selected portions of the North American line. Fuse blocks are
available for most applications.

90 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWA 130V: 1000-4000A

FWA Arc Voltage


UL
This curve gives the peak
Specifications
arc voltage, UL, which
Description: North American 300
may appear across the
style flush-end high speed fuses.
fuse during its operation
Dimensions: See Dimensions as a function of the 200
illustrations.
applied working voltage,
Ratings: Eg, (rms) at a power fac- 100
Volts: — 130Vac tor of 15%. Eg
Amps: — 1000-4000A
Power Losses 50 100 150
IR: — 200kA RMS Sym.
Watts loss at rated current
— 50kA @130Vdc 1.0
is given in the electrical Kp
Agency Information: CE, UL Recognized on 1000-2000A characteristics. The curve 0.8
fuses allows the calculation of 0.6

High Speed
0.5
the power losses at load

Fuses
Electrical Characteristics 0.4
currents lower than the
0.3
Total Clearing I2t rated current. The correc-
1.5 tion factor, Kp, is given as 0.2
The total clearing I2t at K
a function of the RMS load
rated voltage and at power 1.0
current, Ib, in % of the
factor of 15% are given in Ib
rated current. 0.1
the electrical characteris- 30 40 50 60 70 80 90 100%
tics. For other voltages, the 0.5 Catalog Numbers
clearing I2t is found by Electrical Characteristics
multiplying by correction 0.3 I2t (A2 Sec)
factor, K, given as a func- 0.2
Catalog
www.DataSheet.co.kr
Rated Current Clearing Watts
Numbers RMS-Amps Pre-arc at 130V Loss
tion of applied working
Eg FWA-1000AH 1000 170000 460000 60
voltage, Eg, (rms). 0.15
26 65 104 130 FWA-1200AH 1200 270000 730000 70
FWA-1500AH 1500 520000 1400000 78
FWA-2000AH 2000 860000 2400000 108
FWA-2500AH 2500 1500000 4100000 130
FWA-3000AH 3000 2100000 5700000 150
FWA-4000AH 4000 3400000 9200000 257
• Watts loss provided at rated current.
Dimensions (in) • See accessories on page 106.
Catalog Number Fig. B C D Thread Depth
FWA-1000AH-2000AH 1 2.0 1.0 — Tapped 3⁄8”-24 x 1⁄2” Features and Benefits
FWA-2500AH-3000AH 1 3.0 1.5 — Tapped 1⁄2”-20 x 1⁄2”
FWA-4000AH 2 3.5 1.5 1.5 Tapped 1⁄2”-20 x 1⁄2” • Excellent dc performance
1mm = 0.0394∑ / 1∑ = 25.4mm • Low arc voltage and low energy let-through (I2t)
Fig. 1: 1000-3000A Fig. 2: 4000A
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
1.875
1.875 • DC drives
• Power converters/rectifiers
• Reduced voltage starters

B B C
C

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 91


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWA 130V: 1000-4000A

FWA 1000-4000A: 130V


Time-Current Curve
104
6
4
Did You Know?
2

103
6
4 FWA-1000AH Protect Against Downtime with
2
FWA-1200AH Technical Training,
FWA-1500AH
102
FWA-2000AH and Earn CEUs at the Same Time
FWA-2500AH
6
FWA-3000AH
4
FWA-4000AH Our application engineering team offers two training
2 seminars at the Cooper Bussmann St. Louis head-
quarters Technical Center for end-user customers.
Virtual Pre-Arcing Time In Seconds

101
6 These two-day seminars provide participants 1.6
4
Continuing Education Units (CEUs). Attendees are
2
responsible for their own airfare and hotel costs;
0
10 meals and ground transportation are provided.
6
4
Industrial Machinery
2
This two-day seminar highlights overcurrent
10–1
protection considerations for industrial machinery
6
4 and industrial control panels, design standards as
2
well as a review of various overcurrent protective
www.DataSheet.co.kr

devices. The seminar is offered to:


10–2
6
• Engineers for industrials who specify equipment
4 • Electrical panel builders
2 • Machinery builders
10–3
• Electrical designers
6
4 Commercial and Industrial Power Systems
2 This two-day seminar provides a comprehensive
10–4 review of the proper overcurrent protection of
2 4 6 8 2 4 6 8
103 104 105 building power distribution systems including
Prospective Current In Amperes RMS
elevator protection, ground fault protection and
Peak Let-Through Curve
compliance with industry standards. The seminar is
2
targeted to:
105 • Consulting engineers
• Plant engineers
6
• Electrical contractors
4
• Electrical designers
Peak Let-Through Current

2
• Inspectors
FWA-4000AH
FWA-3000AH
104 FWA-2500AH Contact your local district sales engineer or
FWA-2000AH
FWA-1500AH representative, or call our application engineering
6 FWA-1200AH
FWA-1000AH team for more information: 636-527-1270. Check
4
at www.cooperbussmann.com for schedules and
2
seminar cost.

103
103 2 4 6 104 2 4 6 105 2 4 6

Data Sheet: 35785301

92 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWA 150V: 70-1000A

FWA Arc Voltage


UL
Specifications This curve gives the peak
Description: North American style arc voltage, UL, which may
300
stud-mount fuses. appear across the fuse dur-
ing its operation as a func-
Dimensions: See Dimensions 200
tion of the applied working
illustrations.
voltage, Eg, (rms) at a
Ratings: power factor of 15%. 100
Volts: — 150Vac Eg
Amps: — 70-1000A Power Losses
50 100 150
IR: — 100kA Sym. (70-400A) Watts loss at rated current
is given in the electrical 1.0
— 200kA Sym. (450-1000A) Kp
0.8
characteristics. The curve
— 20kA @150Vdc (70-800A) 0.6
allows the calculation of 0.5
— 100kA @ 80Vdc (70-400A) the power losses at load

High Speed
0.4
Agency Information: CE, UL Recognized currents lower than the

Fuses
0.3
rated current. The correc-
Electrical Characteristics tion factor, Kp, is given as 0.2
Total Clearing I2t a function of the RMS load
1.5 current, Ib, in % of the
K Ib
The total clearing I2t at rated rated current. 0.1
1.0
voltage and at power factor of 30 40 50 60 70 80 90 100%
15% are given in the electri- Catalog Numbers
Electrical Characteristics
cal characteristics. For other Rated I2t (A2 Sec)
0.5
voltages, the clearing I2t is 1)
Catalog Current Clearing Watts
found by multiplying by cor- Number RMS-Amps Pre-arc at 150V Loss
0.3 FWA-70B 70 470 4000 6.9
rection factor, K, given as a 2) www.DataSheet.co.kr

FWA-80B 80 670 6000 7.7


0.2
function of applied working FWA-100B 100 1200 12000 9.0
voltage, Eg, (rms). Eg FWA-125B 125 1870 18000 11.2
0.15
22 70 102 150 FWA-150B 150 2700 26000 13.5
FWA-200B 200 4780 45000 17.6
1) 500-1000A Range
2) 70-400A Range
FWA-250B 250 7470 70000 22.5
FWA-300B 300 10760 100000 27.0
FWA-350B 350 15700 140000 30.6
FWA-400B 400 20300 180000 35.2
FWA-500A 500 39000 120000 35.0
FWA-600A 600 46000 140000 47.0
FWA-700A 700 75000 220000 49.0
Dimensions (in) FWA-800A 800 92000 280000 58.0
Fig. 1: 70-400A FWA-1000A 1000 170000 510000 60.0
• Watts loss provided at rated current.
2.656 • See accessories on page 106.
2.188
1.936 Features and Benefits
1.156 0.125
• Excellent dc performance
• Low arc voltage and low energy let-through (I2t)
0.750 0.312 1.000
• Low watts loss
• Superior cycling capability
0.438
Typical Applications
Fig. 2: 500-1000A • DC common bus
3.500 • DC drives
• Power converters/rectifiers
2.438
• Reduced voltage starters
1.250 0.250

1.000 1.500

0.406
1mm = 0.0394 “ / 1” = 25.4mm

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 93


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWA 150V: 70-1000A

FWA 70-1000A: 150V


Time-Current Curve
104
6
4

103
6
4 FWA-500A
FWA-600A
2 FWA-700A
FWA-800A
102 FWA-1000A
6
4

2
Did You Know?
Virtual Pre-Arcing Time In Seconds

101
6
4

2 Cooper Bussmann® Equipped Solar Car


100
6
Wins American Solar Challenge Race
4

2
The University
10–1 of Missouri-
6 FWA-70A
4 FWA-80A Rolla Solar Car
FWA-100A
2 FWA-125A Team won the
10–2
FWA-150A prestigious
6 www.DataSheet.co.kr

American Solar
4
Challenge Race
2
recently with
10–3
6 FWA-200A
circuit protection provided by Cooper Bussmann
4 FWA-250A
FWA-300A
FWX series 80 amp semiconductor fuses.
2 FWA-350A
FWA-400A
10–4
2 4 6 8 2 4 6 8
The grueling endurance test pitted UM-Rolla’s “Solar
102 103 104
Prospective Current In Amperes RMS
Miner IV” against race teams from some of the
most famous engineering schools in the nation. By
Peak Let-Through Curve driving approximately 2,300 miles from Chicago to
106 Claremont (a suburb of Los Angeles), in just 51
6 hours, 47 minutes and 39 seconds, they set a race
4 record by more than four hours.
FWA-400A
FWA-350A
2
FWA-300A
FWA-250A
104 FWA-200A
FWA-150A
Peak Let-Through Current

6 FWA-100A

3
10

6 FWA-80A

4 FWA-70A

102
2 4 6 2 4 6 2 4 6 2
102 103 104 105

Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785310

94 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWX 250V: 35-2500A

FWX Arc Voltage 1.4


1.2 UL
Specifications This curve gives the peak
103
Description: North American arc voltage, UL, which may
800
style stud-mount and flush-end appear across the fuse dur-
fuses. ing its operation as a func- 600
tion of the applied working 500
Dimensions: See Dimensions
voltage, Eg, (rms) at a 400
illustrations. 1)
power factor of 15%. 300
Ratings: 2)
Power Losses Eg
Volts: — 250Vac 200
Amps: — 35-2500A Watts loss at rated current is 50 100 150 200 250
1) 35-800A Range
IR: — 200kA RMS Sym. given in the electrical char 2) 1000-2500A Range
acteristics. The curve allows 1.0
Kp
Agency Information: CE, UL Recognized & CSA 0.8
Component Acceptance on 35-800A fuses (20kA IR the calculation of the power
0.6
@250Vdc). losses at load currents lower 0.5

High Speed
than the rated current . The

Fuses
0.4
Electrical 1.5 correction factor, K p , is 0.3
K
Characteristics given as a function of the 0.2
1.0
RMS load current, Ib , in %
Total Clearing I t 2

of the rated current . Ib


0.1
The total clearing I2t at rated 0.5
1)
30 40 50 60 70 80 90 100%
voltage and at power factor Catalog Numbers
2) Electrical Characteristics
of 15% are given in the 0.3 Rated I2t (A2 Sec)
electrical characteristics. 0.2 Catalog Current Clearing Watts
For other voltages, the Number RMS-Amps Pre-arc at 250V Loss
Eg FWX-35A 35 50 230 4.2
clearing I2t is found by multi- 0.15 www.DataSheet.co.kr
FWX-40A 40 60 310 5.2
plying by correction factor, 75 125 200 250 300 FWX-45A 45 80 390 5.7
K, given as a function of 1) 35-800A Range FWX-50A 50 100 520 6.0
2) 1000-2500A Range FWX-60A 60 140 740 8.1
applied working voltage, Eg, FWX-70A 70 330 1400 7.2
(rms). FWX-80A 80 430 1850 8.1
FWX-90A 90 570 2450 9.0
Dimensions (in) FWX-100A 100 740 3150 10.0
Tapped FWX-125A 125 1130 4850 12.5
Amp Thread FWX-150A 150 1620 6950 15.7
Range Fig. A B C D E F G H J Depth FWX-175A 175 2170 9300 18.5
35-60 1 3.19 0.81 1.59 2.59 2.25 0.34 0.63 0.13 0.52 — FWX-200A 200 2790 12000 22
70-200 1 3.13 1.22 1.59 2.44 2.19 0.34 1.00 0.19 0.47 — FWX-225A 225 3210 14700 24
225-600 1 3.84 1.50 1.59 2.94 2.25 0.41 1.00 0.25 0.75 — FWX-250A 250 3960 18100 27
700-800 1 3.84 2.00 1.59 3.03 2.28 0.41 1.50 0.25 0.78 — FWX-275A 275 4720 21600 31
1000-1200 2 2.59 3.00 1.50 — — — — — — 3
⁄8”-24 x 1⁄2” FWX-300A 300 6000 27300 32
1500-2500 3 2.59 3.50 1.50 1.50 — — — — — 3
⁄8”--24 x 1⁄2” FWX-350A 350 10600 48600 39
1mm = 0.0394” / 1” = 25.4mm FWX-400A 400 14500 66100 44
FWX-450A 450 22100 101000 49
Fig. 1: Fig. 2: Fig. 3: FWX-500A 500 28000 128000 54
35-800A 1000-1200A 1500-2500A FWX-600A 600 41100 188000 62
FWX-700A 700 48800 190000 72
FWX-800A 800 59000 230000 84
J
FWX-1000AH 1000 44000 360000 100
A
A FWX-1200AH 1200 92000 750000 103
FWX-1500AH 1500 120000 880000 140
FWX-1600AH 1600 160000 1200000 140
FWX-2000AH 2000 320000 2300000 151
A D E C D
FWX-2500AH 2500 670000 4700000 163
• Watts loss provided at rated current. • See accessories on page 106.

B C
B C
Features and Benefits Typical Applications
• Excellent dc performance • DC common bus
F • Low arc voltage and low • DC drives
G
energy let-through (I2t) • Power converters/rectifiers
• Superior cycling capability • Reduced voltage starters
H

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 95


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWX 250V: 35-2500A

FWX 35-800A: 250V FWX 1000-2500A(H): 250V


Time-Current Curve Time-Current Curve
104 104
6
4

2
103
3
10
FWX-200A 6
FWX-350A
102 4
FXW-400A
FWX-500A
Virtual Pre-arcing Time In Seconds

FWX-600A 2 FWX-1000AH
FWX-800A
102 FWX-1200AH
101
FWX-1500AH
6
4 FWX-1600AH
FWX-2000AH
100 2 FWX-2500AH
101

Virtual Pre-Arcing Time In Seconds


FWX-35A 6
FWX-40A
10–1 FWX-60A 4
FWX-70A
FWX-100A 2
FWX-150A
10–2 100
6
4

10–3 2

10–1
6
10–4 4
2 102 103 104
Prospective Current In Ampere RMS www.DataSheet.co.kr
2

10–2
6
Peak Let-Through Curve 4

2
105 –3
B 10
6
4

2
FWX-800A
FWX-600A –4
FWX-400A 10
2 4 6 8 2 4 6 8
FWX-300A 103 104 105
FWX-200A
Prospective Current In Amperes RMS
104
Peak Let-Through Current

Peak Let-Through Curve

105

6
FWX-2500AH
4 FWX-2000AH
103
FWX-1600AH
FWX-150A
FWX-1500AH
FWX-100A
FWX-1200AH
Peak Let-Through Current

FWX-70A 2
FWX-60A FWX-1000AH
FWX-45A
A FWX-35A
104

4
102
102 103 104 105

Prospective Short-Circuit Current Symmetrical RMS 2

103
2 4 6 2 4 6 2 4 6
103 104 105
Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 359 Data Sheet: 35785299

96 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWH 500V: 35-1600A

FWH Arc Voltage 2.0


UL
This curve gives the peak 1.6
Specifications
Description: North American style arc voltage, UL, which 1.2
stud-mount fuses. may appear across the 103
fuse during its operation 800
Dimensions: See Dimensions
as a function of the
illustration. 600
2)
applied working voltage,
Ratings: 500
Eg, (rms) at a power factor 1)
Volts: — 500Vac 400
of 15%. Eg
Amps: — 35-1600A 300
Power Losses 100 200 300 400 500
IR: — 200kA Sym. 1) 35-200 & 1000-1600A Range

— 50kA @ 500Vdc Watts loss at rated cur- 2) 225-800A Range


1.0
rent is given in the elec- Kp
Agency Information: CE, UL Recognition & CSA 0.8
trical characteristics. The
Component Acceptance on 35-800A only (50kA 0.6
curve allows the calcula-

High Speed
IR@500Vdc). UL Recognition on 35-1200A only, CSA 0.5
tion of the power losses

Fuses
Component Acceptance: 35-1600A. 0.4
at load currents lower
0.3
Electrical Characteristics than the rated current.
The correction factor, Kp, 0.2
1.5
Total Clearing I2t K is given as a function of
The total clearing I2t at rated 1.0 the RMS load current, Ib,
Ib
in % of the rated current. 0.1
voltage and at power factor of 30 40 50 60 70 80 90 100%
15% are given in the electrical Catalog Numbers
characteristics. For other volt- 0.5
Electrical Characteristics
ages, the clearing I2t is found 1) Rated I2t (A2 Sec)
0.3 Catalog Current Clearing Watts
by multiplying by correction www.DataSheet.co.kr
Numbers RMS-Amps Pre-arc at 500V Loss
factor, K, given as a function of 0.2
2) FWH-35B 35 34 150 8
applied working voltage, Eg, Eg FWH-40B 40 76 320 7.5
0.15 FWH-45B 45 105 450 7.5
(rms). 100 250 400 500 FWH-50B 50 135 670 7.5
1) 35-800A Range FWH-60B 60 210 900 9.9
2) 1000-1600A Range
FWH-70B 70 210 900 10.6
Dimensions (in)
Amp FWH-80B 80 305 1400 12.7
Range Fig. A B C D E F G H J FWH-90B 90 360 1600 15
35-60 1 3.188 0.813 1.593 2.541 2.193 0.344 0.719 0.125 0.518 FWH-100B 100 475 2000 17
70-100 1 3.625 0.947 1.736 2.853 2.807 0.352 0.750 0.125 0.375 FWH-125B 125 800 3500 25
125-200 1 3.625 1.156 1.836 2.892 2.768 0.344 1.000 0.188 0.406 FWH-150B 150 1100 4600 30
225-400 1 4.340 1.500 2.090 3.440 2.750 0.410 1.000 0.250 0.750 FWH-175B 175 1450 6200 35
450-600 1 4.340 2.000 2.090 3.530 2.780 0.410 1.500 0.250 0.780 FWH-200B 200 1900 8500 40
700-800 1 6.340 2.500 2.090 4.970 3.440 0.530 2.000 0.380 1.300 FWH-225A 225 4600 23300 39
1000-1200 1 6.969 3.000 3.219 5.465 4.475 0.625 2.375 0.438 1.120 FWH-250A 250 6300 32200 41
1400-1600 2 See Drawing FWH-275A 275 7900 40300 46
1mm = 0.0394” / 1” = 25.4mm FWH-300A 300 9800 49800 51
FWH-325A 325 13700 63800 53
Fig. 1: 35-1200A FWH-350A 350 14500 72900 58
A
FWH-400A 400 19200 96700 65
D
FWH-450A 450 24700 127000 74
E
FWH-500A 500 29200 149000 84
C H
FWH-600A 600 41300 206000 108
FWH-700A 700 55000 298000 120
G F B
FWH-800A 800 76200 409000 129
FWH-1000A 1000 92000 450000 145
FWH-1200A 1200 122000 600000 180
J FWH-1400A 1400 200000 1000000 210
Fig. 2: 1400-1600A FWH-1600A 1600 290000 1400000 230
10.219 • Watts loss provided at rated current. • See accessories on page 106.
0.125 0.5 3.219 0.625
1.625 Features and Benefits Typical Applications
1.750
• Excellent dc performance • DC common bus
3.5 • DC drives
• Low arc voltage and low
energy let-through (I2t) • Power converters/rectifiers
• Low watts loss • Reduced voltage starters
0.75
6.219 4.25
• Superior cycling capability
8.969

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 97


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWH 500V: 35-1600A

FWH 35-200A(B) & 900-1600A(A): 500V FWH 225-800A: 500V


Time-Current Curve Time-Current Curve
4 103
10
6
4

103
6 102
4

2 FWH-350A
FWH-400A
102 FWH-500A
FWH-600A
6 FWH-800A
4
101
2 FWH-900A
FWH-1000A
101 FWH-1200A
6 FWH-1400A

Virtual Pre-Arcing Time In Seconds


4 FWH-1600A

2
100
100 FWH-80B
6 FWH-90B
4 FWH-100B
FWH-125B
2 FWH-35B FWH-150B
FWH-40B FWH-175B
10–1 FWH-45B FWH-200B 10–1
6 FWH-50B
4 FWH-60B
FWH-70B
2

10–2
6
4 10–2
www.DataSheet.co.kr

10–3
6
4

2 10–3
–4
10
2 4 6 8 2 4 6 8 2 4 6 8
102 103 104
Prospective Current In Amper es RMS

10–4
102 103 104 105
Prospective Current In Amperes RMS
Peak Let-Through Curve Peak Let-Through Curve
105 105
FWH-1600A B
FWH-1400A
6
FWH-1200A
4 FWH-1000A

104 104
Peak Let-Through Current
Peak Let-Through Current

4 FWH-800A
FWH-600A
FWH-500A
FWH-400A
2 FWH-300A
FWH-250A

3
10
103
FWH-200B
6 FWH-150B
FWH-125B
4 FWH-100B
FWH-80B
A
FWH-60B
2 FWH-50B
FWH-40B
FWH-35B
102
2 4 6 2 4 6 2 4 6 2 102
2 3 4
10 10 10 105 102 103 104 105
Prospective Short-Circuit Current Symmetrical RMS Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785304 Data Sheet: 360

98 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — KAC 600V: 1-1000A

KAC KAC-1
Catalog Numbers (-amps)
KAC-25 KAC-175
KAC-2 KAC-30 KAC-200
Specifications KAC-3 KAC-35 KAC-225
Description: North American style KAC-4 KAC-40 KAC-250
stud-mount fuses. These 600V fuses are KAC-5 KAC-45 KAC-300
supplied as replacements only. For new KAC-6 KAC-50 KAC-350
KAC-7 KAC-60 KAC-400
installations, Cooper Bussmann recommends KAC-8 KAC-70 KAC-450
the 700V FWP series fuse. KAC-9 KAC-80 KAC-500
KAC-10 KAC-90 KAC-600
Dimensions: See Dimensions illustrations. KAC-12 KAC-100 KAC-700
Ratings: KAC-15 KAC-110 KAC-800
KAC-17.5 KAC-125 KAC-1000
Volts: — 600Vac KAC-20 KAC-150
Amps: — 1-1000A • Consult Cooper Bussmann for dc ratings.
• See accessories on page 106.
IR: — 200kA RMS Sym.
Agency Information: CE, UL Recognition Features and Benefits
on 1-600A only. • Excellent dc performance

High Speed
• Low arc voltage and low energy let-through (I2t)

Fuses
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
Dimensions (in) • Reduced voltage starters
Amp
Range Fig. A B1 B2 B3 C D E F G H
1-30A 1 2.875 2.500 — — 1.875 0.406 — 0.563 0.063 0.257
35-60A 2 4.375 — 3.750 3.5002.750 0.625 0.3430.813 0.094 0.468
www.DataSheet.co.kr

70-100A 2 5.000 — 4.063 3.6562.750 0.750 0.4061.000 0.125 0.609


110-200A 2 5.140 — 4.390 3.7662.906 1.000 0.4061.500 0.188 0.718
225-400A 2 6.182 — 4.815 4.5653.000 1.625 0.5622.000 0.250 0.687
450-800A 1 6.250 4.750 — — 3.063 2.000 — 2.500 0.250 0.563
1000A 1 7.250 4.750 — — 3.063 2.750 — 3.500 0.375 0.563
1mm = 0.0394” / 1” = 25.4mm

Fig. 1: 1-30 & 450-1000A

B1
C G

D F

Fig. 2: 35-400A

A
B2
B3
C G

D E F

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 99


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — KBC 600V: 35-800A

KBC Catalog Numbers (-amps)


KBC-35 KBC-100 KBC-300
KBC-40 KBC-110 KBC-350
Specifications KBC-45 KBC-125 KBC-400
Description: North American KBC-50 KBC-150 KBC-450
style stud-mount and flush-end KBC-60 KBC-175 KBC-500
fuses. These 600V fuses are KBC-70 KBC-200 KBC-600
KBC-80 KBC-225 KBC-800
supplied as replacements only. KBC-90 KBC-250
For new installations, Cooper • Consult Cooper Bussmann for dc ratings.
• See accessories on page 106.
Bussmann recommends the 700V
FWP series fuse. Features and Benefits
Dimensions: See Dimensions • Excellent dc performance
illustrations. • Low arc voltage and low energy let-through (I2t)
Ratings: • Low watts loss
Volts: — 600Vac • Superior cycling capability
Amps: — 35-800A Typical Applications
IR: — 200kA RMS Sym. • DC common bus
Agency Information: CE, UL Recognition on 35-600A only. • DC drives
• Power converters/rectifiers
• Reduced voltage starters

Dimensions (in)
Amp
Range Fig. A B C D E F G H I
35-60A 1 4.375 3.750 3.500 2.7500.343 0.625 0.8130.094 0.468
70-100A 2 See Drawing
110-200A
225-400A
1
1
4.406 3.719
5.125 4.188
3.594 2.9060.312 0.875 1.2190.187 0.375
3.563 2.9060.406 1.000 1.5000.250 0.719
Did You Know?
450-600A 1 5.125 4.389 3.687 2.8750.406 1.500 2.0000.250 0.757
800A 3 See Drawing
www.DataSheet.co.kr

1mm = 0.0394” / 1” = 25.4mm

Fig. 1: 35-60 and 110-600A Cooper Bussmann® Paul P. Gubany


A Center Receives Prestigious ASTA
B
C
Accreditation
E D H
The Cooper Bussmann Paul P. Gubany Center in St.
F G Louis is certified by Britain’s prestigious ASTA
(Associated Short Circuit Testing Authority) to
I
perform short testing of its own devices designed to
operate to ASTA requirements which are closely tied
Fig. 2: 70-100A
to IEC requirements. The Gubany Center is the only
4.406

testing facility available in North or South America


0.125
3.656

for this product certification.


2.906

The Gubany Center has equipment capable of


generating 300,000A of current at 600Vac three-
1.000
0.750

phase, and 100,000A at 170Vdc, under carefully


controlled conditions. It offers a wider range of
0.312

current voltage and frequency configurations than


Fig. 3: 800A
any other facility of its kind in the world, and is built
4.000
to exceed the short circuit capacity of today’s high
3.750 ‹Ω•" - 24 ≈ ⁄Ω™" power electrical distribution systems.
0.750

2.500 2.859

0.750

100 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWP 700V: 5-1200A

FWP Arc Voltage 2


UL
This curve gives the peak arc 1.6
Specifications 1.4
voltage, UL, which may
Description: North American 1.2
appear across the fuse dur- 1)
style stud-mount fuses. 103
ing its operation as a function 2)
Dimensions: See Dimensions of the applied working volt-
8
illustrations. 6
age, Eg, (rms) at a power
Ratings: 5
factor of 15%.
Volts: — 700Vac 4
Power Losses Eg
Amps: — 5-1200A 3
300 400 500 600 700
IR: — 200kA RMS Sym. Watts loss at rated current is
1) 125-600A Range
given in the electrical charac- 2) 35-100 & 700-1200A Range
— 50kA @700Vdc
teristics. The curve allows
Agency Information: CE, UL Recognition & CSA 1.0
the calculation of the power 0.8
Kp
Component Acceptance on 5-800A losses at load currents lower 0.6

High Speed
than the rated current. The 0.5

Fuses
Electrical Characteristics
correction factor, Kp, is given 0.4

Total Clearing I t 2
as a function of the RMS 0.3
1.5
K load current, Ib, in % of the 0.2
The total clearing I2t at rated
1.0 rated current.
voltage and at power factor of
15% are given in the electrical 2) 0.1
Ib
characteristics. For other volt- 30 40 50 60 70 80 90 100%
0.5 Catalog Numbers
ages, the clearing I2t is found Electrical Characteristics
by multiplying by correction 1) Rated I2t (A2 Sec)
0.3 Catalog Current Clearing Watts
factor, K, given as a function 3)
0.2 Numbers RMS-Amps Pre-arc at 700V Loss
of applied working voltage, www.DataSheet.co.kr
FWP-5B 5 1.6 10 1.5
Eg, (rms). 0.15 Eg FWP-10B 10 3.6 20 4
316 460 604 700 FWP-15B 15 10 75 5.5
1) 35-100A Range FWP-20B 20 26 180 6
2) 125-600A Range FWP-25B 25 44 340 7
3) 700-1200A Range FWP-30B 30 58 450 9
FWP-35B 35 34 160 12
FWP-40B 40 76 320 12
Dimensions (in) FWP-50B 50 135 600 12
Amp
Range Fig. A B C D E F G H I FWP-60B 60 210 950 15.5
5-30 1 2.870 0.563 1.855 2.4772.477 0.250 0.4050.063 0.250 FWP-70B 70 305 2000 18
35-60 1 4.375 0.813 2.750 3.7083.312 0.344 0.7250.125 0.542 FWP-80B 80 360 2400 21
70-100 1 4.406 0.947 2.594 3.6253.563 0.344 0.7500.125 0.375 FWP-90B 90 415 2700 25
125-200 1 5.090 1.500 2.840 4.1903.500 0.410 1.0000.250 0.750 FWP-100B 100 540 3500 27
225-400 1 5.090 2.000 2.840 4.2803.530 0.410 1.5000.250 0.780 FWP-125A 125 1800 7300 28
450-600 1 7.090 2.500 2.840 5.7204.190 0.530 2.0000.380 1.300 FWP-150A 150 2900 11700 32
700-800 1 6.630 2.000 2.844 5.5625.062 0.625 1.5000.250 0.875 FWP-175A 175 4200 16700 35
900-1000 2 See Drawing FWP-200A 200 5500 22000 43
1200 3 See Drawing FWP-225A 225 7700 31300 45
1mm = 0.0394” / 1” = 25.4mm FWP-250A 250 10500 42500 48
FWP-300A 300 17600 71200 58
Fig. 1: 5-800A Fig. 2: 900-1000A Fig. 3: 1200A FWP-350A 350 23700 95600 65
1.375
3.500 FWP-400A 400 31000 125000 78
J 0.125 FWP-450A 450 36400 137000 94
0.500 FWP-500A 500 45200 170000 107
FWP-600A 600 66700 250000 122
9.590 6.840 3.844
FWP-700A 700 54000 300000 125
5.966 3.844 10.844 FWP-800A 800 78000 450000 140
7.594
A D E C 5.154 FWP-900A 900 91500 530000 150
FWP-1000A 1000 120000 600000 170
0.625
1.031 FWP-1200A 1200 195000 1100000 190
1.625 • Watts loss provided at rated current.
0.625 1.750 • See accessories on page 106.
2.750
0.750
0.5 4.250 Features and Benefits Typical Applications
F
G 3.500 • Excellent dc performance • DC common bus
H
• Low arc voltage and low • DC drives
B energy let-through (I2t) • Power converters/rectifiers
• Superior cycling capability • Reduced voltage starters

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 101


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWP 700V: 5-1200A

FWP 5-30A(B): 700V FWP 35-100A(B) & 700-1200A(A): 700V


Time-Current Curve Time-Current Curve
104 104
6 6
4 4

2 2

103 103
6 6
4 4

2 2
FWP-700A
102 102 FWP-800A
6 FWP-900A
6
4 FWP-1000A
4 FWP-1200A
2
2

Virtual Pre-Arcing Time In Seconds


101
101
Virtual Pre-Arcing Time In Seconds

6
6 FWP-35B
4
4 FWP-40B
2 FWP-50B
2 FWP-60B
100 FWP-70B
100 6 FWP-80B
6 4 FWP-90B
FWP-5B FWP-100B
4
FWP-10B 2
2 FWP-15B
FWP-20B 10–1
10–1 FWP-25B 6
6 FWP-30B 4
4 2
2 10–2
10–2 6
4
6
4 2

2 10–3
6
10–3 4
www.DataSheet.co.kr

6
4 2

2 10–4
2 4 6 8 2 4 6 8 2 4 6 8
102 103 104
10–4 Prospective Current In Amperes RMS
2 4 6 8 2 4 6 8 2 4 6 8
101 102 103
Prospective Current In Amperes RMS

Peak Let-Through Curve Peak Let-Through Curve

104 106
FWP-1200A
6 6 FWP-1000A

4 FWP-800A
4
FWP-700A

2
FWP-30B
2
FWP-25B
3
10
Peak Let-Through Current

6 104

4
Peak Let-Through Current

2 4
FWP-20B
2
FWP-15B
10 FWP-10B
2
FWP- 5B
6

4 103

2 6
FWP-100B
4
101 FWP-70B
2 4 6 2 4 6 2 4 6 2 4 6 2
101 102 103 104 105 FWP-60B
Prospective Short-Circuit Current FWP-50B
2
FWP-40B
FWP-35B
102
2 4 6 2 4 6 2 4 6 2
102 103 104 105
Prospective Short-Circuit Current

Data Sheet: 35785316 Data Sheet: 35785308

102 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWP 700V: 5-1200A

FWP 125-600A: 700V


Time-Current Curve
103

102

FWP-150A
FWP-200A
FWP-300A
10 1
FWP-400A
FWP-600A Did You Know?
Virtual Pre-Arcing Time In Seconds

100
Cooper Bussmann Named First in

High Speed
Fuses
Fuses by Readers of Plant
Services Magazine
10–1

Cooper Bussmann has been named as the vendor


offering the highest value in electrical fuses in a
10–2 recent fill-in-the-blank survey of nearly 40,000
qualified readers of Plant Services Magazine. A full
70 percent of survey respondents said Cooper
Bussmann was their number one choice. The
10–3 www.DataSheet.co.kr

nearest competitor weighed in at only 7 percent. The


63 percent spread was the widest of all 63 product
categories, ranging from aerial work platforms to
10–4 welding equipment. According to Plant Services
102 103 104 105
editors, the products chosen are those “that deliver
Prospective Current In Amperes RMS
the combination of functionality, durability and low
Peak Let-Through Curve maintenance that add up to the lowest estimated
life-cycle cost”—those offering the very best value in
their product category.
105
B

104
Peak Let-Through Current

FWP-600A
FWP-400A
FWP-300A
FWP-200A
FWP-150A

103

102
102 103 104 105

Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 361

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 103


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWJ 1000V: 35-2000A

FWJ Arc Voltage 2000


UL
Specifications This curve gives the peak arc 1600
Description: North American voltage, UL, which may
style stud-mount fuses. appear across the fuse dur- 1200
ing its operation as a function
Dimensions: See Dimensions
of the applied working volt- 800
illustration.
age, Eg, (rms) at a power
Ratings: factor of 15%. 400
Volts: — 1000Vac Eg
Amps: — 35-200A Power Losses
200 600 1000 1400 1800
IR: — 25kA (35-200A) Watts loss at rated current is
— 100kA (250-2000A) given in the electrical char- 1.0 Kp
acteristics. The curve 0.8
— 50kA @ 800Vdc (450-
allows the calculation of the 0.6
600A) 0.5
power losses at load cur-
Agency Information: CE, UL 0.4
rents lower than the rated
Recognition on 35-600A only. current. The correction fac- 0.3
tor, Kp, is given as a func- 0.2
Electrical Characteristics tion of the RMS load cur-
Total Clearing I2t rent, Ib, in % of the rated
current. Ib
0.1
The total clearing I2t at rated 1.5 30 40 50 60 70 80 90 100%
K
voltage and at power factor of Catalog Numbers
1.0 Electrical Characteristics
15% are given in the electrical Rated I2t (A2 Sec)
characteristics. For other volt- Catalog Current Clearing Watts
ages, the clearing I2t is found Numbers RMS-Amps Pre-arc at 1000V Loss
0.5 FWJ-35A 35 210 2000 7
by multiplying by correction www.DataSheet.co.kr

FWJ-40A 40 300 2500 8


factor, K, given as a function FWJ-50A 50 470 3500 10
0.3
of applied working voltage, FWJ-60A 60 670 5000 11
0.2 FWJ-70A 70 1100 6900 12
Eg, (rms). FWJ-80A 80 1550 9700 13
Eg
0.15 FWJ-90A 90 1900 12000 14
200 500 800 1000 FWJ-100A 100 2800 17500 15
FWJ-125A 125 4800 35000 16
FWJ-150A 150 6300 45000 25
Dimensions (in) FWJ-175A 175 7500 65000 30
Amp FWJ-200A 200 11700 80000 32
Range Fig. A B C D E F G H I FWJ-250A 250 16000 112000 50
35-60 1 5.000 0.940 3.110 4.2354.180 0.352 0.7500.125 0.380 FWJ-300A 300 23500 164000 56
70-100 1 4.932 1.125 3.085 4.2664.156 0.352 1.0000.188 0.407 FWJ-350A 350 33000 231000 62
125-200 1 5.685 1.526 3.261 4.8034.055 0.445 1.0000.250 0.819 FWJ-400A 400 47000 330000 67
250-400 1 5.768 2.000 3.500 4.8114.150 0.433 1.5000.250 0.764 FWJ-500A 500 39500 329000 95
500-600 1 7.201 2.500 3.465 5.9844.706 0.562 2.0000.375 1.201 FWJ-600A 600 61000 520000 105
800-2000 1 6.811 3.500 3.312 5.4724.962 0.625 2.7500.500 0.880 FWJ-800A 800 87000 500000 182
1mm = 0.0394” / 1” = 25.4mm FWJ-1000A 1000 190000 1100000 206
FWJ-1200A 1200 370000 2100000 240
Fig. 1: 35-2000A FWJ-1400A 1400 470000 2700000 248
A FWJ-1600A 1600 700000 4000000 267
D FWJ-1800A 1800 925000 5300000 239
E FWJ-2000A 2000 1330000 7600000 244
• Watts loss provided at rated current.
C H
• See accessories on page 106.

Features and Benefits


G F B
• Excellent dc performance
• Low arc voltage and low energy let-through (I2t)
J
• Low watts loss
• Superior cycling capability

Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters

104 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American — FWJ 1000V: 35-2000A

FWJ 35-600A: 1000V FWJ 800-2000A: 1000V


Time-Current Curve Time-Current Curve
104 104
6 6
4
4
2
2
103
103
6
6 4
4
2
2
102
102 6
6 FWJ-200A 4 FWJ-800A
4 FWJ-250A
2 FWJ-1000A

Virtual Pre-Arcing Time In Seconds


FWJ-300A FWJ-1200A
2 FWJ-350A 101 FWJ-1400A
FWJ-400A FWJ-1600A
Virtual Pre-Arcing Time In Seconds

101 6
FWJ-500A 4 FWJ-1800A
6 FWJ-2000A
4 FWJ-600A

High Speed
2

Fuses
2 100
6
100
4
6
4 2

2 10–1
6
10–1 4
6
2
4 FWJ-40A
FWJ-50A 10–2
2 FWJ-60A 6
FWJ-70A
10–2 4
FWJ-80A
6 FWJ-90A 2
4 FWJ-100A
10–3
2 FWJ-125A
www.DataSheet.co.kr
6
FWJ-150A
4
10–3 FWJ-175A
6 2
4
10–4
2 4 6 8 2 4 6 8 2 4 6 8
2 103 104 105
Prospective Current In Amperes RMS
10–4
2 4 6 8 2 4 6 8
102 103 104
Prospective Current In Amperes RMS

Peak Let-Through Curve Peak Let-Through Curve


2 2
FWJ-2000A FWJ-2000A
FWJ-1800A FWJ-1800A
105 FWJ-1600A 105 FWJ-1600A
FWJ-1400A FWJ-1400A
FWJ-1250A FWJ-1250A
6 6
FWJ-1000A FWJ-1000A
FWJ-600A FWJ-600A
4 FWJ-800A 4 FWJ-800A
FWJ-400A FWJ-400A
FWJ-500A FWJ-500A
FWJ-350A FWJ-350A
FWJ-300A FWJ-300A
2 FWJ-250A 2 FWJ-250A
FWJ-200A FWJ-200A
FWJ-175A FWJ-175A
Peak Let-Through Current

Peak Let-Through Current

4 FWJ-150A 4
10 10 FWJ-150A
FWJ-125A FWJ-125A
FWJ-100A FWJ-100A
6 FWJ-90A 6 FWJ-90A
FWJ-80A FWJ-80A
4 FWJ-70A FWJ-70A
FWJ-60A 4
FWJ-60A
FWJ-50A FWJ-50A
FWJ-40A FWJ-40A
2 2

103 103

6 6

4 4

2 2

2 2
10 10
2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6 2 4 6
102 103 104 105 102 103 104 105
Prospective Short-Circuit Current Symmetrical RMS

Data Sheet: 35785303 Data Sheet: 35785309

For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp 105


Datasheet pdf - http://www.DataSheet4U.net/
High Speed Fuses

North American fuse accessories

Fuse Bases (Blocks)


Modular Style
Cooper Bussmann offers a comprehensive line of fuse bases
that provide the user with design and manufacturing flexibility.
Two identical half bases make up a Cooper Bussmann®
modular fuse base. These “split” units can be panel mounted
any distance apart to accommodate any length fuse.

Stud Type
Stud Type
The simpler design is the C5268 series modular fuse base.
With this design, the fuse terminal and cable (with
termination) are mounted on the same stud, minimizing labor
needed for installation. The stud type base is available in the
configuration shown in the table below.
Catalog Max Fuse Stud Stud Dia.
Number Amp Rating Height (in) & Threads
C5268-1 200 1.00 5
⁄16”-18
C5268-2 200 1.75 5
⁄16”-18
C5268-3 200 0.75 5
⁄16”-18
C5268-4 100 1.00 1
⁄4”-20
C5268-5 100 1.75 1
⁄4”-20

Connector Type
Connector Type
Cooper Bussmann also offers a modular style fuse base that
utilizes a tin-plated connector (for wire termination and heat
dissipation) and a plated-steel stud (for fuse mounting). The
www.DataSheet.co.kr

connector type fuse base is available in the configurations


shown below. Consult Cooper Bussmann for additional
product details.
Modular Max Max Fuse Data Sheet
Base Style Voltage Amp Rating Number
1BS101 600 100 1206
1BS102 600 400 1207
1BS103 600 400 1208
1BS104 600 600 1209
BH-0xxx 700 100 1200
BH-1xxx 2500 400 1201
BH-2xxx 5000 400 1202
BH-3xxx 1250 700 1203

Fixed Center Base Style


Fixed Center
Cooper Bussmann offers a comprehensive line of fixed mount
style fuse bases under the trademark TRON® rectifier fuse
blocks. The cable and fuse connections are similar to the stud
type fuse base — both are mounted on the same stud.
Consult Cooper Bussmann for complete product details.

106 For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp


Datasheet pdf - http://www.DataSheet4U.net/

You might also like