Getting Started: Digivis 500
Getting Started: Digivis 500
Getting Started
Version 1.0 SP1
DigiVis 500
Getting Started
Version 1.0 SP1
NOTICE
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hard-
ware described in this document.
This document and parts thereof must not be reproduced or copied without written per-
mission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license.
TRADEMARKS
All rights to copyrights and trademarks reside with their respective owners.
Table of Contents
About This Book
Use of Warning, Caution, Information, and Tip Icons ........................................................... 9
Typographic Conventions ..................................................................................................... 10
Terminology.......................................................................................................................... 10
Related Documentation ........................................................................................................ 10
2PAA104347R0203 5
Table of Contents
6 2PAA104347R0203
Table of Contents
Section 3 - Licensing
Introduction .......................................................................................................................... 77
Base License.............................................................................................................. 78
Optional Licenses...................................................................................................... 79
Index
2PAA104347R0203 7
Table of Contents
8 2PAA104347R0203
About This Book
Electrical warning icon indicates the presence of a hazard which could result in
electrical shock.
Warning icon indicates the presence of a hazard which could result in personal
injury.
Tip icon indicates advice on, for example, how to design your project or how to
use a certain function
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all Warning and Caution notices.
2PAA104347R0203 9
Typographic Conventions About This Book
Typographic Conventions
All text entries, shortcuts, prompts, system messages, menu items, screen elements
etc. comply with the Microsoft Windows conventions.
Terminology
You will find a complete and comprehensive glossary at the end of the Engineering
Manual, DigiVis 500 Graphics Builder. This glossary contains terms and
abbreviations that are unique to ABB or have a usage or definition that is different
from standard industry usage. Please make yourself familiar with this glossary.
Related Documentation
The following list gives an overview of the documentation relating to the DigiVis
500 system.
Title Number
Engineering Manual, DigiVis 500 Graphics Builder 2PAA104345R0201
Engineering Manual, Security Lock 2PAA104348R0201
English
The manuals listed above are for the DigiVis 500 system only. These manuals
should be supplemented by the AC500 related documentation (PS501 CD,
Documentation).
10 2PAA104347R0203
Section 1 DigiVis 500 Installation
General Notes
Recommended PC Equipment
2PAA104347R0203 11
General Notes Section 1 DigiVis 500 Installation
They were selected to guarantee a fluent workflow and have good response time.
Depending on the size of your project you might experience good behavior also
with a less powerful PC.
The proper and error-free operation of DigiVis 500 can be guaranteed only if
DigiVis 500 applications are the only ones installed on the PC.
12 2PAA104347R0203
Section 1 DigiVis 500 Installation Mixed systems with Windows XP and Windows 7
System Limits.bmp
2PAA104347R0203 13
Product Options Section 1 DigiVis 500 Installation
Product Options
For DigiVis 500 you need a hardkey and an authorization key. These will enable
you to work with those functions and features of DigiVis 500 Graphics Builder
and/or DigiVis 500 Operations that was ordered.
Hardkey
DigiVis 500 products are protected by means of the hardkey and an associated
authorization key, which activates only those packages and functionalities for which
official orders have been processed.
The following are the versions of the hardkey:
• DigiVis 500 Graphics Builder
• DigiVis 500 Operations
English
In case of a hardkey failure, the software will enter an emergency mode which, just
like the demo mode expires after 100 days. As long as the hardkey is replaced
within these 100 days, the rights conferred by the license will remain in effect.
Similarly, if the hardkey is unplugged after startup the software will go into
emergency mode.
14 2PAA104347R0203
Section 1 DigiVis 500 Installation First Installation of the DigiVis 500 Software
2PAA104347R0203 15
Windows XP Installation Section 1 DigiVis 500 Installation
Windows XP Installation
Check to be sure that the Windows Operating System and the required Service Pack
English
for Windows is installed. For detailed information on required service packs please
refer to the release notes, which are available on the setup CD. The Service Packs
are available free of charge from Microsoft Corporation (also on the internet at
http://www.microsoft.com).
16 2PAA104347R0203
Section 1 DigiVis 500 Installation Windows 7 User Account Control Settings
UAC1
Click Disable UAC to disable the UAC. The setup will disable the UAC and restart
the PC. Ensure that you have no unsaved work and click Yes to restart the computer.
UAC2
2PAA104347R0203 17
Network and IP Address Settings Section 1 DigiVis 500 Installation
After the restart, setup will continue with the DigiVis 500 Installation.
IP Address Settings
Windows XP
> Start > Settings > Network and Dial-up Connections
English
Windows 7
> Start > Control Panel > Click Network and Internet
> Click Network and Sharing Center > Click Change adapter settings
> Right-click a network adapter and select Properties
> Select Internet Protocol Version 4 (TCP/IPv4) and click Properties
18 2PAA104347R0203
Section 1 DigiVis 500 Installation Network and IP Address Settings
installation can be used unchanged to operate a DigiVis 500 system. The TCP/IP
protocol must be used on all PCs.
2PAA104347R0203 19
FTP Server under Windows XP Section 1 DigiVis 500 Installation
20 2PAA104347R0203
Section 1 DigiVis 500 Installation FTP Server under Windows XP
Right-click Default FTP Site and select Properties. The configuration dialog for
the FTP Server is displayed now.
2PAA104347R0203 21
FTP Server under Windows XP Section 1 DigiVis 500 Installation
access.
22 2PAA104347R0203
Section 1 DigiVis 500 Installation FTP Server under Windows XP
2PAA104347R0203 23
FTP Server under Windows 7 Section 1 DigiVis 500 Installation
> Start > Control Panel > Programs > Programs and Features
Click Turn Windows features on or off in the left navigation bar.
English
24 2PAA104347R0203
Section 1 DigiVis 500 Installation FTP Server under Windows 7
> Start > Control Panel > System and Security > Administrative Tools
Double-click Computer Management
Expand Services and Applications > Internet Information Services
The IIS Management Console is displayed. It has a left tree area named
“Connections”, a right area called “Actions” and context dependent area in the
middle.
> In the Connections tree, expand the root node
> Select Sites
> Right-click Sites and then select Add FTP Site
2PAA104347R0203 25
FTP Server under Windows 7 Section 1 DigiVis 500 Installation
26 2PAA104347R0203
Section 1 DigiVis 500 Installation FTP Server under Windows 7
2PAA104347R0203 27
FTP Server under Windows 7 Section 1 DigiVis 500 Installation
Open the configuration dialog of the Windows Firewall with Advanced Security.
> Start > Control Panel > Administrative Tools > Windows Firewall with
Advanced Security > Select Inbound Rules
If the FTP Server is initially installed, the firewall still blocks the traffic until the
service of the FTP Server is restarted.
28 2PAA104347R0203
Section 1 DigiVis 500 Installation Testing the FTP Server
The FTP Server is now restarted and the firewall will use the exception rules now.
Windows 7
> Start > Control Panel > System and Security > System. Select Advanced
system settings. Click Settings in the Performance. In the Performance
Options, click Advanced tab.
2PAA104347R0203 29
Disable Automatic Updates Section 1 DigiVis 500 Installation
The larger the installed physical memory the larger the virtual memory size
should be. It is recommended to configure the size of the virtual memory at 1.5
times the size of the total available memory.
Windows 7
> Start > Control Panel > System and Security >Windows Update.
Select Change settings
Select Never check for updates from the list of.
Press OK.
English
Windows Temp-directories must be excluded for all users working with DigiVis
500. To find the Temp folder for current logged user on Windows XP/Windows 7
Operating Systems.
Select Start > Run Command. Type %temp% in the Run Command box and
click Enter.
30 2PAA104347R0203
Section 1 DigiVis 500 Installation Firewall Configuration
Firewall Configuration
Windows XP
If the Firewall is enabled, following settings for Firewall configuration are
required for both DigiVis 500 Graphics Builder and DigiVis 500 Operations.
1. For OPC Tunnel, add the Tunnel Port with port address (By default 9950) in
the Firewall Exception list.
Go to Start > Settings > Network Connections > Change Windows Firewall
settings > Select Exceptions tab > Add Port > Enter Name for the Port, Port
number as 9950 and select TCP.
2PAA104347R0203 31
Windows XP Section 1 DigiVis 500 Installation
32 2PAA104347R0203
Section 1 DigiVis 500 Installation Windows 7
Windows 7
For Windows 7 the firewall configuration is handled by the DigiVis 500 setup. The
firewall is configured to allow the DigiVis 500 applications to communicate
properly.
There is no specific configuration by the user necessary.
During the installation process the setup will add several DigiVis 500 programs to
the firewall exclusion list. To verify the entries made, you can open the Windows
Advance Firewall configuration as follows:
> Start > Control Panel > System and Security >Windows Firewall
Select Advanced settings.
2PAA104347R0203 33
Disable Screen Saver Section 1 DigiVis 500 Installation
When the setup has finished there are several new entries that start with “DigiVis
500”.
English
For firewall exceptions related to CoDeSys software and OPC Server, refer to
CoDeSys 2.3 User Manual for PLC Programming and CoDeSys OPC Server
V3 Installation and Usage Manual.
The screen saver needs to be disabled in the Windows Operating System settings.
34 2PAA104347R0203
Section 1 DigiVis 500 Installation For Installation of DigiVis: Setting the Theme and Screen
> Start > Control Panel > Appearance and Themes > Display
The Display Properties are displayed.
Select the Screen Saver tab.
In the Screen Saver list, select (None).
Click OK.
> Start > Control Panel > Appearance and Personalization > Personalization
Click Screen Saver in the lower right corner.
In the Screen Saver list, select (None).
Click OK.
2PAA104347R0203 35
For Installation of DigiVis: Setting the Theme and Screen Resolution Section 1 DigiVis 500
Windows XP New
> Start > Control Panel > Appearance and Themes > Display
Appearance:
> Tab Themes > Select Windows XP as theme.
Resolution:
> Tab Settings > Select resolution 1280 x 1024 pixels.
Windows 7 New
36 2PAA104347R0203
Section 1 DigiVis 500 Installation For Installation of DigiVis: Additional Steps to disallow Operating
Windows XP Conventional
> Start > Control Panel > Appearance and Themes > Display
Appearance:
> Tab Themes > Select Windows Classic as theme.
Resolution:
> Tab Settings > Select resolution 1024 x 768 pixels.
Windows 7 Conventional
Windows XP
The taskbar property “Keep the taskbar on top of other windows” must be disabled:
> Right click the taskbar
> Properties
Disable “Keep the taskbar on top of other windows”
2PAA104347R0203 37
For Installation of DigiVis: Additional Steps to disallow Operating System Access Section 1 DigiVis
Windows 7
Background Information
When you start DigiVis in Production Mode the Windows Start button is disabled.
There is no minimize button in DigiVis. This behavior has been implemented
because of security concerns. The DigiVis user cannot switch to other applications.
Only those applications that have been started before the start of DigiVis can be
reached by the DigiVis user by pressing the ALT+TAB keys.
The Windows Operating System can be reached from the DigiVis menu (Tools /
System / Operating System) after entering a password. With this action the
Windows start button is enabled and is displayed with text. This is not a security
English
problem, as long as the taskbar is in the background of DigiVis. DigiVis is not able
to suppress the taskbar in all cases.
In Windows XP, if the taskbar property is configured with “Keep the taskbar on
top of other windows” option, it is shown in front of DigiVis. Therefore, the
taskbar property “Keep the taskbar on top of other windows” option must be
disabled to make sure that the DigiVis user has no access to other applications.
38 2PAA104347R0203
Section 1 DigiVis 500 Installation Upgrade an Existing Version to the New Version
2PAA104347R0203 39
Upgrade from V1.0 to V1.0 SP1 Section 1 DigiVis 500 Installation
Upgrading.png
Click Next.
English
InstallShield.png
Click Install. The existing V1.0 features will be upgraded to V1.0 SP1.
To add new features after the upgrade has finished, run the setup again. The setup
goes into the Maintenance mode.
40 2PAA104347R0203
Section 1 DigiVis 500 Installation Start Setup for New Installation
First select the language (in this case “English”) for the software in the Language
screen. The “setup dialog” with the different software packages is displayed.
tb499.bmp
Release Notes This option opens the document “Release Notes” for reading, which
lists the new features of this version.
DigiVis 500 Software
This option allows the selection of the DigiVis 500 software
packages that can be installed.
2PAA104347R0203 41
Install DigiVis 500 Software Section 1 DigiVis 500 Installation
tb499_1.bmp
42 2PAA104347R0203
Section 1 DigiVis 500 Installation Selecting a Setup type
tb500.bmp
Once you have clicked Next in the “Welcome screen” the “License agreement”
screen is displayed. On selecting the “I accept...” option and clicking on Next, the
“Setup type” screen is displayed.
2PAA104347R0203 43
Selecting a Setup type Section 1 DigiVis 500 Installation
tb500_1.bmp
The destination folder for the installation can be changed using the Browse
button.
44 2PAA104347R0203
Section 1 DigiVis 500 Installation Demo Mode
The table above lists all the possible directories that may be created after the
installation of DigiVis 500 on your PC. Some of these directories may not be
created based on the type of installation and the DigiVis 500 packages that are
selected for installation.
Demo Mode
Selecting this mode will install the software on the system for a try-out. No license
is needed and all functionalities of the software are available to the user. The validity
of this mode is however limited to 100 days.
Selecting the setup type Demo from the Setup type screen and clicking on Next will
display the “Workplace type” screen.
2PAA104347R0203 45
Demo Mode Section 1 DigiVis 500 Installation
tb500_2.bmp
The default selection for the Demo mode is shown in the screen shot above,
However the user can choose any one of the workplace types that are listed on the
screen or choose the custom option.
Detailed description of each of the workplace types can be obtained by clicking
English
on the Help icon provided on the top right side of the screen
The Detail button can be used to view the feature tree showing the components
that will be installed for the workplace type that is selected, in the chosen mode.
This is just a view of the feature tree and the user cannot select or deselect the
components in this view.
Selecting a workstation type and clicking on Next brings up the “Ready to install”
dialog. Refer to Ready to install dialog on page 50.
Custom Option
This option is recommended for advanced users of the DigiVis 500 software. It
gives the user most flexibility in terms of selecting or deselecting the components to
46 2PAA104347R0203
Section 1 DigiVis 500 Installation Demo Mode
be installed. On selecting the setup type Custom and clicking on Next the following
screen with the feature tree appears.
tb500_10.bmp
Click on a component name in the feature tree and a brief description of that
component will be displayed on the right side. The space required on the drive as
shown in the screen above does not include the requirements from the Hardkey,
DigiVis 500 Graphics Builder/Operations Help and ABB OPC Tunnel.
2PAA104347R0203 47
Demo Mode Section 1 DigiVis 500 Installation
The DigiVis 500 software components are listed in a tree structure in the left-hand
section of the dialog. The check box in front of each software package indicates the
state of that component on the PC.
48 2PAA104347R0203
Section 1 DigiVis 500 Installation Production Mode
Production Mode
This mode will modify the setting on the PC besides installing the Software.
License key should be provided for installing the selected components.
On selecting the Production mode in the Setup type screen and clicking on Next the
“Workplace type” screen is displayed.
tb500_8.bmp
The default selection for the production mode is shown in the screen shot above,
however the user can choose any one of the workplace types that are listed.
2PAA104347R0203 49
Production Mode Section 1 DigiVis 500 Installation
Selecting a workstation type and clicking on Next brings up the “Ready to install”
dialog. Refer to Ready to install dialog on page 50.
If the Custom option is selected clicking on Next brings up the feature tree dialog.
Refer to Select Software Packages to Be Installed on page 48.
tb500_11.bmp
50 2PAA104347R0203
Section 1 DigiVis 500 Installation Import Data from Previous DigiVis 500 Installation
tb500_14.bmp
If the project data are to be copied into the new directory, activate checkbox Import
subdirectories of a previous DigiVis 500 Installation and Browse to the directory
name of the previously used DigiVis 500 Installation.
Clicking the Next button copies the data from the previous DigiVis 500 installation,
if so desired. The configuration screen is displayed thereafter.
The configuration dialogs can be used to customize the installation to your
computer and requirements. The settings can be modified retroactively after the
installation has been completed without having to carry out the installation again.
For a detailed description, refer to Configure DigiVis 500 System on page 56.
Click OK on the “Configuration screen” to go to the end of this installation part.
A screen indicating the completion of the Installation is displayed as follows.
2PAA104347R0203 51
Import Data from Previous DigiVis 500 Installation Section 1 DigiVis 500 Installation
tb500_31.bmp
52 2PAA104347R0203
Section 1 DigiVis 500 Installation Maintenance Mode
Maintenance Mode
If one or more DigiVis 500 software component(s) of the same version are already
installed on the System, then Setup goes into Maintenance Mode.
tb500_12.bmp
2PAA104347R0203 53
Modify Option Section 1 DigiVis 500 Installation
Modify Option
This option can be used to add or remove components of the DigiVis 500 Software.
Choosing this option and clicking Next will bring up the “feature-tree” dialog.
tb500_16.bmp
The components that are already installed on the System will appear with a check
English
Repair Option
This option is used to reinstall components that have already been installed on the
System, in order to repair files or settings that may have been overwritten.
The repair option will overwrite the content of the Hot Fix. If you had installed
any Hot Fixes you need to manually re-install them.
54 2PAA104347R0203
Section 1 DigiVis 500 Installation Remove Option
If any file, registry key or content of any installed component is corrupted in the
system, choosing this option will repair or put back the contents of the components.
Setup replaces or repairs and verifies files and registry keys contained in the DigiVis
500 software components.
Select the Repair option and click on Next, the Setup makes the necessary repairs.
The configuration screen is displayed when the repair process is completed. Modify
the settings if required. The settings can be modified retroactively after the
installation has been completed without having to carry out the installation again.
For a detailed description, refer to Configure DigiVis 500 System on page 56.
Click on OK and the Maintenance complete screen is displayed. Click on Install
and the Repair is complete.
Remove Option
This will remove DigiVis 500 components from your System. Choosing this option
and clicking on Next will remove all the installed components from the system. This
is similar to “Remove” option in Add/Remove Programs of the Windows operation
system.
Select the Remove option in the Maintenance screen and the Setup asks the user to
confirm the removal of the components.
Click on Yes and all the DigiVis 500 software components will be removed from the
System. Application data like logs, archives, projects and export files will not be
removed.
These can be deleted manually if they are no longer needed. In case a user account
was created by the setup this user account will also remain.
The Setup displays the Uninstall complete screen. There is an option in this dialog
to choose between restarting the System right away or later. Choose the appropriate
option and click on Finish to complete the removal of the software components.
2PAA104347R0203 55
General Settings Section 1 DigiVis 500 Installation
It is also possible to change these settings after the installation is finished, without
having to repeat the actual installation. For this purpose, start the Configure
program via the Start menu.
> Start > Programs > ABB Industrial IT > DigiVis 500
> Configure
Identical dialogs are used for the initial installation as well as for subsequent
modifications of the software configuration. In the tree structure in the left part of
the dialog box, select all entries one by one to configure the required settings.
General Settings
English
tb500_20.bmp
Installation Modes
The Installation-mode can be changed from Demo to Production or vice versa in
this dialog without having to reinstall the Software.
56 2PAA104347R0203
Section 1 DigiVis 500 Installation General Settings
2PAA104347R0203 57
Settings for DigiVis 500 Graphics Builder Section 1 DigiVis 500 Installation
tb500_21.bmp
English
Resource ID Several software packages can be run at the same time on a PC. To
enable these software packages to be addressed unambiguously,
each one must be assigned a unique number, the resource
identification number.
All the resources within a DigiVis 500 system must also have a
unique resource ID.
Dimension/Message Text
This option is reserved for future use.
58 2PAA104347R0203
Section 1 DigiVis 500 Installation Settings for DigiVis 500 Operations
tb500_23.bmp
Resource ID Several software packages can be run at the same time on a PC. To
enable these software packages to be addressed unambiguously,
each one must be assigned a unique number, the resource
identification number.
All the resources within a DigiVis 500 system must also have a
unique resource ID.
Recover DigiVis System Security
If the DigiVis system security is corrupted (indicated by the
message “DigiVis 500 Operations system security corrupted! Please
use the Configure tool to recover” when DigiVis 500 Operations is
started), for example, after network software has been re-installed,
then this option is used for recovery.
2PAA104347R0203 59
Settings for DigiVis 500 Operations Section 1 DigiVis 500 Installation
Printer Settings
Two printers are supported per operator station. One printer should be used for the
continuous output of the signal sequence log. The other printer is then available for
printing the operation logs. One of the two printers is also
used for hard copies.
Printer 1 Choose a printer installed under Windows, for example, for
continuous stationery.
Printer 2 Choose a printer installed under Windows, for example, a color
printer.
60 2PAA104347R0203
Section 1 DigiVis 500 Installation Settings for DigiBrowse
Hardcopy Printer 1 / 2
Choose one of the installed printers to output a hardcopy from the
operator.
For hardcopies do not choose a printer which is used for producing signal
sequence logs.
Installation Complete
Once all the settings have been made, click OK to finish the Setup program or
Configure tool.
We wish you every success to perform your automation tasks using DigiVis 500.
DigiVis 500 Graphics Builder will greatly reduce the effort required because of
standards such as Windows and the use of Tag Type Library.
Should you have unexpected problems during installation, please contact your local
DigiVis 500 service provider or your local ABB office.
2PAA104347R0203 61
Starting the ABB OPC Tunnel Section 1 DigiVis 500 Installation
tb500_2.bmp
If the software was not installed on your system, then run the DigiVis 500 setup and
use the Modify option to select the software for installation from the feature tree
dialog. Refer to Modify Option on page 54.
English
Configurator
This window is used to specify the PROG ID of the OPC DA and OPC AE Servers
and the port number that are used for the services.
The default entries are shown in the screenshot below. The User can however
modify these values based on his requirement.
62 2PAA104347R0203
Section 1 DigiVis 500 Installation Starting the ABB OPC Tunnel
OPCTunnel_Configurator.bmp
System Tray
A system tray can be enabled for easy access of the ABB OPC Tunnel components.
Start > Programs > ABB Industrial IT > DigiVis 500 > OPC Tunnel >
System Tray
The status of the OPC Tunnel is indicated by an icon in the windows status bar. The
OPC Tunnel components can also be reached by right-clicking on this icon as
shown below.
System-Tray.bmp
Advanced Configurator
This option is for the advanced user for the purpose of configuring additional
options and for diagnostic purposes.
Web Pages
Web interface for diagnostic functionality.
Microsoft Windows XP/Windows 7 has an built in option for every service for its
recovery handling, which is visible in the service applet under the tab
“Recovery”. If the service fails, a restart service shall be configured.
2PAA104347R0203 63
Starting the ABB OPC Tunnel Section 1 DigiVis 500 Installation
Start > Settings > Control Panel > Administrative Tools > Services >ABB
OPC Tunnel.
English
64 2PAA104347R0203
Section 2 Initial Steps
General Notes
Once you have carried out the installation of DigiVis 500 Graphics Builder as
described in the preceding section, you can begin to set up a project.
Use the Start menu to launch DigiVis 500 Graphics Builder.
If the hard key is not plugged in or if the authorization key is not installed, a
message to that effect will be displayed. Correct the cause of the problem and
relaunch the program.
The version details of the installed software are displayed in the “About DigiVis 500
Graphics Builder” window. Click on the OK button to proceed further.
2PAA104347R0203 65
Step 1: Configuring the Software View of the Project Section 2 Initial Steps
The steps described below will guide the user to configure a DigiVis 500 system
in a single PC.
The Tag_Type_Li00 Library gets added under the POOL node in the project tree.
Drag and drop it under the CONF node in the project tree below the TagType_Lib
node. The library may now be used in the project.
English
66 2PAA104347R0203
Section 2 Initial Steps Network Configuration
First_Steps_New project.bmp
Network Configuration
Click on the Network icon in the Toolbar
Specify the IP address and resource IDs for Digivis 500 Operator and DigiVis 500
Graphics Builder stations. The IDs should be unique.
2PAA104347R0203 67
Network Configuration Section 2 Initial Steps
First_Steps_Network_Configuration.bmp
In order to proceed further with the instructions in this chapter, ensure that:
• AC500 Application (AC500_Demo.PRO) is developed and
downloaded to the controller.
• OPC Server and alarm configurations (OPCServer.ini and
English
If not already done, install the ABB OPC Tunnel on the PC where OPC Server
is installed. Select the OPC Tunnel Server option in the “Workplace type” screen
while running the DigiVis 500 installation.
68 2PAA104347R0203
Section 2 Initial Steps Step 2: ABB OPC Tunnel Configuration
OPCTunnel_Configurator.bmp
Specify the IP address of the PC on which the ABB OPC Tunnel is installed. The
port number is the same as the one used for the OPC tunnel configuration, that is
9950.
2PAA104347R0203 69
Step 3: OPC Server Configuration Section 2 Initial Steps
First_Steps_OPC_Config.bmp
English
70 2PAA104347R0203
Section 2 Initial Steps Step 4: Browsing and adding items to the OPC Item list
First_Steps_OPC_Item_List.bmp
Open the OPC Item List and click on the Synchronize button. Select the required
OPC Server from the list and click on OK. This will import all the OPC Items from
the OPC Server into the OPC Item List.
The OPC Item List is thus populated with items from the OPC Server.
2PAA104347R0203 71
Step 5:Instantiate Tags Section 2 Initial Steps
OPC_items_browsed.bmp
English
72 2PAA104347R0203
Section 2 Initial Steps Step 5:Instantiate Tags
OPC_Items_InstantiateAll.bmp
Specify the Tag names for these OPC Items in the New name column and click on
OK. The tags linked to the corresponding OPC Items are created in the Tag list.
2PAA104347R0203 73
Step 6: Assign Variables Section 2 Initial Steps
74 2PAA104347R0203
Section 2 Initial Steps Step 7: Commissioning
OPC_Items_Assign_Variable.bmp
Specify the required “variable name” in the New name column and click on OK. All
the OPC Items with the suggested name will be assigned as a variable in the
variable list.
User can configure free graphics and Trend from the Tags and Variables created in
Step 5:Instantiate Tags on page 72 and Step 6: Assign Variables on page 74.
Step 7: Commissioning
In the project tree perform the plausibility check. If any errors are reported from the
plausibility check, rectify the same. Choose Project / Commissioning to switch
from configuration to commissioning mode.
When switching to commissioning mode, DigiVis 500 Graphics Builder attempts to
establish a communication link with all the configured operator stations and OPC
Servers. As well as the resource nodes, the current states of the connections are
indicated in the project tree.
2PAA104347R0203 75
Step 7: Saving the Project Data Section 2 Initial Steps
An arrow before the node indicates that the data for the node is not yet available
(data has changed from last download) and needs to be loaded.
Select the resource node of Operator Station, if commissioning for the first time,
choose Load / Whole station. Changes and enhancements to the configuration can
be loaded into the operator station at a later stage using the Load / Changed
objects.
If the load operation has concluded successfully, the nodes in the project tree will
appear green and the load arrows will be removed.
As well as the resource nodes, the current states of the connections are indicated in
the project tree.
The process station should be flagged with the connection status running, and the
operator station with Version error. The DigiVis500 Operations software must be
launched; if this is not done, then No connection will be reported for the operator
station.
Select the node for the process station and choose Load / Changed objects; then
select the node for the operator station and choose Load / Entire station.
Switch to the operator station. Choose Display / Using tag list. The name of the
PID1 function block is displayed in a list. The name of the function block should
first be selected, and then its faceplate will be displayed.
The current alarms are listed in the message list along with their current time
stamps.
76 2PAA104347R0203
Section 3 Licensing
Introduction
The licensing for DigiVis 500 system is based on OPC signal based licensing
model.
All used OPC DA Items are counted as OPC signals. DigiVis 500 Operations will
refuse to work, if more than the licensed items are used in the actual configuration.
Used OPC DA Items are those that are configured in:
• Variable list
• Tags List (instantiated tags)
The number of OPC Items (OPC signals) that are used in DigiVis 500 Operations
are displayed in the header dialog for the VIS node in the project tree.
Select operator station object in Project Tree > Project > Header
2PAA104347R0203 77
Base License Section 3 Licensing
English
td004us.bmp
Base License
The following versions are available:
• DigiVis 500 Graphics Builder
• DigiVis 500 Operations (available for 50, 100, 250, 500, 1000, 2000 or Unlimited
OPC signals)
• Combination - DigiVis 500 Graphics Builder with DigiVis 500 Operations
(available for 50, 100, 250, 500, 1000, 2000 or Unlimited OPC signals)
78 2PAA104347R0203
Section 3 Licensing Optional Licenses
Optional Licenses
Additional options for DigiVis 500 Operations
• WEB display runtime
Web display functionality is used to load the local web browser. Calling the
web display from DigiVis 500 Operations will activate the link to the
configured Web site.
• Dual monitor support
Windows Dualview feature support is provided for DigiVis 500 Operations
station provided the graphic card which supports this feature and the
appropriate device driver is installed.
• DigiBrowse
DigiBrowse permits viewing archived trend, log files and reports without the
use of DigiVis 500 Operations.
Additional options for the DigiVis 500 system
• Security Lock
Provides access control for configuration with DigiVis 500 Graphics Builder
and for operation and observation with DigiVis 500 Operations.
If the number of OPC signals exceed the maximum limit of the OPC signal based
license for DigiVis 500 Operations, then a message indicating the same is
displayed and the loading of the operator station is aborted.
Any OPC Item that is assigned as a variable and not used in any DigiVis 500
Operations display is still counted as a OPC signal.
All the OPC Items which has been assigned either as a variable or Tag from the
OPC Server will be counted as a signal from all the DigiVis Operator station(s)
linked to that OPC Server. This means that for a given OPC Server all the
connected DigiVis 500 Operations stations must have the license for the same
number of OPC signals. If one DigiVis 500 Operations station is connected to 2
OPC Servers then the license should consider the combined OPC signal count
from both the OPC Servers.
2PAA104347R0203 79
Optional Licenses Section 3 Licensing
License Expansion
The signal based license for DigiVis 500 Operations can be expanded as follows:
• 50, 100, 250, 500, 1000, 2000 OPC signals
• From any number to Unlimited OPC signals
English
80 2PAA104347R0203
Index
A F
ABB OPC Tunnel .................................... 61, 63 FTP Server under Windows XP ..................... 20
AC 500 Controller ........................................... 13
AC500 HA pairs ............................................. 13 G
AC500 High availability ................................. 13 Glossary .......................................................... 10
AC500 Tag Type Library ................................ 66 Graphics Builder ............................................ 79
Advanced Configurator ................................... 63
Authorization key ............................................ 14 H
Authorization Key Installation ........................ 57 Hardkey .......................................................... 14
Autostart .......................................................... 60 Host names ..................................................... 19
B I
Base License ................................................... 78 Initial Steps ..................................................... 65
Browsing ......................................................... 71 Installation
Printer ...................................................... 60
C Instantiate Tags .............................................. 72
English
Checklist for first Installation ......................... 15 IP address ....................................................... 57
Commissioning ............................................... 75
L
D License agreement .......................................... 43
Default nodes in project tree ........................... 65 License Expansion .......................................... 80
Demo Mode .................................................... 57
Demo mode ..................................................... 14 M
DigiBrowse .............................................. 61, 79 monitor resolution .......................................... 16
DigiVis 500 Operations ................. 59 to 60, 79
DigiVis 500 System Limits ............................. 12
N
Dimension ....................................................... 58
Network protocol ............................................ 15
Dual monitor support ...................................... 79
Number of used signals .................................. 77
E O
Emergency mode ............................................ 14
OPC DA Items ............................................... 77
OPC Item list .................................................. 72
2PAA104347R0203 81
Index
P
Ping ................................................................. 19
Production Mode ............................................ 57
Project ............................................................. 75
R
Recommended PC Equipment ........................ 11
Related documentation ................................... 10
S
Security Lock .................................................. 79
Settings .................................................... 59, 61
Setup ............................................................... 41
Signal .............................................................. 77
Start ................................................................. 41
Subnet mask .................................................... 57
English
U
User account details ........................................ 57
V
Virtual memory ............................................... 29
W
WEB display runtime ..................................... 79
82 2PAA104347R0203
2PAA104347R0203 Printed in Germany, January 2012
Copyright © 2012 ABB, All Rights Reserved
® Registered Trademark of ABB
™ Trademark of ABB