Project Summary: Location and Weather

The document provides information on a project located in a hot climate with summer temperatures reaching 43°C. It summarizes the building as an office with 30m2 area. Peak cooling load is 6,520W in June at 3PM, while peak heating load is 668W. The default zone covers the entire 30m2 area and has a peak cooling load of 5,023W. Roof has the highest percentage of cooling load at 43.94% while people contribute most to heating load at -25.37%.

Uploaded by

Avdhesh Chandra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views4 pages

Project Summary: Location and Weather

The document provides information on a project located in a hot climate with summer temperatures reaching 43°C. It summarizes the building as an office with 30m2 area. Peak cooling load is 6,520W in June at 3PM, while peak heating load is 668W. The default zone covers the entire 30m2 area and has a peak cooling load of 5,023W. Roof has the highest percentage of cooling load at 43.94% while people contribute most to heating load at -25.37%.

Uploaded by

Avdhesh Chandra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 4

Project Summary

Location and Weather


Project Project Name
Address
Calculation Time Saturday, June 6, 2020 11:45 AM
Report Type Standard
Latitude 26.28°
Longitude 80.20°
Summer Dry Bulb 43 °C
Summer Wet Bulb 29 °C
Winter Dry Bulb 7 °C
Mean Daily Range 10 °C

Building Summary
Inputs
Building Type Office
Area (m²) 30
Volume (m³) 92.07
Calculated Results
Peak Cooling Total Load (W) 6,520
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (W) 5,401
Peak Cooling Latent Load (W) 1,120
Maximum Cooling Capacity (W) 6,520
Peak Cooling Airflow (L/s) 371.2
Peak Heating Load (W) 668
Peak Heating Airflow (L/s) 98.6
Checksums
Cooling Load Density (W/m²) 215.87
Cooling Flow Density (L/(s·m²)) 12.29
Cooling Flow / Load (L/(s·kW)) 56.92
Cooling Area / Load (m²/kW) 4.63
Heating Load Density (W/m²) 22.12
Heating Flow Density (L/(s·m²)) 3.26

Zone Summary - Default


Inputs
Area (m²) 30
Volume (m³) 92.07
Cooling Setpoint 23 °C
Heating Setpoint 21 °C
Supply Air Temperature 12 °C
Number of People 8
Infiltration (L/s) 0.0
Air Volume Calculation Type VAV - Single Duct
Relative Humidity 46.00% (Calculated)
Psychrometrics
Psychrometric Message None
Cooling Coil Entering Dry-Bulb Temperature 25 °C
Cooling Coil Entering Wet-Bulb Temperature 17 °C
Cooling Coil Leaving Dry-Bulb Temperature 10 °C
Cooling Coil Leaving Wet-Bulb Temperature 10 °C
Mixed Air Dry-Bulb Temperature 25 °C
Calculated Results
Peak Cooling Load (W) 6,520
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (W) 5,401
Peak Cooling Latent Load (W) 1,120
Peak Cooling Airflow (L/s) 371.2
Peak Heating Load (W) 668
Peak Heating Airflow (L/s) 98.6
Peak Ventilation Airflow (L/s) 28.1
Checksums
Cooling Load Density (W/m²) 215.87
Cooling Flow Density (L/(s·m²)) 12.29
Cooling Flow / Load (L/(s·kW)) 56.92
Cooling Area / Load (m²/kW) 4.63
Heating Load Density (W/m²) 22.12
Heating Flow Density (L/(s·m²)) 3.26
Ventilation Density (L/(s·m²)) 0.93
Ventilation / Person (L/s) 3.5

Cooling Heating
Components Percentage of Percentage of
Loads (W) Loads (W)
Total Total
Wall 1,168 17.92% 858 24.73%
Window 81 1.24% 34 0.97%
Door 165 2.53% 103 2.97%
Roof 2,207 33.85% 597 17.19%
Skylight 0 0.00% 0 0.00%
Partition 0 0.00% 0 0.00%
Infiltration 0 0.00% 0 0.00%
Ventilation 1,356 20.80% 478 13.77%
Lighting 398 6.11% -398 -11.47%
Power 244 3.75% -244 -7.04%
People 759 11.65% -759 -21.87%
Plenum 0 0.00%
Fan Heat 141 2.16%
Reheat 0 0.00%
Total 6,520 100% 668 100%

Default Spaces
Space Area Volume Peak Cooling Load Cooling Airflow Peak Heating Load Heating Airflow
Name (m²) (m³) (W) (L/s) (W) (L/s)
1 Space 30 92.07 5,023 371.2 190 98.6

Space Summary - 1 Space

Inputs

Area (m²) 30
Volume (m³) 92.07
Wall Area (m²) 77
Roof Area (m²) 33
Door Area (m²) 2
Partition Area (m²) 0
Window Area (m²) 1
Skylight Area (m²) 0
Lighting Load (W) 530
Power Load (W) 325
Number of People 8
Sensible Heat Gain / Person (W) 73
Latent Heat Gain / Person (W) 59
Infiltration Airflow (L/s) 0.0
Space Type Audience/Seating Area - Auditorium
Calculated Results
Peak Cooling Load (W) 5,023
Peak Cooling Month and Hour June 3:00 PM
Peak Cooling Sensible Load (W) 4,648
Peak Cooling Latent Load (W) 375
Peak Cooling Airflow (L/s) 371.2
Peak Heating Load (W) 190
Peak Heating Airflow (L/s) 98.6

Cooling Heating
Components Percentage of Percentage of
Loads (W) Loads (W)
Total Total
Wall 1,168 23.26% 858 28.67%
Window 81 1.61% 34 1.12%
Door 165 3.28% 103 3.45%
Roof 2,207 43.94% 597 19.93%
Skylight 0 0.00% 0 0.00%
Partition 0 0.00% 0 0.00%
Infiltration 0 0.00% 0 0.00%
Lighting 398 7.93% -398 -13.30%
Power 244 4.86% -244 -8.16%
People 759 15.12% -759 -25.37%
Plenum 0 0.00%
Total 5,023 100% 190 100%