Evaporator Pressure Regulating Valve Sporlan
Evaporator Pressure Regulating Valve Sporlan
SORIT-12
ORIT-6
ORIT-PI
®
Page 2 / RACE Catalogue 90-20 UK
Table of Contents
Application ............................................................................................................................................................................................................. 3
Selection Procedures...................................................................................................................................................................................... 8
Figure 2
Receiver
Normal Condenser
10 psig Replaceable
-30°F Catch-All
See•All
Liquid Line Liquid Header
24 psig Solenoid
Valve
SORIT Valve -10°F TEV
Check Valve
Suction Header
Evaporator A
16 psig
Defrost Header
Distributor Check Valve
Compressors with Replaceable Suction -20°F
2-Way Solenoid
Filter and Oil Level Control
Suction Header
the compressors was set for -30°F (10.0 psig) then an Direct acting ORIT-6 and -10 EPRs are used in these
EPR would also be required on evaporator B. In many applications with a solenoid valve in parallel (see
applications, EPRs are installed with every evaporator Evaporator C, Figure 2). If a normally closed solenoid
group to act as a suction stop solenoid valve for valve is used, energizing the coil will bypass the EPR
defrost while still maintaining the flexibility to set the and allow the case to pull down to the common suction
evaporator saturation pressure if necessary. pressure. De-energizing the coil will return control to
the EPR. Some applications with ORI-6 or -10s use a
As with the single evaporator applications, proper valve
normally open solenoid in parallel to allow the system
selection will always yield the optimum performance
to “fail-safe” in low temperature mode. In these appli-
under all operating conditions (See selection procedure
cations energizing the coil will cause the valve to close,
for more detail).
diverting refrigerant flow to the EPR. The EPR will then
control the evaporator at the higher pressure setting.
Loop Systems:
Pilot Operated EPRs are wide open in the low tempera-
On these systems, the evaporator groups are piped
ture operating mode and can be electrically switched
to a common liquid and suction trunk line “looped”
to control at the valve set point. The (S)ORIT-PIE inter-
throughout the store. EPRs are installed in or near the
nally piloted EPRs are offered with an optional Electric
case on loop systems. Sporlan direct acting ORITs and
open feature designed specifically for these applica-
the internally piloted (S)ORIT-PIs are recommended
tions. In addition the (S)ORIT-PIE can be installed at
for loop systems requiring EPRs. Externally piloted (S)
the rack, or in the case, since a high-side pilot connec-
ORITs are not recommended, as high pressure vapor is
tion is not necessary. Operation details of the electric
required to operate the valve.
open feature of the (S)ORIT-PIE are covered on Page
7. The (S)ORIT high pressure piloted EPRs can be con-
Dual Temperature Applications:
verted for dual temperature applications by installing
Dual temperature applications allow a supermarket an A3/E3 solenoid valve in the high pressure vapor
to operate a refrigerated display case at either low or pilot line.
medium temperature to meet the promotional needs
of the store. Typically a refrigerated display case (or Defrost Applications:
cases) applied in this manner would be piped to the
Most refrigeration applications require occasional
low temperature suction group.
defrosting of the evaporator to maintain proper
performance and temperature control of the refrigerated
RACE Catalogue 90-20 UK / Page 5
the compressors.
Flow
Some gas defrost applications require reverse flow Pressure
Tap
through the EPR. The SORIT-PI internally piloted P1
EPRs will allow reverse flow of defrost gas through
the valve. This allows the valve to be installed in the
refrigerated display case or in the store piping trench
on gas defrost systems without additional check valve
piping. The SORIT-PI suction stop solenoid coil must To indicate this trait, the valve nomenclature describes
be de-energized for proper reverse flow operation. valve operation as Open on Rise of Inlet pressure or
ORI.
Paralleling Evaporator Pressure Regulators:
For pressure regulating valves to modulate closed or
If the system capacity is greater than the largest EPR open, requires a change in the pressure being regulat-
model available for the application, like model and ed by the valve. The amount of change in valve stroke,
size valves can be applied in parallel. The valve should for a given change in pressure, is the valve gradient.
be selected for half the system capacity to provide the Every valve has a gradient designed to provide the best
proper selection, and both valves adjusted to control possible operation. Valve sensitivity or “gain” relates
the same setting. This will ensure that the pressure to how the valve reacts with the system and how well
drop across each valve is the same. it controls the regulated pressure. Valve gain is a func-
tion of both the valve gradient and the valve capacity.
Piping Suggestions: The more “over-sized” a valve and the “steeper” the
The piping schematics used in this bulletin are for gradient, the more sensitive or higher the gain will be,
illustration purposes only to demonstrate general and the more the flow will change with a change in
location of the evaporator pressure regulating valve inlet pressure. Generally speaking, a more sensitive
in the system. Sporlan recommends that recognized valve will provide closer control of the inlet pressure.
piping references be consulted for assistance in piping However, a grossly oversized valve can cause hunting
procedures. Sporlan is not responsible for system and fluctuating system pressures. Direct acting models
design, any damage resulting from faulty system design, require more valve gradient to fully stroke the valve,
or for the misapplication of its products. Sporlan and are generally more sensitive to over-sizing than
reserves the right to void the product warranty if the the pilot operated models.
product is not applied as described in this bulletin.
Valve setting is defined as the minimum control pres-
sure, or the opening inlet pressure of the valve. Below
Refrigerants:
the setting the valve will close and stop refrigerant
Sporlan evaporator pressure regulating valves can be flow until the valve setting is reached. As inlet pressure
applied with any of the commonly used CFC, HCFC, increases above the valve setting, the valve will open at
and HFC refrigerants. None of the Sporlan EPR prod- the rate of the valve’s gradient, to provide more flow.
ucts are suitable for R717(Ammonia).
operating on the seat disc across the area of the port, • High pressure supply source to the pilot valve.
opposes the force exerted by the adjustment spring
• The pilot supply line should be kept as short as pos-
(P2), and provides the two operating forces for these
sible to minimize refrigerant condensation.
direct acting evaporator pressure regulating valves.
The force exerted by the valve’s adjustment spring • The high pressure supply source should be at least 50
determines the valve’s pressure setting. As the inlet psi greater than the downstream, or common suction
pressure increases above the valve setting, the inlet pressure, at the outlet of the pressure regulating valve.
pressure acting on the seat disc at the port of the valve • If used with gas defrost, the pilot supply source must
will overcome the force exerted by the adjustment be at the same supply source or higher pressure sup-
spring and will cause the valve to open. This allows flow ply source than the defrost gas.
through the valve. Increasing the adjustment spring
force will increase the valve setting and the pressure The pilot valve modulates in response to the upstream,
required to open the valve. As evaporator loads drop, or inlet pressure, as shown in Figure 4. As the inlet or
and less refrigerant is boiled off in the evaporator, the evaporator pressure drops (P1 acting on the underside
evaporator pressure will decrease and cause the seat of the pilot valve diaphragm through the inlet pilot
disc to move to a more closed position, until it reaches tube connection), the adjustment spring (P2 on top
the valve setting or minimum evaporator pressure. Any of the pilot valve diaphragm) modulates the pilot port
decrease in pressure below the setting will cause the open, and allows high side pressure (P5) to enter the
valve to close. chamber on top of the main valve piston. As soon as the
pressure in the chamber (P3) exceeds the evaporator
Since direct acting valves are set at the minimum pressure, the main piston begins to move closed against
evaporator pressure, and require an increase in inlet the opening spring (P4). As the valve inlet/evaporator
pressure to open against the valve gradient, Sporlan’s pressure increases under the diaphragm the pilot port
direct acting EPRs are rated for capacity at a design will modulate closed, and decrease the flow of high
evaporator pressure higher than the valve setting (see side pressure on top of the piston. This will allow the
Selection Procedures for more information). pressure on the top of the piston to vent to the outlet of
the valve through the bleed orifice. Once the pressure
Externally Pilot Operated Valves – (S)ORIT-12, approaches the valve inlet pressure the opening spring
-15, and -20: will open the main port and allow additional flow from
the evaporator.
Pressure Regulating Operation: These pilot oper-
ated EPRs use high side pilot pressure to control the Defrost Operation: The SORIT version is equipped
main valve piston that regulates upstream/inlet pres- with a suction stop feature in the pilot valve. This feature
sure. The high side pressure source allows this valve will immediately close the valve for defrost applications.
to be provided normally open. This allows the valve to With the pilot solenoid de-energized, as shown in Figure
be operated at minimal pressure drop to ensure maxi- 5, high side pressure is allowed to enter on top of the
mum capacity by minimizing suction line pressure piston, bypassing the pilot valve port. The high side
pressure forces the main piston closed as long as the
losses. The high side pressure source must meet the
inlet pressure to the valve does not exceed the pressure
following criteria to ensure optimum performance of
of the high side source to the pilot.
the pilot operated pressure regulating valve:
P2
P3
P5
Flow P1 Flow
P4
RACE Catalogue 90-20 UK / Page 7
When defrost is terminated, the pilot solenoid coil is Internally Pilot Operated Valves – (S)ORIT-PI-2,
energized and the pilot solenoid port is closed. High -3, -4, and -5:
side pressure on top of the piston is vented to the
Pressure Regulating Operation: Since these EPRs
outlet of the valve through the bleed orifice. Once the
are Piloted Internally, they do not require a high side
pressure approaches the valve setting the valve begins
to modulate to control the inlet pressure setting. pressure source to operate. The valves are operated by
the pressure differential across the valve and require a
Operation Savings: (S)ORIT high side piloted EPRs minimum pressure drop of 1 psi to obtain full capacity.
can provide significant energy savings by reducing The pilot valve modulates in response to the upstream
suction line pressure drop. Piloting with high side vapor or inlet pressure. The inlet pressure (P1) is transmitted
allows a normally open valve design that can be applied through internal passages to the underside of the pilot
at pressure drops less than 0.5 psi. This allows the valve diaphragm as shown in Figure 6. As the inlet or
common suction to run at the highest possible pressure
evaporator pressure drops, the adjustment spring (P2)
and still maintain the coldest evaporator temperature
on top of the pilot valve diaphragm modulates the
on the rack. Table 1 shows the percentage of compressor
pilot port open, and allows inlet pressure to enter the
capacity loss due to suction line pressure drop. As shown
in the table, this capacity loss increases considerably at chamber on top of the valve piston. As the pressure
lower evaporator temperatures. For example, an R-22 in the piston chamber (P3) approaches the inlet or
system running at a -25°F common suction would use evaporator pressure (P1), the closing spring force
approximately 3.5% less compressor power with high (P4) causes the valve piston to modulate to a more
side piloted EPRs sized at a 0.5 psi drop, when compared closed position. With the valve piston further closed an
to internally piloted EPRs sized for a 1 psi drop. increase in inlet or evaporator pressure (P1) will move
the pilot port to a more closed position and allow the
Table 1
piston chamber pressure (P3) to decrease by venting
to the outlet of the valve through the bleed orifice. As
% of Compressor Capacity the piston chamber pressure (P3) decreases, the inlet
Loss due to Pressure Drop pressure (P1) will push against the valve piston causing
Suction Line
Pressure Drop R22 R22 R404A it to modulate open and compress the closing spring.
+10°F / -12°C Evap. -25°F / -32°C Evap. -25°F / -32°C Evap. Defrost Operation: The SORIT-PI version is equipped
0 — — — with a suction stop feature in the pilot that allows the
1 2.2 5.6 6.1 valve to completely close for defrost applications. This
2 4.4 12.7 10.4 is accomplished with a 3-way solenoid operator, date
3 7.1 18.1 15.3
codes 26-02 and after, as shown in Figures 6 and 7.
With the pilot solenoid coil de-energized, as shown
4 9.5 24.2 19.5
in Figure 7, inlet pressure (P1) is allowed to enter
Based on compressor capacity curves at 100°F condensing. the piston chamber through the upper solenoid port.
At the same time, the lower solenoid port is closed,
Page 8 / RACE Catalogue 90-20 UK
to as the “natural” pressure drop for these systems. The Pilot Operated EPR Selection:
Quick Pick Selection tables on Pages 14 and 15, allow
As previously described, pilot operated EPRs have a
easy selection of a pilot operated EPR, based on the
high gain relationship and steep gradient. As a result
applicable conditions and considers the “natural” pres-
they require negligible allowable evaporator pressure
sure drop for the system design criteria listed.
change to control from valve setting to full valve stroke.
Therefore, pilot operated EPRs are rated for capacity
Direct Acting ORI(T)-6 & ORI(T)-10 Selection: at a full open position, and no correction factors for
As described in Valve Operation-Direct Acting Valves – minimum evaporator temperatures are necessary.
ORIT-6 & ORIT-10, Page 5, the reported valve capacities Example: Select a pilot operated EPR for a 20ºF R22
are provided with the minimum evaporator pressure evaporator line up, with a 86,800 Btu/hr load, and
assumed to be 8 psi lower than the evaporator pressure piped to a 10ºF rack suction header temperature. The
at design load for the 0 – 50 psig adjustment range refrigerant liquid entering the TEV is 60ºF, and the
product, and 12 psi lower than the evaporator pressure return gas temperature entering the EPR is 45ºF (20ºF
for the 30 – 100 psig adjustment range product. The Evaporator + 25ºF Superheat = 45ºF return gas).
difference between the design evaporator pressure and
the minimum evaporator pressure is referred to as the Using quick-pick selection table (Page 14):
allowable evaporator pressure change. Therefore, for an 1. Locate 10ºF “Common Suction” temperature.
ORI-6 0/50 rated for a 40ºF R22 evaporator, the nominal
2. Locate 20ºF “Circuit Temperature”
capacity would allow the evaporator pressure to drop from
the design 68.5 psig to the minimum evaporator pressure 3. If necessary appropriate correction factor for
of 60.5 psig or a minimum evaporator temperature liquid temperatures from the table on page
of approximately 34ºF. Refer to Table 3 for capacity 14 that vary from the 60ºF liquid used for the
multipliers for other allowable pressure changes. capacities in this table (see step 3 below).
Table 3 4. Scan horizontally across capacity columns
ALLOWABLE EVAPORATOR to select the first model (of desired type) that
2 4 6 8 10 12 14
PRESSURE CHANGE – psi exceeds the specified capacity in Btu/hr for R22
CORRECTION
ORIT-6, 10-0/50 .3 .6 .8 1.0 1.2 1.3 1.4 refrigerant. In this case a SORIT-PI-3 or a SORIT-
FACTOR
ORIT-6, 10-30/100 — .2 .6 .7 .9 1.0 1.1
12 would be selected at 132,100 and 96,700 Btu/
hr respectively.
It is considered acceptable to size most single evaporator
systems with a 2 psi available pressure drop across the
direct acting ORIT valves. This is not to be confused Using conventional capacity tables (Page 13):
with the allowable evaporator pressure change. This 1. Determine the “natural” pressure drop across
is the pressure drop across the valve when open at the the valve by subtracting the saturated pressure at
rated condition with the specified amount of refrigerant the 10ºF rack suction header temperature from
flowing through the valve. the saturated pressure at the 20ºF. In this case
Example: Select a direct acting ORIT for a R404A the 33 psi header pressure is subtracted from the
single evaporator refrigeration system with a design 43 psi circuit pressure to provide a 10 psi drop
evaporator temperature of 20ºF, a design capacity of 1.4 across the valve.
tons, a minimum allowable evaporator temperature of 2. Converting 86,800 Btu/hr to tons by dividing by
14ºF, and an available pressure drop of 2 psi. 12,000 Btu/ton, yields 7.23 tons.
1. From the capacity table on Page 13 the ORIT-10 is 3. Locate the liquid temperature correction factor for
capable of providing 2.29 tons at the design evaporator 60ºF from the table on page 13, since the capacity
temperature and available pressure drop. table is calculated with a 90ºF liquid temperature.
2. From the capacity table on Page 13 the saturation Divide the 7.23 ton load from step 2, by the correc-
pressure at the design evaporator is 55.7 psig. This tion factor 1.13. Only 6.51 tons are required.
application will require a 30 – 100 psig adjustment
4. Scan vertically down the 10 psi R22 column
range valve, and the minimum evaporator pressure
and select the first model (of desired type) that
for the nominal capacity selected in step 1 will be
exceeds the tons for 20ºF evaporator design tem-
44 psig (10ºF) or 12 psi lower. Since the specified
perature. As above, the SORIT-12 or SORIT-PI-3
minimum allowable evaporator temperature is 14ºF
are the appropriate selections.
(48 psig) a correction factor will have to be used to the
nominal capacity to check the selection. The allowable Sporlan also offers a computer selection program that
evaporator pressure change is approximately 8 psi can provide quick and easy product selections for a
(56 – 48) so the resulting capacity is 1.6 tons (2.29 x wide variety of operating conditions. Contact your
.7). The ORIT-10 is the proper selection. Sporlan representative for more information.
Page 10 / RACE Catalogue 90-20 UK
5/8 ODF Soldar 24.77 13.33 16.21 10.31 1.27 1.00 1.25 825-5
0/50 7/8 ODF Soldar 24.77 13.33 16.21 10.31 1.91 1.00 1.25 825-7
(Factory set 30)*
ORIT-6 1-1/8 ODF Soldar 24.77 13.33 16.21 10.31 2.31 1.25 1.50 825-9
30/100
(Factory set 60)* 1/2 SAE Flare 16.28 6.81 7.26 2.39 — 1.00 1.25
Not Available
5/8 SAE Flare 16.21 7.14 7.62 2.69 — 1.00 1.25
0/50 7/8 ODF Soldar 28.42 14.45 16.51 8.26 1.91 2.50 2.75 825-7
(Factory set 30)*
ORIT-10 1-1/8 ODF Soldar 28.42 14.45 16.51 8.26 2.31 2.50 2.75 825-9
30/100
(Factory set 60)* 1-3/8 ODF Soldar 28.42 14.45 16.51 8.26 2.31 2.50 2.75 825-11
Valve Nomenclature:
Optional
Solenoid
Specifications Stop Feature
• Maximum Rated Pressure = 450 psig
• Maximum Test Pressure = 450 psig
• MOPD = 300 psi (SORIT model only) D A
• Maximum Ambient Temperature = 120°F
• Maximum Fluid Temperature = 240°F
• Minimum Ambient/Fluid Temperature = -40°F
• Factory Setting = See table C
• Agency Certifications:
B B
Recognized
and and
Agency Product Guide File Country
UL SORIT-12, -15, -20 YI0Z MH4576 USA
Valve Nomenclature:
(S)ORIT-PI-2, -3, -4 y -5
Features 2.98
• Piloted internally (no high side
connection required)
• Adjustable settings up to 150 psig
• Optional solenoid stop feature to
close valve during system defrost
• Optional electric open feature for
“two temperature operation” 1.56 Coil Removal
• Corrosion resistant construction
• Manual lift stem to allow system evacuation
Specifications
• Maximum Rated Pressure = 400 psig G
• Maximum Test Pressure = 400 psig F
• MOPD = 190 psig (SORIT-PI model only) C
• Maximum Ambient Temperature = 120°F
• Maximum Fluid Temperature = 240°F
• Minimum Ambient/Fluid Temperature = -40°F
• Factory Setting = See table
E
• Agency Certifications:
D
A
B
Agency Product Guide File Country
UL SORIT-PI-2, -3, -4, -5 YI0Z MH4576 USA Recognized
Valve Nomenclature:
Capacities are calculated in accordance with ASHRAE Standard 158.2, “Methods of testing Capacity of Refrigerant Refrigerant Liquid Temperature Correction Factors for 90°F Liquid
Pressure Regulators”. Capacities are based on 90°F Liquid Temperature entering the expansion valve and 25°F super- -15 -10 -5 0 5 10 15 20 25 32 38
heated vapor entering the compressor.
R-22 1.35 1.31 1.28 1.24 1.21 1.17 1.13 1.09 1.05 1.00 0.95
ORIT-6 and ORIT-10 are rated based on a valve setting 8 psi lower than the Evaporator Design Temperature for the R-134a 1.43 1.39 1.35 1.30 1.26 1.21 1.16 1.12 1.07 1.00 0.94
0/50 psi adjustment range, and 12 psi lower for the 30/100 psi adjustment range. R-404A/R-507 1.59 1.53 1.47 1.41 1.35 1.29 1.23 1.16 1.10 1.00 0.92
RACE Catalogue 90-20 UK / Page 13
QUICK PICK SELECTION TABLES for SUPERMARKET MULTIPLE EVAPORATOR SYSTEMS – Valve Capacity Btuh
COMMON REFRIGERANT 22 REFRIGERANT 404A & 507
CIRCUIT or EVAP.
SUCTION (S)ORIT-PI (S)ORIT (S)ORIT-PI (S)ORIT
°F
°F 2 3 4 5 12 15 20 2 3 4 5 12 15 20
-35* 9,800 17,000 25,200 30,800 12,100 20,300 43,900 9,600 16,900 25,000 30,700 12,100 20,300 43,700
-34 13,400 23,500 34,900 42,600 16,800 28,100 60,500 13,200 23,200 34,600 42,500 16,700 28,100 60,400
-33 19,100 33,500 50,600 61,300 24,100 40,400 86,800 19,100 33,500 51,900 61,200 24,100 40,400 86,700
-35
-32 23,600 41,500 64,500 76,500 30,100 50,400 107,800 23,600 41,400 64,500 76,500 30,100 50,400 107,700
-31 27,500 48,400 75,500 90,000 35,400 59,200 126,300 27,500 48,400 75,500 90,100 35,400 59,200 126,300
-30 31,000 54,800 85,500 102,600 40,300 67,400 143,300 31,000 54,800 85,600 102,800 40,300 67,500 143,400
-30* 11,900 20,800 30,700 37,600 14,800 24,800 53,500 11,700 20,500 30,600 37,600 14,800 24,900 53,600
-29 16,200 28,500 42,400 51,900 20,400 34,300 73,800 16,000 28,200 42,200 52,000 20,500 34,400 74,000
Page 14 / RACE Catalogue 90-20 UK
-28 23,100 40,800 61,300 74,700 29,400 49,300 105,700 22,800 40,500 61,200 74,900 29,500 49,400 106,100
-30 -27 28,800 50,500 78,600 93,100 36,600 61,300 131,200 28,900 50,700 78,900 93,500 36,700 61,600 131,800
-26 33,500 59,000 91,800 109,400 43,000 72,000 153,600 33,600 59,200 92,300 110,000 43,200 72,400 154,400
-25 37,700 66,600 104,000 124,600 48,900 81,900 174,200 37,900 67,000 104,600 125,400 49,200 82,400 175,200
-20 55,900 100,100 157,600 193,800 75,900 126,500 265,700 56,300 100,900 158,900 195,800 76,600 127,700 268,100
-25* 14,200 24,900 37,000 45,400 17,900 30,000 64,700 14,100 24,700 37,000 45,700 18,000 30,200 65,100
-24 19,400 34,100 51,000 62,600 24,700 41,400 89,100 19,100 33,900 51,000 63,100 24,800 41,700 89,800
-23 27,600 48,900 73,600 90,100 35,400 59,400 127,600 27,300 48,700 73,800 90,800 35,700 59,900 128,600
-25 -22 34,800 61,000 94,800 102,200 44,100 73,900 158,300 35,000 61,500 95,600 113,200 44,500 74,600 159,700
-21 40,400 71,100 110,800 131,800 51,800 86,800 185,200 40,800 71,800 111,800 133,100 52,300 87,600 187,000
-20 45,500 80,400 125,400 150,000 58,900 98,600 209,900 46,000 81,100 126,600 151,600 59,500 99,600 212,000
-15 67,300 120,400 189,400 232,200 91,000 151,700 319,100 68,100 121,900 191,800 235,700 92,300 153,900 323,300
-15* 19,900 35,000 52,300 64,700 25,500 42,800 92,300 19,800 35,100 52,800 65,700 25,900 43,400 93,600
-14 27,000 47,800 71,900 89,100 35,100 58,900 126,800 26,900 48,000 72,600 90,500 35,600 59,800 128,800
-13 38,300 68,400 103,700 128,000 50,300 84,500 181,400 38,300 68,700 104,800 130,000 51,200 85,800 184,400
-15 -12 49,400 86,700 134,700 159,200 62,600 104,900 224,800 50,300 88,100 136,900 161,900 63,700 106,700 228,700
-11 57,500 101,000 157,200 186,700 73,400 122,900 262,800 58,500 102,800 160,000 190,100 74,700 125,200 267,500
-10 64,700 114,100 177,800 212,200 83,300 139,500 297,500 65,900 116,100 181,000 216,200 84,900 142,200 303,000
-5 95,400 170,100 267,100 326,000 127,700 213,200 449,500 97,300 173,700 273,000 333,600 130,700 218,100 459,500
-10* 23,300 41,100 61,600 76,400 30,100 50,500 109,000 23,300 41,300 62,400 77,800 30,600 51,500 101,000
-9 31,500 56,000 84,500 105,100 41,300 69,400 149,600 31,600 56,400 85,700 107,100 42,200 70,800 152,500
-8 44,700 80,100 121,700 150,800 59,300 99,500 213,900 44,900 80,800 123,600 153,900 60,500 101,600 218,300
-10 -7 58,300 102,200 158,700 187,500 73,700 123,600 265,000 59,500 104,400 162,100 191,500 75,300 126,300 270,600
-6 67,800 119,100 185,200 219,800 86,400 144,800 309,600 69,200 121,700 189,300 224,800 88,300 148,000 316,400
-5 76,300 134,400 209,300 249,600 98,000 164,200 350,300 78,000 137,400 214,100 255,400 100,300 168,000 358,300
0 112,300 200,000 313,800 382,200 149,800 250,100 527,800 115,100 205,200 322,200 393,000 154,000 257,000 542,100
-5* 27,000 47,900 71,900 89,600 35,300 59,200 127,700 27,200 48,400 73,200 91,700 36,100 60,600 130,700
-4 36,600 65,200 98,700 123,000 48,400 81,300 175,200 36,800 66,000 100,500 126,000 49,600 83,300 179,400
-3 51,900 93,100 141,900 176,500 69,400 116,500 250,400 52,200 94,300 144,700 181,000 71,200 119,500 256,700
-5
-2 68,300 119,700 185,800 219,300 86,200 144,600 310,100 70,000 122,700 190,600 225,100 88,500 148,400 318,200
-1 79,400 139,400 216,800 257,000 101,000 169,300 362,200 81,500 143,100 222,600 264,000 103,800 173,900 371,900
0 89,300 157,200 244,900 291,600 114,600 191,900 409,600 91,800 161,600 251,700 299,900 117,800 197,300 421,000
Capacities are calculated in accordance with ASHRAE Standard 158.2, “Methods of testing Capacity of Refrigerant Pressure
Regulators”. Capacities are based on 60°F Liquid Temperature entering the expansion valve and 25°F superheated vapor Refrigerant Liquid Temperature Correction Factors for 60°F Liquid
entering the compressor. -10 -5 0 5 10 15 20 25 30 35 40
R-22 1.16 1.13 1.10 1.07 1.03 1.00 0.97 0.93 0.90 0.86 0.82
*Capacities are calculated at 1 psi ΔP when common suction and circuit evaporator temperatures are the same. For capaci-
ties at conditions other than those shown in the tables, use Sporlan Selection Program or contact Sporlan Headquarters. R-404A &
1.26 1.21 1.16 1.10 1.05 1.00 0.95 0.89 0.84 0.78 0.72
R-507
QUICK PICK SELECTION TABLES for SUPERMARKET MULTIPLE EVAPORATOR SYSTEMS – Valve Capacity Btuh
conditions other than those shown in the tables, use Sporlan Selection Program, or contact Sporlan Headquarters.
RACE Catalogue 90-20 UK - 06/2010 - Zalsman