Advanced Direct Digital Controller Manual
Advanced Direct Digital Controller Manual
NDA320D
Carefully
C f ll read
d thi
this manuall and
d all
ll off the
th warning
i message before
b f installing
i t lli
and operating
2
FEATURES change & innovation
Features
Black Box
▪ Black box can automatically store up to 200 events, and provide of the data
LCD A
Auto
t CContrast
t t
3
CONTENTS change & innovation
1 Safety Summary
Definitions and symbols
3 Operation
O
Operation
ti precautions
ti
Keypad features
Lamp features
Overview LCD main display (Enable the pressure switch control)
Overview LCD main display
(Select the pressure sensor control, Discharge pressure and temp. ON state)
Overview LCD main display
(Select the pressure sensor control, Discharge pressure and temp. , Spare 1 temp. ON state)
Overview LCD main display
(S l
(Select the
h pressure sensor control,
l Di
Discharge
h pressure and
d temp. ,Inlet
I l pressure ON state))
Overview LCD main display
(Select the pressure sensor control, Discharge pressure and temp. ,Inlet pressure, Spare 1 temp. ON state)
LCD main display : Display temperature
LCD Main display : Display digital output
LCD main display : Display digital input
LCD main display : Display run & stop states logo
LCD main display : Display loading states logo
LCD main display : Display main motor run states logo
LCD main
i di
display
l : Di
Display
l run, alarm
l & ttrip
i states
t t
LCD main display : Display local & remote
LCD main display : Display current time
System menu : Overview system menu
LCD Menu Display : Operation environment sub menu
Menu Selection : 1. Operation Settings(1/8)
Menu Selection : 2. Alarm History(2/8)
Menu Selection : 3. Temperature Information(3/8)
Menu Selection : 4. Equipment
q p Information(4/8)
( )
Menu Selection : 5. Time Settings(5/8)
Menu Selection : 6. Language Selection(6/8)
Menu Selection : 7. Communication Settings (7/8)
Menu Selection : 8. Maintenance Settings(8/8)
Network Solution
Warranty
4
1. SAFETY SUMMARY change & innovation
Logo Description
Indicates a potentially hazardous situation which,
!
if not avoided, can result in serious injury or death.
WARNING
Indicates a potentially hazardous situation which,
!
if not avoided, can result in minor to moderate
injury,
j y or serious damageg to the pproduct.
CAUTION
5
2. INSTALLATION AND WIRING change & innovation
Specifications
CAUTION
It
Item NDA320D
Supply voltage AC24V 50/60Hz
Power <20VA
consumption
LCD 240X128 Dot Graphic, LED BL
Weight(+-1g)
Storage -40°C ~ 80°C
temperature
Operating -20°C
20 C ~ 70
70°C
C
temperature
Operating 90% RH or less (no condensing)
humidity
Operating area indoors
Digital input 10 Channel Photo Isolation
6
2. INSTALLATION AND WIRING change & innovation
Installation precautions
!
WARNING
B sure nott to
Be t place
l any flammable
fl bl materials
t i l near th
the DDC
7
2. INSTALLATION AND WIRING change & innovation
Dimensions
8
2. INSTALLATION AND WIRING change & innovation
9
2. INSTALLATION AND WIRING change & innovation
WARNING
J9 Sensor In Description
J9-1 Pt100_W0 Spare 1 Temp. Common (White)
J9-2 Pt100_W0 Spare 1 Temp. Common (White)
J9-3 Pt100_R0 Spare 1 Temp. Pt100 (Red)
Step 1
J9-1 terminal is connected to white line of inlet sensor.
Step 2
J9-2 terminal is connected to white line of inlet sensor.
Step 3
J9-3 terminal is connected to red line of inlet sensor.
10
2. INSTALLATION AND WIRING change & innovation
Step 1
J10-1 terminal is connected to white line of discharge sensor
Step 2
J10-2 terminal is connected to white line of discharge sensor
Step 3
J10-3 terminal is connected to red line of discharge sensor
Step 4
J11-1 terminal is connected to white line of spare sensor
Step 5
J11-2 terminal is connected to white line of spare sensor
Step 6
J11 3 tterminal
J11-3 i l iis connected
t d tto red
d liline off spare sensor
11
2. INSTALLATION AND WIRING change & innovation
J7 Digital In Description
J7-1 LINE24V AC24V In
J7-2 DI0 Overload Fan Motor
J7-3 DI1 Overload Main Motor
J7-4 DI2 Reverse Phase Voltage
J7-5 DI3 Overload C.W Pump
J7-6 DI4 Emergency Stop S/W
Step 1
J7-1 terminal is connected to line 24V
Step 2
J7-2 terminal is connected to Overload Fan Motor Signal
Step 3
J7-3 terminal is connected to Overload Main Motor Signal
Step 4
J7-4 terminal is connected to Reverse Phase Voltage Signal
Step 5
J7-5 terminal is connected to Overload C.W Pump
Signal
Step 6
J7-6 terminal is connected to Emergency Stop S/W Signal
12
2. INSTALLATION AND WIRING change & innovation
J8 Digital In Description
J8-1 DI5 Lube Oil Press Low
J8-2 DI6 C.W Flow Low
J8-3 DI7 Spare
J8-4 DI8 Load Press Switch
J8-5 DI9 Remote Start/Stop
Step 1
J8-1 terminal is connected to Lube Oil Press Low Signal
g
Step 2
J8-2 terminal is connected to C.W Flow Low Signal
Step 3
J8-4 terminal is connected to Load Press Switch Signal
Step 4
J8-5 terminal is connected to Remote Start/Stop Signal
13
2. INSTALLATION AND WIRING change & innovation
Step 1
J4-2 terminal is connected to Load Sol Valve Contact
Step 2
J4-3 terminal is connected to Dryer Magnetic Contact
Step 3
J4-4 terminal is connected to Purge Sol Valve Contact
Step 4
J4-5
J4 5 terminal is connected to RUN Signal Out Contact
Step 5
J4-1 terminal is connected to AC220V Power Line
14
2. INSTALLATION AND WIRING change & innovation
J5-3
J5 3 DC6 Delta Magnetic
Step 1
J5-2 terminal is connected to Fan Motor Magnetic Contact
Step 2
J5-3 terminal is connected to Delta Magnetic Contact
Step 3
J5-4 terminal is connected to Star Magnetic Contact
Step 4
J5-5 terminal is connected to Main Magnetic Contact
Step 5
J5-1 terminal is connected to AC220V Power Line
15
2. INSTALLATION AND WIRING change & innovation
Step 1
J6-2 terminal is connected to Alarm Signal Out Signal
Step 2
J6 1 terminal is connected to AC220V Power Line
J6-1
16
2. INSTALLATION AND WIRING change & innovation
Step 1
J12-3 terminal is connected to Discharge
Pressure Sensor
Step 2
J12-4 terminal is connected to Inlet
Pressure Sensor
Step 3
J12-5 terminal is connected to line 24V
17
2. INSTALLATION AND WIRING change & innovation
Step 1
J13-1 terminal is connected to Common Signal
Step 2
J13-2 terminal is connected to Spare 2 Temp. or
Spare Press Transmit signal
Step 3
J13-3 terminal is connected to Common Signal
Step 4
J13-4 terminal is connected to Spare 1 Temp.
Or Inlet Press Transmit signal
Step 5
J13-5 terminal is connected to Common Signal
Step 6
J13-6 terminal is connected to Discharge Temp. or
Discharge Press Transmit signal
18
2. INSTALLATION AND WIRING change & innovation
J3 Communication Description
Step 1
J3-1 terminal is connected to TRX- Signal
Step 2
J3-2 terminal is connected to TRX+ Signal
19
2. INSTALLATION AND WIRING change & innovation
J1 Power In Description
J1-1 FG Frame Ground
J1-2 N Neutral
J1-3 LINE24V AC24V In
Step 1
J1-1 terminal is connected to Frame Ground
Step 2
J1-2 terminal is connected to AC24V Neutral
St 3
Step
J1-3 terminal is connected to AC24V Line
20
3. OPERATION change & innovation
Operation precautions
Do not press
Press the MENU key and modify Parameters in the suitable environment.
Page 17~41
21
3. OPERATION change & innovation
Keypad features
22
3. OPERATION change & innovation
Lamp features
2 1
1 Run State LED
OFF : Stop
O N : Running
Blinking : Starting, Stopping
23
3. OPERATION change & innovation
2.2 3.2 1
6 7 8 9 10 11
24
3. OPERATION change & innovation
2.1 2.2
6 7 8 9 10 11
21
2.1 Display discharge pressure 6 Display run & stop state
25
3. OPERATION change & innovation
6 7 8 9 10 11
2.1 Display
p y discharge
g ppressure 6 Display run & stop state
26
3. OPERATION change & innovation
6 7 8 9 10 11
2.1 Display
p y discharge
g ppressure 6 Display run & stop state
27
3. OPERATION change & innovation
6 7 8 9 10 11
2.1 Display
p y discharge
g ppressure 6 Display run & stop state
28
3. OPERATION change & innovation
29
3. OPERATION change & innovation
O N : Stop O N : run
Blinking : Stopping Blinking : Running
7 Di l lloading
Display di states
t t llogo
30
3. OPERATION change & innovation
Display run Display run Display alarm Display alarm Display trip Display trip
state state state state state state
Run Wait Motor Stop #1 Comp. Check #1 Spare
Delay Temperature Time Temperature Pressure
Al
Alarm Ab
Abnormal
l Ab
Abnormal l
Pressure Restart Delay Discharge Overhaul Time #1 Spare
Switch Temperature Temperature Pressure Trip
Alarm Trip
Running Delay Auto Start/Stop #2 Discharge Over Current
Temperature Temperature Fan Motor
Alarm Abnormal
Star Running Running Ban Oil Pressure Discharge Over Current
Pressure Alarm Temperature Motor
Trip
Delta Running Discharge #2 Reverse Phase
Pressure Alarm Temperature Fail
Abnormal
Sol Running Spare #2 Oil Press Drop
D l
Delay P
Pressure Al
Alarm T
Temperature
t
Trip
Loading Running Ban Internal Cooling Water
Pressure Pressure Press Drop
Abnormal
Unloading Separator Filter Internal Cooling Water
Exchange Pressure Trip Pump
31
3. OPERATION change & innovation
32
3. OPERATION change & innovation
Menu Selection
1. Operation Settings
2. Alarm History
3. Temp. & Pressure Information
4. Equipment Information
5. Time Settings Temp. & Pressure Information(3/8)
6. Language Selection 1. Current Discharge
g Temp. p : 30.2 °C
7. Communication Settings 2. Discharge Temp. Revision : 0.0 °C
8. Maintenance Settings 3. Current Spare 1 Temp. : 18.2 °C
4. Current Spare 1 Revision : 0.0 °C
5. Current Spare 2 Temp. : 18.2 °C
6. Current Spare 2 Revision : 0.0 °C
Operation Settings (1/8) 000 Alarm History (2/8) 7. Current Discharge Pressure : 1.2 bar
1. Select loading method 8. Discharge Pressure Revision : 0.0 bar
:Pressure Sensor 9. Current Internal Pressure : 1.3 bar
2. Running Process Setting 10. Internal Pressure Revision : 0.0 bar
3 Running Temp.
3. Temp Setting 11 Current Spare Pressure : 1.3
11. 1 3 bar
4. Running Pressure Setting 12. Spare Pressure Revision : 0.0 bar
5. Pressure Sensor Range 13. Discharge Transfer Setting : Pressure
Setting 14. Current Discharge Transfer : mA
6. Running Mode Select : Local 15. Discharge Transfer Revision : bit
7. Abnormal Alarm Setting 16. Internal Transfer Setting : Pressure
8. Sensor Setting 17. Current Internal Transfer : mA
18. Internal Transfer Revision : bit
33
3. OPERATION change & innovation
Running Process Setting Running Temp. Setting (3/8) Running Pressure Setting (4/8)
(2/8) 1. Discharge Temperature Alarm : 100.0 °C 1. Loading Pressure : 6.0 bar
2. Discharge Temperature Trip : 110.0 °C 2. Unloading Pressure : 7.0 bar
1. Auto stop time : OFF
3. Spare 1 Temperature Alarm : 100.0 °C 3. Running Ban Pressure : 0.5 bar
Y/D transfer time : 5 Sec. 4. Spare 1 Temperature Trip : 110.0 °C 4. Alarm Discharge Pressure : 7.5 bar
3. Sol valve run delay : 60 Sec. 5. Spare 2 Temperature Alarm : 55.0 °C 5. Trip Discharge Pressure : 7.8 bar
4. Motor stop delay : 60 Sec 6. Spare 2 Temperature Trip : 65.0 °C 6. Alarm Internal Pressure : 7.8 bar
7. Fan Run Select : Discharge Temp. 7. Trip Internal Pressure : 8.0 bar
8. Fan Run Temperature : 85.0 °C 8. Alarm Spare Pressure : 7.5 bar
9. Fan Stop Temperature : 75.0 °C 9. Trip Spare Pressure : 8.0 bar
Pressure Sensor Range Abnormal Alarm Setting (7/8) Sensor Setting (8/8)
Setting(5/8) 1. Oil Pressure Drop : OFF 1. Discharge Temp. Sensor : ON
1. Discharge Pressure Lower : 0.0 bar 2. C.W Pressure Drop : OFF 2. Internal Pressure Sensor : ON
2. Discharge Pressure Upper : 16.0 bar 3. C.W Pump Overload : OFF 3. Spare Pressure Sensor : OFF
3. Internal Pressure Lower : 0.0 bar 4. Main Motor Overload : ON 4. Discharge Temp. Sensor : ON
4. Internal Pressure Upper :16.0 bar 5. Serve Motor Overload : ON 5. Spare 1 Temp. Sensor : OFF
5. Spare Pressure Lower : 0.0 bar 6. Reverse Phase Fail : ON 6. Spare 2 Temp. Sensor : OFF
6 Spare Pressure Upper : 16
6. 16.00 bar 7. Emergency
g y Stop
p Trip
p : ON
7. Pressure Unit Setting : kgf/cm2 8. Abnormal History Initial : NO
9. Internal Pressure Alarm Signal : NO
34
3. OPERATION change & innovation
S
Save C
Cancel
l
Description or
It is possible to select a pressure sensor or pressure switch for loading & unloading
decision.
If it is select a pressure sensor, It is loading & unloading that gets input for discharge
pressure sensor.
If it is select a pressure switch, It is loading & unloading according to short-circuit open &
close of p pressure switch input.
p
35
3. OPERATION change & innovation
Save Cancel
Description or or
36
3. OPERATION change & innovation
Save Cancel
Description or or
37
3. OPERATION change & innovation
Menu Selection : 1. Operation Settings(1/8)
4. Running Pressure Settings(4/8) X3
4 Alarm Discharge Pressure bar 0.1 0.0 ~ Trip Discharge Pressure 7.5
8 Alarm Spare Pressure bar 0.1 0.0 ~ Trip Spare Pressure 7.5
Save Cancel
Description or or
1. Loading Pressure
While loading method selection set pressure sensor, it is start loading if discharge pressure
sensor value decrease below loading.
2. Unloading Pressure
While loading method selection set pressure sensor, it is start loading if discharge pressure
sensor value increase beyond unloading.
3 R
3. Runningi B Ban PPressure
If internal pressure increase beyond running ban pressure, it is peal and mark running
ban pressure alarm.
4. Alarm Discharge Pressure
If discharge pressure increase beyond alarm discharge pressure, it is peal and mark discharge
pressure alarm as this time operation continue.
5. Trip Discharge Pressure
If discharge pressure increase beyond trip discharge pressure, it is emergency stop and mark
discharge pressure alarm.
6. Alarm Internal Pressure
If internal pressure increase beyond internal setting pressure, it is peal and mark internal
pressure alarm as this time operation continues.
7. Trip Internal Pressure
If internal pressure increase beyond trip discharge pressure, it is emergency stop and mark
internal pressure trip-alarm.
p
8. Alarm Spare Pressure
If spare pressure increase beyond alarm spare pressure, it is peal and mark spare
pressure alarm as this time operation continues.
9. Trip Spare Pressure
If spare pressure increase beyond trip spare pressure, it is emergency stop and mark spare
pressure alarm.
38
3. OPERATION change & innovation
X4
5. Pressure Sensor Setting (5/8)
Item Unit Resolution Range Default
1 Discharge Pressure Lower bar 0.1 -10.0 ~ 70.0 0.0
2 Discharge Pressure Upper bar 0.1 -10.0 ~ 70.0 16.0
3 Internal Pressure Lower bar 01
0.1 -10
10.0
0 ~ 70.0
70 0 00
0.0
4 Internal Pressure Upper bar 0.1 -10.0 ~ 70.0 16.0
5 Spare Pressure Lower bar 0.1 -10.0 ~ 70.0 0.0
6 Spare Pressure Upper bar 0.1 -10.0 ~ 70.0 16.0
7 Pressure Unit Setting kg/cm2, bar, MPa kg/cm2
Save Cancel
Description or or
39
3. OPERATION change & innovation
Save Cancel
Description or
or Save Cancel
Description or
1. Oil Pressure Drop Alarm, 2. C.W Pressure Drop Alarm, 3. C.W Pump Overload Alarm,
4. Main Motor Overload Alarm, . Serve Motor Overload Alarm, 6. Reverse Phase Fail Alarm,
7. Emergency Stop Trip Alarm can ON or OFF mode.
8. Alarm History Initial
Alarm history initial can delete all storage alarm.
Alarm delete possible to only during operation standby, it is impossible to delete during operation.
9. If it is select internal pressure alarm the plus, it is operate high alarm and high high trip and
if it is select internal pressure alarm the minus
minus, it is operate low alarm and low low trip
trip.
Save Cancel
Description or or
41
3. OPERATION change & innovation
Description or
42
3. OPERATION change & innovation
X2
Menu Selection : 3. Temperature Information(3/8)
It
Item U it
Unit R
Resolution
l ti R
Range D f lt
Default
1 Current Discharge Temp. °C 0.2 -20 ~ 190 View Only
2 Discharge Temp. Revision °C 0.1 -20 ~ 190 Don’t care
3 Current Spare 1 Temp. °C 0.2 -20 ~ 190 View Only
4 Current Spare 1 Revision °C 0.1 -20 ~ 190 Don’t care
5 Current Spare 2 Temp. °C 0.2 -20 ~ 190 View Onlyy
6 Current Spare 2 Revision °C 0.1 -20 ~ 190 Don’t care
7 Current Discharge Pressure bar 0.1 Discharge Pressure Min ~ Max View Only
8 Discharge Pressure Revision bar 0.1 -20.0 ~ 20.0 Don’t care
9 Current Internal Pressure bar 0.1 Oil Pressure Min ~ Max View Only
10 Internal Pressure Revision bar 0.1 -20.0 ~ 20.0 Don’t care
11 Current Spare Pressure bar 0.1 Discharge Pressure Min ~ Max View Only
12 Spare Pressure Revision bar 0.1 -20.0 ~ 20.0 Don’t care
13 Discharge Transfer Setting Pressure
14 Current Discharge Transfer mA 0.1 4mA ~ 20mA View Only
15 Discharge Transfer Revision bit 1 -30.0 ~ 30.0 Don’t care
16 Internal Transfer Setting Pressure
17 Current Internal Transfer mA 0.1 4mA ~ 20mA View Only
18 Internal Transfer Revision bit 1 -30.0 ~ 30.0 Don’t care
Save Cancel
Description or or
1~6 It is possible to see a Current Discharge Temp. and Current Spare 1 Temp. and Current
Spare 2 Temp.
7~12 It is possible to see a Current Discharge Pressure and Current Internal Pressure and
Current Spare Pressure
13. It is possible to set Discharge Transfer Pressure or Temp.
14. In case you have selected by pressure, if discharge pressure range has the 0.0bar ~ 50.0bar,
transfer ampere is 4mA while the present discharge pressure is 0.0 bar and transfer ampere is
20mA while the present discharge pressure is 50.0 bar.
16. It is p
possible to set Internal Transfer Pressure or Temp.
p
17. In case you have selected by internal transfer mode, if internal pressure range has the 0.0bar
~ 16.0bar, transfer ampere is 4mA while the present internal pressure is 0.0 bar and transfer
ampere is 20mA while the present discharge pressure is 16.0 bar.
43
3. OPERATION change & innovation
X3
Menu Selection : 4. Equipment Information(4/8)
Save Cancel
Description or or
X4
Menu Selection : 5. Time Settings(5/8)
Save Cancel
D
Description
i ti or
X5
Menu Selection : 6. Language Selection(6/8)
Save Cancel
Description or
X6
Menu Selection : 7. Communication Settings (7/8)
Save Cancel
Description or or
44
3. OPERATION change & innovation
Save Cancel
Description or or
Save Cancel
Description or or
45
3. OPERATION change & innovation
Save Cancel
Description or or
Save Cancel
Description or or
46
3. OPERATION change & innovation
Save Cancel
Description or or
6. Overhaul Setting(6/6) X7 X5
Save Cancel
Description or or
47
3. OPERATION change & innovation
Network Solution
RS-485
NDA320D
RS-485
48
WARRANTY change & innovation
Warranty
If the defective part has been identified under normal and proper use
within theguarantee term, contact your local authorized
DongHwa
g Pneutec distributor or DongHwa
g Pneutec Service center.