Controls: Thin-Profile Slide Dimmer
Controls: Thin-Profile Slide Dimmer
Controls www.lutron.com/novat
DIMMERS
Select Incandescent
light level Slide-to-Off Dimmers 1
with slider;
slide down SMALL CONTROL
to off Single pole 600W NT-600-AU-
Single pole 1000W NT-1000-AU-
Single pole 1800W NT-1800-AU-
Slide-to-off Dimmer
Magnetic Low Voltage
PRODUCT FAMILY FEATURES Slide-to-Off Dimmers 1
SMALL CONTROL
• Aesthetically pleasing linear-slide dimmer Single pole 600VA (450W) NTLV-600-AU-
• Linear-slide position directly corresponds to the light level perceived by
Single pole 1000VA (800W) NTLV-1000-AU-
the eye
• Heavy duty components for surge protection and long product life LARGE CONTROL
• Multigang wallplates, personalized engraving, company logos, and Single pole 1500VA (1200W) NTLV-1500-AU-
custom color matching complete a coordinated look
• Precise color matching across all controls
Fluorescent
Slide-to-Off Dimmer 2
SMALL CONTROL
Single pole 8A NTF-10-AU-
DIMENSIONS Note: Use with Lutron Hi-lume or Eco-10 (ECO-Series) line
voltage control Electronic Dimming Ballasts only. Contact Lutron
Front Front for 60Hz units.
Small Large
Control Control Profile
7.6mm
(.30")
116mm 116mm LINEAR-SLIDE SWITCHES
(4.56") (4.56") 70mm
(2.75") General Purpose Switching
of All Sources and Motor Loads
70mm 116mm Linear-Slide Switch
(2.75") (4.56") 33mm*
(1.31" ) SMALL CONTROL
*some models up to 1 or 2 way 16A NT-2WS-AU-
43.4mm (1.71")
CONTROLS TA SWITCHBOXES
Slide-to-Off Dimmers Gangable Switch Box
1-gang 241-218-
SPECIFICATION SERIES
STANDARD FEATURES JOB NAME AREA CONTROLLED
WH White
BE Beige 220-240 VAC
50/60Hz Green/Yellow**
IV Ivory Lighting
Blue Load
GR Gray
BR Brown
BL Black Neutral
Ground
TP Taupe *or Screw Terminal
**or Green Screw Terminal Wire Connectors
SPECIAL ORDER MULTIGANG
AND METAL WALLPLATES
Multigang and metal wallplates are available. When ordering product for use with
metal wallplates, the product and wallplate must be ordered separately.
See below for complete list of metal finishes.
h. Dimmers shall meet the applicable requirements of UL20 B. Wallplates Lutron Nova Ta Style
and UL 1472, referring to the inclusion of a visible, 1. Wallplates shall be manufactured from durable polycarbonate
accessible air-gap off switch and the limited short circuit plastic with matte finish, and shall attach to the basic
test. components without using exposed hardware or screws.
i. Slider shall be captured behind wallplate. 2. Multigang wallplates shall provide a continuous, seamless cover
j. Controls shall be able to have their visible plastic parts for control and/or accessory combinations with no exposed
replaced, for color changes in the field, without removing the hardware or screws. Custom wallplate configurations shall be
body of the control from the wall and with requiring special available.
tools. 3. Multigang wallplates shall include snap in auto-align adapter
k. Dimmers shall meet IEEE Std. C62.41-1980, tested to plate for proper device alignment and wallplate attachment.
withstand voltage surges of up to 6000V and current surges 4. Control, accessory and wallplate profiles shall not exceed
of up to 200A. 6mm (.30”) from wall surface to faceplate front surface.
l. Within rated capacity, dimmers shall be available for direct 5. To ensure a precise color match between all plastic parts, color
control of incandescent, magnetic low voltage, and variation of any matte finish control or wallplate shall not exceed
fluorescent. delta E of 1, CIE L*a*b* color units.
m. Dimmer shall include voltage compensation to compensate 6. Visible parts of any control or any wallplate shall exhibit
light output for variation in the AC line-voltage. Dimmers in ultraviolet stability when tested with multiple actinic light sources
which the light output is not held constant with varying AC as defined in ASTM D4674-89.
line-voltage shall not be acceptable. 2.03 SOURCE QUALITY CONTROL
n. Contractors shall install all backboxes with a minimum A. All dimming controls shall be 100% function tested at the time of
wallbox depth of 63mm (2.5 inches). manufacture. Statistical sampling plan shall not be acceptable.
2. Incandescent Dimmers
a. Provide incandescent dimmers for direct control of up to
1800 Watts. PART 3 – EXECUTION
3. Magnetic Low Voltage (MLV) Transformer Dimmers
a. Dimmers shall contain circuitry specifically designed to 3.01 INSTALLATION
control and provide a symmetrical AC waveform to the A. Contractor shall furnish all devices (dimmers, switches and wallplate
input of magnetic low voltage transformers per UL 1472 kits), labor and other services necessary for the proper installation of
section 5.11. the devices as indicated on the drawings and specified herein.
b. Provide MLV dimmers for direct control of up to 1500VA of B. Contractor shall be responsible for derating dimmer capacity if side
magnetic low voltage load. sections are removed.
c. Dimmers shall not cause a magnetic low voltage C. Contractor shall run separate neutral wires in 220/380 VAC
transformer to operate above the transformer’s rated installations.
operating current or temperature. D. Devices shall be installed utilizing manufacturer's recommended
4. Fluorescent Dimming Ballast Dimmers application, wiring and installation instructions.
a. Dimmers shall be designed to operate the following ballasts. E. Contractor to provide seamless wallplate covers per specification
Dimmers and ballasts shall be produced by the same 2.02 for all devices ganged in a common box. Contractor shall
manufacturer to ensure proper ballast/control compatibility: provide barriers within the box where required by code.
1) Hi-lume® Architectural Dimming Ballasts (1% 3-wire)
3.02 FIELD QUALITY CONTROL
2) Hi-lume® CompactTM Lamp Dimming Ballasts
A. Twenty-four hours a day, seven days a week, global customer
(5% 3-wire)
service and technical hotline available.
3) Eco-10TM Lighting Management Dimming Ballasts
B. Supplemental information shall be provided by manufacturers
(10% 3-wire)
Internet site.
5. Switches:
a. Switches shall provide on/off control of any 240/277 VAC
load up to 16A.