A Novel Power Quality Improvement Technique Using Multi-Connected Distributed Power Flow Controller (MC-DPFC)
A Novel Power Quality Improvement Technique Using Multi-Connected Distributed Power Flow Controller (MC-DPFC)
ABSTRACT: This paper presents a new component within the flexible ac-transmission system (FACTS) family, called
multi connected distributed power-flow controller (MC-DPFC) capable of simultaneous compensation for voltage and
current in multibus/multifeeder systems. In this configuration, one shunt voltage-source converter (shunt VSC) and two
or more series VSCs exist. The system can be applied to adjacent feeders to compensate for supply-voltage and load
current imperfections on the main feeder and full compensation of supply voltage Imperfections on the other feeders.
The DPFC can be considered as a UPFC with an eliminated common dc link. The active power exchange between the
shunt and series converters, which is through the common dc link in the UPFC, is now through the transmission lines at
the third-harmonic frequency. The DPFC employs the distributed FACTS (D-FACTS) concept, which is to use
multiple small-size single-phase converters instead of the one large-size three-phase series converter in the UPFC. In
this proposed system we connected DPFC for multiple bus bars instead of using two custom power devices (CUPS).
The large number of series converters provides redundancy, thereby increasing the system reliability. As the D-FACTS
converters are single-phase and floating with respect to the ground, there is no high-voltage isolation required between
the phases. Accordingly, the cost of the DPFC system is lower than the UPFC. The DPFC has the same control
capability as the UPFC, which comprises the adjustment of the line impedance, the transmission angle, and the bus
voltage. The principle and analysis of the DPFC are presented.
Keywords: Power Quality, Facts Technology, Distributed Power Flow Controller (DPFC), Total Harmonic Distortion.
I.INTRODUCTION
With increasing applications of nonlinear and electronically switched devices in distribution systems and industries, power-quality
(PQ) problems, such as harmonics, flicker, and imbalance have become serious concerns. In addition, lightning strikes on
transmission lines, switching of capacitor banks, and various network faults can also cause PQ problems, such as transients, voltage
sag/swell, and interruption. On the other hand, an increase of sensitive loads involving digital electronics and complex process
controllers requires a pure sinusoidal supply voltage for proper load operation. In order to meet PQ standard limits, it may be
necessary to include some sort of compensation. Modern solutions can be found in the form of active rectification or active
filtering. A shunt active power filter is suitable for the suppression of negative load influence on the supply network, but if there are
supply voltage imperfections, a series active power filter may be needed to provide full compensation. And also we have
compensation techniques such as tapping transformers, shunt condensers etc.
In recent years, solutions based on flexible ac transmission systems (FACTS) have appeared. The application of FACTS concepts
in distribution systems has resulted in a new generation of compensating devices. Currently, the distributed power-flow controller
(DPFC) shown in Fig. is the most powerful FACTS device, which can simultaneously control all the parameters of the system: sag,
swell, flickers and bus bar voltages. It is similar to Unified Power Flow Controller (UPFC). The UPFC is the combination of a static
synchronous compensator (STATCOM) and a static synchronous series compensator (SSSC), which are coupled via a common dc
link, to allow bidirectional flow of active power between the series output terminals of the SSSC and the shunt output terminals of
the STATCOM. The unified power quality conditioner (UPQC) compensator seems to be a particularly promising power
conditioner device. This apparatus is constituted of a series and a shunt unit, with a common dc section through which power can be
exchanged. Its function is to improve the quality levels of the current absorbed at the mains and the load supply voltage. The
installation investments are also quite high relative to the power quality level obtained. A solution that has similar performances and
advantages, but also makes cost reduction possible, is the proposed MC-DPFC.
Advance of UPFC is DPFC. The DPFC is able to control all system parameters. The DPFC eliminates the common dc link between
the shunt and series converters. The active power exchange between the shunt and the series converter is through the transmission
line at the third-harmonic frequency.
The DPFC consists of one shunt and several series-connected converters. The shunt converter is similar as a STATCOM,
while the series converter employs the D-FACTS concept, which is to use multiple single-phase converters instead of one
large rated converter. Each converter within the DPFC is independent and has its own dc capacitor to provide the required dc
voltage. The configuration of the DPFC is shown in Fig 2 , besides the key components, namely the shunt and series
converters, the DPFC also requires a high-pass filter that is shunt connected at the other side of the transmission line, and two
Y–Δ transformers at each side of the line. The unique control capability of the UPFC is given by the back-to-back connection
between the shunt and series converters, which allows the active power to exchange freely. To ensure that the DPFC have the
same control capability as the UPFC, a method that allows the exchange of active power between converters with eliminated
dc link is the prerequisite. Within the DPFC, there is a common connection between the ac terminals of the shunt and the
series converters, which is the transmission line. Therefore, it is possible to exchange the active power through the ac
terminals of the converters. The method is based on the power theory of non sinusoidal components.
By applying this method to the DPFC, the shunt converter can absorb active power from the grid at the fundamental
frequency and inject the current back into the grid at a harmonic frequency. This harmonic current will flow through the
transmission line. According to the amount of required active power at the fundamental frequency, the DPFC series
converters generate a voltage at the harmonic frequency, thereby absorbing the active power from harmonic components.
Assuming a lossless converter, the active power generated at fundamental frequency is equal to the power absorbed from the
harmonic frequency. For a better understanding, Fig. 3 indicates how the active power exchanges between the shunt and the
series converters in the DPFC system. The high-pass filter within the DPFC blocks the fundament frequency components
and allows the harmonic components to pass, thereby providing a return path for the harmonic components. The shunt and
series converters, the high-pass filter, and the ground form the closed loop for the harmonic current. Due to the unique
characters of third-harmonic frequency components, the third harmonic is selected to exchange the active power in the DPFC.
In a three-phase system, the third harmonic in each phase is identical, which is referred to as “zero-sequence.” The zero-
sequence harmonic can be naturally blocked by Y–Δ transformers, which are widely used in power system to change voltage
level. Therefore, there is no extra filter required to prevent the harmonic leakage to the rest of the network. In addition, by
using the third harmonic, the costly high-pass filter, as shown in Fig. 3, can be replaced by a cable that is connected between
the neutral point of the Y–Δ transformer on the right side in Fig. 3 and the ground. Because the Δ winding appears open
circuit to the third-harmonic current, all harmonic current will flow through the Y-winding and concentrate to the grounding
cable, as shown in Fig. 4. Therefore, the large-size high-pass filter is eliminated.
Fig 4 : Utilize Grounded Y–∆ transformer to provide the path for the zero-sequence third harmonic
Fig.5 Route the harmonic current by using the grounding status of the Y–∆ transformer
Theoretically, the third-, sixth-, and ninth-harmonic frequencies are all zero-sequence, and all can be used to exchange active
power in the DPFC. As it is well known, the capacity of a transmission line to deliver power depends on its impedance. Since
the transmission-line impedance is inductive and proportional to the frequency, high-transmission frequencies will cause high
impedance. Consequently, the zero-sequence harmonic with the lowest frequency—third harmonic is selected.
Here we used Multi Connected Distributed Power Flow Controller (MC-DPFC) which is used for more than one bus bars
simultaneously. The schematic diagram of MC-DPFC is as shown in Fig 6.
The STATCOM smoothly and continuously controls voltage from V1 to V2. However, if the system voltage exceeds a low-
voltage (V1) or high-voltage limit (V2), the STATCOM acts as a constant current source by controlling the converter voltage
(Vi) appropriately. DVR is series connected FACT device. The main function of a DVR is the protection of sensitive loads
from voltage sags/swells coming from the network. The DVR is located on approach of sensitive loads. If a fault occurs on
other lines, DVR inserts series voltage VDVR and compensates load voltage to pre fault value. The momentary amplitudes of
the three injected phase voltages are controlled such as to eliminate any detrimental effects of a bus fault to the load voltage
VL. This means that any differential voltages caused by transient disturbances in the ac feeder will be compensated by an
equivalent voltage generated by the converter and injected on the medium voltage level through the booster transformer.
The DVR works independently of the type of fault or any event that happens in the system, provided that the whole system
remains connected to the supply grid, i.e. the line breaker does not trip. For most practical cases, a more economical design
can be achieved by only compensating the positive and negative sequence components of the voltage disturbance seen at the
input of the DVR. This option is Reasonable because for a typical distribution bus configuration, the zero sequence part of a
disturbance will not pass through the step down transformer because of infinite impedance for this component. The DVR has
two modes of operation which are: standby mode and boost mode. In standby mode (VDVR=0), the booster transformer’s low
voltage winding is shorted through the converter. No switching of semiconductors occurs in this mode of operation, because
the individual converter legs are triggered such as to establish a short-circuit path for the transformer connection. Therefore,
only the comparatively low conduction losses of the semiconductors in this current loop contribute to the losses. The DVR
will be most of the time in this mode. In boost mode (VDVR>0), the DVR is injecting a compensation voltage through the
booster transformer due to a detection of a supply voltage disturbance.
IV.DPFC CONTROL
To control the multiple converters, DPFC consists of three types of controllers; they are central controller, shunt control, and
series control, as shown in Fig 11
A. Central Control
The central control generates the reference signals for both the shunt and series converters of the DPFC. It is focused on the
DPFC tasks at the power-system level, such as power-flow control, low-frequency power oscillation damping, and balancing
of asymmetrical components. According to the system requirement, the central control gives corresponding voltage-reference
signals for the series converters and reactive current signal for the shunt converter. All the reference signals generated by the
central control are at the fundamental frequency.
B. Shunt Control
C. Series Control
Each series converter has its own series control. The controllers used to maintain the capacitor dc voltage of its own converter
by using the third-harmonic frequency components and to generate series voltage at the fundamental frequency that is
prescribed by the central control. The third-harmonic frequency control is the major control loop with the DPFC series
converter control. The principle of the vector control is used here for the dc-voltage control. The third-harmonic current
through the line is selected as the rotation reference frame for the single-phase park transformation, because it is easy to be
captured by the phase-locked loop (PLL) in the series converter. As the line current contains two frequency components, a
third high-pass filter is needed to reduce the fundamental current. The d-component of the third harmonic voltage is the
parameter that is used to control the dc voltage, and its reference signal is generated by the dc-voltage control loop. To
minimize the reactive power that is caused by the third harmonic, the series converter is controlled as a resistance at the third-
harmonic frequency. The q-component of the third-harmonic voltage is kept zero during the operation. As the series converter
is single phase, there will be voltage ripple at the dc side of each converter. The frequency of the ripple depends on the
frequency of the current that flows through the converter. As the current contains the fundamental and third harmonic
frequency component, the dc-capacitor voltage will contain 100-, 200-, and 300-Hz frequency component there are two
possible ways to reduce this ripple. One is to increase the turn ratio of the single-phase transformer of the series converter to
reduce the magnitude of the current that flows into the converter. The other way is to use the dc capacitor with a larger
capacitance.
A simulation setup has been built to verify the principle and control of the DPFC. One shunt converter and six single phase
series converters are built and tested in a scaled network, as shown in Fig13. Two isolated buses with phase difference are
connected by the line. Within the experimental setup, the shunt converter is a single-phase inverter that is connected between
the neutral point of the Y–Δ transformer and the ground. The inverter is powered by a constant dc-voltage source.
V. CONCLUSION
This paper has presented a new concept called MC-DPFC. The MC-DPFC emerges from the UPFC and inherits the control
capability of the UPFC, which is the simultaneous adjustment of the line impedance, the transmission angle, and the bus-
voltage magnitude. The common dc link between the shunt and series converters, which is used for exchanging active power
in the UPFC, is eliminated. This power is now transmitted through the transmission line at the third-harmonic frequency. The
series converter of the DPFC employs the D-FACTS concept, which uses multiple small single-phase converters instead of
one large-size converter. The reliability of the DPFC is greatly increased because of the redundancy of the series converters.
The total cost of the DPFC is also much lower than the UPFC, because no high-voltage isolation is required at the series-
converter part and the rating of the components of is low. The DPFC concept has been verified by an experimental setup. It is
proved that the shunt and series converters in the DPFC can exchange active power at the third-harmonic frequency, and the
series converters are able to inject controllable active and reactive power at the fundamental frequency.
REFERENCES
[1] Y.-H. Song and A. Johns, Flexible ac Transmission Systems (FACTS) (IEEE Power and Energy Series), vol. 30. London, U.K.: Institution of
Electrical Engineers, 1999.
[2] N. G. Hingorani and L. Gyugyi, Understanding FACTS : Concepts and Technology of Flexible AC Transmission Systems. New York: IEEE
Press, 2000.
[3] G.Satyanarayana., K.N.V Prasad, G.Ranjith Kumar, K. Lakshmi Ganesh, "Improvement of power quality by using hybrid fuzzy controlled based
IPQC at various load conditions," Energy Efficient Technologies for Sustainability (ICEETS), 2013 International Conference on , vol., no.,
pp.1243,1250, 10-12 April 2013.
[4] A.-A. Edris, “Proposed terms and definitions for flexible ac transmission system (facts),” IEEE Trans. Power Del., vol. 12, no. 4, pp. 1848–1853,
Oct. 1997.
[5] K.N.V. Prasad, G.Ranjith Kumar, Y.S. Anil Kumar, G. Satyanarayana, "Realization of cascaded H-bridge 5-Level multilevel inverter as Dynamic
Voltage Restorer," Computer Communication and Informatics (ICCCI), 2013 International Conference on , vol., no., pp.1,6, 4-6 Jan. 2013.
[6] M. D. Deepak, E. B. William, S. S. Robert, K. Bill, W. G. Randal, T. B. Dale, R. I. Michael, and S. G. Ian, “A distributed static series
compensator system for realizing active power flow control on existing power lines,” IEEE Trans. Power Del., vol. 22, no. 1, pp. 642–649, Jan.2007.
[7] K.N.V Prasad, G.Ranjith Kumar, T. Vamsee Kiran, G.Satyanarayana., "Comparison of different topologies of cascaded H-Bridge multilevel
inverter," Computer Communication and Informatics (ICCCI), 2013 International Conference on , vol., no., pp.1,6, 4-6 Jan. 2013
[8] Y. Zhihui, S.W. H. de Haan, and B. Ferreira, “Utilizing distributed power flow controller (dpfc) for power oscillation damping,” in Proc. IEEE
Power Energy Soc. Gen. Meet. (PES), 2009, pp. 1–5.
[9] G. Satya Narayana, Ch. Narendra Kumar, Ch. Rambabu “ A Comparative Analysis of PI Controller and Fuzzy Logic Controller for Hybrid
Active Power Filter Using Dual Instantaneous Power Theory” International Journal of Engineering Research & Development, Vol-4, Issue-6, p.p. 29-
39, Oct, 2012.
[10] Y. Sozer and D. A. Torrey, “Modeling and control of utility interactive inverters,” IEEE Trans. Power Electron., vol. 24, no. 11, pp. 2475–2483,
Nov. 2009.
[11] K.N.V Prasad, G.Ranjith Kumar, T. Vamsee Kiran, G.Satyanarayana., "Comparison of different topologies of cascaded H-Bridge multilevel
inverter," Computer Communication and Informatics (ICCCI), 2013 International Conference on , vol., no., pp.1,6, 4-6 Jan. 2013.