System Stability
System Stability
KARENG/2013/51589
Low Frequency Oscilla ons in Power Systems and their Mi ga on …….. Editor:
.......................................................................................................... K.R. Padiyar 13
M.M. Babu Narayanan
Enhancing Power System Stability and Control Using Special Protec on Systems
………………………………………………….……..... Nitesh Kumar. D and Faraz Zafar Khan 16 Members:
Stability Studies for Industrial Power Systems ..................................................... Faraz Zafar Khan
....................................................... Maheedhar Patnala and T. Guru Charan Das 20 Poornima T.R.
PRDC Provides LED Ligh ng Solu on for the Holy City of Puri ............................. 26 Venkatesh H.R.
Maheedhar Patnala
PRDC Annual Day - April 2015 ............................................................................... 27
Rajesh Kanchan
Our Exper se in Training ……………………………………………………………….………………... 28 Thimmappa N.
bandwidth of these control parameters connected on the grid-side would get secure, reliable and stable power system.
to give best system performance. affected. For grid connected CPPs,
transient stability studies are performed
to arrive at the proper se ngs for the I thank all those who have
Another typical applica on of the islanding relays and also devise scheme contributed to this issue of PRDC
transient stability study is the analysis for under frequency load shedding or Newsle er though their technical
of the behaviour of a cap ve power generator tripping as the case may be, ar cles. I wish all the readers, their family
plant (CPP) with its process load in case of excess load or surplus and friends a happy fes ve season
connected through one or two lines to genera on. ahead.
the U lity grid. Most of the CPPs are
synchronized with the grid mainly to
support their manufacturing processes Finally, the importance of stability studies Dr. R. Nagaraja
consis ng of me-varying or cyclic loads is emphasized in the context of Managing Director
wherein grid support is essen al viz., protec ve relay se ng based on cri cal PRDC, Bangalore
arc furnace loads, rolling mills; clearing me for ensuring system
processes where no interrup on of stability. Special protec ons schemes are
power is envisaged and cases wherein best designed with the help of stability
grid support provides enough system studies. Also, as a measure of preven ng
strength for star ng of large motors. In undesirable trippings during power
case of certain grid disturbances or swings in transmission lines, it is the
even failure of grid, the process of general prac ce to block the distance
disconnec ng the CPP from the U lity relay tripping when the power swing
grid is called islanding of the CPP. Grid enters zone 3 or zone 2 and allow the
islanding scheme consists of a single or tripping only when the power swing
a set of protec ve relays connected at enters zone 1. However, the best
the point of islanding (also called point of prac ce is to block all the zones for
common coupling) which will sense the power swings, as a distance relay should
disturbance in the grid and give a trip operate only during the fault condi on.
command to the islanding breaker A separate out-of-step protec on
whenever the set parameters exceeds scheme has to be designed to safeguard
the limit. By opening the islanding the system during unstable power
breaker, the CPP and CPP side loads are swings. Stability studies are performed
isolated from the grid for secure to determine the out-of-step relay
opera on of CPP with its cri cal loads. se ngs in such cases as well. To
The load on the grid side will survive if conclude, transient stability study is one
the grid survives during the islanding. of the important aspects of the power
However, if the U lity grid collapses system studies and u li es, industries
following the disturbance, only part of and prac cing engineers should give
the plant load (o en referred to as non- adequate emphasis to conduct the
cri cal loads) that was originally requisite studies to design and operate a
Power Research and Development Consultants
Page 4
Newsletter
Technical Article
Detailed Case Study to Understand the Concepts of Transient Stability Analysis
R. Nagaraja
1. Introduc on In the transient stability studies, one is 2. Sample System
generally interested in the rotor angle swing
Electrical power system is one of the most whereas in the dynamic stability study, the To understand the various aspects of
dynamic and complex human made systems performance of the various control func ons transient stability study, typical steel plant
on earth. Complexity is due to different to bring down the oscilla ons of different system shown in figure 1 is considered. The
voltage levels, amount of power being state variables in the system is studied. sample system consists of an industrial plant
handled and the varie es of equipment Reference [1] gives the elaborate concept of having its own cap ve genera on. The
being used. Dynamic is because of the me the power system stability and control, being industrial plant is connected to the 220 kV
frame and response to system disturbances, wri en by a prac cing power system grid though 220 kV double circuit line of
which is several days for energy resource engineer. Reference [2] gives the various zebra conductor of 100 km length. Cap ve
dynamics and of the order of micro seconds aspects of power system stability studies. generators are of 2x120 MW capacity;
to nano seconds during fast and very fast genera on voltage being at 11 kV and the
transients in the power system. Power This paper is wri en to help the prac cing genera on is stepped up to 220 kV using
system stability studies fall under electro- system study engineers to understand the 141.5 MVA genera ng transformer (GT). Unit
mechanical oscilla on studies. These studies concept of stability studies through a typical auxiliary transformer (UAT) load at 6.6 kV is
are further classified into transient stability case study. Emphasis is given to understand fed by a 16 MVA transformer. UAT load
studies for large disturbances and small the physical concept and interpreta on of consists of 6 MW lumped load at 0.9 power
signal stability study or dynamic stability results rather than detailed mathema cal factor and a largest boiler feed pump (BFP)
studies for small disturbances in the system. analysis. motor of 3.6 MW ra ng.
The industrial process load consists of non- governor system control blocks are and line loadings are within the permissible
varying power plant auxiliary load and other considered and all relevant data is furnished limits and about 100 MW of power is being
clean and firm loads of steel plant and in annexure. SVC control block considered is exported to grid.
varying rolling mill load. The fixed load is taken from reference [1] and values are fine
distributed at 33 kV through a 220/33 kV, tuned to minimize the oscilla ons in the
100 MVA power transformer. The sta on system. SVC control block schema c and the
auxiliary load is not explicitly shown in the transfer func on parameters are also 4. Transient analysis for typical
diagram, as lower voltage buses are not furnished in annexure. All the simula on case of single machine
explicitly depicted in the sample system and studies have been performed using the connected to infinite bus
all lower voltage loads are lumped at 33 kV. MiPower™ so ware package.
Transient stability concepts are be er
The rolling mill load is cyclic in nature having
understood through classical representa on
a cyclic period of 200 seconds. The varying
of all the machines, i.e. constant voltage
load is connected at 33 kV through a
3. Steady state load flow results behind the transient reactance xd'. The
dedicated 220/33 kV transformer. While
analysis is similar to single machine
designing the industrial system, it is always
For any transient study simula on, it is connected to infinite bus, grid being treated
be er to segregate the varying load and the
essen al to define the steady state condi on as infinite bus having an equivalent machine
fixed process loads to different transformers,
and analyse the load flow problem to with fault level of about 4000 MVA and large
so that the voltage varia ons and harmonics
establish the ini al condi on to solve the iner a constant of 1000 MJ/MVA on 100
of the varying load do not affect the plant
differen al equa ons being used in the MVA base. A three phase to ground fault is
auxiliary loads. In this case study, the average
transient problem. Figure 1 also depicts the considered at the 220 kV grid bus occurring
power of varying load is 21.75 MW at 0.707
base case load flow results. Both the at 1 second from the start of the simula on.
power factor. Figure 1 also shows the MVA
generators are scheduled to generate 110 Fault is cleared at 1.1 second (corresponding
ra ng of the transformer in the system along
MW each, with machine terminal voltage set to zone 1 fault clearing me of 5 cycles).
with the percentage impedance value on
at 1 pu. The GT taps are set at 105% to push Figure 2 shows the plot of machine terminal
transformer MVA ra ng.
the required reac ve power to the system. voltage. When the fault occurs at 220 kV grid
For the load flow condi on, the average bus, voltage at 220 kV grid bus is zero during
power of the varying load has been the fault and the plant generator terminal
One more important aspect of the industrial considered. BFP motors are set to operate at voltage comes down to almost 55%, as the
system design is to iden fy the islanding 2% slip. SVC opera on is not considered for machine feeds to the fault. Once the fault is
breaker with a view to isolate the essen al steady state simula on. It is seen from the removed, the voltages restore to pre-fault
plant load and genera on from the rest of load flow results, that all the bus voltages values.
the system for severe grid faults. In the
sample system considered, one of the
generators along with the varying load and
grid lines are connected onto the 220 kV grid
side bus. The second generator and the fixed
part of the plant load are connected onto the
220 kV plant side bus. Bus coupler breaker
connects both the 220 kV buses and gets
isolated for severe gird faults/disturbances.
Annexure gives the various data considered
in the sample system. Informa on given in
the SLD and the data given in annexure is
adequate to re-produce the results using any
power system analysis tool. Sta c Var
Compensator (SVC) of 100 MVAR is
considered at 33 kV bus of rolling mill load. Figure 2: Classical representa on - machine terminal voltage plot for three phase to
IEEE Type 1 excita on system and turbine ground fault
Power Research and Development Consultants
Page 6
Newsletter
Figure 4: Classical representa on - swing curve plot for three phase to ground fault
Wherein, H is the iner al constant of the
power Pe will suddenly increase and at this ensuring the system stability. In figure 3, area
rota ng masses of the generator, Pm and Pe
instant it will be more than the mechanical of the hatched por on in red colour indicates
are the mechanical and electrical power of
power Pm. Under this condi on, machine the energy available for the rotor angle to
the generator, respec vely.
speed starts de-accelera ng and rotor angle accelerate and the area of the hatched
During the fault, as electrical power output is decreases. As power system engineer, one por on in green colour indicates the energy
less compared to mechanical power output, should appreciate this beau ful available for the rotor angle to decelerate. As
the rotor starts accelera ng and rotor angle phenomenon in-built in our electro- long as the decelera ng area is more
increases. Figure 4 shows the plot of the mechanical system. Fault has occurred compared to accelera ng area, the system
machine swing curve. At 1.1 second, the fault somewhere in the system and the protec on angular stability is ensured. Cri cal clearing
is removed and hence terminal voltage system si ng in the vicinity of the fault has me is defined as the maximum fault
restores to its original value (Ref figure 2). By operated and isolated the fault. At the clearing me, at which the fault should be
this me, the rotor angle δ would have machine terminal, without any control isolated in order to ensure the system
increased and since sinδ is more now ac on, the rotor angle which started angular stability. If the fault is isolated at the
compared to pre-fault condi on, electrical increasing automa cally starts coming down, cri cal clearing me, area under the
Power Research and Development Consultants
Page 7
Newsletter
6. Motor Star ng
While designing the industrial system, one Figure 8: Voltage dip during motor star ng
should always conduct the motor star ng
studies to ascertain the extent of voltage dip
while star ng the largest motor within the
plant, while other motors and loads are s ll
connected to the same bus at which the
largest sized motor is connected. Figure 8
shows the voltage dip at the 6.6 kV power
plant auxiliary bus, when the 3.6 MW BFP
motor is started. It is assumed that the motor
load torque varies as the square of the motor
speed. It is concluded that the voltage dips to
the extent of 0.91 pu on 6.6 kV base and the
motor star ng me is around 5 seconds. If
the voltage dips to less than 0.85 pu or as
Figure 9: Motor electrical and load torques
specified in the industrial system design
standards, remedial measures like star-delta transformer with lower impedance, etc. to slip. If the load torque at the star ng is
star ng, so star ng, resistance star ng, should be studied as alterna ves to arrive at more than the star ng electrical torque,
auto-transformer star ng, series capacitor a suitable op on. Figure 9 shows the plots of motor will not start. Opera ng point of the
star ng, higher ra ng of the incoming motor electrical and load torque with respect motor is at that slip, wherein the
Power Research and Development Consultants
Page 9
Newsletter
electrical torque cuts the load torque. Data generator performance and also opera on. lines from the grid. The reac ve power
required to model the motor for star ng Too much frequency varia on will cause varia on is minimized by installing the
studies are obtained from the no load and sha vibra on and damage. Most of the dynamic var compensa ng devices like SVC.
short circuit tests of the motor. When the manufactures prescribe that the transient U lity should ascertain from the system
mul ple motors are started at the plant bus electrical power varia on for con nuous studies that the transient and steady state
simultaneously, the motor star ng current opera on should be less than 25% of the voltage dip & voltage flicker level at the PCC
and the star ng me may cause the tripping machine ra ng and current harmonic distor on limits in the
of the incomer feeder or transformer over 4. To determine whether it is possible to grid lines are within the acceptable limits as
current relay. In such cases, instantaneous run the cap ve power plant and the plant per the grid code. Even though the ac ve
and over current relay se ngs should be varying load without the grid support power is varying, within the demand block
properly co-ordinated with the motor 5. To study the requirement of the dynamic period of say 15 minutes, industries are
star ng current and the star ng me to Var compensators like SVC or STATCOM and required to maintain the scheduled demand
avoid the nuisance trippings. designing the ra ng and control ranges for i.e., either import or export of ac ve power.
the same and It is quite un-fortunate that at mes without
7. Cyclic Load Varia on 6. To study the system performance knowing the power system behaviour,
Using the transient/dynamic stability improvement with the installa on of the SVC u li es insist on limi ng the sudden ac ve
analysis program, it is also possible to and compute the flicker levels before and power varia on and also curtail the voltage
ascertain the effect of the varying load on the a er installing the SVC harmonic limits at PCC. Current harmonic
system performance. Varying loads can be Figure 10 shows the voltage plot at 33 kV distor on can be curtailed by the industry
represented as cyclic loads in most of the rolling mill load bus without and with SVC. It and voltage harmonic distor on needs to be
so ware tools by defining the me period can be seen that with the help of SVC, the ascertained by the u lity. As seen in figure 3,
and ac ve and reac ve power load at voltage dip is curtailed to a large extent. even during system fault, there is sudden
different me intervals. Rolling mill load Figure 11 gives the voltage plot at 220 kV varia on in the ac ve power and it cannot
considered in the present case study has the bus. It is concluded that with the help of the be curtailed. Transient and steady state
me period of 200 seconds. The cyclic load SVC, the 220 kV bus voltage varia on is voltage dip, frequency varia on, current
data is given in annexure. The data pertains within the acceptable limits. harmonic distor on limits and the flicker
to typical hot strip mill having 5 roughing Most of the steel plant loads are me- level are the key parameters to be measured
passes and 7 finishing stands. Equal me varying in nature and it is not possible to limit and controlled, rather than the sudden ac ve
interval is considered for each pass and the ac ve power varia on on the incoming power varia on.
stand, even though in reality, the me
interval will vary. The cyclic load varia on
study is required to ascertain the following:
1. To determine the transient voltage dip at
the point of common coupling (PCC) and
compare this with the acceptable values
prescribed in the u lity grid code
2. To determine the voltage varia on at the
plant 33 kV bus and ascertain the effect of
this voltage varia on on the other loads
3. To determine the voltage, frequency and
power varia on at the generator terminal to
determine the effect of these on the
Figure 10: 33 kV rolling mill bus voltage without and with SVC
Power Research and Development Consultants
Page 10
Newsletter
6. Grid islanding
For major disturbances in the u lity, cap ve
power plant generator along with the
essen al plant load should be disconnected
and their tripping should be minimized to
avoid total black out in the plant. Design of
the proper grid islanding scheme is done by
performing various transient simula on
studies and arriving at the proper se ngs for
the islanding relays and incorpora ng the
required control func ons. For the sample
system considered in this paper, whenever a
major grid disturbance occurs, the islanding
breaker trips. CPP unit 1 along with the
Figure 11: 220 kV plant bus voltage without and with SVC
essen al load is always protected from
tripping. If the grid survives, the CPP unit 2
along with the rolling mill load survives and if
grid dies, the CPP unit 2 collapses along with
the rolling mill load.
For the sample system considered, the
importance of segrega ng one of the power
plants with the essen al load from that of
the second unit and the varying load is
illustrated by considering a severe fault at the
grid (3 phase bus bar fault at grid bus). As a
consequence of the fault, it is assumed that
both the grid lines trip. Following cases are
simulated:
Case 1: No opera on of the islanding breaker
Figure 12: Plant generator #1 terminal voltage for grid islanding cases
and
Case 2: Tripping of the islanding breaker
within the plant Figure 12 shows the CPP
generator terminal voltage for both the
cases. It can be concluded that voltage
recovers and system is secure. However, it is
not just sufficient to look at the voltage plot,
but it is essen al to observe the frequency
plot. Figure 13 shows the plot of generator 1
frequency for both the cases. In case 1,
machine frequency raises to almost 55 Hz
and in the reverse swing reaches to almost
46 Hz and then se les at about 50.5 Hz.
Power system engineer without the
protec on background may conclude that it
is stable opera on as both voltage and Figure 13: Frequency of plant generator #1 for grid islanding cases
frequency are finally se ling. However, it is
important to note that the turbine delay of 1 to 2 seconds and generator under frequency protec on would operate and
mechanical over speed trip is at 55 Hz, frequency protec on limit is generally set at trip both the units, resul ng in plant
instantaneous and generator over frequency 47.5 Hz with a me delay of 1 to 2 seconds. total black out. On sensing the tripping
protec on is generally at 52.5 Hz with a me Hence, it is quite certain that generator of grid lines, if the islanding
Power Research and Development Consultants
Page 11
Newsletter
breaker also trips within a me delay of Annexure – System Data Turbine & Governor Control Block Data
about 2-3 cycles, generator unit 1 along with Plant Generator Data – 120M W IEEE Type 1
the essen al plant load survives. From Rated MVA: 141.5 MVA
Droop: 5%, T1: 0.1 s, T2: 0.03 s, T3: 0.4 s
frequency plot in figure 13, it is concluded Terminal Voltage: 11 kV
K 1 : 0.276 pu, K 3 : 0.324 pu, K 5 : 0.4 pu,
that the generator frequency excursions are
Iner a constant: 3.1 MJ/MVA K7: 0 pu
well within the generator over and under
Xd: 1.95 pu, Xq: 1.84 pu K2: 0 pu, K4: 0 pu, K6: 0 pu, K8: 0 pu
frequency relay se ngs. On the similar lines,
if there is import of power at the islanding X'd: 0.22 pu, X'q: 0.38 pu Thp: 0.26 s, Trh: 10 s, Tip: 0.5s
breaker during the islanding, part of the X"d: 0.17 pu, X"q: 0.18 pu Gpup: 0.1, Gpdown: -1, P m a x : 1.05 pu,
loads can be tripped to mi gate the Pmin: 0 pu
Td0': 7.15 s, Tq0': 2.5 s
overloading of the generator. The under
Td0": 0.039 s, Tq0": 0.15 s
frequency load shedding se ng should be AVR Data
Transmission Line L1&L2 Data
co-ordinated with the generator under
IEEE Type 1
frequency tripping se ng, so that the load Voltage Level: 220 kV
Tr: 0.05 s
shedding occurs before the generator Length: 100 km
tripping takes place. Ka: 100, Ke: -0.05, Kf: 0.05
Z: 0.0748746+j 0.3992516 ohm/km
Ta: 0.1 s, Te: 0.5 s, Tf: 0.5
B/2: j1.466942e-006mho/km
9. Conclusions Vse1: 0.06, Vse2: 0.3
Grid Data
In this ar cle, the concept of transient Vrmax: 1, Vrmin: -1
Voltage Level: 220 kV
stability study is explained through a typical Efdmax: 2.7, Efdmin: 0
Iner a constant: 1000 MJ/MVA on 100
case study. The methodology explained MVA base
star ng from the data requirement, studies
Fault level: 4000 MVA
to be performed etc. to the analysis of results
Source X/R Ra o: 20
can be used by the beginners of the system
stability studies to move forward from the
usual steady state analysis like load flow to Motor Data
gain exper se in power system stability MVA ra ng: 4.6875
studies.
MW ra ng: 3.6
Voltage ra ng: 6.6 kV
10. References
Stator resistance: 0.00591 pu
[1.] PrabhaKundur, “Power System
Stator reactance: 0.11111 pu
Stability and Control”, (Book), Tata
McGraw Hill Educa on, 1994. Rotor resistance: 0.02565 pu
[2.] R. Nagaraja, “Power System Stability Rotor reactance: 0.11111 pu
Studies”, PRDC Newsle er special
Magne zing reactance: 3.98938 pu
issue on 'Power system studies', vol.
2, issue 1-3, January-September Iner a constant: 1.4881 second
2012, pp 12.
Running slip: 0.02
Star ng method: Direct On Line (DOL)
Load Torque characteris c: Propor onal
to square of the speed
Power Research and Development Consultants
Page 12
Newsletter
From -
To - second Laod in MW Remarks
second
0 10 0
10 20 10 Roughing pass 1
20 30 0
30 40 15 Roughing pass 2
40 50 0
50 60 20 Roughing pass 3
60 70 0
70 80 25 Roughing pass 4
80 90 0
90 100 30 Roughing pass 5
100 120 0
120 130 35 Finishing stand 1
130 140 45 Finishing stand 2
140 150 55 Finishing stand 3
150 160 65 Finishing stand 4
160 170 55 Finishing stand 5
170 180 45 Finishing stand 6
180 190 35 Finishing stand 7
190 200 0
SVC control Block Schema c
Technical Article
Low Frequency Oscillationsin Power Systemsand their Mitigation
K.R. Padiyar
1. Introduc on require special control measures for their examples.
mi ga on. Normally, damper(amor sseur)
During normal opera on of power systems, windings provided on the generator rotor are 2.. Review of PSS
the voltages and currents in the transmission adequate.
lines remain steady and vary slowly as the While analog PSS with the input signal based
power outputs of generators vary depending Mi ga on of local and inter-area modes are on the integral of accelera ng power is
on the changes in the load. The load a empted using Power System Stabilizers available since eigh es, the digital PSS
varia ons are assumed to be slow. However, (PSS). PSS using speed or frequency, (labelled as PSS 2B) was proposed in the
even in steady state opera on, there are electrical power signals have been used. nine es. Subsequently, PSS4B was
small disturbances present due to small, With sa sfactory design, they are useful in introduced based on the work carried out at
random changes in the load. If the system is damping local mode oscilla ons. The block IREQ, Canada. The advantages are be er
small signal stable (steady state stable), diagram of a PSS is shown in Figure 1.The performance at low frequencies of
the transients due to perturba ons in the input signal to PSS can be derived from oscilla ons (0.1 -0.8 Hz). Kamwaet al(2005)
system decay and do not pose any problem. speed, frequency or electrical power. claim that in spite of usage of PSS for a long
However, if the opera ng point(equilibrium However, speed and frequency signals can me, “ it may s ll be one of the most
point) is not stable, then even small destabilize the torsional modes of the misunderstood and misused pieces of
perturba ons in the system can lead to turbine generator sha . The power signal generator control equipment. Following the
spontaneous oscilla ons that can grow and can cause excessive Var modula on during western U.S. interconnec on blackouts in
lead to loss of synchronism. These mechanical power changes. Thus, a 1996, was found that key PSS's were either
oscilla ons are normally caused by composite signal that represents the integral out of service or poorly tuned. Even today,
oscilla ons of the generator rotors that have of accelera ng power is used in PSS. a er these problems have been fixed, large
frequencies in the range of 0.1 to 2.5 Hz. If
there are N generators in the system, the
number of frequencies are (N-1). The
frequencies of oscilla ons depend on the
loading of generators and system
configura on. The modes of oscilla on Figure 1: Block diagram of PSS
having frequencies in the range of 0.8 to 1.8 The development and applica on of FACTS disturbances tend to induce 0.2 Hz low
Hz are labelled as local modes and typically, controllers in AC transmission lines has made frequency oscilla ons in the grid. In Brazil,
small number of generators in a specified it feasible to apply damping controllers in the north-south interconnec on has given
area, par cipate in these oscilla ons. The these power electronic devices. Both shunt rise to a new low-frequency inter-area mode
modes of oscilla on having frequencies in FACTS controllers (SVC and STATCOM) and between 0.17 and 0.25 Hz, necessita ng a
the range of 0.1 to 0.5 Hz are labelled as series FACTS controllers(TCSC) are being retuning of PSSs throughout the system.
inter-area modes and several generators, widely used for control of voltage and power Inter-area oscilla ons have also been
spread over a large area par cipate. In flow. In addi on, it is feasible to modulate reported on the UCTE / CENTREL
general, it can be said that as the frequency is the voltage and power flow based on interconnec on in Europe, at 0.36, 0.26, and
reduced, more number of generators varia ons inthe signals derived from local even 0.19 Hz. The recent 2003 blackout in
par cipate. Conversely, less number of measurements of voltage and power flow. eastern Canada and the U.S. was equally
generatorspar cipate in oscilla on having The control law and the op mum loca on of accompanied by severe 0.4-Hz oscilla ons in
higher frequencies. When only generators in these damping controllers can be obtained several post-con ngency stages.”
a power plant par cipate, the modes of from energy concepts, The methodology for
oscilla on are called as intra-plant modes. the design of damping controllers based on
Typically, the intra-plant modes do not FACTS will be presented in the paper with
Power Research and Development Consultants
Page 14
Newsletter
3. Energy Based Damping We have, the two swing modes, with the controller
Controllers using FACTS are:
The low frequency oscilla ons are due
to exchange of the kine c energy stored and
in the generator rotors and the magne c
energy stored in the transmission lines.
The natural damping arises from the
mechanical damping encountered by the T h i s c l e a r l y s h o w s t h e ro l e o f t h e
rotors and frequency dependent load Figure 2 shows the damping controller for controller in damping Mode 2.
characteris cs. By providing a series a series FACTS controller that includes a With mul ple controllers there is a
connected FACTS controller (say, TCSC) washout circuit. Tm can be chosen as need for coordinated control, that is
i n s e r i e s w i t h a t ra n s m i s s i o n l i n e 0.01s. simultaneous tuning of all the control
( t y p i c a l l y, a e l i n e b e t w e e n t w o parameters.
coherent groups of generators), it is
possible to provide damping of the low
frequency oscilla ons of power flow in
the line by modula ng the capaci ve
reactance injected by the TCSC. The
control signal is obtained from the
difference in frequencies of two buses,
one of them is the terminal bus of the Figure 2: Damping controller for a series FACTS Controller
line (say, k) and the other, a fic ous bus
such that the reactance between two
buses is the sum of the net line reactance 4. Example
and a Thevenin reactance (which can be Consider the 3 machine system shown 5. Shunt FACTS
viewed as a tunable parameter). The in Figure 3. The data is essen ally same Controller (STATCOM)
increment in the power flow in the line is as in [4] except for the following The damping controller termed as SMC
given by, m o d i fic a o n s . A l l g e n e r a t o r s a r e (Supplementary Modula on Controller)
equipped with sta c exciters with associated with the STATCOM is designed
KE = 200, TE = 0.05. A shunt susceptance to modulate the reac ve current injected
of 0.5 pu is provided at bus 5 for by the STATCOM. At bus j,
voltage support. The loads are assumed
Where,Bk = Pko / Xk. to be constant impedance type and
If we propose a control law given by, mechanical damping is assumed to be
zero.
The eigenvalues for the swing modes at
the opera ng point are calculated as,
6. References
[1] K.R.Padiyar, 'Power System Dynamics-
Stability and Control', (Book), Second
Edi on,BS Publica ons, 2002,
Hyderabad
[2] I.Kamwa, R.Grondin and G.Trudel,
'IEEE PSS2B versus PSS4B: The limits
of performance of modern power
system stabilizers', IEEE Trans. on
Power Systems, Vol. 20(2), 2005,
pp.903-915
[3] K.R.Padiyar, 'FACTS Controllers in
Power Transmission and Distribu on'
( B o o k ) , N ew A ge I nte r n a o n a l .
Publishers, 2007, New Delhi
[4] P.M.Anderson and A.A. Fouad, 'Power
System Control and Stability', (Book),
Iowa State University Press, 1977,
Ames, U.S.A.
[5] K . R . P a d i y a r a n d H . V . S a i
Kumar,'Inves ga ons of strong
resonancein mul -machine power
systems with STSTCOM
supplementary modula on
c o n t r o l l e r ' , I E E E Tr a n s . P o w e r
Systems, Vol.21(2), 2006, pp.754-
762. Figure 3: A three machine system (Anderson and Fouad)
Rotary Bangalore –TTK Blood Bank organized a Blood dona on camp in PRDC on 16th April 2015. In all
there were 45 donors from PRDC, a great contribu on for a social cause by any standard! Rotary
Bangalore were so apprecia ve of the event and even desired to have this as a biennial CSR ac vity of
PRDC.
Power Research and Development Consultants
Page 16
Newsletter
Technical Article
Enhancing Power System Stability and Control Using Special Protection Systems
Nitesh Kumar. D and Faraz Zafar Khan
1. Overview 2. Design aspects of SPS 3. Sample System
Power system protec on is o en limited Designing SPS for any system can be divided The system under considera on represents
either to equipment protec on or adjacent into various major ac vi es such as [2]: two area systems as shown in Figure 1, with
faulty equipment in vicinity. The size and Area 1 being genera on rich supplying
complexity of the power system makes it System Study for the considered system power to Area 2. Area 1 has 2500 MW of
vulnerable and subject to collapse under genera on and nearly 1400 MW of load.
cri cal situa ons such as power conges on, Developing Logical Solu on Area 2 has 2000 MW of genera on and
frequency and voltage viola ons, power around 3000 MW of load. Area 2(a) is cri cal
swings, etc. In order to secure wide area Design and Implementa on of SPS industrial zone requiring high reliability. The
opera ons, different class of protec on addi onal load in Area 2 is supplied by Area 1
schemes are proposed which are popularly Periodic Review and Records over two 400 kV single circuit lines. In Area 1,
known as Special Protec on Systems (SPS). the governors of Gen 1, Gen 5 and Gen 9 are
Most commonly used protec on measures There are many issues which can impact considered to be opera ng in droop mode.
for such SPS are genera on rejec on, load reliable power system opera on. However, The other governors of area 1 are in constant
rejec on, under frequency load shedding, the most common issue is typically the power mode. In area 2, all the governors
system separa on and their combina on [1]. heavily loaded transmission system. are considered to be opera ng in droop
It is important to note that the response me The tripping of heavily loaded line is mode. MiPowerTM so ware is u lized to
and the quantum of load/ genera on o en seen as the root cause of system build the sample system and carrying out
balancing required are key indices for the transient stability simula ons [4].
instability [3]. The understanding of this
successful opera on of SPS.
issue is cri cal in power community, since it
can lead to poten al blackout scenarios. This
SPS is intended to safeguard the power grid
during un-planned outage (con ngency) or ar cle highlights one such scenario on a Under the situa ons when any one of the
system opera ng condi ons where power sample two area system. It also suggests the 400 kV line i.e. Line 1/Line 2 is not available,
demand cannot be met. Implementa on of logic to implement SPS in order to safeguard the two areas become vulnerable to stability
such schemes involves many factors such as the system to the extent possible and avoid problems under the con ngency of another
[2]: system blackout. line outage. The following con ngencies can
be envisaged under which ac on of SPS will
be required to safeguard the study system.
4. Implementa on of
conven onal frequency
based scheme
Figure 4: Frequency of Area 1 and Area 2 for case 1 with simple load shedding scheme
Frequency relays are placed in the Area 1 to It can be inferred that for case 1, 1000 MW system.
trip around 1000 MW of genera on at of load shedding in Area 2 is sufficient to
frequency of 52 Hz. In Area 2, the frequency maintain the frequency profile of the system. Further, in order to analyze whether
relays are placed such that around 100 MW However, for case 2 when the second outage addi onal load shedding in area 2 can help
of load is shed at 48.5 Hz. The frequencies of occurs before the system equilibrium is safe guard the system, a case is studied by
the two areas following islanding in the two a ained following the fault and first outage, tripping around 1500 MW of load in area 2
cases are shown in Figure 4 and Figure 5 the simple load shedding based approach for case 2. The result of this case is shown in
respec vely. may not be adequate to safe guard the Figure 6.
Power Research and Development Consultants
Page 18
Newsletter
5. Implementa on of Special
Protec on System (SPS) Figure 5: Frequency of Area 1 and Area 2 for case 2 with simple load shedding scheme
Protec ve
R e l a y E n g i n e e r s , Te x a s A & M
University, Mar 30 – Apr 1, 2004,
pp.1-12.
Figure 9: Frequency of Area 1 and Area 2 for case 2 with logic based SPS
Also, it can be clearly observed that the 7. References
damage to the system, in terms of load shed,
depends on the response me.
[1] P. M . A n d e r s o n a n d B . K .
In fact there is exponen al rela onship of
LeReverend, “Industry Experience
damage to the system with respect to the
with Special Protec on Schemes”,
response me. Design of fast ac ng SPS
I E E E Tr a n s a c o n s o n P o w e r
could reduce the poten al deteriora on of
Systems, Vol. 11, No. 3, Aug 1996,
the system in the cri cal fault condi ons.
pp.1166-1179.
[2] VahidMadani, Mark Adamiak and
M a n i s h T h a k u r, “ D e s i g n a n d
Implementa on of Wide
AreaSpecial Protec on Schemes”,
57th Annual Conference for
Technical Article
Stability Studies for Industrial Power Systems
MaheedharPatnala and T. Guru Charan Das
1. Introduc on therefore it is not advisable. For sensing such assessment, find protec ve device se ngs,
a condi on, careful selec on of islanding and apply the necessary remedy or
Technical Ar cle Stability Studies for relay se ngs is required. Also a er islanding, enhancement to improve the system
Industrial Power Systems load genera on balance need to be stability.
maintained in the island formed. Thus
Maheedhar Patnala and T. Guru Charan Das
transient stability study plays a vital role in
When an industrial plant with cap ve power
islanding studies by establishing the CCT for
genera on is connected to u lity, it may 2. Case Study
industrial plant generators for external faults.
result in stability problems to the cap ve
generators in the plant due to transient The stability study is carried out for a steel
M/s PRDC has carried out a number of
disturbances such as three phase faults, loss plant with a combined capacity of 860,000
projects rela ng to stability studies for
of genera on or loss of a large load etc., both TPA of Sponge Iron, 300,000 TPA of Steel,
industrial power systems. The calcula on of
in grid and plant. For a given disturbance, the and 60,000 TPA of Ferro Alloys and power
CCT for industrial plant generators for a three
longest fault dura on which does not result genera on facility of 170MW and is
phase fault both in u lity and industrial plant
in instability of the generators is referred to interconnected to u lity at 132 kV level.
usingMiPower™ so ware is briefly described
as the Cri cal Clearing Time (CCT). The CCT in this technical ar cle.
for the cap ve generators need to be
calculated by conduc ng transient stability A. Network model forconsidera on
The MiPower™ transient stability analysis
for various disturbances. The most onerous
program inves gates the stability limits of a
abrupt change is usually a three-phase fault; For stability studies, the en re industrial
power system before, during and a er
a three-phase fault causes the power network from High Voltage (HV) to either
system changes or disturbances. The
transfer through the line to be reduced to Medium Voltage (MV) or Low Voltage (LV)
program models dynamic characteris cs of a
zero from the working condi on. level needs to be modeled for base case load
power system, implements the user-defined
flow and short circuit analysis. Dynamic
During transient disturbances in the events and ac ons, solves the system
modeling (sub transient or transient model)
industrial plant (internal faults), the faulty network equa on and machine differen al
of plant cap ve generators along with
sec on isola on needs to be carried out by equa ons interac vely to find out system
automa c voltage regulators (AVR) & turbine
protec ve relay within CCT so as to avoid and machine responses in me domain with
governors need to be carried out. It is not
instability of the cap ve generators. Thus a user defined reference. From these
required to model complete grid network for
transient stability study plays a vital role in responses, users can determine the system
the stability studies, only grid substa on
relay coordina on by establishing the CCT for transient behaviour, make stability
model with its equivalent short circuit
industrial plant generators so as to co-
ordinate the relay se ngs in such a way that
the protec on relay gives the trip signal
before cap ve generators trip or become
unstable for internal faults.
MVA shall be sufficient to carry out bus is 700 ms. protec ve system opera ng me is
stability studies. For large induc on longer than the CCT of plant generators,
machines (MV motors) the detailed Exis ng protec on system opera ng me system will become unstable.
dynamic representa on is needed, calcula on: For the corresponding
however small induc on machines (LV loca on of fault, exis ng protec on Remedial Ac on: The exis ng protec on
motors) are represented as a sta c load
(constant power).
Time t =1.1 s Fault cleared. Figure 3: Swing curve for TG1, TG2 & TG3 - Fault clearing me of 710ms
The next step is to itera vely change the system opera ng me is calculated by schemes are modified and a new unit
inspec ng the exis ng protec on protec on schemes are recommended so as
to isolate the faulty sec on from the system
within CCT of plant generators. Similar
methodology is adopted and CCT at
different loca ons in the plant is calculated
and is summarized in Table 2. For the
corresponding loca on of fault, the exis ng
protec on system opera ng me is
fault clearing me and observe the swing schemes and se ngs. calculated by inspec ng the exis ng
curve of the plant generators. The Figures protec on schemes and se ngs. The
2 and 3 illustrate the swing curve with In present case, the minimum IDMT
opera ng me of the exis ng protec on maximum exis ng protec on system
different fault clearing mes. It can be opera ng me for faults at different
obser ved that the CCT of the plant system (i.e. overcurrent protec on) for a
fault at 33kV plant bus is 800 ms. As the loca ons is calculated and is summarized in
generators for a three fault at 33kV plant Table 2.
Power Research and Development Consultants
Page 22
Newsletter
Unstable case(s) [i.e. here CASE C] is Table 2:Summary for CCT for internal faults
iden fied from the stability analysis and
recommenda ons are suggested so as to Opera ng
maintain the stability of plant generators for Bus Cri cal me of
Fault System
internal faults in the plant. Case voltage Clearing exis ng
Loca on stability
(kV) Time (s) protec on
b. External Faults: system (s)
The transient disturbances in the u lity grid
132kV
at transmission voltage level termed as
CASE A Power 132 0.21 0.10 Stable
external faults to the industrial plant.
Plant Bus
132kV
CCT Calcula on: The following sequences of
CASE B Auxiliary 132 0.21 0.10 Stable
the events are simulated in the transient
stability program of MiPower so ware. Bus
33kV
Time t =1.0 s Se ng a temporary
CASE C Plant 33 0.70 1.0 Unstable
three phase fault at 132 kV grid bus.
Bus
Time t =1.1 s Fault cleared.
6.6kV
The fault clearing me is itera vely changed CASE D Plant 6.6 1.5 1.0 Stable
and the swing curve of the plant generators Bus
is observed for assessing stability of plant
generators. The Figures 4 and 5 illustrate the
swing curve with different fault clearing me.
It can be observed that CCT of the plant
generators for a three phase fault at grid bus
is 220 ms.
Exis ng protec on system opera ng me
calcula on: For the corresponding loca on
of faults in the u lity grid, the exis ng
protec on system opera ng me is
calculated by inspec ng the exis ng
protec on schemes and se ngs. The
exis ng protec on se ngs of distance
protec on which is meant to take care for
Figure 4: Swing curve for TG1, TG2 & TG3 - Fault clearing me of 220ms
faults in the u lity grid are given in below
Table 3.
In present case, the minimum opera ng
me of the exis ng protec ve system for a
fault at 132kV Grid is 400ms on zone2 of
distance relay. As the protec ve system
opera ng me is longer than the CCT of
plant generators, system will become
unstable.
Remedial Ac on: New protec on scheme
with under voltage in conjunc on with
direc onal overcurrent (logic and se ng) is
proposed in the islanding relay so as to
isolate from the fault in the u lity within CCT
of plant generators. The proposed scheme
(logic & se ngs) are given in below Table 4. Figure 5: Swing curve for TG1, TG2 & TG3 - Fault clearing me of 230ms
Power Research and Development Consultants
Page 23
Newsletter
3. Conclusion
For a given disturbance, the longest fault Figure 8: Frequency response a er islanding from u lity on over frequency
dura on which does not result in instability
of the generators is referred as the cri cal
clearing me (CCT).
The stability studies for industrial power
system are different from stability studies
carried out for transmission system as the
la er studies deal with only establishing CCT
and checking whether the calculated CCT's
are within the range s pulated by the grid
standards. Transient stability plays a vital role
in understanding the stability problems of
cap ve generators when connected to u lity
grid. The CCT for the cap ve generators need
to be calculated by conduc ng transient
stability for various disturbances. The stability
study for industrial power system was
discussed in this ar cle right from modeling
Figure 9: Frequency response a er islanding from u lity on over frequency & posi ve dF/dT
to the significance of the results.
Power Research and Development Consultants
Page 25
Newsletter
4. References
[1] P r a b h a K u n d u r, ' P o w e r S y s t e m
Stabilityand Control' (Book), McGraw
Hill Educa on, 1994
PRDC Provides LED Lighting Solution for the Holy City of Puri
PRDC has emerged as one of the major
u lity consul ng firms in India in providing
LED ligh ng solu ons using modern tools.
The company has provided LED ligh ng
solu on for six important areas of the Holy
city of Puri in Odisha. The responsibility of
PRDC included survey, design, prepara on of
tender specifica on, tender evalua on, GTP
and drawings approval and supervision
during execu on of work. Overall project
cost for LED ligh ng scheme is Rs. 12 Crores.
PRDC being PMC for all the ligh ng projects,
was responsible for ensuring quality job and
mely comple on.
Figure 1: High mast LED lights at the Lord Jagannath Temple entrance
LED ligh ng is one of the revolu onary
technologies over conven onal ligh ng
system in the recent years. It is widely
accepted due to its many advantages
such as long life me, energy efficiency,
eco-friendliness, dimmability, instant ligh ng
capability etc. Also, it has been proved that
LED ligh ng is one of the best energy saving
drives accepted across the globe.
Level 1 Batch:
Level 2 Batch:
marke [email protected]
Power Research and Development Consultants
Page 29
Newsletter
Source: pib.nic.in
In the year 2014-15, an amount of Rs The Union Cabinet has approved the
16,388.81 crore has been collected as coal proposals for amendment in Electricity Act,
cess for Na onal Clean Energy Fund (NCEF). 2003 on 10th December, 2014 as contained
As per the budget es mates, during 2015-16 in the Electricity (Amendment) Bill 2014. The
an amount of Rs 13,118.04 crore will be Electricity (Amendment) Bill, 2014 was
collected as coal cess for NCEF. Na onal introduced in the Lok Sabha on 19th
Clean Energy Fund (NCEF) is created for December, 2014. This was referred to
funding research and innova ve projects in Parliamentary Standing Commi ee on
clean energy technologies. Out of 44 projects Energy and the commi ee has submi ed its
recommended for NCEF support in report to the Parliament on 7th May, 2015.
renewable energy, 30 projects are awai ng The amendments proposed in Electricity
alloca on of fund. (Amendment) Bill, 2014 seeks to end the
monopoly of power distribu on companies
Source: pib.nic.in by segrega ng the carriage (distribu on
sector/network) from the content (electricity
Power Research and Development Consultants
Page 30
Newsletter
Dr. R. Nagaraja is the founder and Managing Prof K.R. Padiyar is associated with Indian Faraz Zafar Khan is presently working as
Director of M/s. Power Research & Ins tute of Science, Bangalore since 1987, Senior Engineer in Power Research and
Development Consultants Pvt. Ltd., where he is currently an Honorary Professor Development Consultants Pvt. Ltd. He is also
Bangalore- one of the reputed Power System in the Department of Electrical Engineering. pursuing his PhD under VTU in the research
Consultants in the country. Prior to joining IISc, he was with Indian area of “Advanced Protec on and Analysis
Ins tute of Technology, Kanpur. He obtained Schemes for Transmission System”. He
R. Nagaraja has done his B.E. in Electrical and M.E degree in 1964 from IISc and Ph.D completed M-Tech in Power system from
Electronics Engineering from Mysore degree from University of Waterloo, Canada VNIT, Nagpur.
University (India) in 1986. He obtained his in 1972. He has taught and lectured at
M.E in 1988, specialized in Computer various Universi es in Canada and USA. Nitesh Kumar D
Applica ons to Power System and Drives
and Ph.D. Degree in the field of Energy He has authored over 200 papers and 4
Management System from Indian Ins tute of Books including 'Power system dynamics,
Science (IISc). His specializa ons are Power stability and control'. His research interest are
System Analysis, Simula on, Power in the areas of HVDC and FACTS, power
Engineering Educa on and Power System system stability and control. He was a
Protec on. Dr. Nagaraja has authored several member of the Review commi ee on the
technical papers and conducted a number of Na onal HVDC project. He is the recipient
workshops / conferences / seminars of 1999 Prof. Rustom Choksi award for
throughout the country. excellence in research. He was ABB chair Nitesh Kumar D is presently working
professor (2001-03). He is fellow of Indian as Engineer in Power Research and
Dr. Nagaraja is the brain behind the na onal academy of Engineering. Development Consultants Pvt. Ltd. He
architecture, design and development of the
MiPower™ – Power system analysis so ware completed BE in Electrical and Electronics
package widely used by Electric u li es, Engineering from VTU and is presently
Industries, Consultants and Engineering pursuing M.Sc (Engg.) by research under VTU
colleges. Dr. Nagaraja has been involved in in the research area of generator protec on
the planning studies of State U li es and enhancement. His area of interest includes
Industries in India and abroad. power system stability, automa on &
control, Power system protec on and PMU
applica on.
Power Research and Development Consultants
Page 31
Newsletter
Printed & Published by : Dr. R. Nagaraja on behalf of Power Research & Development Consultants Pvt. Ltd.
Printed at : M/s. Art Print, Dr. Modi Hospital Main, WOC Road, Bengaluru - 560 086. Cell : 98452 33516. Editor : M.M. Babu Narayanan