This document provides engineering data for various grille sizes including nominal duct size, duct area, core velocity, negative static pressure, airflow (CFM), and noise criteria (NC) ratings. Airflow and pressure drop values are given for different grille sizes across a range of core velocities from 300 to 1500 feet per minute. Notes provide information on test standards and units of measurement.

Uploaded by

Talha Baig
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views24 pages

Return Grill PDF

This document provides engineering data for various grille sizes including nominal duct size, duct area, core velocity, negative static pressure, airflow (CFM), and noise criteria (NC) ratings. Airflow and pressure drop values are given for different grille sizes across a range of core velocities from 300 to 1500 feet per minute. Notes provide information on test standards and units of measurement.

Uploaded by

Talha Baig
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

ENGINEERING DATA

A70, A80
3/4” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 900 1100 1300 1500
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.050 0.075 0.105 0.140
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.012 0.022 0.034 0.049 0.067 0.111 0.165 0.231 0.307

Airflow (CFM) 57 76 95 114 133 171 209 247 285


6x6 0.25
NC - - - - 13 20 26 31 35

Airflow (CFM) 78 104 130 156 182 234 286 338 390
8x6 0.33
NC - - - - 14 22 27 32 36

Airflow (CFM) 102 136 170 204 238 306 374 442 510
10x6 0.42
NC - - - 11 16 23 28 33 37

Airflow (CFM) 111 148 185 222 259 333 407 481 555
8x8 0.44
NC - - - 12 16 23 29 34 38

Airflow (CFM) 123 164 205 246 287 369 451 533 615
12x6 0.50
NC - - - 12 16 24 29 34 38

Airflow (CFM) 144 192 240 288 336 432 528 624 720
14x6 0.58
NC - - - 13 17 24 30 35 39

16x6 Airflow (CFM) 171 228 285 342 399 513 627 741 855
0.67
12x8 NC - - - 14 18 25 31 36 40
Registers
Grilles &

Airflow (CFM) 177 236 295 354 413 531 649 767 885
10x10 0.69
NC - - - 14 18 25 31 36 40

Airflow (CFM) 189 252 315 378 441 567 693 819 945
18x6 0.75
NC - - - 14 18 25 31 36 40

20x6 Airflow (CFM) 216 288 360 432 504 648 792 936 1080
0.83
12x10 NC - - - 14 19 26 32 37 41

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR74 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A70, A80
3/4” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 900 1100 1300 1500
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.050 0.075 0.105 0.140
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.012 0.022 0.034 0.049 0.067 0.111 0.165 0.231 0.307

Airflow (CFM) 231 308 385 462 539 693 847 1001 1155
22x6 0.92
NC - - - 15 19 26 32 37 41

24x6 Airflow (CFM) 264 352 440 528 616 792 968 1144 1320
1.00
12x12 NC - - - 15 20 27 33 37 42

30x6 Airflow (CFM) 333 444 555 666 777 999 1221 1443 1665
1.25
18x10 NC - - 11 16 21 28 34 38 43

Airflow (CFM) 366 488 610 732 854 1098 1342 1586 1830
14x14 1.36
NC - - 11 17 21 28 34 39 43

36x6 Airflow (CFM) 405 540 675 810 945 1215 1485 1755 2025
1.50
18x12 NC - - 13 17 22 29 35 39 43

Airflow (CFM) 411 548 685 822 959 1233 1507 1781 2055
22x10 1.53
NC - - 12 17 22 29 35 39 43

30x8 Airflow (CFM) 477 596 745 894 1043 1341 1639 1937 2235
1.67
24x10 NC - - 12 18 22 29 35 40 44

Registers
Grilles &
42x6 Airflow (CFM) 477 636 795 954 1113 1431 1749 2067 2385
1.75
18x14 NC - - 13 18 22 29 35 40 44

Airflow (CFM) 486 648 810 972 1134 1458 1782 2106 2430
16x16 1.78
NC - - 13 18 22 30 35 40 44

24x12 Airflow (CFM) 546 728 910 1092 1274 1638 2002 2366 2730
2.00
18x16 NC - - 13 18 23 30 36 41 45

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR75


ENGINEERING DATA
A70, A80
3/4” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 900 1100 1300 1500
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.050 0.075 0.105 0.140
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.012 0.022 0.034 0.049 0.067 0.111 0.165 0.231 0.307

Airflow (CFM) 621 828 1035 1242 1449 1863 2277 2691 3105
18x18 2.25
NC - - 14 19 23 31 36 41 45

Airflow (CFM) 642 856 1070 1284 1498 1926 2354 2782 3210
24x14 2.33
NC - - 14 19 24 31 37 41 45

Airflow (CFM) 687 916 1145 1374 1603 2061 2519 2977 3435
30x12 2.50
NC - - 14 19 24 31 37 42 46

Airflow (CFM) 738 984 1230 1476 1722 2214 2706 3198 3690
24x16 2.67
NC - - 15 20 24 31 37 42 46

Airflow (CFM) 771 1028 1285 1542 1799 2313 2827 3341 3855
20x20 2.78
NC - - 15 20 24 32 37 42 46

Airflow (CFM) 825 1100 1375 1650 1925 2475 3025 3575 4125
36x12 3.00
NC - - 15 20 25 32 38 42 47

30x16 Airflow (CFM) 933 1244 1555 1866 2177 2799 3421 4043 4665
3.33
24x20 NC - - 16 21 25 32 38 43 47
Registers
Grilles &

Airflow (CFM) 942 1256 1570 1884 2198 2826 3454 4082 4710
22x22 3.36
NC - - 16 21 25 32 38 43 47

42x12 Airflow (CFM) 966 1288 1610 1932 2254 2898 3542 4186 4830
3.50
36x14 NC - - 16 21 25 33 38 43 47

Airflow (CFM) 1029 1372 1715 2058 2401 3087 3773 4459 5145
24x22 3.67
NC - - 16 21 26 33 39 43 47

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR76 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A70, A80
3/4” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 900 1100 1300 1500
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.050 0.075 0.105 0.140
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.012 0.022 0.034 0.049 0.067 0.111 0.165 0.231 0.307

Airflow (CFM) 1050 1400 1750 2100 2450 3150 3850 4550 5250
30x18 3.75
NC - - 16 21 26 33 39 43 48

48x12 Airflow (CFM) 1125 1500 1875 2250 2625 3375 4125 4875 5625
4.00
24x24 NC - - 16 22 26 33 39 44 48

Airflow (CFM) 1266 1688 2110 2532 2954 3798 4642 5486 6330
36x18 4.50
NC - - 17 22 27 34 39 44 48

36x20 Airflow (CFM) 1413 1884 2355 2826 3297 4239 5181 6123 7065
5.00
30x24 NC - 11 17 23 27 34 40 45 49

Airflow (CFM) 1482 1976 2470 2964 3458 4446 5434 6422 7410
42x18 5.25
NC - 11 18 23 27 34 40 45 49

Airflow (CFM) 1548 2064 2580 3096 3612 4644 5676 6708 7740
28x28 5.44
NC - 11 18 23 27 35 40 45 49

42x20 Airflow (CFM) 1653 2204 2755 3306 3857 4959 6061 7163 8265
5.83
30x28 NC - 12 18 23 28 35 41 45 50

Registers
Grilles &
48x18 Airflow (CFM) 1698 2264 2830 3396 3962 5094 6226 7358 8490
6.00
36x24 NC - 12 18 23 28 35 41 46 50

Airflow (CFM) 1782 2376 2970 3564 4158 5346 6534 7722 8910
30x30 6.25
NC - 12 18 24 28 35 41 46 50

42x24 Airflow (CFM) 1998 2664 3330 3996 4662 5994 7326 8658 9990
7.00
36x28 NC - 12 19 24 28 36 41 46 50

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR77


ENGINEERING DATA
A70, A80
3/4” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 900 1100 1300 1500
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.050 0.075 0.105 0.140
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.012 0.022 0.034 0.049 0.067 0.111 0.165 0.231 0.307

Airflow (CFM) 2004 2672 3340 4008 4676 6012 7348 8684 10020
46x22 7.03
NC - 12 19 24 29 36 41 46 50

Airflow (CFM) 2034 2712 3390 4068 4746 6102 7458 8814 10170
32x32 7.11
NC - 13 19 24 29 36 42 46 50

Airflow (CFM) 2148 2864 3580 4296 5012 6444 7876 9308 10740
36x30 7.50
NC - 13 19 24 29 36 42 47 51

48x24 Airflow (CFM) 2289 3052 3815 4578 5341 6867 8393 9919 11445
8.00
36x32 NC - 13 19 25 29 36 42 47 51

Airflow (CFM) 2304 3072 3840 4608 5376 6912 8448 9984 11520
34x34 8.03
NC - 13 19 25 29 36 42 47 51

Airflow (CFM) 2442 3256 4070 4884 5698 7326 8954 10582 12210
36x34 8.50
NC - 13 20 25 29 37 42 47 51

Airflow (CFM) 2514 3352 4190 5028 5866 7542 9218 10894 12570
42x30 8.75
NC - 13 20 25 29 37 42 47 51
Registers
Grilles &

Airflow (CFM) 2589 3452 4315 5178 6041 7767 9493 11219 12945
36x36 9.00
NC - 14 20 25 30 37 43 47 43

42x34 Airflow (CFM) 2880 3840 4800 5760 6720 8640 10560 12480 14400
10.00
48x30 NC - 14 20 26 30 37 43 48 52

Airflow (CFM) 2892 3856 4820 5784 6748 8676 10604 12532 14460
38x38 10.03
NC - 14 20 26 30 37 43 48 52

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR78 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A70, A80
3/4” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 900 1100 1300 1500
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.050 0.075 0.105 0.140
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.012 0.022 0.034 0.049 0.067 0.111 0.165 0.231 0.307

Airflow (CFM) 3030 4040 5050 6060 7070 9090 11110 13130 15150
42x36 10.50
NC - 14 21 26 30 38 43 48 52

Airflow (CFM) 3135 4180 5225 6270 7315 9405 11495 13585 15675
46x34 10.86
NC - 14 21 26 30 38 43 48 52

Airflow (CFM) 3201 4268 5335 6402 7469 9603 11737 13871 16005
42x38 11.08
NC - 14 21 26 31 38 44 48 52

Airflow (CFM) 3201 4280 5350 6420 7490 9630 11770 13910 16050
40x40 11.11
NC - 15 21 26 31 38 44 48 52

Airflow (CFM) 3471 4628 5785 6942 8099 10413 12727 15041 17355
48x36 12.00
NC - 15 21 26 31 38 44 49 53

Airflow (CFM) 3546 4728 5910 7092 8274 10638 13002 15366 17730
42x42 12.25
NC - 15 21 27 31 38 44 49 53

Airflow (CFM) 3897 5196 6495 7794 9093 11691 14289 16887 19485
44x44 13.44
NC - 15 22 27 31 39 44 49 53

Registers
Grilles &
Airflow (CFM) 4062 5416 6770 8124 9478 12186 14894 17602 20310
48x42 14.00
NC - 16 22 27 32 39 45 49 53

Airflow (CFM) 4266 5688 7110 8532 9954 12798 15642 18486 21330
46x46 14.69
NC - 16 22 27 32 39 45 50 54

Airflow (CFM) 4455 5940 7425 8910 10395 13365 16335 19305 22275
48x46 15.33
NC - 16 22 28 32 39 45 50 54

Airflow (CFM) 4650 6200 7750 9300 10850 13950 17050 20150 23250
48x48 16.00
NC - 16 23 28 32 39 45 50 54

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR79


ENGINEERING DATA
A70D, A80D
3/4” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.002 0.008 0.018 0.018 0.051 0.073 0.099 0.130 0.164

Airflow (CFM) 19 38 57 76 95 114 133 152 171


6x6 0.25
NC - - - - - 13 19 25 29

Airflow (CFM) 26 52 78 104 130 156 182 208 234


8x6 0.33
NC - - - - - 15 20 26 30

Airflow (CFM) 34 68 102 136 170 204 238 272 306


10x6 0.42
NC - - - - - 16 21 28 32

Airflow (CFM) 37 74 111 148 185 222 259 296 333


8x8 0.44
NC - - - - - 16 22 28 32

Airflow (CFM) 41 82 123 164 205 246 287 328 369


12x6 0.50
NC - - - - - 17 22 30 34

Airflow (CFM) 48 96 144 192 240 288 336 384 432


14x6 0.58
NC - - - - - 18 24 30 34

16x6 Airflow (CFM) 57 114 171 228 285 342 399 456 513
0.67
12x8 NC - - - - 10 19 25 30 35
Registers
Grilles &

Airflow (CFM) 59 118 177 236 295 354 413 472 531
10x10 0.69
NC - - - - 10 19 25 31 35

Airflow (CFM) 63 126 189 252 315 378 441 504 567
18x6 0.75
NC - - - - 10 19 25 32 35

20x6 Airflow (CFM) 72 144 216 288 360 432 504 576 648
0.83
12x10 NC - - - - 11 19 25 30 35

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR80 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A70D, A80D
3/4” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.002 0.008 0.018 0.018 0.051 0.073 0.099 0.130 0.164

Airflow (CFM) 77 154 231 308 385 462 539 616 693
22x6 0.92
NC - - - - 11 19 25 30 35

24x6 Airflow (CFM) 88 176 264 352 440 528 616 704 792
1.00
12x12 NC - - - - 11 19 25 30 35

30x6 Airflow (CFM) 111 222 333 444 555 666 777 888 999
1.25
18x10 NC - - - - 12 20 26 32 35

Airflow (CFM) 122 244 366 488 610 732 854 976 1098
14x14 1.36
NC - - - - 12 20 27 32 35

36x6 Airflow (CFM) 135 270 405 540 675 810 945 1080 1215
1.50
18x12 NC - - - - 13 20 27 32 35

Airflow (CFM) 137 274 411 548 685 822 959 1096 1233
22x10 1.53
NC - - - - 13 20 27 32 36

30x8 Airflow (CFM) 149 298 447 596 745 894 1043 1192 1341
1.67
24x10

Registers
NC - - - - 14 21 27 33 37

Grilles &
42x6 Airflow (CFM) 159 318 477 636 795 954 1113 1272 1431
1.75
18x14 NC - - - - 14 21 27 33 37

Airflow (CFM) 162 324 486 648 810 972 1134 1296 1458
16x16 1.78
NC - - - - 14 21 27 33 37

24x12 Airflow (CFM) 182 364 546 728 910 1092 1274 1456 1638
2.00
18x16 NC - - - - 14 21 28 33 38
Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR81


ENGINEERING DATA
A70D, A80D
3/4” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.002 0.008 0.018 0.018 0.051 0.073 0.099 0.130 0.164

Airflow (CFM) 207 414 621 828 1035 1241 1449 1656 1863
18x18 2.25
NC - - - - 14 21 28 33 38

Airflow (CFM) 214 428 642 856 1070 1284 1498 1712 1926
24x14 2.33
NC - - - - 14 22 28 33 38

Airflow (CFM) 229 458 687 916 1145 1374 1603 1832 2061
30x12 2.50
NC - - - - 15 22 28 33 38

Airflow (CFM) 246 492 738 984 1230 1476 1722 1968 2214
24x16 2.67
NC - - - - 15 22 29 34 39

Airflow (CFM) 257 514 771 1028 1285 1542 1799 2056 2313
20x20 2.78
NC - - - - 16 23 29 34 39

Airflow (CFM) 275 550 825 1100 1375 1650 1925 2200 2475
36x12 3.00
NC - - - - 16 23 29 34 39

30x16 Airflow (CFM) 311 622 933 1244 1555 1866 2177 2488 2799
3.33
24x20 NC - - - - 17 24 30 35 40
Registers
Grilles &

Airflow (CFM) 314 628 942 1256 1570 1884 2198 2512 2826
22x22 3.36
NC - - - - 17 24 30 35 40

42x12 Airflow (CFM) 322 644 966 1288 1610 1932 2254 2576 2898
3.50
36x14 NC - - - - 17 24 30 36 40

Airflow (CFM) 343 686 1029 1372 1715 2058 2401 2744 3087
24x22 3.67
NC - - - - 17 24 30 36 40

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR82 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A70D, A80D
3/4” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.002 0.008 0.018 0.018 0.051 0.073 0.099 0.130 0.164

Airflow (CFM) 350 700 1050 1400 1750 2100 2450 2800 3150
30x18 3.75
NC - - - - 17 24 30 36 40

48x12 Airflow (CFM) 375 750 1125 1500 1875 2250 2625 3000 3375
4.00
24x24 NC - - - - 18 25 37 38 41

Airflow (CFM) 422 844 1266 1688 2110 2532 2954 3376 3798
36x18 4.50
NC - - - - 18 25 31 38 41

36x20 Airflow (CFM) 471 942 1413 1884 2355 2826 3297 3768 4239
5.00
30x24 NC - - - - 18 25 31 38 41

Airflow (CFM) 494 988 1482 1976 2470 2964 3458 3952 4446
42x18 5.25
NC - - - - 18 25 31 38 41

Airflow (CFM) 516 1032 1548 2064 2580 3096 3612 4128 4644
28x28 5.44
NC - - - - 18 25 32 38 41

42x20 Airflow (CFM) 551 1102 1653 2204 2755 3306 3857 4408 4959
5.83
30x28 NC - - - 10 18 26 32 38 41

Registers
Grilles &
48x18 Airflow (CFM) 566 1132 1698 2264 2830 3396 3962 4528 5094
6.00
36x24 NC - - - 10 18 26 32 38 41

Airflow (CFM) 594 1188 1782 2376 2970 3564 4158 4752 5346
30x30 6.25
NC - - - 10 18 26 32 38 41

42x24 Airflow (CFM) 666 1332 1998 2664 3330 3996 4662 5328 5994
7.00
36x28 NC - - - 10 19 26 32 38 41

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR83


ENGINEERING DATA
A70D, A80D
3/4” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.002 0.008 0.018 0.018 0.051 0.073 0.099 0.130 0.164

Airflow (CFM) 668 1336 2004 2672 3340 4008 4676 5344 6012
46x22 7.03
NC - - - 10 19 27 32 38 42

Airflow (CFM) 678 1356 2034 2712 3390 4068 4746 5424 6102
32x32 7.11
NC - - - 10 19 27 32 38 42

Airflow (CFM) 716 1432 2148 2864 3580 4296 5012 5728 6444
36x30 7.50
NC - - - 10 19 27 32 38 42

48x24 Airflow (CFM) 763 1526 2289 3052 3815 4578 5341 6104 6867
8.00
36x32 NC - - - 10 19 27 32 38 42

Airflow (CFM) 768 1536 2304 3072 3840 4608 5376 6144 6912
34x34 8.03
NC - - - 10 19 27 32 38 42

Airflow (CFM) 814 1628 2442 3256 4070 4884 5698 6512 7326
36x34 8.50
NC - - - 11 19 27 32 38 42

Airflow (CFM) 838 1676 2514 3352 4190 5028 5866 6704 7542
42x30 8.75
NC - - - 11 20 27 32 38 42
Registers
Grilles &

Airflow (CFM) 863 1726 2589 3452 4315 5178 6041 6904 7767
36x36 9.00
NC - - - 11 20 27 33 38 43

42x34 Airflow (CFM) 960 1920 2880 3840 4800 5760 6720 7680 8640
10.00
48x30 NC - - - 11 20 27 33 38 43

Airflow (CFM) 964 1928 2892 3856 4820 5784 6748 7712 8676
38x38 10.03
NC - - - 11 20 27 33 38 43

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR84 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A70D, A80D
3/4” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.002 0.008 0.018 0.018 0.051 0.073 0.099 0.130 0.164

Airflow (CFM) 1010 2020 3030 4040 5050 6060 7070 8080 9090
42x36 10.50
NC - - - 11 20 27 33 38 43

Airflow (CFM) 1045 2090 3135 4180 5225 6270 7315 8360 9405
46x34 10.86
NC - - - 11 20 27 33 38 43

Airflow (CFM) 1067 2134 3201 4268 5335 6402 7469 8536 9603
42x38 11.08
NC - - - 11 20 27 33 38 43

Airflow (CFM) 1070 2140 3210 4280 5350 6420 7490 8560 9630
40x40 11.11
NC - - - 11 20 27 33 38 43

Airflow (CFM) 1157 2314 3471 4628 5785 6942 8099 9256 10413
48x36 12.00
NC - - - 11 20 27 33 39 44

Airflow (CFM) 1182 2364 3546 4728 5910 7092 8274 9456 10638
42x42 12.25
NC - - - 11 20 27 33 39 44

Airflow (CFM) 1299 2598 3897 5196 6495 7794 9093 10392 11691
44x44 13.44
NC - - - 12 21 28 34 39 44

Registers
Grilles &
Airflow (CFM) 1354 2708 4062 5416 6770 8124 9478 10832 12186
48x42 14.00
NC - - - 12 21 28 34 40 45

Airflow (CFM) 1422 2844 4266 5688 7110 8532 9954 11376 12798
46x46 14.69
NC - - - 12 21 28 35 40 45

Airflow (CFM) 1485 2970 4455 5940 7425 8910 10395 11880 13365
48x46 15.33
NC - - - 12 22 28 35 40 45

Airflow (CFM) 1550 3100 4650 6200 7750 9300 10850 12400 13950
48x48 16.00
NC - - - 13 22 29 35 40 45

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR85


ENGINEERING DATA
A75, A85
1/2” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 800 900 1000 1100
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.075
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.013 0.022 0.035 0.050 0.068 0.089 0.113 0.140 0.169

Airflow (CFM) 57 76 95 114 133 152 171 190 209


6x6 0.25
NC - - - 12 16 20 23 25 28

Airflow (CFM) 78 104 130 156 182 208 234 260 286
8x6 0.33
NC - - - 13 17 21 24 27 29

Airflow (CFM) 102 136 170 204 238 272 306 340 374
10x6 0.42
NC - - - 15 19 22 24 28 31

Airflow (CFM) 111 148 185 222 259 296 333 370 407
8x8 0.44
NC - - - 15 19 23 26 28 31

Airflow (CFM) 123 164 205 246 287 328 369 410 451
12x6 0.50
NC - - 11 15 19 23 26 29 31

Airflow (CFM) 144 192 240 288 336 384 432 480 528
14x6 0.58
NC - - 11 16 20 24 27 30 32

16x6 Airflow (CFM) 171 228 285 342 399 456 513 570 627
0.67
12x8 NC - - 12 17 21 24 27 30 33
Registers
Grilles &

Airflow (CFM) 177 236 295 354 413 472 531 590 649
10x10 0.69
NC - - 12 17 21 25 28 30 33

Airflow (CFM) 189 252 315 378 441 504 567 630 693
18x6 0.75
NC - - 12 17 21 25 28 31 33

20x6 Airflow (CFM) 216 288 360 432 504 576 648 720 792
0.83
12x10 NC - - 13 18 22 25 29 31 34

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR86 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A75, A85
1/2” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 800 900 1000 1100
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.075
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.013 0.022 0.035 0.050 0.068 0.089 0.113 0.140 0.169

Airflow (CFM) 231 308 385 462 539 616 693 770 847
22x6 0.92
NC - - 13 18 22 26 29 32 34

24x6 Airflow (CFM) 264 352 440 528 616 704 792 880 968
1.00
12x12 NC - - 14 19 23 26 29 32 35

30x6 Airflow (CFM) 333 444 555 666 777 888 999 1110 1221
1.25
18x10 NC - - 15 20 24 27 30 33 36

Airflow (CFM) 366 488 610 732 854 976 1098 1220 1342
14x14 1.36
NC - - 15 20 24 28 31 34 36

36x6 Airflow (CFM) 405 540 675 810 945 1080 1215 1350 1485
1.50
18x12 NC - - 16 21 25 28 31 34 37

Airflow (CFM) 411 548 685 822 959 1096 1233 1370 1507
22x10 1.53
NC - - 16 21 25 28 31 34 37

30x8 Airflow (CFM) 477 596 745 894 1043 1192 1341 1490 1639
1.67
24x10 NC - - 16 21 25 29 32 34 37

Registers
Grilles &
42x6 Airflow (CFM) 477 636 795 954 1113 1272 1431 1590 1749
1.75
18x14 NC - 11 17 21 25 29 32 35 37

Airflow (CFM) 486 648 810 972 1134 1296 1458 1620 1782
16x16 1.78
NC - 11 17 21 25 29 32 35 37

24x12 Airflow (CFM) 546 728 910 1092 1274 1456 1638 1820 2002
2.00
18x16 NC - 11 17 22 26 29 33 35 38

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR87


ENGINEERING DATA
A75, A85
1/2” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 800 900 1000 1100
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.075
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.013 0.022 0.035 0.050 0.068 0.089 0.113 0.140 0.169

Airflow (CFM) 621 828 1035 1242 1449 1656 1863 2070 2277
18x18 2.25
NC - 12 18 22 26 30 33 36 38

Airflow (CFM) 642 856 1070 1284 1498 1712 1926 2140 2354
24x14 2.33
NC - 12 18 23 27 30 33 36 39

Airflow (CFM) 687 916 1145 1374 1603 1832 2061 2290 2519
30x12 2.50
NC - 12 18 23 27 30 34 36 39

Airflow (CFM) 738 984 1230 1476 1722 1968 2214 2460 2706
24x16 2.67
NC - 13 18 23 27 31 34 37 39

Airflow (CFM) 771 1028 1285 1542 1799 2056 2313 2570 2827
20x20 2.78
NC - 13 19 23 27 31 34 37 39

Airflow (CFM) 825 1100 1375 1650 1925 2200 2475 2750 3025
36x12 3.00
NC - 13 19 24 28 31 34 37 40

30x16 Airflow (CFM) 933 1244 1555 1866 2177 2488 2799 3110 3421
3.33
24x20 NC - 14 19 24 28 32 35 38 40
Registers
Grilles &

Airflow (CFM) 942 1256 1570 1884 2198 2512 2826 3140 3454
22x22 3.36
NC - 14 19 24 28 32 35 38 40

42x12 Airflow (CFM) 966 1288 1610 1932 2254 2576 2898 3220 3542
2.50
36x14 NC - 14 20 24 28 32 35 38 40

Airflow (CFM) 1029 1372 1715 2058 2401 2744 3087 3430 3773
24x22 3.67
NC - 14 20 25 29 32 35 38 41

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR88 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A75, A85
1/2” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 800 900 1000 1100
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.075
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.013 0.022 0.035 0.050 0.068 0.089 0.113 0.140 0.169

Airflow (CFM) 1050 1400 1750 2100 2450 2800 3150 3500 3850
30x18 3.75
NC - 14 20 25 29 32 35 38 41

Airflow (CFM) 1482 1976 2470 2964 3458 3952 4446 4940 5434
42x18 5.25
NC - 16 21 26 30 34 37 40 42

Airflow (CFM) 1548 2064 2580 3096 3612 4128 4644 5160 5676
28x28 5.44
NC - 16 22 26 30 34 37 40 42

42x20 Airflow (CFM) 1653 2204 2755 3306 3857 4408 4959 5510 6061
5.83
30x28 NC - 16 22 27 31 34 37 40 43

48x18 Airflow (CFM) 1698 2264 2830 3396 3962 4528 5094 5660 6226
6.00
36x24 NC - 16 22 27 31 34 37 40 43

Airflow (CFM) 1782 2376 2970 3564 4158 4752 5346 5940 6534
30x30 6.25
NC - 16 22 27 31 35 38 40 43

42x24 Airflow (CFM) 1998 2664 3330 3996 4662 5328 5994 6660 7326
7.00
36x28 NC - 17 23 28 32 35 38 41 43

Registers
Grilles &
Airflow (CFM) 2004 2676 3340 4008 4676 5344 6012 6680 7348
46x22 7.03
NC - 17 23 28 32 35 38 41 43

Airflow (CFM) 2034 2712 3390 4068 4746 5424 6102 6780 7458
32x32 7.11
NC - 17 23 28 32 35 38 41 44

Airflow (CFM) 2148 2864 3580 4296 5012 5728 6444 7160 7876
36x30 7.50
NC - 17 23 28 32 35 38 41 44

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR89


ENGINEERING DATA
A75, A85
1/2” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 800 900 1000 1100
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.075
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.018 0.032 0.051 0.073 0.099 0.129 0.164 0.202 0.245

48x24 Airflow (CFM) 2289 3052 3815 4578 5341 6104 6867 7630 8393
8.00
36x32 NC - 17 23 28 32 36 39 42 44

Airflow (CFM) 2304 3072 3840 4608 5376 6144 6912 7680 8448
34x34 8.03
NC - 18 23 28 32 36 39 42 44

Airflow (CFM) 2589 3452 4315 5178 6041 6904 7767 8630 9493
36x36 9.00
- 18 24 29 33 36 39 42 45

42x34 Airflow (CFM) 2880 3840 4800 5760 6720 7680 8640 9600 10560
9.92
48x30 NC 11 18 24 29 33 37 40 43 45

Airflow (CFM) 2892 3856 4820 5784 6748 7712 8676 9640 10604
38x38 10.03
NC 11 18 24 29 33 37 40 43 45

Airflow (CFM) 3030 4040 5050 6060 7070 8080 9090 10100 11110
42x36 10.50
NC 11 19 25 29 33 37 40 43 45

Airflow (CFM) 3135 4180 5225 6270 7315 8360 9405 10450 11495
46x34 10.86
NC 11 19 25 29 34 37 40 43 45
Registers
Grilles &

Airflow (CFM) 3201 4268 5335 6402 7469 8536 9603 10670 11737
42x38 11.08
NC 11 19 25 30 34 37 40 43 45

Airflow (CFM) 3201 4280 5350 6420 7490 8560 9630 10700 11770
40x40 11.11
NC 11 19 25 30 34 37 40 43 45

Airflow (CFM) 3471 4628 5785 6942 8099 9256 10413 11570 12727
48x36 12.00
NC 12 19 25 30 34 37 41 43 46

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR90 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A75, A85
1/2” Spacing, 0° Blade Deflection
Nom. Core Vel. (fpm) 300 400 500 600 700 800 900 1000 1100
Nom.
Duct
Duct Vel. Pressure 0.006 0.010 0.016 0.022 0.031 0.040 0.050 0.062 0.075
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.013 0.022 0.035 0.050 0.068 0.089 0.113 0.140 0.169

Airflow (CFM) 3546 4728 5910 7092 8274 9456 10638 11820 13002
42x42 12.25
NC 12 19 25 30 34 38 41 43 46

Airflow (CFM) 3897 5198 6495 7794 9093 10392 11691 12990 14289
44x44 13.44
NC 12 20 26 30 34 38 41 44 46

Airflow (CFM) 4062 5416 6770 8124 9478 10832 12186 13540 14894
48x42 14.00
NC 12 20 26 31 35 38 41 44 47

Airflow (CFM) 4266 5688 7110 8532 9954 11376 12798 14220 15642
46x46 14.69
NC 13 20 26 31 35 38 41 44 47

Airflow (CFM) 4455 5940 7425 8910 10395 11880 13365 14850 16335
48x46 15.33
NC 13 20 26 31 35 39 42 44 47

Airflow (CFM) 4650 6200 7750 9300 10850 12400 13950 15500 17050
48x48 16.00
NC 13 21 26 31 35 39 42 45 47
Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

Registers
Grilles &

www.tuttleandbailey.com 7/14 GR91


ENGINEERING DATA
A75D, A85D
1/2” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.003 0.011 0.026 0.045 0.071 0.102 0.139 0.182 0.230

Airflow (CFM) 19 38 57 76 95 114 133 152 171


6x6 0.25
NC - - - - 10 18 25 29 33

Airflow (CFM) 26 52 78 107 130 156 182 208 234


8x6 0.33
NC - - - - 11 19 25 30 35

Airflow (CFM) 34 68 102 136 170 204 238 272 306


10x6 0.42
NC - - - - 12 20 26 31 36

Airflow (CFM) 41 82 123 164 205 246 287 328 369


12x6 0.50
NC - - - - 12 20 26 32 36

Airflow (CFM) 48 96 144 192 240 288 336 384 432


14x6 0.58
NC - - - - 12 20 26 32 37

16x6 Airflow (CFM) 57 114 171 228 285 342 399 456 513
0.67
12x8 NC - - - - 13 21 27 32 38

Airflow (CFM) 59 118 177 236 295 354 413 472 531
10x10 0.69
NC - - - - 13 21 27 32 38
Registers
Grilles &

Airflow (CFM) 63 126 189 252 315 378 441 504 567
18x6 0.75
NC - - - - 14 22 28 33 38

20x6 Airflow (CFM) 72 144 216 288 360 432 504 576 648
0.83
12x10 NC - - - - 14 22 28 33 38

Airflow (CFM) 77 154 231 308 385 462 539 616 693
22x6 0.92
NC - - - - 14 22 28 34 38

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR92 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A75D, A85D
1/2” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.003 0.011 0.026 0.045 0.071 0.102 0.139 0.182 0.230

24x6 Airflow (CFM) 88 176 264 352 440 528 616 704 792
1.00
12x12 NC - - - - 15 22 28 34 39

30x6 Airflow (CFM) 111 222 333 444 555 666 777 888 999
1.25
18x10 NC - - - - 15 22 28 34 39

Airflow (CFM) 122 244 366 488 610 732 854 976 1098
14x14 1.36
NC - - - - 16 23 29 34 39

36x6 Airflow (CFM) 135 270 405 540 675 810 945 1080 1215
1.50
18x12 NC - - - - 16 24 29 34 39

Airflow (CFM) 137 274 411 548 685 822 959 1096 1233
22x10 1.53
NC - - - - 16 24 30 35 39

30x8 Airflow (CFM) 149 298 447 596 745 894 1043 1192 1341
1.67
24x10 NC - - - - 16 24 30 35 39

42x6 Airflow (CFM) 159 318 477 636 795 954 1113 1272 1431
1.75
18x14 NC - - - - 17 24 30 35 39

Registers
Grilles &
Airflow (CFM) 162 324 486 648 810 972 1134 1296 1458
16x16 1.78
NC - - - - 17 24 30 35 39

24x12 Airflow (CFM) 182 364 546 728 910 1092 1274 1456 1638
2.00
18x16 NC - - - - 17 24 30 35 39

Airflow (CFM) 207 414 621 828 1035 1241 1449 1656 1863
18x18 2.25
NC - - - - 18 25 31 35 40

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR93


ENGINEERING DATA
A75D, A85D
1/2” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.003 0.011 0.026 0.045 0.071 0.102 0.139 0.182 0.230

Airflow (CFM) 214 428 642 856 1070 1284 1498 1712 1926
24x14 2.33
NC - - 17 25 31 35 39 43 46

Airflow (CFM) 229 458 687 916 1145 1374 1603 1832 2061
30x12 2.50
NC - - 18 25 31 36 40 43 46

Airflow (CFM) 246 492 738 984 1230 1476 1722 1968 2214
24x16 2.67
NC - - 18 25 31 36 40 43 46

Airflow (CFM) 257 514 771 1028 1285 1542 1799 2056 2313
20x20 2.78
NC - - 18 26 31 36 40 44 47

Airflow (CFM) 275 550 825 1100 1375 1650 1925 2200 2475
36x12 3.00
NC - - 19 26 32 36 40 44 47

30x16 Airflow (CFM) 311 622 933 1244 1555 1866 2177 2488 2799
3.33
24x20 NC - - 19 26 32 37 41 44 47

Airflow (CFM) 314 628 942 1256 1570 1884 2198 2512 2826
22x22 3.36
NC - - 19 27 32 37 41 44 47
Registers
Grilles &

42x12 Airflow (CFM) 322 644 966 1288 1610 1932 2254 2576 2898
3.50
36x14 NC - - 19 27 32 37 41 44 48

Airflow (CFM) 343 686 1029 1372 1715 2058 2401 2744 3087
24x22 3.67
NC - - 20 27 33 37 41 45 48

Airflow (CFM) 350 700 1050 1400 1750 2100 2450 2800 3150
30x18 3.75
NC - - 20 27 33 37 41 45 48

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR94 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A75D, A85D
1/2” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.003 0.011 0.026 0.045 0.071 0.102 0.139 0.182 0.230

48x12 Airflow (CFM) 375 750 1125 1500 1875 2250 2625 3000 3375
4.00
24x24 NC - - - 10 19 26 33 39 43

Airflow (CFM) 422 844 1266 1688 2110 2532 2954 3376 3798
36x18 4.50
NC - - - 10 19 26 33 39 43

36x20 Airflow (CFM) 471 942 1413 1884 2355 2826 3297 3768 4239
5.00
30x24 NC - - - 11 19 27 33 38 43

Airflow (CFM) 494 988 1482 1976 2470 2964 3458 3952 4446
42x18 5.25
NC - - - 12 20 28 34 39 44

Airflow (CFM) 516 1032 1548 2064 2580 3096 3612 4128 4644
28x28 5.44
NC - - - 12 21 28 34 40 44

42x20 Airflow (CFM) 551 1102 1653 2204 2755 3306 3857 4408 4959
5.83
30x28 NC - - - 12 21 28 34 40 44

48x18 Airflow (CFM) 566 1132 1698 2264 2830 3396 3962 4528 5094
6.00
36x24 NC - - - 12 21 28 35 40 44

Registers
Grilles &
Airflow (CFM) 594 1188 1782 2376 2970 3564 4158 4752 5346
30x30 6.25
NC - - - 12 21 28 35 40 44

42x24 Airflow (CFM) 666 1332 1998 2664 3330 3996 4662 5328 5994
7.00
36x28 NC - - - 13 22 29 35 40 45

Airflow (CFM) 668 1336 2004 2672 3340 4008 4676 5344 6012
46x22 7.03
NC - - - 13 22 29 35 40 45

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR95


ENGINEERING DATA
A75D, A85D
1/2” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2)
Neg. Static Pressure 0.003 0.011 0.026 0.045 0.071 0.102 0.139 0.182 0.230

Airflow (CFM) 678 1356 2034 2712 3390 4068 4746 5424 6102
32x32 7.11
NC - - - 13 22 29 35 40 45

Airflow (CFM) 716 1432 2148 2864 3580 4296 5012 5728 6444
36x30 7.50
NC - - - 14 23 30 36 41 46

48x24 Airflow (CFM) 763 1526 2289 3052 3815 4578 5341 6104 6867
8.00
36x32 NC - - - 14 23 30 36 41 46

Airflow (CFM) 768 1536 2304 3072 3840 4608 5376 6144 6912
34x34 8.03
NC - - - 14 23 30 36 41 46

Airflow (CFM) 814 1628 2442 3256 4070 4884 5698 6512 7326
36x34 8.50
NC - - - 14 23 30 36 41 46

Airflow (CFM) 838 1676 2514 3352 4190 5028 5866 6704 7542
42x30 8.75
NC - - - 14 23 30 36 41 46

Airflow (CFM) 863 1726 2589 3452 4315 5178 6041 6904 7767
36x36 9.00
NC - - - 14 23 30 36 41 46
Registers
Grilles &

42x34 Airflow (CFM) 960 1920 2880 3840 4800 5760 6720 7680 8640
9.92
48x30 NC - - - 14 23 30 36 41 46

Airflow (CFM) 964 1928 2892 3856 4820 5784 6748 7712 9676
38x38 10.03
NC - - - 14 23 330 36 41 46

Airflow (CFM) 1010 2020 3030 4040 5050 6060 7070 8080 9090
42x36 10.50
NC - - - 15 23 31 37 42 47

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

GR96 7/14 www.tuttleandbailey.com


ENGINEERING DATA
A75D, A85D
1/2” Spacing, 35° Blade Deflection
Nom. Core Vel. (fpm) 100 200 300 400 500 600 700 800 900
Nom.
Duct
Duct Vel. Pressure 0.001 0.002 0.006 0.010 0.016 0.022 0.031 0.040 0.050
Area
Size (in.)
(ft.2) Neg. Static Pressure 0.003 0.011 0.026 0.045 0.071 0.102 0.139 0.182 0.230

Airflow (CFM) 1045 2090 3135 4180 5225 6270 7315 8360 9405
46x34 10.86
NC - - - 15 23 31 37 42 47

Airflow (CFM) 1067 2134 32001 4268 5335 6402 7469 8536 9603
42x38 11.08
NC - - - 15 23 31 37 42 47

Airflow (CFM) 1070 2140 3210 4280 5350 6420 7490 8560 9630
40x40 11.11
NC - - - 15 23 31 37 42 47

Airflow (CFM) 1157 2314 3471 4628 5785 6942 8099 9256 10413
48x36 12.00
NC - - - 15 23 31 37 42 47

Airflow (CFM) 1182 2364 3546 4728 5910 7092 8274 9456 10638
42x42 12.25
NC - - - 15 24 31 37 42 47

Airflow (CFM) 1299 2598 3897 5196 6495 7794 9093 10392 11691
44x44 13.44
NC - - - 15 24 32 38 43 48

Airflow (CFM) 1354 2708 4062 5416 6770 8124 9478 10832 12186
48x42 14.00
NC - - - 16 24 32 38 43 48

Registers
Grilles &
Airflow (CFM) 1422 2844 4266 5688 7110 8532 9954 11376 12798
46x46 14.69
NC - - - 16 25 32 39 44 48

Airflow (CFM) 1485 2970 4455 5940 7425 8910 10395 11880 13365
48x46 15.33
NC - - - 16 25 32 39 44 48

Airflow (CFM) 1550 3100 4650 6200 7750 9300 10850 12400 13950
48x48 16.00
NC - - - 16 25 32 39 44 48

Notes:
1. Tests conducted in accordance with ANSI/ASHRAE 70-2006 at isothermal conditions.
2. Units: Face Velocity = fpm; Total Pressure = in. wc
3. NC is based upon 10dB room absorption (Re: 10-12 watts) evaluated at 125 through 4000 Hz octave bands.
4. Dash “-” indicates NC value less than 10.

www.tuttleandbailey.com 7/14 GR97